Short answer

The VT8650 is the rooftop unit and heat pump version of the Viconics VT8000 room controller. It is a BACnet application-specific controller (B-ASC) on BACnet MS/TP, with BACnet IP and Wi-Fi status objects for units set up through the Wi-Fi configuration web page. MV 119 Application selects rooftop or heat pump; the objects cover G/Y1/Y2/W1/W2-OB stage outputs, economizer and fresh-air limits, CO2-based IAQ control, supply and mixed air temperatures, and the common VT8000 display, Lua and ZigBee wireless sensor objects.

This page lists 456 BACnet objects for the Viconics VT8650 Rooftop Unit and Heat Pump Controller — 280 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Viconics’s own free documentation, linked below.

Manufacturer
Viconics
Model
VT8650 Rooftop Unit and Heat Pump Controller
Equipment
Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
456 (280 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
2.6
Also known as
VT8650, Viconics VT8650, VT8000 VT8650, Schneider Electric VT8650
Source document
VT8650 BACnet Integration Guide - Roof Top Unit (RTU), Heat Pump and Indoor Air Quality (IAQ) - Firmware Revision 2.6 · 028-0437-07_IG-VT8650-BNET_A4_EN (Version 7) · rev. 2022-07
Download CSV 456 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Viconics VT8650 Rooftop Unit and Heat Pump Controller

Integration in brief

Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy, MV 112 control status, the G fan output BO 25 and the fan lock alarm BV 39. Write at priorities 4-16 for live control; avoid 1-3.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10Occupancy CommandBMS occupancy: local, occupied or unoccupiedCommand
MV 16System ModeOff / auto / cool / heatCommand
MV 17Fan ModeFan mode: on / auto / smartCommand
AV 39Occupied Heat SetpointOccupied heating setpointCommand
AV 40Occupied Cool SetpointOccupied cooling setpointCommand
MV 112Control StatusCurrent state: off, cooling or heatingCommand
BO 25G Fan StatusFan (G) output stateCommand
MI 33Effective OccupancyActual occupancy stateRead
AV 100Room TemperatureSpace temperature used for controlCommand
BV 39Fan Lock AlarmFan lock alarm (1 = on)Command

Enable & remote start

No enable switch is needed. The BMS writes MV 10 Occupancy Command (1 = Loc. occ, the controller decides locally; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.

Sensors & values from the BMS

The guide has no BMS-written room temperature object: MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.

