Networked room controller (thermostat) · BACnet points list

Viconics TRCVT 3.0 Room Controller BACnet points list

Updated 28 October 2026

Short answer

Viconics TRC room controllers are wall thermostats that run fan coil (TRC3500) or rooftop / heat pump (TRC6500) sequences and expose them as a BACnet application-specific controller on BACnet MS/TP or BACnet IP. One object list covers all models; each object is marked for all models, wireless models only, or one of the two model families. Besides HVAC control the list has lighting and blind commands, demand-response (ADR) points, Zigbee wireless sensor data and Lua script variables.

This page lists 593 BACnet objects for the Viconics TRCVT 3.0 Room Controller — 438 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Viconics’s own free documentation, linked below.

Manufacturer
Viconics
Model
TRCVT 3.0 Room Controller
Equipment
Networked room controller (thermostat)
Equipment type
Thermostats, sensors & meters
BACnet objects
593 (438 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
3.0
Also known as
TRCVT, TRC3500, TRC6500, TRCn500nnnn-VC, Viconics Room Controller
Source document
Viconics Room Controller TRCn500nnnn-VC BACnet Integration Guide, Firmware Revision 3.0 · 998-23139903-5_EN · rev. 2026-09
Download CSV 593 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Viconics TRCVT 3.0 Room Controller

Integration in brief

Set the COM address (AV 10) and baud rate (MV 8) for BACnet MS/TP, or the IP settings for BACnet IP. The BMS then writes Occupancy Command (MV 10), System Mode (MV 16), Fan Mode (MV 17) and the occupied setpoints (AV 39, AV 40), and reads Room Temperature (AV 100), Effective Occupancy (MI 33), Control Status (MV 112) and the alarm BVs. Write live commands at priorities 4-16; priorities 1-3 lock the value in EEPROM.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10Occupancy CommandBMS occupancy: local, occupied or unoccupiedCommand
MV 16System ModeOff / auto / cool / heatCommand
MV 17Fan ModeFan mode; states differ on TRC3500 and TRC6500Command
AV 39Occupied Heat SetpointOccupied heating setpointCommand
AV 40Occupied Cool SetpointOccupied cooling setpointCommand
MV 112Control StatusCurrent state: off, cooling or heatingCommand
MI 326Fan Speed StatusFan speed status: off / low / medium / highRead
MI 33Effective OccupancyActual occupancy stateRead
AV 100Room TemperatureSpace temperature used for controlCommand
BV 37Service AlarmService alarm from an input set to ServiceCommand

Enable & remote start

There is no separate enable point. Occupancy Command (MV 10) selects local occupancy, occupied or unoccupied; in local mode the controller follows its Occupancy Source (MV 110: motion, schedule or both). System Mode (MV 16) and Fan Mode (MV 17) act directly.

Sensors & values from the BMS

The guide lists no BACnet-written room temperature input. Room Temperature Sensor (MV 150) selects the wired, internal or one of 20 wireless sensors; humidity (MV 154) and CO2 (MV 155) have similar source selectors.

