Viconics VT7200 / VT7300 Series PIR-Ready Thermostats BACnet points list

Updated 28 October 2026

Short answer

Viconics VT7200 and VT73xx thermostats join a BACnet MS/TP trunk through a plug-in communication module and act as BACnet application-specific controllers. One object list covers the VT7200 zoning models, the VT73xx fan coil models and the VTR73xx models, which add their own configuration and valve status objects (instances 81-95). The thermostats do not support COV, so the BMS must poll them.

This page lists 87 BACnet objects for the Viconics VT7200 / VT7300 Series PIR-Ready Thermostats — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Viconics’s own free documentation, linked below.

Manufacturer
Viconics
Model
VT7200 / VT7300 Series PIR-Ready Thermostats
Equipment
Networked room thermostat
Equipment type
Thermostats, sensors & meters
BACnet objects
87 (58 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
72000 + MAC (VT7200), 73000 + MAC (VT73xx)
Also known as
VT7200, VT7300, VT7305, VT7350, VT7355, VTR7300, VTR7305, VTR7350, VTR7355, VT72xx, VT73xx
Source document
PIR Ready VT72xx & VT(R)73xx Series BACnet Integration Manual · 028-6009 R11 (ITG-VT(R) 72_73-BAC-E11) · rev. 2012-02-07
Download CSV 87 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Viconics VT7200 / VT7300 Series PIR-Ready Thermostats

Integration in brief

Give each thermostat a MAC address from 0 to 127 (the factory 254 leaves BACnet off) and let it auto-baud. The BMS writes Occupancy Command (MV 18), System Mode (MV 16), Fan Mode (MV 17) and the setpoints, and reads Room Temperature (AV 7), Effective Occupancy (MV 33), Fan Status (MV 28) and the alarm inputs. Poll no faster than every 5 seconds, since there is no COV.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 18Occupancy CommandBMS occupancy: local, occupied or unoccupiedWrite
MV 16System ModeOff / auto / cool / heatWrite
MV 17Fan ModeFan mode; states set by Fan Mode Sequence (MV 57)Write
AV 39Occupied Heat SetpointOccupied heating setpointWrite
AV 40Occupied Cool SetpointOccupied cooling setpointWrite
MV 28Fan StatusFan speed status: off / low / medium / highRead
MV 33Effective OccupancyActual occupancy stateRead
AV 7Room TemperatureSpace temperature used for controlWrite
BI 37Service AlarmService alarm from an input set to ServiceRead

Enable & remote start

There is no separate enable point. Occupancy Command (MV 18) selects local occupancy, occupied or unoccupied; System Mode (MV 16) and Fan Mode (MV 17) act directly.

Heartbeat & communication loss

No heartbeat point. If the thermostat goes offline, the room temperature, outdoor temperature and occupancy values written over the network are released.

Sensors & values from the BMS

Room Temperature (AV 7) can be written only after Room Temp Override (BV 8) is set to Override; Room Humidity (AV 10) needs Room Humid Override (BV 11) the same way. Outdoor Temperature (AV 9) is writable and is one of the global values the guide shows a BMS sending to all thermostats.

Network setup

Watch out for

Viconics VT7200 / VT7300 Series PIR-Ready Thermostats BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

