- Home
- BACnet points lists
- AbsolutAire
- LX-4 control system (JENEsys Edge534 with touch-screen HMI)
Make-up air unit controls (heating, ventilating, optional cooling) · BACnet points list
AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI) BACnet points list
Updated 12 November 2026
The LX-4 option runs AbsolutAire units on a JENEsys Edge534 Niagara controller with a touch-screen HMI. It offers BACnet IP, BACnet MS/TP and Modbus TCP as standard. The BMS can run the unit, pick heat/vent/cool/auto, override occupancy, write heating and cooling setpoints, discharge limits and economizer/VFD settings, and read temperatures, airflow, energy and alarm objects.
This page lists 88 BACnet objects for the AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI) — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AbsolutAire’s own free documentation, linked below.
- Manufacturer
- AbsolutAire
- Model
- LX-4 control system (JENEsys Edge534 with touch-screen HMI)
- Equipment
- Make-up air unit controls (heating, ventilating, optional cooling)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 88 (40 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Niagara 4.7 (as described in the guide)
- Also known as
- LX-4, LX-4 User Guide 072020, JENEsys Edge534, AbsolutAire touch-screen controls
- Source document
- LX-4 User Guide - points list · LX-4 User Guide 072020
Reference only, provided as-is: verify against AbsolutAire’s current documentation and the live device before use. Not official AbsolutAire information. Terms of use.
BMS integration notes: AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI)
Command the unit with UnitRunCommand (1 off, 2 on) and OperationMode, and use OccupancyOverride to force occupied or unoccupied or follow the schedule. Write the occupied heating (and cooling) setpoints and read Fan_ON, BurnerOn, temperatures and the alarm BIs. All writable objects are commandable with a priority array.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 0 | UnitRunCommand | Unit run: 1 off, 2 on | Command |
| MV 1 | OperationMode | 1 heat, 2 vent, 3 cool, 4 auto | Command |
| MV 2 | OccupancyOverride | 1 manual unocc, 2 manual occ, 3 follow schedule | Command |
| AV 7 | OccupiedHeatSetPoint | Occupied heating setpoint, °F | Command |
| AV 9 | OccupiedCoolSetPoint | Occupied cooling setpoint, °F (if cooling) | Command |
| BI 13 | Fan_ON | Fan running status | Read |
| BI 14 | BurnerOn | Burner on status | Read |
| AI 23 | DischargeTemperature | Discharge air temperature | Read |
| BI 7 | BurnerLockoutAlarm | Burner lockout (1 = alarm) | Read |
| BI 6 | MotorNotRespondingAlarm | Fan motor not responding (1 = alarm) | Read |
Enable & remote start
UnitRunCommand (MV 0): 1 = off, 2 = on.
Network setup
- BACnet IP, BACnet MS/TP and Modbus TCP are standard on the Edge534 controller (2 Ethernet and 2 RS-485 ports).
Watch out for
- Burner reset and maintenance run-time reset act on a toggle (1 to 2 or 2 to 1).
- PID tuning MVs take 1 (most aggressive) to 11 (least); 6 is the default.
AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 0 | UnitRunCommand | Unit run command | Command | 1=Off, 2=On | |
| MVmin | 1 | OperationMode | Operation mode command | Command | 1=Heat, 2=Vent, 3=Cool, 4=Auto | |
| AV | 1 | MinimumDischarge | Minimum allowed discharge temperature | °F | Command | |
| AV | 0 | MaximumDischarge | Maximum allowed discharge temperature | °F | Command | |
| AV | 2 | HeatLockoutSetPoint | Burner disabled above this mixed air temperature | °F | Command | |
| AV | 4 | CoolLockoutSetPoint | Cooling disabled below this mixed air temperature | °F | Command | |
| AV | 3 | LowTempAlarmSetPoint | Unit shuts down below this discharge temperature | °F | Command | |
| AV | 5 | LowTempAlarmDelayMinutes | Low temperature lockout alarm delay | min | Command | |
| AVmin | 7 | OccupiedHeatSetPoint | Occupied heating setpoint | °F | Command | |
| AV | 6 | UnoccupiedHeatSetPoint | Unoccupied heating setpoint | °F | Command | |
| AVmin | 9 | OccupiedCoolSetPoint | Occupied cooling setpoint (if cooling fitted) | °F | Command | |
| AV | 8 | UnoccupiedCoolSetPoint | Unoccupied cooling setpoint (if cooling fitted) | °F | Command | |
| MVmin | 2 | OccupancyOverride | Occupancy override | Command | 1=Manual unoccupied, 2=Manual occupied, 3=Auto (follow schedule) | |
| MV | 3 | ManualVFD_Override | Manual VFD speed / economizer override | Command | 1=No, 2=Yes | |
| AV | 10 | ManualEconSpeed | Manual VFD speed or economizer setpoint | % | Command | |
| AV | 11 | BuildingPressureSetPoint | Building pressure setpoint | inWC | Command | |
| AV | 12 | MaintenanceSetPointHours | Run time between maintenance reminders | h | Command | |
| MV | 4 | ElapsedRunTimeReset | Reset maintenance run time (toggle 1/2) | Command | ||
| AV | 14 | InletFilterPressureSetPoint | Inlet dirty filter pressure setpoint | Command | ||
| AV | 15 | PreFilterPressureSetPoint | Pre-filter pressure setpoint | Command | ||
| AV | 13 | FinalFilterPressureSetPoint | Final filter pressure setpoint | Command | ||
| AV | 17 | Electric_KWH_Price | Electricity price per kWh | Command | ||
| AV | 16 | GasThermPrice | Gas price per therm | Command | ||
| AV | 18 | BurnerWatchdogDelayTime | Burner watchdog notification delay | Command | ||
| AV | 19 | MotorAlarmDelayTime | Motor not responding alarm delay | min | Command | |
| AV | 21 | MinimumEconomizer | Minimum VFD speed / economizer setting | % | Command | |
| AV | 20 | MaximumEconomizer | Maximum VFD speed / economizer setting | % | Command | |
| MV | 5 | Speed_Position | Two-position economizer / two-speed fan setting | Command | 1=Minimum, 2=Maximum | |
| MV | 7 | HeatBurnerCommand_PID_Tuning | Burner command PID tuning (1 fast - 11 slow, 6 default) | Command | ||
| MV | 8 | HeatRoomDemand_PID_Tuning | Heating room demand PID tuning (1-11, 6 default) | Command | ||
| MV | 9 | CoolingRoomDemand_PID_Tuning | Cooling room demand PID tuning (1-11, 6 default) | Command | ||
| MV | 10 | CoolingCommandControl_PID_Tuning | Cooling command PID tuning (1-11, 6 default) | Command | ||
| MV | 6 | BuildingPressureControl_PID_Tuning | Building pressure PID tuning (1-11, 6 default) | Command | ||
| MV | 11 | BurnerReset | Burner reset (toggle 1 to 2 or 2 to 1) | Command | ||
| AV | 22 | ChangeoverHysteresis | Auto mode changeover space deadband | °F | Command | |
| AV | 24 | OutsideAirAlarmDelay | Outside air alarm start delay (0-30 min) | min | Command | |
| AV | 25 | OutsideAirAlarmDuration | Outside air alarm duration (10-45 min) | min | Command | |
| AV | 23 | OutsideAirAlarmHornTime | Outside air alarm horn time (1-30 s) | s | Command | |
| BV | 0 | NetworkPowerExhaustCommand | Power exhaust enable command | Command | 0=Off, 1=Enable | |
| MV | 12 | ControlType | Space or discharge temperature control | Command | 1=Space, 2=Discharge | |
| BI | 0 | OutsideTempSensorAlarm | Outside temperature sensor alarm | Read | 0=Normal, 1=Alarm | |