Network setup

Watch out for

Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

456 of 456 shown
Type
Access
Show
Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet Points List
DescriptionStates
AI2Light Sensor LevelRange 0 to 30000Read
AI4Relative Humidity Raw ValueRange 0 to 1000Read
AI5UI20 Raw ValueRange 0 to 4095Read
AI7UI23 Raw ValueRange 0 to 4095Read
AI8UI22 Raw ValueRange 0 to 4095Read
AI9UI24 Raw ValueRange 0 to 4095Read
AI31UI19 Raw ValueRange 0 to 4095Read
AI32Temperature Raw ValueRange -400 to 1220Read
AI33UI16 Raw ValueRange 0 to 4095Read
AI34UI17 Raw ValueRange 0 to 4095Read
AI315Wireless Device 1 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI316Wireless Device 2 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI317Wireless Device 3 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI318Wireless Device 4 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI319Wireless Device 5 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI320Wireless Device 6 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI321Wireless Device 7 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI322Wireless Device 8 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI323Wireless Device 9 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI324Wireless Device 10 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI329Effective SetpointRange 40°F (4°C) to 100°F (38°C)°F/°CRead
AI330Paired ZigBee DevicesRange 0 to 20Read
AI340Therm. Raw ValueRange -400 to 1220Read
AI341SH Therm. Raw ValueRange -400 to 1220Read
AI343Wi-Fi Module Boot CountRange 0 to 32767Read
AI355Wireless Device 11 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI356Wireless Device 12 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI357Wireless Device 13 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI358Wireless Device 14 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI359Wireless Device 15 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI360Wireless Device 16 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI361Wireless Device 17 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI362Wireless Device 18 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI363Wireless Device 19 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI364Wireless Device 20 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI365Wireless Device 1 - HumidityRange 0 to 100%RHRead
AI366Wireless Device 2 - HumidityRange 0 to 100%RHRead
AI367Wireless Device 3 - HumidityRange 0 to 100%RHRead
AI368Wireless Device 4 - HumidityRange 0 to 100%RHRead
AI369Wireless Device 5 - HumidityRange 0 to 100%RHRead
AI370Wireless Device 6 - HumidityRange 0 to 100%RHRead
AI371Wireless Device 7 - HumidityRange 0 to 100%RHRead
AI372Wireless Device 8 - HumidityRange 0 to 100%RHRead
AI373Wireless Device 9 - HumidityRange 0 to 100%RHRead
AI374Wireless Device 10 - HumidityRange 0 to 100%RHRead
AI375Wireless Device 11 - HumidityRange 0 to 100%RHRead
AI376Wireless Device 12 - HumidityRange 0 to 100%RHRead
AI377Wireless Device 13 - HumidityRange 0 to 100%RHRead
AI378Wireless Device 14 - HumidityRange 0 to 100%RHRead
AI379Wireless Device 15 - HumidityRange 0 to 100%RHRead
AI380Wireless Device 16 - HumidityRange 0 to 100%RHRead
AI381Wireless Device 17 - HumidityRange 0 to 100%RHRead
AI382Wireless Device 18 - HumidityRange 0 to 100%RHRead
AI383Wireless Device 19 - HumidityRange 0 to 100%RHRead
AI384Wireless Device 20 - HumidityRange 0 to 100%RHRead
AI385Wireless Device 1 - CO2Range 0 to 5000ppmRead
AI386Wireless Device 2 - CO2Range 0 to 5000ppmRead
AI387Wireless Device 3 - CO2Range 0 to 5000ppmRead
AI388Wireless Device 4 - CO2Range 0 to 5000ppmRead
AI389Wireless Device 5 - CO2Range 0 to 5000ppmRead
AI390Wireless Device 6 - CO2Range 0 to 5000ppmRead
AI391Wireless Device 7 - CO2Range 0 to 5000ppmRead
AI392Wireless Device 8 - CO2Range 0 to 5000ppmRead
AI393Wireless Device 9 - CO2Range 0 to 5000ppmRead
AI394Wireless Device 10 - CO2Range 0 to 5000ppmRead
AI395Wireless Device 11 - CO2Range 0 to 5000ppmRead
AI396Wireless Device 12 - CO2Range 0 to 5000ppmRead
AI397Wireless Device 13 - CO2Range 0 to 5000ppmRead
AI398Wireless Device 14 - CO2Range 0 to 5000ppmRead
AI399Wireless Device 15 - CO2Range 0 to 5000ppmRead
AI400Wireless Device 16 - CO2Range 0 to 5000ppmRead
AI401Wireless Device 17 - CO2Range 0 to 5000ppmRead
AI402Wireless Device 18 - CO2Range 0 to 5000ppmRead
AI403Wireless Device 19 - CO2Range 0 to 5000ppmRead
AI404Wireless Device 20 - CO2Range 0 to 5000ppmRead
AO21PI Heating DemandDefault 0, range 0 to 100%Command
AO22PI Cooling DemandDefault 0, range 0 to 100%Command
AO23Economizer DemandDefault 0, range 0 to 100%Command
AO24Analog Output Heat DemandDefault 0, range 0 to 100%Command
AO123UO11 Analog OutputDefault 0, range 0 to 10VCommand
AO124UO12 Analog OutputDefault 0, range 0 to 10VCommand
AO125UO9 Analog OutputDefault 0, range 0 to 10VCommand
AO126UO10 Analog OutputDefault 0, range 0 to 10VCommand
AV2User HMIDefault 0, range 0 to 12Command
AV3Low BacklightDefault 60, range 0 to 100%Command