87 of 87 shown
Type
Multi-stateOther
Access
Show
Viconics VT7200 / VT7300 Series PIR-Ready Thermostats BACnet Points List
DescriptionStates
AVmin7Room TemperatureRoom temperature; writable only when BV 8 = Override°FWrite
BV8Room Temp OverrideEnables writing AV 7 from the networkWrite0=Normal, 1=Override
AV9Outdoor TemperatureOutdoor temperature; can be written from the BMS°FWrite
AV10Room Humidity / A02 ECM ValueRoom RH on humidity models; A02 ECM value (0-100 %) on others%Write
BV11Room Humid OverrideEnables writing room humidity from the networkWrite0=Normal, 1=Override
AI12Supply TemperatureSupply air temperature, if a sensor is fitted°FRead
BV13Dehumidification LockoutWrite0=Disabled, 1=Enabled
BV14AUX CommandAuxiliary output commandWrite0=Off, 1=On
MV15Sequence of OperationWrite1=Cooling Only, 2=Heating Only, 3=Cooling & Reheat, 4=Heating & Reheat, 5=Cool/Heat4P, 6=Cool/Heat4P&Reht
MVmin16System ModeAvailable states depend on MV 15Write1=Off, 2=Auto, 3=Cool, 4=Heat
MVmin17Fan ModeFan mode command; state list follows Fan Mode SequenceWriteSet by MV 57: Low-Med-High, Low-High, with Auto, or On-Auto
MVmin18Occupancy CommandWrite1=Local Occupancy, 2=Occupied, 3=Unoccupied
MV19Keypad LockoutWrite1=Level 0, 2=Level 1, 3=Level 2, 4=Level 3, 5=Level 4, 6=Level 5
Other20Control OutputGroup object (bundle of related points)Read
AV21PI Heating Demand%Read
AV22PI Cooling Demand%Read
BI23Dehumidification StatusRead0=Off, 1=On
Other24Controller StatusGroup object (bundle of related points)Read
BI25AUX StatusRead0=Off, 1=On
MV26Output 2Name and states depend on BV 75 and MV 52Read1=Closed, 2=Open (on/off) or 1=Stopped, 2=Opening, 3=Closing (floating)
MV27Output 1Name and states depend on BV 75 and MV 52Read1=Closed, 2=Open (on/off) or 1=Stopped, 2=Opening, 3=Closing (floating)
MVmin28Fan StatusRead1=Off, 2=Low, 3=Med, 4=High
BI29BI 1 StatusRead0=Deactivated, 1=Activated
BI30BI 2 StatusRead0=Deactivated, 1=Activated
BI31UI 3 StatusFollows UI 3 configuration (MV 48)Read0=Deactivated, 1=Activated
BI32Local MotionPIR motion detectedRead0=No Motion, 1=Motion
MVmin33Effective OccupancyRead1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Stand-by
Other34Controller AlarmsGroup object (bundle of related points)Read
BI35Window AlarmRead0=Off, 1=On
BI36Filter AlarmRead0=Off, 1=On
BImin37Service AlarmRead0=Off, 1=On
Other38Temperature SetpointsGroup object (bundle of related points)Read
AVmin39Occupied Heat SetpointRange 40 to 90 °F, default 72 °F.°FWrite
AVmin40Occupied Cool SetpointRange 54 to 100 °F, default 74 °F.°FWrite
AV41Stand-by Heat SetpointRange 40 to 90 °F, default 72 °F.°FWrite
AV42Stand-by Cool SetpointRange 54 to 100 °F, default 74 °F.°FWrite
AV43Unoccupied Heat SetpointRange 40 to 90 °F, default 62 °F.°FWrite
AV44Unoccupied Cool SetpointRange 54 to 100 °F, default 80 °F.°FWrite
Other45General Options 1Group object (bundle of related points)Read
MV46BI 1 ConfigurationWrite1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window
MV47BI 2 ConfigurationWrite1=None, 2=Door Dry, 3=Override, 4=Filter, 5=Service
MV48UI 3 configurationWrite1=None, 2=COC/NH, 3=COC/NC, 4=COS, 5=SS
BV49Menu ScrollWrite0=No Scroll, 1=Scroll Active
BV50Auto Mode EnableWrite0=Disabled, 1=Enabled
BV51Temperature ScaleWrite0=°C, 1=°F
MV52Pipe NumberWrite1=2 Pipe, 2=4 Pipe
MV53Out#1 ConfigWrite1=2, 2=4
MV54AUX ConfigurationWrite1=Not used, 2=NO with Occ, 3=NC with Occ, 4=NO with Occ & Fan, 5=NC with Occ & Fan, 6=Network controlled
Other55General Options 2Group object (bundle of related points)Read
AV56Password ValueRange 0 to 1000. Read-only on VTR models.Write
MV57Fan Mode SequenceShown as MV 58 in part of the guideWrite1=Low-Med-High, 2=Low-High, 3=Low-Med-High-Auto, 4=Low-High-Auto, 5=On-Auto
AV58Heating Setpoint LimitRange 40 to 90 °F, default 90 °F.°FWrite
AV59Cooling Setpoint LimitRange 54 to 100 °F, default 54 °F.°FWrite
BV60Setpoint TypeWrite0=Permanent, 1=Temporary
BV61Setpoint FunctionWrite0=Dual Setpoints, 1=Attached Setpoints
MV62Temporary Occupancy TimeDefault 2 hoursWrite1=0 hour ... 25=24 hours (1-hour steps)
AV63DeadbandRange 2 to 5 °F, default 2 °F.°FWrite
BV64Reheat Time BaseWrite0=15 minutes, 1=10 seconds
MV65Proportional BandWrite1=3 °F, 2=4 °F, 3=5 °F, 4=6 °F, 5=7 °F, 6=8 °F, 7=9 °F, 8=10 °F
BV66Auto FanWrite0=Auto Speed, 1=Auto Speed / Auto Demand
AV67Stand-by TimeRange 0.5 to 24 h, default 0.5 h.hWrite
AV68Unoccupied TimeRange 0 to 24 h, default 0 h.hWrite
Other69Humidity Models Config OptionsGroup object (bundle of related points)Read
BV70RH DisplayWrite0=Disabled, 1=Enabled
AV71RH SetpointRange 30 to 95 %, default 50 %.%Write
AV72Dehumidification HysterisysRange 2 to 20 %, default 5 %.%Write
AV73Dehumidification MAX CoolingRange 20 to 100 %, default 100 %.%Write
Other74Output Configuration OptionsGroup object (bundle of related points)Read
BV75Control typeWrite0=On/Off, 1=Floating
MV76Floating Motor timingDefault 1.5 minutesWrite1=0.5 minute ... 18=9 minutes (0.5-minute steps)
MV77On Off Control CPHWrite1=3 CPH, 2=4 CPH, 3=5 CPH, 4=6 CPH, 5=7 CPH, 6=8 CPH
BV78Direct Reverse ActingWrite0=Direct Acting, 1=Reverse Acting
Other81VTR models Configuration Options and StatusGroup object (bundle of related points). VTR models.Read
MV82RUI 1 ConfigurationVTR modelsWrite0=None, 1=Filter, 2=Service, 3=COC/NH, 4=COC/NC, 5=COS
MV83RBI 2 ConfigurationVTR modelsWrite0=None, 1=Filter, 2=Service
MV84Heat CPHVTR modelsWrite3=3 CPH, 4=4 CPH, 5=5 CPH, 6=6 CPH, 7=7 CPH, 8=8 CPH
MV85Cool CPHVTR modelsWrite3=3 CPH, 4=4 CPH, 5=5 CPH, 6=6 CPH, 7=7 CPH, 8=8 CPH
BV86Heat NO NCVTR modelsWrite0=Normally Opened, 1=Normally Closed
BV87Cool NO NCVTR modelsWrite0=Normally Opened, 1=Normally Closed
AV88Heat Demand LimitRange 0 to 100 %. VTR models.%Write
AV89Cool Demand LimitRange 0 to 100 %. VTR models.%Write
MV90Pulsed HeatVTR modelsWrite0=Off, 1=On, 2=Occupancy Output
BI91RUI 1 StatusVTR modelsRead0=Deactivated, 1=Activated
BI92RBI 2 StatusVTR modelsRead0=Deactivated, 1=Activated
BI93Cooling Valve StatusVTR modelsRead0=Off, 1=On
BI94Heating Valve StatusVTR modelsRead0=Off, 1=On
MV95Fan ControlVTR modelsWrite0=On, 1=Off-Auto, 2=Off-All