Network setup

Watch out for

Viconics TRCVT 3.0 Room Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

593 of 593 shown
Type
Access
Show
Viconics TRCVT 3.0 Room Controller BACnet Points List
DescriptionStates
AI1UI1 Raw ValueRange 0 to 4095, default 0.Read
AI2UI2 Raw ValueRange 0 to 4095, default 0.Read
AI3UI3 Raw ValueRange 0 to 4095, default 0.Read
AI4UI4 Raw ValueRange 0 to 4095, default 0.Read
AI5UI5 Raw ValueRange 0 to 4095, default 0.Read
AI6UI6 Raw ValueRange 0 to 4095, default 0.Read
AI7UI7 Raw ValueRange 0 to 4095, default 0.Read
AI8UI8 Raw ValueRange 0 to 4095, default 0.Read
AI20Light Sensor LevelRange 0 to 30000, default 0.Read
AI32RH Temperature Raw ValueRange -40 to 180 °F, default -40 °F.°FRead
AI40Relative Humidity Raw ValueRange 0 to 100 % RH, default 0 % RH.% RHRead
AI315Wireless Device 1 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI316Wireless Device 2 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI317Wireless Device 3 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI318Wireless Device 4 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI319Wireless Device 5 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI320Wireless Device 6 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI321Wireless Device 7 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI322Wireless Device 8 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI323Wireless Device 9 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI324Wireless Device 10 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI329Effective SetpointHeating or cooling setpoint currently in effect°FRead
AI330Paired ZigBee DevicesRange 0 to 20, default 0. Wireless models only.Read
AI342WiFi Network Signal Strength PercentageRange 0 to 100 %, default 0 %. Wireless models only.%Read
AI355Wireless Device 11 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI356Wireless Device 12 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI357Wireless Device 13 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI358Wireless Device 14 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI359Wireless Device 15 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI360Wireless Device 16 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI361Wireless Device 17 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI362Wireless Device 18 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI363Wireless Device 19 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI364Wireless Device 20 - TemperatureRange -40 to 185 °F, default -40 °F. Wireless models only.°FRead
AI365Wireless Device 1 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI366Wireless Device 2 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI367Wireless Device 3 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI368Wireless Device 4 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI369Wireless Device 5 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI370Wireless Device 6 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI371Wireless Device 7 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI372Wireless Device 8 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI373Wireless Device 9 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI374Wireless Device 10 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI375Wireless Device 11 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI376Wireless Device 12 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI377Wireless Device 13 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI378Wireless Device 14 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI379Wireless Device 15 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI380Wireless Device 16 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI381Wireless Device 17 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI382Wireless Device 18 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI383Wireless Device 19 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI384Wireless Device 20 - HumidityRange 0 to 100 % RH, default 0 % RH. Wireless models only.% RHRead
AI385Wireless Device 1 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI386Wireless Device 2 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI387Wireless Device 3 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI388Wireless Device 4 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI389Wireless Device 5 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI390Wireless Device 6 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI391Wireless Device 7 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI392Wireless Device 8 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI393Wireless Device 9 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI394Wireless Device 10 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI395Wireless Device 11 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI396Wireless Device 12 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI397Wireless Device 13 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI398Wireless Device 14 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI399Wireless Device 15 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI400Wireless Device 16 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI401Wireless Device 17 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI402Wireless Device 18 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI403Wireless Device 19 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI404Wireless Device 20 - CO2Range 0 to 5000 ppm, default 0 ppm. Wireless models only.ppmRead
AI405WiFi ChannelRange 0 to 165, default 0. Wireless models only.Read
AO21PI Heating DemandRange 0 to 100 %, default 0 %.%Command
AO22PI Cooling DemandRange 0 to 100 %, default 0 %.%Command
AO23Economizer DemandRange 0 to 100 %, default 0 %. TRC6500 (rooftop / heat pump) only.%Command
AO24Analog Output Heat DemandRange 0 to 100 %, default 0 %. TRC6500 (rooftop / heat pump) only.%Command
AO101AO1 VoltageRange 0 to 10 V, default 0 V.VCommand
AO102AO2 VoltageRange 0 to 10 V, default 0 V.VCommand
AO103AO3 VoltageRange 0 to 10 V, default 0 V.VCommand
AO104AO4 VoltageRange 0 to 10 V, default 0 V.VCommand
AV3Low BacklightRange 0 to 100 %, default 60 %.%Command
AV4Night BacklightRange 0 to 100 %, default 5 %.%Command
AV5Purge Sample PeriodRange 0 to 4 h, default 2 h. TRC3500 (fan coil) only.hCommand
AV6Purge OpenRange 1 to 3 min, default 2 min. TRC3500 (fan coil) only.minCommand
AV7Calibrate Room Temperature SensorRange -5 to 5 Δ°F, default 0 Δ°F.Δ°FCommand
AV8Calibrate Humidity SensorRange -15 to 15 % RH, default 0 % RH.% RHCommand
AV10COM AddressNetwork COM address (BACnet or Modbus), 0 to 254, default 254Command
AV16BACnet Stack Poll RateRange 1 to 5, default 1.Command
AV20Supply Temperature Low LimitRange 35 to 65 °F, default 45 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV21Minimum Fresh AirRange 0 to 20000 cfm, default 0 cfm. TRC6500 (rooftop / heat pump) only.cfmCommand
AV22Maximum Fresh AirRange 0 to 20000 cfm, default 0 cfm. TRC6500 (rooftop / heat pump) only.cfmCommand
AV23Minimum CO2Range 0 to 4800 ppm, default 800 ppm. TRC6500 (rooftop / heat pump) only.ppmCommand