AV4Night BacklightDefault 5, range 0 to 100%Command
AV7Calibrate Room Temperature SensorDefault 0°F (0.0°C), range -5°F (-2.5°C) to 5°F (2.5°C)Δ°F/Δ°CCommand
AV8Calibrate Humidity SensorDefault 0, range -15 to 15%RHCommand
AV10COM AddressDefault 254, range 0 to 254Command
AV16BACnet Stack Poll RateDefault 4, range 1 to 5Command
AV20Discharge Low LimitDefault 45°F (7°C), range 35°F (2°C) to 65°F (18°C)°F/°CCommand
AV21Minimum Fresh AirDefault 0, range 0 to 20000CFMCommand
AV22Maximum Fresh AirDefault 0, range 0 to 20000CFMCommand
AV23Minimum CO2Default 800, range 0 to 5000ppmCommand
AV24Maximum CO2Default 1200, range 0 to 5000ppmCommand
AV25Lua Parameter A (AV25)Default 0, range -32768 to 32767Command
AV26Lua Parameter B (AV26)Default 0, range -32768 to 32767Command
AV27Lua Parameter C (AV27)Default 0, range -32768 to 32767Command
AV28Lua Parameter D (AV28)Default 0, range -32768 to 32767Command
AV29Lua Parameter E (AV29)Default 0, range -32768 to 32767Command
AV30Lua Parameter F (AV30)Default 0, range -32768 to 32767Command
AVmin39Occupied Heat SetpointDefault 72°F (22°C), range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AVmin40Occupied Cool SetpointDefault 75°F (24°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV41Standby Heat SetpointDefault 69°F (21°C), range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AV42Standby Cool SetpointDefault 78°F (21°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV43Unoccupied Heat SetpointDefault 62°F (17°C), range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AV44Unoccupied Cool SetpointDefault 80°F (27°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV45Default Heating SetpointDefault 72°F (22°C), range 65°F (18°C) to 80°F (27°C)°F/°CCommand
AV46Standby Temperature DifferentialDefault 4°F (2.0°C), range 1°F (0.5°C) to 5°F (2.5°C)Δ°F/Δ°CCommand
AV56Main PasswordDefault 0, range 0 to 9999Command
AV57User PasswordDefault 0, range 0 to 9999Command
AV58Heating Setpoint LimitDefault 90°F (32°C), range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AV59Cooling Setpoint LimitDefault 54°F (12°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV62Temporary Occupancy TimeDefault 2, range 0 to 24hCommand
AV63Minimum DeadbandDefault 3°F (1.5°C), range 2°F (1.0°C) to 5°F (2.5°C)Δ°F/Δ°CCommand
AV65Proportional BandDefault 3, range 3 to 10Command
AV67Standby TimeDefault 0.5, range 0.5 to 24hCommand
AV68Unoccupied TimeDefault 0, range 0 to 24hCommand
AV71Dehumidification SetpointDefault 50, range 30 to 95%RHCommand
AV72Dehumidification HysteresisDefault 5, range 2 to 20%RHCommand
AV74Calibrate Outside Temperature SensorDefault 0°F (0°C), range -5°F (-2.5°C) to 5°F (2.5°C)Δ°F/Δ°CCommand
AV75Number of Cooling StagesDefault 2, range 1 to 2Command
AV76Power-up DelayDefault 10, range 10 to 120sCommand
AV78Economizer Minimum PositionDefault 0, range 0 to 100%Command
AV81Economizer Maximum PositionDefault 100, range 0 to 100%Command
AV82High balance pointDefault 90°F (32°C), range 34°F (1°C) to 90°F (32°C)°F/°CCommand
AV83Low balance pointDefault -12°F (-24°C), range -40°F (-40°C) to 30°F (-1°C)°F/°CCommand
AV84Heating CPHDefault 4, range 3 to 8cycles/hCommand
AV85Cooling CPHDefault 4, range 3 to 4cycles/hCommand
AV86Anti Short Cycle TimeDefault 2, range 0 to 5minCommand
AV87Number of Heating StagesDefault 2, range 0 to 2Command
AV88Heating Demand LimitDefault 0, range 0 to 100%Command
AV89Cooling Demand LimitDefault 0, range 0 to 100%Command
AV91Heating Lockout from Outside Air TemperatureDefault 120°F (49°C), range -15°F (-26°C) to 120°F (49°C)°F/°CCommand
AV92Keyboard ValueDefault 0, range 0 to 35Command
AV93Cooling LockoutDefault -40°F (-40°C), range -40°F (-40°C) to 95°F (35°C)°F/°CCommand
AV94Supply Air SetpointDefault 55°F (13°C), range 50°F (10°C) to 90°F (32°C)°F/°CCommand
AV95Changeover SetpointDefault 55°F (13°C), range 14°F (10°C) to 70°F (21°C)°F/°CCommand
AV96Fresh Air Range Upper LimitDefault 0, range 0 to 20,000CFMCommand
AV97Minimum Supply HeatDefault 64°F (18°C), range 50°F (10°C) to 72°F (22°C)°F/°CCommand
AV98Supply Heat LockoutDefault 32°F (0°C), range -15°F (-26°C) to 120°F (49°C)°F/°CCommand
AV99Discharge High LimitDefault 120°F (49°C), range 70°F (21°C) to 150°F (65.5°C)°F/°CCommand
AVmin100Room TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 122°F (50°C)°F/°CCommand
AV101Outdoor TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV102UI22 Supply TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV103Room HumidityDefault 0, range 0 to 100%RHCommand
AV104UI19 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV105UI20 Remote TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV106CO2 LevelDefault 0, range 0 to 5000ppmCommand
AV107Airflow LevelDefault 0, range 0 to 20,000CFMCommand
AV108UI19 Analog InputDefault 0, range 0 to 10VCommand
AV109UI24 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV111UI16 Analog InputDefault 0, range 0 to 10VCommand
AV112UI17 Analog InputDefault 0, range 0 to 10VCommand
AV113UI20 Analog InputDefault 0, range 0 to 10VCommand