| BI | 1 | DischargeTempSensorAlarm | Discharge temperature sensor alarm | Read | 0=Normal, 1=Alarm | |
| BI | 2 | SpaceTempSensorAlarm | Space temperature sensor alarm | Read | 0=Normal, 1=Alarm | |
| BI | 3 | ReturnTempSensorAlarm | Return temperature sensor alarm | Read | 0=Normal, 1=Alarm | |
| BI | 4 | CoolingCoilTempSensorAlarm | Cooling coil temperature sensor alarm | Read | 0=Normal, 1=Alarm | |
| BI | 5 | LowDischargeTempAlarm | Low discharge temperature alarm | Read | 0=Normal, 1=Alarm | |
| BImin | 6 | MotorNotRespondingAlarm | Fan motor not responding alarm | Read | 0=Normal, 1=Alarm | |
| BImin | 7 | BurnerLockoutAlarm | Burner lockout alarm | Read | 0=Normal, 1=Alarm | |
| BI | 8 | BurnerWatchdogAlarm | Burner watchdog alarm | Read | 0=Normal, 1=Alarm | |
| BI | 9 | DirtyPreFilterAlarm | Dirty pre-filter alarm | Read | 0=Normal, 1=Alarm | |
| BI | 10 | DirtyFinalFilterAlarm | Dirty final filter alarm | Read | 0=Normal, 1=Alarm | |
| BI | 11 | DirtyInletFilterAlarm | Dirty inlet filter alarm | Read | 0=Normal, 1=Alarm | |
| BI | 12 | DamperFeedbackFault | Damper feedback fault | Read | 0=Normal, 1=Alarm | |
| MI | 0 | HVAC_Mode | Current HVAC mode | Read | 1=Heat, 2=Vent, 3=Cool | |
| AI | 0 | MixedAirTemperature | Mixed air temperature (mixed air units) | °F | Read | |
| AI | 1 | ANSI_MaxDischarge | Calculated maximum allowed discharge temperature | °F | Read | |
| AI | 2 | UnitCFM | Unit listed airflow | CFM | Read | |
| AI | 3 | Current_OA_CFM | Current outside airflow (mixed air units) | CFM | Read | |
| AI | 4 | OA_Percent | Current outside air percent | % | Read | |
| AI | 5 | RA_Percent | Current return air percent (mixed air units) | % | Read | |
| AI | 6 | BurnerCommand | Burner command | % | Read | |
| AI | 7 | CoolingCommand | Cooling command (if fitted) | % | Read | |
| AI | 8 | ActiveCoolingStages | Active cooling stages (staged cooling) | Read | ||
| AI | 9 | VFD_Speed_Economizer_Command | VFD speed or economizer command | % | Read | |
| AI | 10 | DischargeAirDensity | Discharge air density | Read | ||
| AI | 11 | DischargeAirCubicFeetPerPound | Discharge air specific volume | Read | ||
| MI | 1 | MaintenanceMessage | Maintenance message | Read | ||
| AI | 12 | ElapsedMaintenanceRunTime | Run time since last maintenance reset | Read | ||
| AI | 13 | DailyElectricUsage | Previous day electric usage | Read | ||
| AI | 14 | DailyGasUsage | Previous day gas usage | Read | ||
| AI | 15 | DailyAverageOutsideTemperature | Previous day average outside temperature | °F | Read | |
| AI | 16 | DailyElectricCost | Previous day electric cost | Read | ||
| AI | 17 | DailyGasCost | Previous day gas cost | Read | ||
| AI | 18 | DailyAverageVfdFrequency | Previous day average VFD speed | % | Read | |
| AI | 19 | DailyAverageOAPercent | Previous day average outside air | % | Read | |
| AI | 20 | YesterdayHeatingDegreeDays | Previous day heating degree days (65 °F base) | Read | ||
| AI | 21 | YesterdayCoolingDegreeDays | Previous day cooling degree days (65 °F base) | Read | ||
| BImin | 13 | Fan_ON | Fan status | Read | 0=Off, 1=On | |
| BImin | 14 | BurnerOn | Burner status | Read | 0=Off, 1=On | |
| AI | 22 | BuildingPressure | Building pressure | Read | ||
| AImin | 23 | DischargeTemperature | Discharge temperature | °F | Read | |
| AI | 24 | OutsideTemperature | Outside temperature | °F | Read | |
| AI | 25 | ReturnTemperature | Return temperature (mixed air units) | °F | Read | |
| AI | 26 | SpaceTemperature | Space temperature (space control units) | °F | Read | |
| AI | 27 | CoolingCoilTemperature | Cooling coil exit temperature | °F | Read | |
| BI | 15 | OccupancyStatus | Occupancy status | Read | 0=Unoccupied, 1=Occupied | |
| AI | 28 | TotalFanHours | Total unit run hours | h | Read | |
| BI | 16 | PowerExhaustMode | Power exhaust mode | Read | 0=Inactive, 1=Active |
No points match these filters.