AV24Maximum CO2Range 200 to 5000 ppm, default 1200 ppm.ppmCommand
AV25Lua Parameter A (AV25)Range -32768 to 32767, default 0.Command
AV26Lua Parameter B (AV26)Range -32768 to 32767, default 0.Command
AV27Lua Parameter C (AV27)Range -32768 to 32767, default 0.Command
AV28Lua Parameter D (AV28)Range -32768 to 32767, default 0.Command
AV29Lua Parameter E (AV29)Range -32768 to 32767, default 0.Command
AV30Lua Parameter F (AV30)Range -32768 to 32767, default 0.Command
AV31Lua Parameter G (AV31)Range -32768 to 32767, default 0.Command
AV32Lua Parameter H (AV32)Range -32768 to 32767, default 0.Command
AV33Lua Parameter I (AV33)Range -32768 to 32767, default 0.Command
AV34Lua Parameter J (AV34)Range -32768 to 32767, default 0.Command
AV35Lua Parameter K (AV35)Range -32768 to 32767, default 0.Command
AV36Lua Parameter L (AV36)Range -32768 to 32767, default 0.Command
AVmin39Occupied Heat SetpointRange 40 to 90 °F, default 72 °F.°FCommand
AVmin40Occupied Cool SetpointRange 54 to 100 °F, default 75 °F.°FCommand
AV41Standby Heat SetpointRange 40 to 90 °F, default 69 °F.°FCommand
AV42Standby Cool SetpointRange 54 to 100 °F, default 78 °F.°FCommand
AV43Unoccupied Heat SetpointRange 40 to 90 °F, default 62 °F.°FCommand
AV44Unoccupied Cool SetpointRange 54 to 100 °F, default 80 °F.°FCommand
AV45Default Cooling SetpointRange 54 to 100 °F, default 75 °F.°FCommand
AV46Standby Temperature DifferentialRange 1 to 5 Δ°F, default 4 Δ°F.Δ°FCommand
AV47Default Heating SetpointRange 40 to 90 °F, default 72 °F.°FCommand
AV52Number of PipesPipes: 0 (reheat only), 2 or 4; default 2. TRC3500 (fan coil) only.Command
AV58Maximum Heating Setpoint LimitRange 40 to 90 °F, default 77 °F.°FCommand
AV59Minimum Cooling Setpoint LimitRange 54 to 100 °F, default 68 °F.°FCommand
AV60Minimum Occupied Heating Setpoint LimitRange 40 to 90 °F, default 65 °F.°FCommand
AV61Maximum Occupied Cooling Setpoint LimitRange 54 to 100 °F, default 80 °F.°FCommand
AV62Temporary Occupancy TimeRange 0 to 24 h, default 2 h.hCommand
AV63Minimum DeadbandRange 2 to 5 Δ°F, default 3 Δ°F.Δ°FCommand
AV65Proportional BandRange 3 to 10 Δ°F, default 3 Δ°F.Δ°FCommand
AV67Standby TimeRange 0.5 to 24 h, default 0.5 h.hCommand
AV68Unoccupied TimeRange 0 to 24 h, default 0 h.hCommand
AV71Dehumidification SetpointRange 30 to 95 % RH, default 50 % RH.% RHCommand
AV72Dehumidification HysteresisRange 2 to 20 % RH, default 5 % RH.% RHCommand
AV73Dehumidification Max Cooling LimitRange 20 to 100 %, default 100 %. TRC3500 (fan coil) only.%Command
AV74Calibrate Outside Temperature SensorRange -5 to 5 Δ°F, default 0 Δ°F.Δ°FCommand
AV75Number of Cooling StagesCooling stages: 0 = modulating, 1 or 2; default 2. TRC6500 (rooftop / heat pump) only.Command
AV76Power-up DelayRange 10 to 120 s, default 10 s.sCommand
AV78Economizer Minimum PositionRange 0 to 99 %, default 0 %. TRC6500 (rooftop / heat pump) only.%Command
AV81Economizer Maximum PositionRange 1 to 100 %, default 100 %. TRC6500 (rooftop / heat pump) only.%Command
AV82High balance pointRange 34 to 90 °F, default 90 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV83Low balance pointRange -40 to 30 °F, default -12 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV84Heating CPHRange 3 to 8, default 4.Command
AV85Cooling CPHRange 3 to 8 (TRC3500) or 3 to 4 (TRC6500), default 4.Command
AV86Anti Short Cycle TimeRange 0 to 5 min, default 2 min. TRC6500 (rooftop / heat pump) only.minCommand
AV87Number of Heating StagesHeating stages: 0 = modulating, 1 or 2; default 2. TRC6500 (rooftop / heat pump) only.Command
AV88Heating Demand LimitRange 0 to 100 %, default 100 %.%Command
AV89Cooling Demand LimitRange 0 to 100 %, default 100 %.%Command
AV90Floating Actuator TimeRange 0.5 to 9 min, default 1.5 min. TRC3500 (fan coil) only.minCommand
AV91Heating Lockout from Outside Air TemperatureRange -15 to 120 °F, default 120 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV93Cooling LockoutRange -40 to 95 °F, default -40 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV94Supply Air Temperature SetpointRange 50 to 90 °F, default 55 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV95Changeover SetpointRange 14 to 70 °F, default 55 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV96Fresh Air Range Upper LimitRange 0 to 20000 cfm, default 0 cfm. TRC6500 (rooftop / heat pump) only.cfmCommand
AV97Minimum Supply HeatRange 50 to 72 °F, default 64 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV98Supply Heat LockoutRange -15 to 120 °F, default 32 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AV99Supply Temperature High LimitRange 70 to 150 °F, default 120 °F. TRC6500 (rooftop / heat pump) only.°FCommand
AVmin100Room TemperatureRoom temperature used for control°FCommand
AV101Outdoor TemperatureOutdoor air temperature°FCommand
AV102Supply TemperatureSupply air temperature°FCommand
AV103Room HumidityRoom relative humidity% RHCommand
AV104Changeover TemperatureRange -40 to 180 °F, default -40 °F. TRC3500 (fan coil) only.°FCommand
AV105Wired Temperature SensorRange -40 to 180 °F, default -40 °F.°FCommand
AV106CO2 LevelRoom CO2 levelppmCommand
AV107Airflow LevelRange 0 to 20000 cfm, default 0 cfm.cfmCommand
AV111UI1 VoltageRange 0 to 10 V, default 0 V.VCommand
AV112UI2 VoltageRange 0 to 10 V, default 0 V.VCommand
AV113UI3 VoltageRange 0 to 10 V, default 0 V.VCommand
AV114UI4 VoltageRange 0 to 10 V, default 0 V.VCommand
AV115UI5 VoltageRange 0 to 10 V, default 0 V.VCommand
AV116UI6 VoltageRange 0 to 10 V, default 0 V.VCommand
AV117UI7 VoltageRange 0 to 10 V, default 0 V.VCommand
AV118UI8 VoltageRange 0 to 10 V, default 0 V.VCommand
AV121UI1 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV122UI2 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV123UI3 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV124UI4 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV125UI5 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV126UI6 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV127UI7 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV128UI8 TemperatureRange -40 to 180 °F, default -40 °F.°FCommand
AV212ECM Fan Low VoltageRange 0.0 to 9.8 V (TRC3500) or 0.0 to 9.9 V (TRC6500), default 2.2 V.VCommand
AV213ECM Fan Medium VoltageRange 0.1 to 9.9 V, default 6 V. TRC3500 (fan coil) only.VCommand
AV214ECM Fan High VoltageRange 0.2 to 10 V (TRC3500) or 0.1 to 10 V (TRC6500), default 8.6 V.VCommand
AV231Inactivity TimeRange 1 to 10 min, default 3 min.minCommand
AV232Backlight BrightnessRange 0 to 100 %, default 60 %.%Command
AV233Halo Red ColorRange 0 to 255, default 0. Wireless models only.Command
AV234Halo Green ColorRange 0 to 255, default 0. Wireless models only.Command
AV235Halo Blue ColorRange 0 to 255, default 0. Wireless models only.Command
AV236Halo Maximum BrightnessRange 0 to 100 %, default 100 %. Wireless models only.%Command
AV280ADR Setpoint Offset - Load SheddingRange 1 to 10 Δ°F, default 4 Δ°F.Δ°FCommand
AV281ADR Setpoint Offset - PricingRange 1 to 10 Δ°F, default 4 Δ°F.Δ°FCommand
AV283Timezone OffsetRange -1440 to 1440 min, default 0 min.minCommand
AV284Light 1 StatusRange 0 to 201, default 0.Command
AV285Light 2 StatusRange 0 to 201, default 0.Command
AV286Light 3 StatusRange 0 to 201, default 0.Command