AV114UI22 Analog InputDefault 0, range 0 to 10VCommand
AV115UI23 Analog InputDefault 0, range 0 to 10VCommand
AV116UI24 Analog InputDefault 0, range 0 to 10VCommand
AV117UI16 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV118UI17 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV120UI20 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV121UI22 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV122UI23 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV125Mixed Air TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV202UI19 LuaDefault 0, range -32768 to 32767Command
AV203UI20 LuaDefault 0, range -32768 to 32767Command
AV204UI22 LuaDefault 0, range -32768 to 32767Command
AV205UI23 LuaDefault 0, range -32768 to 32767Command
AV206UI24 LuaDefault 0, range -32768 to 32767Command
AV209Ambient Low Temperature ThresholdDefault 40°F (4°C), range 32°F (0°C) to 50°F (10°C)°F/°CCommand
AV210Temperature Alarm HysteresisDefault 2°F (1°C), range 0°F (0°C) to 10°F (5.5°C)Δ°F/Δ°CCommand
AV211Load Shedding OffsetDefault 4°F (2°C), range 4°F (2°C) to 10°F (5.5°C)Δ°F/Δ°CCommand
AV225Lua Parameter G (AV225)Default 0, range -32768 to 32767Command
AV226Lua Parameter H (AV226)Default 0, range -32768 to 32767Command
AV227Lua Parameter I (AV227)Default 0, range -32768 to 32767Command
AV228Lua Parameter J (AV228)Default 0, range -32768 to 32767Command
AV229Lua Parameter K (AV229)Default 0, range -32768 to 32767Command
AV230Lua Parameter L (AV230)Default 0, range -32768 to 32767Command
AV270Standby Screen DelayDefault 150, range 5 to 300sCommand
AV275Ambient High Temperature ThresholdDefault 86°F (30°C), range 32°F (0°C) to 122°F (50°C)°F/°CCommand
AV276Refrigeration High Temperature ThresholdDefault 40°F (4°C), range 32°F (0°C) to 60°F (16°C)°F/°CCommand
AV277Refrigeration Low Temperature ThresholdDefault 32°F (0°C), range 32°F (0°C) to 50°F (10°C)°F/°CCommand
AV278Freezer High Temperature ThresholdDefault 0°F (-18°C), range -40°F (-40°C) to 32°F (0°C)°F/°CCommand
BI29UI16 Binary InputRead0=Activated, 1=Not Activated
BI30UI17 Binary InputRead0=Activated, 1=Not Activated
BI91UI19 Binary InputRead0=Activated, 1=Not Activated
BI94UI20 Binary InputRead0=Activated, 1=Not Activated
BI95UI22 Binary InputRead0=Activated, 1=Not Activated
BI96UI23 Binary InputRead0=Activated, 1=Not Activated
BI97UI24 Binary InputRead0=Activated, 1=Not Activated
BOmin25G Fan StatusDefault 0Command0=Off, 1=On
BO26Y1 StatusDefault 0Command0=Off, 1=On
BO27Y2 StatusDefault 0Command0=Off, 1=On
BO28W1 StatusDefault 0Command0=Off, 1=On
BO29W2/OB StatusDefault 0Command0=Off, 1=On
BO94UO10 Binary OutputDefault 0Command0=Off, 1=On
BO98BO1 Auxiliary Binary OutputDefault 0Command0=Off, 1=On
BO101UO11 Binary OutputDefault 0Command0=Off, 1=On
BO102UO12 Binary OutputDefault 0Command0=Off, 1=On
BV1Door Contact StatusDefault 0Command0=Closed, 1=Open
BV2Door Contact InstalledDefault 0Command0=No, 1=Yes
BV3Window Contact StatusDefault 0Command0=Closed, 1=Open
BV4Window Contact InstalledDefault 0Command0=No, 1=Yes
BV5Low Battery AlarmDefault 0Command0=Off, 1=On
BV6Force High BacklightDefault 0Command0=Off, 1=On
BV7Display Long Screen MessageDefault 0Command0=Off, 1=On
BV8Clock AlarmDefault 0Command0=Off, 1=On
BV10Exception StatusDefault 0Command0=Off, 1=On
BV32PIR Local MotionDefault 0Command0=No motion, 1=Motion
BV35Window AlarmDefault 0Command0=Off, 1=On
BV36Filter AlarmDefault 0Command0=Off, 1=On
BV37Service AlarmDefault 0Command0=Off, 1=On
BV38Dehumidification StatusDefault 0Command0=Off, 1=On
BVmin39Fan Lock AlarmDefault 0Command0=Off, 1=On
BV40Smart Recovery StatusDefault 0Command0=Off, 1=On
BV41CO2 AlarmDefault 0Command0=Off, 1=On
BV42Low Fresh Air AlarmDefault 0Command0=Off, 1=On
BV43Frost Protection AlarmDefault 0Command0=Off, 1=On
BV44Water LeakDefault 0Command0=Off, 1=On
BV45Water Leak Sensor InstalledDefault 0Command0=No, 1=Yes
BV46Water leak sensor statusDefault 0Command0=Normal, 1=Leak
BV47Low TemperatureDefault 0Command0=Off, 1=On
BV48Load Shedding DemandDefault 0Command0=Off, 1=On
BV49Load Shedding StatusDefault 0Command0=Off, 1=On
BV50Load Shedding OverrideDefault 0Command0=Off, 1=On
BV53High TemperatureDefault 0Command0=Off, 1=On
BV200ZigBee PIR Sensor InstalledDefault 0Command0=Off, 1=On
BV201ZigBee Sensor MotionDefault 0Command0=No motion, 1=Motion
CSV1Short Screen Message TextText, up to 26 charactersWrite
CSV2Long Screen Message TextText, up to 480 charactersWrite
CSV3External Memory RevisionTextWrite
CSV4Wi-Fi Device NameTextWrite
CSV5Wi-Fi Firmware VersionTextWrite
CSV6MAC AddressTextWrite
CSV7Wi-Fi Network SSIDTextWrite
CSV8Wi-Fi Network IP AddressTextWrite
CSV9ZigBee Firmware RevisionTextWrite
CSV10Zigbee IEEE AddressTextWrite
CSV11Wireless Device 1 - AddressTextWrite
CSV12Wireless Device 2 - AddressTextWrite
CSV13Wireless Device 3 - AddressTextWrite
CSV14Wireless Device 4 - AddressTextWrite
CSV15Wireless Device 5 - AddressTextWrite
CSV16Wireless Device 6 - AddressTextWrite
CSV17Wireless Device 7 - AddressTextWrite
CSV18Wireless Device 8 - AddressTextWrite
CSV19Wireless Device 9 - AddressTextWrite
