Make-up air unit controls (heating and ventilating unit) · BACnet points list

AbsolutAire UC-3 HTLV control system (heating and ventilating) BACnet points list

Updated 12 November 2026

Short answer

The UC-3 HTLV is AbsolutAire's controller for heat-and-vent make-up air units: it runs the burner to hold a discharge or space temperature, with occupied/unoccupied setpoints, a low-temperature limit and a mild-weather heat lockout. It joins a BACnet MS/TP network with the MAC address set on DIP switches. The BMS enables the unit through NetworkUnitEnable, sets occupancy and vent/heat mode, and writes the space and discharge setpoints.

This page lists 37 BACnet objects for the AbsolutAire UC-3 HTLV control system (heating and ventilating) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AbsolutAire’s own free documentation, linked below.

Manufacturer
AbsolutAire
Model
UC-3 HTLV control system (heating and ventilating)
Equipment
Make-up air unit controls (heating and ventilating unit)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
37 (13 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
3640 followed by the MAC address (MAC 25 = 364025)
Also known as
UC-3 HTLV, UC-3 HT/LV, HTLV, Smart-Vue, UC-3 HTLV User Guide 010622
Source document
UC-3 HTLV User Guide - Network Integration / Network Points List · UC-3 HTLV User Guide 010622
Download CSV 37 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AbsolutAire’s current documentation and the live device before use. Not official AbsolutAire information. Terms of use.

BMS integration notes: AbsolutAire UC-3 HTLV control system (heating and ventilating)

Integration in brief

Write NetworkUnitEnable = 2 to run the unit (the guide marks it as the point to enable the unit), then set NetworkOccupancy and HVAC_Mode and the occupied/unoccupied space or discharge setpoints. Read the current temperatures, burner command and status, and the multistate alarms; BurnerReset clears a lockout when its value is changed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 51NetworkUnitEnableUnit enable: 1 off, 2 onWrite
MV 52NetworkOccupancy1 occupied, 2 unoccupied, 3 follow scheduleWrite
MV 53HVAC_Mode1 vent, 2 heatWrite
AV 51OccupiedSpaceSetPointOccupied space temperature setpoint, °FWrite
AV 53DischargeTempSetPointDischarge temperature setpoint, °FWrite
MV 15CurrentBurnerStatusBurner status (ENABLE / OFF)Read
AV 35CurrentDischargeTemperatureDischarge air temperatureRead
AV 33CurrentSpaceTemperatureSpace temperatureRead
MV 12BurnerLockoutAlarmBurner lockoutRead
MV 11MotorNotRespondingAlarmFan motor did not startRead

Enable & remote start

NetworkUnitEnable (MV 51): 1 = off, 2 = on. The guide marks it as the point to use to enable the unit.

Network setup

Watch out for

AbsolutAire UC-3 HTLV control system (heating and ventilating) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