AV287Light 4 StatusRange 0 to 201, default 0.Command
AV288Light 5 StatusRange 0 to 201, default 0.Command
AV289Light 6 StatusRange 0 to 201, default 0.Command
AV290Light 7 StatusRange 0 to 201, default 0.Command
AV291Light 8 StatusRange 0 to 201, default 0.Command
AV292Blind 1 StatusRange 0 to 201, default 0.Command
AV293Blind 2 StatusRange 0 to 201, default 0.Command
AV294Blind 3 StatusRange 0 to 201, default 0.Command
AV295Blind 4 StatusRange 0 to 201, default 0.Command
AV296Blind 5 StatusRange 0 to 201, default 0.Command
AV297Blind 6 StatusRange 0 to 201, default 0.Command
AV298Blind 7 StatusRange 0 to 201, default 0.Command
AV299Blind 8 StatusRange 0 to 201, default 0.Command
AV300Light 1 CmdRange 0 to 201, default 0.Command
AV301Light 2 CmdRange 0 to 201, default 0.Command
AV302Light 3 CmdRange 0 to 201, default 0.Command
AV303Light 4 CmdRange 0 to 201, default 0.Command
AV304Light 5 CmdRange 0 to 201, default 0.Command
AV305Light 6 CmdRange 0 to 201, default 0.Command
AV306Light 7 CmdRange 0 to 201, default 0.Command
AV307Light 8 CmdRange 0 to 201, default 0.Command
AV308Blind 1 CmdRange 0 to 201, default 0.Command
AV309Blind 2 CmdRange 0 to 201, default 0.Command
AV310Blind 3 CmdRange 0 to 201, default 0.Command
AV311Blind 4 CmdRange 0 to 201, default 0.Command
AV312Blind 5 CmdRange 0 to 201, default 0.Command
AV313Blind 6 CmdRange 0 to 201, default 0.Command
AV314Blind 7 CmdRange 0 to 201, default 0.Command
AV315Blind 8 CmdRange 0 to 201, default 0.Command
AV316Light 1 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV317Light 2 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV318Light 3 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV319Light 4 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV320Light 5 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV321Light 6 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV322Light 7 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV323Light 8 CfgCommand0=Non dimmable, Disabled; 1=Non dimmable, Enabled; 2=Dimmable, Disabled; 3=Dimmable, Enabled
AV324Blind 1 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV325Blind 2 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV326Blind 3 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV327Blind 4 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV328Blind 5 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV329Blind 6 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV330Blind 7 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV331Blind 8 CfgRange 0=Disabled, 1=Enabled, default 0=Disabled.Command
AV332Lua Parameter M (AV332)Range -32768 to 32767, default 0.Command
AV333Lua Parameter N (AV333)Range -32768 to 32767, default 0.Command
AV334Lua Parameter O (AV334)Range -32768 to 32767, default 0.Command
AV335Lua Parameter P (AV335)Range -32768 to 32767, default 0.Command
AV336Lua Parameter Q (AV336)Range -32768 to 32767, default 0.Command
AV337Lua Parameter R (AV337)Range -32768 to 32767, default 0.Command
AV338Lua Scratchpad 1Range -32768 to 32767, default 0.Command
AV339Lua Scratchpad 2Range -32768 to 32767, default 0.Command
AV340Lua Scratchpad 3Range -32768 to 32767, default 0.Command
AV341Lua Scratchpad 4Range -32768 to 32767, default 0.Command
AV342Lua Scratchpad 5Range -32768 to 32767, default 0.Command
AV343Lua Scratchpad 6Range -32768 to 32767, default 0.Command
AV344Lua Scratchpad 7Range -32768 to 32767, default 0.Command
AV345Lua Scratchpad 8Range -32768 to 32767, default 0.Command
AV346Lua Scratchpad 9Range -32768 to 32767, default 0.Command
AV347Lua Scratchpad 10Range -32768 to 32767, default 0.Command
AV348Lua Scratchpad 11Range -32768 to 32767, default 0.Command
AV349Lua Scratchpad 12Range -32768 to 32767, default 0.Command
AV350Lua Scratchpad 13Range -32768 to 32767, default 0.Command
AV351Lua Scratchpad 14Range -32768 to 32767, default 0.Command
AV352Lua Scratchpad 15Range -32768 to 32767, default 0.Command
AV353Lua Scratchpad 16Range -32768 to 32767, default 0.Command
AV354Lua Scratchpad 17Range -32768 to 32767, default 0.Command
AV355Lua Scratchpad 18Range -32768 to 32767, default 0.Command
AV365Fan Pre-occupancy Purge DurationRange 0 to 240 min, default 60 min.minCommand
AV366Optimal Start DurationRange 15 to 240 min, default 90 min.minCommand
AV367Optimal Stop DurationRange 5 to 120 min, default 45 min.minCommand
BI1UI1 BinaryRead0=Activated, 1=Not activ.
BI2UI2 BinaryRead0=Activated, 1=Not activ.
BI3UI3 BinaryRead0=Activated, 1=Not activ.
BI4UI4 BinaryRead0=Activated, 1=Not activ.
BI5UI5 BinaryRead0=Activated, 1=Not activ.
BI6UI6 BinaryRead0=Activated, 1=Not activ.
BI7UI7 BinaryRead0=Activated, 1=Not activ.
BI8UI8 BinaryRead0=Activated, 1=Not activ.
BO1DO1 Binary OutputCommand0=Off, 1=On
BO2DO2 Binary OutputCommand0=Off, 1=On
BO3DO3 Binary OutputCommand0=Off, 1=On
BO4DO4 Binary OutputCommand0=Off, 1=On
BO5DO5 Binary OutputCommand0=Off, 1=On
BO6DO6 Binary OutputCommand0=Off, 1=On
BO7DO7 Binary OutputCommand0=Off, 1=On
BO8DO8 Binary OutputCommand0=Off, 1=On
BO9DO9 Binary OutputCommand0=Off, 1=On
BV1Door Contact StatusCommand0=Closed, 1=Opened
BV2Door Contact InstalledCommand0=No, 1=Yes
BV3Window Contact StatusCommand0=Closed, 1=Opened
BV4Window Contact InstalledCommand0=No, 1=Yes
BV5Low Battery AlarmWireless models only.Command0=Off, 1=On
BV8Clock AlarmCommand0=Off, 1=On
BV10Exception StatusCommand0=Off, 1=On
BV11AI Eco Schedule WarningCommand0=Off, 1=On
BV12AI Eco Setpoint WarningCommand0=Off, 1=On
BV13AI Eco Dehumidification WarningCommand0=Off, 1=On
BV20Optimal Start StatusCommand0=Off, 1=On
BV21Optimal Stop StatusCommand0=Off, 1=On
BV32PIR Local MotionCommand0=No motion, 1=Motion
BV33PIR Local ProximityWireless models only.Command0=No proximity, 1=Proximity
BV34Overheat Protection AlarmCommand0=Off, 1=On
BV35Window AlarmCommand0=Off, 1=On
BV36Filter AlarmCommand0=Off, 1=On
BVmin37Service AlarmCommand0=Off, 1=On
BV38Dehumidification StatusCommand0=Off, 1=On
BV39Fan Lock Off AlarmCommand0=Off, 1=On
BV41CO2 AlarmCommand0=Off, 1=On
BV42Low Fresh Air AlarmTRC6500 (rooftop / heat pump) only.Command0=Off, 1=On
BV43Frost Protection AlarmCommand0=Off, 1=On
BV44Water Leak AlarmCommand0=Off, 1=On
BV45Water Leak Sensor InstalledCommand0=No, 1=Yes
BV46Water Leak Sensor StatusCommand0=Normal, 1=Leak
BV49Fan Lock On AlarmCommand0=Off, 1=On
BV50Wireless Sensor Communication AlarmWireless models only.Command0=Off, 1=On
BV51Condensate Leak AlarmCommand0=Off, 1=On
BV60Changeover Purge StatusTRC3500 (fan coil) only.Command0=Off, 1=On
BV61Fan Pre-occupancy Purge StatusCommand0=Off, 1=On
BV80ADR Utility Signal - Load SheddingDemand-response load-shed signalCommand0=Off, 1=On
BV81ADR Status - Load SheddingCommand0=Off, 1=On
BV82ADR Override - Load SheddingCommand0=Off, 1=On
BV83ADR Utility Signal - PricingDemand-response pricing signalCommand0=Off, 1=On
BV84ADR Status - PricingCommand0=Off, 1=On
BV85ADR Override - PricingCommand0=Off, 1=On
BV200ZigBee Motion Sensor InstalledWireless models only.Command0=Off, 1=On
BV201ZigBee Sensor MotionWireless models only.Command0=No motion, 1=Motion
BV202Incompatible Base AlarmCommand0=Off, 1=On
BV203CO2 Calibration WarningCommand0=Off, 1=On
CSV1Short Screen Message TextMessage text shown on the screenWrite