CSV20Wireless Device 10 - AddressTextWrite
CSV21Wireless Device 11 - AddressTextWrite
CSV22Wireless Device 12 - AddressTextWrite
CSV23Wireless Device 13 - AddressTextWrite
CSV24Wireless Device 14 - AddressTextWrite
CSV25Wireless Device 15 - AddressTextWrite
CSV26Wireless Device 16 - AddressTextWrite
CSV27Wireless Device 17 - AddressTextWrite
CSV28Wireless Device 18 - AddressTextWrite
CSV29Wireless Device 19 - AddressTextWrite
CSV30Wireless Device 20 - AddressTextWrite
MI2ZigBee Network StatusRead1=Not det., 2=Pwr on, 3=No NWK, 4=Joined, 5=Online
MImin33Effective OccupancyRead1=Occupied, 2=Unoccupied, 3=Override, 4=Standby
MI180Wireless Device 1 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI181Wireless Device 2 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI182Wireless Device 3 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI183Wireless Device 4 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI184Wireless Device 5 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI185Wireless Device 6 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI186Wireless Device 7 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI187Wireless Device 8 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI188Wireless Device 9 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI189Wireless Device 10 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI190Wireless Device 11 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI191Wireless Device 12 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI192Wireless Device 13 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI193Wireless Device 14 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI194Wireless Device 15 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI195Wireless Device 16 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI196Wireless Device 17 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI197Wireless Device 18 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI198Wireless Device 19 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI199Wireless Device 20 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI210Wireless Device 1 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI211Wireless Device 1 - BatteryRead1=None, 2=Normal, 3=Low
MI212Wireless Device 1 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI220Wireless Device 2 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI221Wireless Device 2 - BatteryRead1=None, 2=Normal, 3=Low
MI222Wireless Device 2 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI230Wireless Device 3 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI231Wireless Device 3 - BatteryRead1=None, 2=Normal, 3=Low
MI232Wireless Device 3 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI240Wireless Device 4 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI241Wireless Device 4 - BatteryRead1=None, 2=Normal, 3=Low
MI242Wireless Device 4 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI250Wireless Device 5 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI251Wireless Device 5 - BatteryRead1=None, 2=Normal, 3=Low
MI252Wireless Device 5 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI260Wireless Device 6 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI261Wireless Device 6 - BatteryRead1=None, 2=Normal, 3=Low
MI262Wireless Device 6 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI270Wireless Device 7 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI271Wireless Device 7 - BatteryRead1=None, 2=Normal, 3=Low
MI272Wireless Device 7 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI280Wireless Device 8 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI281Wireless Device 8 - BatteryRead1=None, 2=Normal, 3=Low
MI282Wireless Device 8 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI290Wireless Device 9 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI291Wireless Device 9 - BatteryRead1=None, 2=Normal, 3=Low
MI292Wireless Device 9 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI300Wireless Device 10 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI301Wireless Device 10 - BatteryRead1=None, 2=Normal, 3=Low
MI302Wireless Device 10 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI309Effective Temperature SensorRead1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20
MI310Wireless Device 11 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI311Wireless Device 11 - BatteryRead1=None, 2=Normal, 3=Low
MI312Wireless Device 11 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI313Effective Relative Humidity SensorRead1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20
MI314Effective System ModeRead1=Cool, 2=Heat
MI315Wi-Fi Module StatusRead1=Offline, 2=Initializing, 3=Ready, 4=Booting, 5=Resetting, 6=Fail, 7=Testing
MI316Wi-Fi StatusRead1=Idle, 2=Associate, 3=Config., 4=Ready, 5=Online, 6=Disconn., 7=Failure
MI317BACnet IP StatusRead1=Disabled, 2=Enabled
MI318SMTP Server StatusRead1=Unkown, 2=Disabled, 3=Offline, 4=Online
MI319Facility Expert EnabledRead1=Disabled, 2=Enabled