Object ID lookup: AbsolutAire LX-4 control system point IDs by name
MV0UnitRunCommandMV1OperationModeAV1MinimumDischargeAV0MaximumDischargeAV2HeatLockoutSetPointAV4CoolLockoutSetPointAV3LowTempAlarmSetPointAV5LowTempAlarmDelayMinutesAV7OccupiedHeatSetPointAV6UnoccupiedHeatSetPointAV9OccupiedCoolSetPointAV8UnoccupiedCoolSetPointMV2OccupancyOverrideMV3ManualVFD_OverrideAV10ManualEconSpeedAV11BuildingPressureSetPointAV12MaintenanceSetPointHoursMV4ElapsedRunTimeResetAV14InletFilterPressureSetPointAV15PreFilterPressureSetPointAV13FinalFilterPressureSetPointAV17Electric_KWH_PriceAV16GasThermPriceAV18BurnerWatchdogDelayTimeAV19MotorAlarmDelayTimeAV21MinimumEconomizerAV20MaximumEconomizerMV5Speed_PositionMV7HeatBurnerCommand_PID_TuningMV8HeatRoomDemand_PID_TuningMV9CoolingRoomDemand_PID_TuningMV10CoolingCommandControl_PID_TuningMV6BuildingPressureControl_PID_TuningMV11BurnerResetAV22ChangeoverHysteresisAV24OutsideAirAlarmDelayAV25OutsideAirAlarmDurationAV23OutsideAirAlarmHornTimeBV0NetworkPowerExhaustCommandMV12ControlTypeBI0OutsideTempSensorAlarmBI1DischargeTempSensorAlarmBI2SpaceTempSensorAlarmBI3ReturnTempSensorAlarmBI4CoolingCoilTempSensorAlarmBI5LowDischargeTempAlarmBI6MotorNotRespondingAlarmBI7BurnerLockoutAlarmBI8BurnerWatchdogAlarmBI9DirtyPreFilterAlarmBI10DirtyFinalFilterAlarmBI11DirtyInletFilterAlarmBI12DamperFeedbackFaultMI0HVAC_ModeAI0MixedAirTemperatureAI1ANSI_MaxDischargeAI2UnitCFMAI3Current_OA_CFMAI4OA_PercentAI5RA_PercentAI6BurnerCommandAI7CoolingCommandAI8ActiveCoolingStagesAI9VFD_Speed_Economizer_CommandAI10DischargeAirDensityAI11DischargeAirCubicFeetPerPoundMI1MaintenanceMessageAI12ElapsedMaintenanceRunTimeAI13DailyElectricUsageAI14DailyGasUsageAI15DailyAverageOutsideTemperatureAI16DailyElectricCostAI17DailyGasCostAI18DailyAverageVfdFrequencyAI19DailyAverageOAPercentAI20YesterdayHeatingDegreeDaysAI21YesterdayCoolingDegreeDaysBI13Fan_ONBI14BurnerOnAI22BuildingPressureAI23DischargeTemperatureAI24OutsideTemperatureAI25ReturnTemperatureAI26SpaceTemperatureAI27CoolingCoilTemperatureBI15OccupancyStatusAI28TotalFanHoursBI16PowerExhaustMode
Integration notes
- The points list (guide pages 25-26) is printed as a rotated image; values were keyed by hand from the rendered page and checked row by row.
- Writable AV, BV and MV objects list priority levels 1-16, so they are shown as commandable; inputs list none.