CSV4WiFi Device NameText, 0 to 63 characters. Wireless models only.Write
CSV5WiFi Firmware VersionText, 0 to 63 characters. Wireless models only.Write
CSV6MAC AddressText, 0 to 18 characters.Write
CSV7WiFi Network SSIDText, 0 to 33 characters. Wireless models only.Write
CSV10ZigBee IEEE AddressText, 0 to 18 characters. Wireless models only.Write
CSV11Wireless Device 1 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV12Wireless Device 2 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV13Wireless Device 3 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV14Wireless Device 4 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV15Wireless Device 5 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV16Wireless Device 6 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV17Wireless Device 7 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV18Wireless Device 8 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV19Wireless Device 9 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV20Wireless Device 10 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV21Wireless Device 11 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV22Wireless Device 12 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV23Wireless Device 13 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV24Wireless Device 14 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV25Wireless Device 15 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV26Wireless Device 16 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV27Wireless Device 17 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV28Wireless Device 18 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV29Wireless Device 19 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV30Wireless Device 20 - AddressText, 0 to 18 characters. Wireless models only.Write
CSV31Active User IdText, 0 to 33 characters.Write
CSV35LocationText, 0 to 49 characters.Write
CSV36Install CodeText, 0 to 46 characters.Write
CSV40TimezoneText, 0 to 32 characters.Write
CSV41Custom Standby Heading TextText, 0 to 65 characters.Write
CSV42Custom Standby Body TextText, 0 to 161 characters.Write
CSV43WiFi Country CodeText, 0 to 64 characters. Wireless models only.Write
CSV44Light 1 Short Display NameText, 0 to 31 characters.Write
CSV45Light 2 Short Display NameText, 0 to 31 characters.Write
CSV46Light 3 Short Display NameText, 0 to 31 characters.Write
CSV47Light 4 Short Display NameText, 0 to 31 characters.Write
CSV48Light 5 Short Display NameText, 0 to 31 characters.Write
CSV49Light 6 Short Display NameText, 0 to 31 characters.Write
CSV50Light 7 Short Display NameText, 0 to 31 characters.Write
CSV51Light 8 Short Display NameText, 0 to 31 characters.Write
CSV52Blind 1 Short Display NameText, 0 to 31 characters.Write
CSV53Blind 2 Short Display NameText, 0 to 31 characters.Write
CSV54Blind 3 Short Display NameText, 0 to 31 characters.Write
CSV55Blind 4 Short Display NameText, 0 to 31 characters.Write
CSV56Blind 5 Short Display NameText, 0 to 31 characters.Write
CSV57Blind 6 Short Display NameText, 0 to 31 characters.Write
CSV58Blind 7 Short Display NameText, 0 to 31 characters.Write
CSV59Blind 8 Short Display NameText, 0 to 31 characters.Write
CSV60AI Model WeightsText, 0 to 257 characters.Write
CSV61AI Model VersionText, 0 to 16 characters.Write
CSV62Alerts TitleText, 0 to 33 characters.Write
CSV63Alerts DescriptionText, 0 to 134 characters.Write
CSV66Light 1 Long Display NameText, 0 to 31 characters.Write
CSV67Light 2 Long Display NameText, 0 to 31 characters.Write
CSV68Light 3 Long Display NameText, 0 to 31 characters.Write
CSV69Light 4 Long Display NameText, 0 to 31 characters.Write
CSV70Light 5 Long Display NameText, 0 to 31 characters.Write
CSV71Light 6 Long Display NameText, 0 to 31 characters.Write
CSV72Light 7 Long Display NameText, 0 to 31 characters.Write
CSV73Light 8 Long Display NameText, 0 to 31 characters.Write
CSV74Blind 1 Long Display NameText, 0 to 31 characters.Write
CSV75Blind 2 Long Display NameText, 0 to 31 characters.Write
CSV76Blind 3 Long Display NameText, 0 to 31 characters.Write
CSV77Blind 4 Long Display NameText, 0 to 31 characters.Write
CSV78Blind 5 Long Display NameText, 0 to 31 characters.Write
CSV79Blind 6 Long Display NameText, 0 to 31 characters.Write
CSV80Blind 7 Long Display NameText, 0 to 31 characters.Write
CSV81Blind 8 Long Display NameText, 0 to 31 characters.Write
MI2ZigBee Network StatusWireless models only.Read1=Disabled, 2=Initializing, 3=Upgrading, 4=Searching, 5=Joining, 6=Forming, 7=Resuming, 8=Online, 9=Failed
MImin33Effective OccupancyOccupancy state in effectRead1=Occupied, 2=Unoccupied, 3=Temp. Occupancy, 4=Standby
MI210Wireless Device 1 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI211Wireless Device 1 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI212Wireless Device 1 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI220Wireless Device 2 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI221Wireless Device 2 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI222Wireless Device 2 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI230Wireless Device 3 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI231Wireless Device 3 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI232Wireless Device 3 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI240Wireless Device 4 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI241Wireless Device 4 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI242Wireless Device 4 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI250Wireless Device 5 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI251Wireless Device 5 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI252Wireless Device 5 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI260Wireless Device 6 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI261Wireless Device 6 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI262Wireless Device 6 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI270Wireless Device 7 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI271Wireless Device 7 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI272Wireless Device 7 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI280Wireless Device 8 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI281Wireless Device 8 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI282Wireless Device 8 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI290Wireless Device 9 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI291Wireless Device 9 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI292Wireless Device 9 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI300Wireless Device 10 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI301Wireless Device 10 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI302Wireless Device 10 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI309Effective temperature sensorRead1=Wired, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MI310Wireless Device 11 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI311Wireless Device 11 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI312Wireless Device 11 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI313Effective relative humidity sensorRead1=None, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MI314Effective System ModeEffective heat or cool modeRead1=Cool, 2=Heat