MI320Wireless Device 12 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI321Wireless Device 12 - BatteryRead1=None, 2=Normal, 3=Low
MI322Wireless Device 12 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI323Facility Expert StatusRead1=Disabled, 2=Offline, 3=Connect., 4=Online, 5=Failure, 6=Unknown
MI324CO2 Effective SourceRead1=None, 2=Internal, 3=Error, 4=Wired, 5=WL 1, 6=WL 2, 7=WL 3, 8=WL 4, 9=WL 5, 10=WL 6, 11=WL 7, 12=WL 8, 13=WL 9, 14=WL 10, 15=WL 11, 16=WL 12, 17=WL 13, 18=WL 14, 19=WL 15, 20=WL 16, 21=WL 17, 22=WL 18, 23=WL 19, 24=WL 20
MI325Time sourceRead1=None, 2=Local, 3=BACnet, 4=NTP, 5=Cloud
MI326Fan Speed StatusRead1=Off, 2=Low, 3=Medium, 4=High
MI330Wireless Device 13 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI331Wireless Device 13 - BatteryRead1=None, 2=Normal, 3=Low
MI332Wireless Device 13 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI340Wireless Device 14 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI341Wireless Device 14 - BatteryRead1=None, 2=Normal, 3=Low
MI342Wireless Device 14 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI350Wireless Device 15 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI351Wireless Device 15 - BatteryRead1=None, 2=Normal, 3=Low
MI352Wireless Device 15 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI360Wireless Device 16 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI361Wireless Device 16 - BatteryRead1=None, 2=Normal, 3=Low
MI362Wireless Device 16 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI370Wireless Device 17 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI371Wireless Device 17 - BatteryRead1=None, 2=Normal, 3=Low
MI372Wireless Device 17 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI380Wireless Device 18 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI381Wireless Device 18 - BatteryRead1=None, 2=Normal, 3=Low
MI382Wireless Device 18 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI390Wireless Device 19 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI391Wireless Device 19 - BatteryRead1=None, 2=Normal, 3=Low
MI392Wireless Device 19 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI400Wireless Device 20 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI401Wireless Device 20 - BatteryRead1=None, 2=Normal, 3=Low
MI402Wireless Device 20 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MV1Long Message Background ColorDefault 1Command1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black, 11=Default
MV2HMI ColorDefault 1Command1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black
MV3Main DisplayDefault 1Command1=Temperature, 2=Setpoint
MV4Display LanguageDefault 1Command1=English, 2=French, 3=Spanish, 4=Chinese, 5=Russian, 6=Arabic, 7=Bulgarian, 8=Czech, 9=Danish, 10=Dutch, 11=Finnish, 12=German, 13=Hungarian, 14=Indonesian, 15=Italian, 16=Norwegian, 17=Polish, 18=Portuguese, 19=Slovak, 20=Swedish, 21=Turkish, 22=Japanese, 23=Hebrew
MV5Time FormatDefault 1Command1=AM-PM, 2=24 Hours
MV6Network UnitsDefault 1Command1=SI, 2=Imperial
MV7Network LanguageDefault 1Command1=English, 2=French, 3=Spanish
MV8BACnet Baud RateDefault 7Command1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto
MVmin10Occupancy CommandDefault 2Command1=Loc. occ, 2=Occupied, 3=Unocc.
MV11Standby Mode ConfigurationDefault 1Command1=Absolute, 2=Offset
MV12Fan DelayDefault 2Command1=Off, 2=On
MV13Dehumidification LockoutDefault 1Command1=Disabled, 2=Enabled
MVmin16System ModeDefault 4Command1=Off, 2=Auto, 3=Cool, 4=Heat
MVmin17Fan ModeDefault 2Command1=On, 2=Auto, 3=Smart
MV32Use Standby ScreenDefault 1Command1=No, 2=Yes, 3=Occ. only, 4=Screen sav
MV46UI16 ConfigurationDefault 1Command1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window, 6=Fan lock
MV47UI17 ConfigurationDefault 1Command1=None, 2=Door dry, 3=Override, 4=Filter, 5=Service
MV49UI19 ConfigurationDefault 1Command1=None, 2=CO2
MV51Temperature ScaleDefault 1Command1=°C, 2=°F
MV55Frost ProtectionDefault 1Command1=Off, 2=On
MV58Setpoint FunctionDefault 2Command1=Dual SP, 2=Attach SP
MV70Room Humidity DisplayDefault 1Command1=Disabled, 2=Enabled
MV71Enable Smart RecoveryDefault 1Command1=Off, 2=On
MV72Economizer ConfigurationDefault 1Command1=Off, 2=On
MV73Schedule MenuDefault 2Command1=Disabled, 2=Enabled, 3=Dis. no. clk., 4=En. no. clk.
MV79Mechanical Cooling AllowedDefault 1Command1=Off, 2=On
MV92BO1 Auxiliary Output ConfigurationDefault 1Command1=NO, 2=NC
MV95Fan Control in Heating ModeDefault 2Command1=Off, 2=On
MV96UO9 ConfigurationDefault 4Command1=Analog, 2=Binary, 3=Relay RC, 4=Relay RH
MV97UO10 ConfigurationDefault 1Command1=Analog, 2=Binary, 3=Relay RC
MV98UO11 ConfigurationDefault 1Command1=Analog, 2=Binary
MV99UO12 ConfigurationDefault 2Command1=Analog, 2=Binary
MV101FrenchDefault 2Command1=Disabled, 2=Enabled
MV102SpanishDefault 2Command1=Disabled, 2=Enabled
MV103ChineseDefault 2Command1=Disabled, 2=Enabled
MV104RussianDefault 2Command1=Disabled, 2=Enabled
MV110Occupancy SourceDefault 1Command1=Motion, 2=Schedule, 3=Mot. occ., 4=Mot. unoc.