37 of 37 shown
Type
AnalogBinaryMulti-state
Access
Show
AbsolutAire UC-3 HTLV control system (heating and ventilating) BACnet Points List
DescriptionStates
AV1DesignTempRiseUnit design temperature rise (configuration, do not write)°FRead
AV32CurrentBurnerCommandCurrent burner command (do not write)%Read
AVmin33CurrentSpaceTemperatureCurrent space temperature (do not write)°FRead
AV34CurrentOutsideTemperatureCurrent outside temperature (do not write)°FRead
AVmin35CurrentDischargeTemperatureCurrent discharge temperature (do not write)°FRead
AVmin51OccupiedSpaceSetPointOccupied space temperature setpoint°FWrite
AV52UnoccupiedSpaceSetPointUnoccupied space temperature setpoint°FWrite
AVmin53DischargeTempSetPointDischarge temperature setpoint°FWrite
AV54MinimumDischargeTempMinimum allowed discharge temperature°FWrite
AV55MaximumDischargeTempMaximum allowed discharge temperature°FWrite
AV56LowTempAlarmSetPointLow temperature alarm setpoint°FWrite
AV57LowTempAlarmDelayMinutesLow temperature alarm delayminWrite
AV58network_ControlDeadbandSpace temperature control deadband°FWrite
AV59network_HeatLockoutHeat lockout setpoint (mild weather)°FWrite
BV1Space Sensor TypeSpace sensor type (configuration, do not write)ReadBoolean (REMOTE WIRED;HMI SENSOR)
BV2ScheduleAvailableSchedule available (configuration, do not write)ReadBoolean (YES;NO)
BV3LTL_AvailableLow temperature alarm available (configuration)ReadBoolean (YES;NO)
BV4HeatLockoutAvailableHeat lockout available (configuration)ReadBoolean (YES;NO)
MV1Override Output 1Network override alarm on hardware output 1ReadEnumeration ALARM / NORMAL
MV2Override Output 3Network override alarm on hardware output 3ReadEnumeration ALARM / NORMAL
MV3Override Output 4Network override alarm on hardware output 4ReadEnumeration ALARM / NORMAL
MV4Override Output 5Network override alarm on hardware output 5ReadEnumeration ALARM / NORMAL
MV5Override Output 12Network override alarm on hardware output 12ReadEnumeration ALARM / NORMAL
MV6BurnerNotRespondingAlarmBurner not responding alarmReadEnumeration ALARM / NORMAL
MV7BurnerWatchdogAlarmBurner watchdog alarmReadEnumeration ALARM / NORMAL
MV8SpaceTempSensorAlarmSpace temperature sensor alarmReadSensorReliability enumeration
MV9OutsideTempSensorAlarmOutside temperature sensor alarmReadSensorReliability enumeration
MV10DischargeTempSensorAlarmDischarge temperature sensor alarmReadSensorReliability enumeration
MVmin11MotorNotRespondingAlarmFan motor not responding alarmReadEnumeration ALARM / NORMAL
MVmin12BurnerLockoutAlarmBurner lockout alarmReadEnumeration LOCKOUT / NORMAL
MV13DirtyFilterAlarmDirty filter alarmReadEnumeration DIRTY / CLEAN
MV14LowTempLockoutAlarmLow temperature lockout alarmReadEnumeration ALARM / NORMAL
MVmin15CurrentBurnerStatusCurrent burner statusReadEnumeration ENABLE / OFF
MVmin51NetworkUnitEnableUnit enable commandWrite1=Off, 2=On
MVmin52NetworkOccupancyOccupancy commandWrite1=Occupied, 2=Unoccupied, 3=Follow schedule
MVmin53HVAC_ModeHVAC modeWrite1=Vent, 2=Heat
MV54BurnerResetBurner reset (change 1 to 2 or 2 to 1)Write
Object ID lookup: AbsolutAire UC-3 HTLV control system point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UC-3 HTLV control system (heating and ventilating) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AbsolutAire UC-3 HTLV control system (heating and ventilating)

How many BACnet points does the AbsolutAire UC-3 HTLV control system (heating and ventilating) have?

This list has 37 BACnet objects: 14 analog values, 4 binary values, 19 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AbsolutAire UC-3 HTLV control system (heating and ventilating) BACnet points are writable?

13 of the 37 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AbsolutAire UC-3 HTLV control system (heating and ventilating) BACnet documentation?

The source is UC-3 HTLV User Guide - Network Integration / Network Points List (UC-3 HTLV User Guide 010622), published free by AbsolutAire at https://www.absolutaire.com/wp-content/uploads/uc-3_htlv_user_guide_0.pdf.

What are the minimum BACnet points to integrate the AbsolutAire UC-3 HTLV control system (heating and ventilating)?

Start with MV 51 NetworkUnitEnable (Unit enable: 1 off, 2 on); MV 52 NetworkOccupancy (1 occupied, 2 unoccupied, 3 follow schedule); MV 53 HVAC_Mode (1 vent, 2 heat); AV 51 OccupiedSpaceSetPoint (Occupied space temperature setpoint, °F); AV 53 DischargeTempSetPoint (Discharge temperature setpoint, °F); MV 15 CurrentBurnerStatus (Burner status (ENABLE / OFF)); AV 35 CurrentDischargeTemperature (Discharge air temperature); AV 33 CurrentSpaceTemperature (Space temperature); MV 12 BurnerLockoutAlarm (Burner lockout); MV 11 MotorNotRespondingAlarm (Fan motor did not start).

How do I enable BMS control of the AbsolutAire UC-3 HTLV control system (heating and ventilating)?

NetworkUnitEnable (MV 51): 1 = off, 2 = on. The guide marks it as the point to use to enable the unit.

How do I check these points on the real UC-3 HTLV control system (heating and ventilating)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AbsolutAire BACnet points lists

Source: UC-3 HTLV User Guide - Network Integration / Network Points List · UC-3 HTLV User Guide 010622. Object names, instances and units are reproduced as published; descriptions are our own.