MI315IP StatusRead1=Offline, 2=Initializing, 3=Ready, 4=Booting, 5=Resetting, 6=Fail, 7=Testing
MI316WiFi Network StatusWireless models only.Read1=Offline, 2=Associate, 3=Online, 4=Failure
MI320Wireless Device 12 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI321Wireless Device 12 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI322Wireless Device 12 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI324CO2 Effective SourceRead1=None, 2=Expansion Module, 3=Error, 4=Wired, 5=Wireless Sensor 1, 6=Wireless Sensor 2, 7=Wireless Sensor 3, 8=Wireless Sensor 4, 9=Wireless Sensor 5, 10=Wireless Sensor 6, 11=Wireless Sensor 7, 12=Wireless Sensor 8, 13=Wireless Sensor 9, 14=Wireless Sensor 10, 15=Wireless Sensor 11, 16=Wireless Sensor 12, 17=Wireless Sensor 13, 18=Wireless Sensor 14, 19=Wireless Sensor 15, 20=Wireless Sensor 16, 21=Wireless Sensor 17, 22=Wireless Sensor 18, 23=Wireless Sensor 19, 24=Wireless Sensor 20
MI325Time sourceRead1=None, 2=Local, 3=BACnet, 4=NTP, 5=Cloud
MImin326Fan Speed StatusCurrent fan speedRead1=Off, 2=Low, 3=Medium, 4=High
MI327WiFi Network Signal StrengthWireless models only.Read1=Poor, 2=Fair, 3=Good, 4=Excellent
MI330Wireless Device 13 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI331Wireless Device 13 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI332Wireless Device 13 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI340Wireless Device 14 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI341Wireless Device 14 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI342Wireless Device 14 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI350Wireless Device 15 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI351Wireless Device 15 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI352Wireless Device 15 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI360Wireless Device 16 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI361Wireless Device 16 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI362Wireless Device 16 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI370Wireless Device 17 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI371Wireless Device 17 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI372Wireless Device 17 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI380Wireless Device 18 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI381Wireless Device 18 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI382Wireless Device 18 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI390Wireless Device 19 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI391Wireless Device 19 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI392Wireless Device 19 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI400Wireless Device 20 - StatusWireless models only.Read1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI401Wireless Device 20 - BatteryWireless models only.Read1=None, 2=Normal, 3=Low
MI402Wireless Device 20 - Communication StatusWireless models only.Read1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI406WiFi BandWireless models only.Read1=None, 2=5 GHz, 3=2.4 GHz
MV2Color ThemeCommand1=Light, 2=Dark
MV3HMI Main Display ValueCommand1=None, 2=Temperature
MV4Display LanguageCommand1=English, 2=French, 3=Spanish, 4=Chinese, 5=Russian, 6=Arabic, 7=Danish, 8=Italian, 9=German, 10=Indonesian, 11=Polish, 12=Swedish, 13=Norwegian, 14=Finnish, 15=Hungarian, 16=Turkish, 17=Dutch, 18=Czech, 19=Portuguese, 20=Bulgarian, 21=Slovak, 22=Japanese, 23=Hebrew, 24=Korean
MV5Time FormatCommand1=12 Hour (AM-PM), 2=24 Hour
MV6Network UnitsUnits used on the networkCommand1=SI, 2=Imperial
MV8BACnet Baud RateMS/TP baud rateCommand1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto
MVmin10Occupancy CommandOccupancy command (local, occupied, unoccupied)Command1=Loc occ., 2=Occupied, 3=Unocc.
MV11Standby Mode ConfigurationCommand1=Absolute, 2=Offset
MV12Fan DelayTRC6500 (rooftop / heat pump) only.Command1=Off, 2=On
MV13Dehumidification EnabledCommand1=Disabled, 2=Enabled
MV14Standby FanCommand1=Auto, 2=Follow occupied
MV15Sequence of OperationTRC3500 (fan coil) only.Command1=Cooling Only, 2=Heating Only, 3=Reheat Only, 4=Cooling/Heating, 5=Cooling/Reheat, 6=Heating/Reheat, 7=Cooling/Heating/Reheat
MVmin16System ModeSystem mode commandCommand1=Off, 2=Auto, 3=Cool, 4=Heat
MVmin17Fan ModeFan mode command; states differ by modelCommandTRC3500: 1=On, 2=Auto, 3=Smart, 4=Low, 5=Medium, 6=High; TRC6500: 1=On, 2=Auto
MV32Use Standby ScreenCommand1=Disabled, 2=Custom Image, 3=Default
MV46UI1 ConfigurationCommand1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window, 6=Fan Status
MV47UI2 ConfigurationCommand1=None, 2=Door dry, 3=Temp. Occupancy, 4=Filter, 5=Service
MV49UI3 ConfigurationCommandTRC3500: 1=None, 2=CO2, 3=COC/NH, 4=COC/NC, 5=COS, 6=Condensate Leak; TRC6500: 1=None, 2=CO2, 6=Condensate Leak
MV51Temperature ScaleCommand1=°C, 2=°F
MV55Frost ProtectionCommand1=Off, 2=On
MV56Overheat ProtectionCommand1=Off, 2=On
MV57Fan SequenceTRC3500 (fan coil) only.Command1=Auto, 2=Smart, 3=Auto-Smart, 4=Speeds-Auto, 5=Speeds-Smart, 6=Speeds-Auto-Smart
MV58Setpoint FunctionCommand1=Dual SP, 2=Attach SP
MV70Optimal StopCommand1=Off, 2=Fixed Duration, 3=Based on outdoor temp.
MV71Optimal StartCommand1=Off, 2=Fixed Duration, 3=Based on outdoor temp.
MV72Economizer ConfigurationTRC6500 (rooftop / heat pump) only.Command1=Off, 2=On
MV79Mechanical Cooling AllowedTRC6500 (rooftop / heat pump) only.Command1=Off, 2=On
MV81Valve 1 TypeTRC3500 (fan coil) only.Command1=On/Off, 2=Floating, 3=0-10V Direct Acting, 4=0-10V Reverse Acting
MV82Valve 2 TypeTRC3500 (fan coil) only.Command1=On/Off, 2=Floating, 3=0-10V Direct Acting, 4=0-10V Reverse Acting
MV91Reheat Time BaseTRC3500 (fan coil) only.Command1=On/Off (4 CPH), 2=PWM (10s Duty Cycle)
MV92Auxiliary Output / BO1 Auxiliary Output ConfigurationNamed Auxiliary Output on TRC3500, BO1 Auxiliary Output Configuration on TRC6500CommandTRC3500: 1=Reheat (Normally Open), 2=Occupancy (Normally Open), 3=Occupancy (Normally Closed), 4=Aux Fan (Normally Open), 5=Aux Fan (Normally Closed), 6=Reheat (Normally Closed); TRC6500: 1=NO, 2=NC
MV95Fan Control in Heating ModeCommandTRC3500: 1=Enabled, 2=Forced Off-Auto/Smart, 3=Forced Off-All Modes; TRC6500: 1=Off, 2=On
MV96DO6-AO1 ConfigurationCommand1=Analog, 2=Binary RC, 3=Binary RH
MV97DO7-AO2 ConfigurationCommand1=Analog, 2=Binary RC
MV98DO8-AO3 ConfigurationCommand1=Analog, 2=Binary RC
MV99DO9-AO4 ConfigurationCommand1=Analog, 2=Binary RC
MV101FrenchEnables French in the language selection listCommand1=Disabled, 2=Enabled
MV102SpanishEnables Spanish in the language selection listCommand1=Disabled, 2=Enabled
MV103ChineseEnables Chinese in the language selection listCommand1=Disabled, 2=Enabled
MV104RussianEnables Russian in the language selection listCommand1=Disabled, 2=Enabled
MV110Occupancy SourceCommand1=Motion, 2=Schedule, 3=Motion during Schedule, 4=Motion or Schedule
MVmin112Control StatusCurrent control state: off, cooling or heatingCommand1=Off, 2=Cool, 3=Heat