MV111Mode ButtonDefault 1Command1=Normal, 2=Off-Auto
MVmin112Control StatusDefault 1Command1=Off, 2=Cool, 3=Heat
MV114Custom button iconDefault 1Command1=Default Button, 2=No Button, 3=System Mode Heat/Cool, 4=System Mode On/Off, 5=Fan mode, 6=Override Button, 7=Units Button, 8=Help Button, 9=Language Button, 10=Schedule Button, 11=Lighting Button, 12=Blind Button, 13=Lamp Button, 14=Energy Button, 15=Make Room Button, 16=Setting Button, 17=Timer Button
MV115Custom button behaviorDefault 1Command1=Default function, 2=No function, 3=System mode function, 4=Fan function, 5=Override function, 6=Schedule function, 7=Units function, 8=Help function, 9=Language function, 10=Configuration function, 11=Custom function, 12=Standby function
MV116Comfort or economy modeDefault 1Command1=Comfort, 2=Economy
MV117Reversing valve operationDefault 1Command1=O, 2=B
MV118Compressor - auxiliary interlockDefault 1Command1=Off, 2=On
MV119ApplicationDefault 1Command1=Rooftop, 2=Heatpump
MV120ArabicDefault 1Command1=Disabled, 2=Enabled
MV122CzechDefault 1Command1=Disabled, 2=Enabled
MV123DanishDefault 1Command1=Disabled, 2=Enabled
MV124DutchDefault 1Command1=Disabled, 2=Enabled
MV125FinnishDefault 1Command1=Disabled, 2=Enabled
MV126GermanDefault 1Command1=Disabled, 2=Enabled
MV127HungarianDefault 1Command1=Disabled, 2=Enabled
MV128IndonesianDefault 1Command1=Disabled, 2=Enabled
MV129ItalianDefault 1Command1=Disabled, 2=Enabled
MV130NorwegianDefault 1Command1=Disabled, 2=Enabled
MV131PolishDefault 1Command1=Disabled, 2=Enabled
MV132PortugueseDefault 1Command1=Disabled, 2=Enabled
MV133SlovakDefault 1Command1=Disabled, 2=Enabled
MV134SwedishDefault 1Command1=Disabled, 2=Enabled
MV135TurkishDefault 1Command1=Disabled, 2=Enabled
MV136Schedule TypeDefault 1Command1=7 days, 2=5 + 2 days, 3=5 + 1 + 1 days
MV138UI16 Input TypeDefault 2Command1=Therm., 2=Binary, 3=Voltage
MV139UI17 Input TypeDefault 2Command1=Therm., 2=Binary, 3=Voltage
MV140UI19 Input TypeDefault 3Command1=Therm., 2=Binary, 3=Voltage
MV141UI20 Input TypeDefault 1Command1=Therm., 2=Binary, 3=Voltage
MV142UI22 Input TypeDefault 1Command1=Therm., 2=Binary, 3=Voltage
MV143UI23 Input TypeDefault 1Command1=Therm., 2=Binary, 3=Voltage
MV144UI24 Input TypeDefault 3Command1=Therm., 2=Binary, 3=Voltage
MV145Room Temperature SensorDefault 1Command1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20
MV146CO2 DisplayDefault 2Command1=Disabled, 2=Enabled
MV147CO2 AutocalibrationDefault 2Command1=Disabled, 2=Enabled
MV148Lock ScreenDefault 1Command1=No, 2=Yes
MV149Relative humidity sensorDefault 2Command1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20
MV150CO2 sourceDefault 2Command1=None, 2=Local, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20
MV151Temperature Alarm EnabledDefault 1Command1=Off, 2=On
MV152ADR PermissionDefault 1Command1=Off, 2=On
MV155JapaneseDefault 1Command1=Disabled, 2=Enabled
MV156HebrewDefault 1Command1=Disabled, 2=Enabled
MV180Display the Fan Status iconDefault 2Command1=Disabled, 2=Enabled
MV181Display the System Status iconDefault 2Command1=Disabled, 2=Enabled
MV182Display the Help buttonDefault 2Command1=Disabled, 2=Enabled
MV185UI20 ConfigurationDefault 2Command1=None, 2=RS, 3=MAT
MV210Wireless Device 1 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV220Wireless Device 2 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV230Wireless Device 3 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV240Wireless Device 4 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV250Wireless Device 5 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV260Wireless Device 6 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV270Wireless Device 7 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV280Wireless Device 8 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV290Wireless Device 9 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV300Wireless Device 10 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV310Wireless Device 11 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV320Wireless Device 12 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV330Wireless Device 13 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV340Wireless Device 14 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV350Wireless Device 15 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV360Wireless Device 16 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV370Wireless Device 17 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV380Wireless Device 18 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV390Wireless Device 19 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV400Wireless Device 20 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
FILE1Custom Lua FileLua script file (read/write the custom script)Write
Other1Lua Program 1Monitors and controls the Lua script programWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VT8650 Rooftop Unit and Heat Pump Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Viconics VT8650 Rooftop Unit and Heat Pump Controller