- The guide covers standard features only; custom-built units can differ, and objects for options a unit does not have (cooling, mixed air, filter transmitters, power exhaust) carry no meaning.
- Units are only partly printed in the table; °F, %, CFM and hours here follow the descriptions.
- MaintenanceMessage is an enumerated multistate input over BACnet; the guide does not list its states.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LX-4 control system (JENEsys Edge534 with touch-screen HMI) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI)
How many BACnet points does the AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI) have?
This list has 88 BACnet objects: 29 analog inputs, 26 analog values, 17 binary inputs, 1 binary value, 2 multi-state inputs, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI) BACnet points are writable?
40 of the 88 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI) BACnet documentation?
The source is LX-4 User Guide - points list (LX-4 User Guide 072020), published free by AbsolutAire at https://www.absolutaire.com/wp-content/uploads/lx-4_user_guide.pdf.
What are the minimum BACnet points to integrate the AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI)?
Start with MV 0 UnitRunCommand (Unit run: 1 off, 2 on); MV 1 OperationMode (1 heat, 2 vent, 3 cool, 4 auto); MV 2 OccupancyOverride (1 manual unocc, 2 manual occ, 3 follow schedule); AV 7 OccupiedHeatSetPoint (Occupied heating setpoint, °F); AV 9 OccupiedCoolSetPoint (Occupied cooling setpoint, °F (if cooling)); BI 13 Fan_ON (Fan running status); BI 14 BurnerOn (Burner on status); AI 23 DischargeTemperature (Discharge air temperature); BI 7 BurnerLockoutAlarm (Burner lockout (1 = alarm)); BI 6 MotorNotRespondingAlarm (Fan motor not responding (1 = alarm)).
How do I enable BMS control of the AbsolutAire LX-4 control system (JENEsys Edge534 with touch-screen HMI)?
UnitRunCommand (MV 0): 1 = off, 2 = on.
How do I check these points on the real LX-4 control system (JENEsys Edge534 with touch-screen HMI)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AbsolutAire BACnet points lists
- Energy recovery make-up air unit controller
AbsolutAire ER-3 control system (energy recovery)
AbsolutAire heating and ventilating units with plate or heat-pipe heat recovery, supply and exhaust fans, controlled by the ER-3 control system.
Also known as: ER-3, Smart-Vue - Make-up air unit controls (discharge temperature and humidity)
AbsolutAire PC-3 / LC-3 psychrometric control system
AbsolutAire units with the PC-3 (LC-3) psychrometric control package for discharge temperature, dehumidification, humidification and optional airflow control.
Also known as: PC-3, LC-3, LC-3 Psychrometric Controls Package, Smart-Vue, PC-3 User Guide 010220 - Make-up air / heating and ventilating unit controller
AbsolutAire TC-3 control system
AbsolutAire gas-fired heating and ventilating (make-up air) units with the TC-3 control system and Smart-Vue user interface.
Also known as: TC-3, Smart-Vue - Make-up air / heating and ventilating unit controller
AbsolutAire UC-3 control system
AbsolutAire gas-fired heating and ventilating (make-up air) units with the UC-3 or IC-3 control system and Smart-Vue user interface.
Also known as: UC-3, IC-3, IC-3 control system, Smart-Vue - Make-up air unit controls (heating and ventilating unit)
AbsolutAire UC-3 HTLV control system (heating and ventilating)
AbsolutAire heating and ventilating units with the UC-3 HTLV control system.
Also known as: UC-3 HTLV, UC-3 HT/LV, HTLV, Smart-Vue, UC-3 HTLV User Guide 010622 - Make-up air unit controls (heating and ventilating unit)
AbsolutAire UC-3 Lite control system (heating and ventilating)
AbsolutAire heating and ventilating units with the UC-3 Lite control system.
Also known as: UC-3 Lite, UC-3 LITE, Smart-Vue, UC-3 Lite User Guide 091121
Source: LX-4 User Guide - points list · LX-4 User Guide 072020. Object names, instances and units are reproduced as published; descriptions are our own.