MV116Comfort or economy modeTRC6500 (rooftop / heat pump) only.Command1=Comfort, 2=Economy
MV117Reversing valve operationTRC6500 (rooftop / heat pump) only.Command1=O, 2=B
MV118Compressor - auxiliary interlockTRC6500 (rooftop / heat pump) only.Command1=Off, 2=On
MV119ApplicationApplication: fan coil, rooftop or heat pumpCommandTRC3500: 3=FCU; TRC6500: 1=Rooftop Unit, 2=Heat Pump
MV120ArabicEnables Arabic in the language selection listCommand1=Disabled, 2=Enabled
MV122CzechEnables Czech in the language selection listCommand1=Disabled, 2=Enabled
MV123DanishEnables Danish in the language selection listCommand1=Disabled, 2=Enabled
MV124DutchEnables Dutch in the language selection listCommand1=Disabled, 2=Enabled
MV125FinnishEnables Finnish in the language selection listCommand1=Disabled, 2=Enabled
MV126GermanEnables German in the language selection listCommand1=Disabled, 2=Enabled
MV127HungarianEnables Hungarian in the language selection listCommand1=Disabled, 2=Enabled
MV128IndonesianEnables Indonesian in the language selection listCommand1=Disabled, 2=Enabled
MV129ItalianEnables Italian in the language selection listCommand1=Disabled, 2=Enabled
MV130NorwegianEnables Norwegian in the language selection listCommand1=Disabled, 2=Enabled
MV131PolishEnables Polish in the language selection listCommand1=Disabled, 2=Enabled
MV132PortugueseEnables Portuguese in the language selection listCommand1=Disabled, 2=Enabled
MV133SlovakEnables Slovak in the language selection listCommand1=Disabled, 2=Enabled
MV134SwedishEnables Swedish in the language selection listCommand1=Disabled, 2=Enabled
MV135TurkishEnables Turkish in the language selection listCommand1=Disabled, 2=Enabled
MV136Schedule TypeCommand1=7 days, 2=5+2 days, 3=5+1+1 day
MV137Schedule ModeCommand1=None, 2=Occupancy, 3=Event Based
MV141UI1 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV142UI2 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV143UI3 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV144UI4 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV145UI5 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV146UI6 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV147UI7 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV148UI8 TypeCommand1=Therm., 2=Binary, 3=Voltage
MV150Room Temperature SensorSelects which sensor supplies room temperatureCommand1=Wired, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MV154Relative humidity sensorCommand1=None, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MV155CO2 sourceCommand1=None, 2=Local, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MV157ADR PermissionCommand1=Disabled, 2=Enabled
MV158Fan TypeCommandTRC3500: 1=1 Speed (H), 2=2 Speed (L-H), 3=3 Speed (L-M-H), 4=ECM; TRC6500: 1=1 Speed, 4=Variable Frequency Drive
MV159JapaneseEnables Japanese in the language selection listCommand1=Disabled, 2=Enabled
MV160HebrewEnables Hebrew in the language selection listCommand1=Disabled, 2=Enabled
MV161KoreanEnables Korean in the language selection listCommand1=Disabled, 2=Enabled
MV183Enable Static IPCommand1=Dynamic, 2=Static
MV184Enable WIFIWireless models only.Command1=Disabled, 2=Enabled
MV185Hidden WIFIWireless models only.Command1=Disabled, 2=Enabled
MV186Notification TypeCommand1=Disabled, 2=Critical, 3=Warning, 4=Ok, 5=Informative
MV187Notification Display TypeCommand1=Disabled, 2=Custom Only, 3=All
MV188Occupancy SensorCommand1=Off, 2=Low, 3=Medium, 4=High
MV189Proximity SensorWireless models only.Command1=Off, 2=Low, 3=Medium, 4=High
MV190Custom Standby Text ColorCommand1=White, 2=Black
MV192HMI SetpointCommand1=None, 2=Slider, 3=Buttons (Attached SP Only)
MV193Remote Device AccessCommand1=Disabled, 2=Enabled
MV194Halo ModeWireless models only.Command1=Disabled, 2=Heat/Cool
MV195Button 1Command1=Disabled, 2=System Mode, 3=Fan Mode, 4=AI Eco Mode, 5=Do Not Disturb, 6=Make Up Room, 7=Temp. Occupancy
MV196Button 2Command1=Disabled, 2=System Mode, 3=Fan Mode, 4=AI Eco Mode, 5=Do Not Disturb, 6=Make Up Room, 7=Temp. Occupancy
MV197Button 3Command1=Disabled, 2=System Mode, 3=Fan Mode, 4=AI Eco Mode, 5=Do Not Disturb, 6=Make Up Room, 7=Temp. Occupancy
MV198Button 4Command1=Disabled, 2=System Mode, 3=Fan Mode, 4=AI Eco Mode, 5=Do Not Disturb, 6=Make Up Room, 7=Temp. Occupancy
MV200Info Item 1Command1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 (PPM), 5=CO2 (Text)
MV201Info Item 2Command1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 (PPM), 5=CO2 (Text)
MV202Info Item 3Command1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 (PPM), 5=CO2 (Text)
MV205Default SetpointsCommand1=Disabled, 2=Enabled
MV206WiFi Security TypeWireless models only.Command1=WPA2 AES PSK, 2=WPA2 TKIP PSK, 3=WPA2 MIXED PSK, 4=WPA3 SAE, 5=WPA3 WPA2 PSK, 6=UNKNOWN SECURITY
MV207BBMD StatusCommand1=Offline, 2=DNS Lookup, 3=DNS Fail, 4=Registering, 5=Registered, 6=Registration Failed
MV210Wireless Device 1 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV211Enable AI Eco Setpoint ControlCommand1=Disabled, 2=Enabled
MV212AI Eco ModeCommand1=Disabled, 2=Enabled
MV213AI Eco Optimal SetpointCommand1=Disabled, 2=Enabled
MV214AI Eco Optimal StartCommand1=Disabled, 2=Enabled
MV215AI Eco Optimal StopCommand1=Disabled, 2=Enabled
MV216AI Eco Verbose LoggingCommand1=Disabled, 2=Enabled
MV217Alerts ModeCommand1=Disabled, 2=Critical, 3=Warning, 4=Informative, 5=All Clear
MV218Do Not DisturbCommand1=Off, 2=On
MV219Make Up RoomCommand1=Off, 2=On
MV220Wireless Device 2 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV230Wireless Device 3 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV240Wireless Device 4 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV250Wireless Device 5 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV260Wireless Device 6 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV270Wireless Device 7 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV280Wireless Device 8 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV290Wireless Device 9 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV300Wireless Device 10 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV310Wireless Device 11 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV320Wireless Device 12 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV330Wireless Device 13 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV340Wireless Device 14 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV350Wireless Device 15 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV360Wireless Device 16 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV370Wireless Device 17 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV380Wireless Device 18 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV390Wireless Device 19 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV400Wireless Device 20 - FunctionWireless models only.Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
FILE1Custom Lua FileLua script file; can also be loaded over USBWrite
Other1Lua Program 1Program object that runs and monitors the Lua scriptWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TRCVT 3.0 Room Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Viconics TRCVT 3.0 Room Controller