How many BACnet points does the Viconics VT8650 Rooftop Unit and Heat Pump Controller have?

This list has 456 BACnet objects: 75 analog inputs, 8 analog outputs, 100 analog values, 7 binary inputs, 9 binary outputs, 29 binary values, 1 file, 94 multi-state inputs, 102 multi-state values, 30 characterstring values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet points are writable?

280 of the 456 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet documentation?

The source is VT8650 BACnet Integration Guide - Roof Top Unit (RTU), Heat Pump and Indoor Air Quality (IAQ) - Firmware Revision 2.6 (028-0437-07_IG-VT8650-BNET_A4_EN (Version 7)), revision 2022-07, published free by Viconics at https://www.veris.com/ASSETS/DOCUMENTS/CMS/EN/Static_Documents/DownloadCenter/028-0437-07_IG-VT8650-2.6-BNET_A4_EN_RH20220708.pdf.

What are the minimum BACnet points to integrate the Viconics VT8650 Rooftop Unit and Heat Pump Controller?

Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode: on / auto / smart); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); BO 25 G Fan Status (Fan (G) output state); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 39 Fan Lock Alarm (Fan lock alarm (1 = on)).

How do I enable BMS control of the Viconics VT8650 Rooftop Unit and Heat Pump Controller?

No enable switch is needed. The BMS writes MV 10 Occupancy Command (1 = Loc. occ, the controller decides locally; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.

Can the BMS supply sensor values to the Viconics VT8650 Rooftop Unit and Heat Pump Controller?

The guide has no BMS-written room temperature object: MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.

How do I check these points on the real VT8650 Rooftop Unit and Heat Pump Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Viconics BACnet points lists

Source: VT8650 BACnet Integration Guide - Roof Top Unit (RTU), Heat Pump and Indoor Air Quality (IAQ) - Firmware Revision 2.6 · 028-0437-07_IG-VT8650-BNET_A4_EN (Version 7) · rev. 2022-07. Object names, instances and units are reproduced as published; descriptions are our own.