How many BACnet points does the Viconics TRCVT 3.0 Room Controller have?

This list has 593 BACnet objects: 75 analog inputs, 8 analog outputs, 180 analog values, 8 binary inputs, 9 binary outputs, 41 binary values, 1 file, 72 multi-state inputs, 129 multi-state values, 69 characterstring values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Viconics TRCVT 3.0 Room Controller BACnet points are writable?

438 of the 593 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Viconics TRCVT 3.0 Room Controller BACnet documentation?

The source is Viconics Room Controller TRCn500nnnn-VC BACnet Integration Guide, Firmware Revision 3.0 (998-23139903-5_EN), revision 2026-09, published free by Viconics at https://www.veris.com/ASSETS/DOCUMENTS/CMS/EN/Static_Documents/DownloadCenter/998-23139903-5_TRCVT-3.0-BACnet-Integration-Guide_EN_RH20260908.pdf.

What are the minimum BACnet points to integrate the Viconics TRCVT 3.0 Room Controller?

Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode; states differ on TRC3500 and TRC6500); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); MI 326 Fan Speed Status (Fan speed status: off / low / medium / high); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 37 Service Alarm (Service alarm from an input set to Service).

How do I enable BMS control of the Viconics TRCVT 3.0 Room Controller?

There is no separate enable point. Occupancy Command (MV 10) selects local occupancy, occupied or unoccupied; in local mode the controller follows its Occupancy Source (MV 110: motion, schedule or both). System Mode (MV 16) and Fan Mode (MV 17) act directly.

Can the BMS supply sensor values to the Viconics TRCVT 3.0 Room Controller?

The guide lists no BACnet-written room temperature input. Room Temperature Sensor (MV 150) selects the wired, internal or one of 20 wireless sensors; humidity (MV 154) and CO2 (MV 155) have similar source selectors.

How do I check these points on the real TRCVT 3.0 Room Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Viconics BACnet points lists

Source: Viconics Room Controller TRCn500nnnn-VC BACnet Integration Guide, Firmware Revision 3.0 · 998-23139903-5_EN · rev. 2026-09. Object names, instances and units are reproduced as published; descriptions are our own.