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VT7200 / VT7300 Series PIR-Ready Thermostats and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Viconics VT7200 / VT7300 Series PIR-Ready Thermostats

How many BACnet points does the Viconics VT7200 / VT7300 Series PIR-Ready Thermostats have?

This list has 87 BACnet objects: 1 analog input, 22 analog values, 13 binary inputs, 16 binary values, 26 multi-state values, 9 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Viconics VT7200 / VT7300 Series PIR-Ready Thermostats BACnet points are writable?

58 of the 87 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Viconics VT7200 / VT7300 Series PIR-Ready Thermostats BACnet documentation?

The source is PIR Ready VT72xx & VT(R)73xx Series BACnet Integration Manual (028-6009 R11 (ITG-VT(R) 72_73-BAC-E11)), revision 2012-02-07, published free by Viconics at https://www.veris.com/ASSETS/DOCUMENTS/CMS/EN/Static_Documents/DownloadCenter/028-6009-R11-ITG-VT-R-72-73-PIR-BAC-E11.pdf.

What are the minimum BACnet points to integrate the Viconics VT7200 / VT7300 Series PIR-Ready Thermostats?

Start with MV 18 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode; states set by Fan Mode Sequence (MV 57)); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 28 Fan Status (Fan speed status: off / low / medium / high); MV 33 Effective Occupancy (Actual occupancy state); AV 7 Room Temperature (Space temperature used for control); BI 37 Service Alarm (Service alarm from an input set to Service).

How do I enable BMS control of the Viconics VT7200 / VT7300 Series PIR-Ready Thermostats?

There is no separate enable point. Occupancy Command (MV 18) selects local occupancy, occupied or unoccupied; System Mode (MV 16) and Fan Mode (MV 17) act directly.

Does the Viconics VT7200 / VT7300 Series PIR-Ready Thermostats need a BACnet heartbeat or have a communication timeout?

No heartbeat point. If the thermostat goes offline, the room temperature, outdoor temperature and occupancy values written over the network are released.

Can the BMS supply sensor values to the Viconics VT7200 / VT7300 Series PIR-Ready Thermostats?

Room Temperature (AV 7) can be written only after Room Temp Override (BV 8) is set to Override; Room Humidity (AV 10) needs Room Humid Override (BV 11) the same way. Outdoor Temperature (AV 9) is writable and is one of the global values the guide shows a BMS sending to all thermostats.

How do I check these points on the real VT7200 / VT7300 Series PIR-Ready Thermostats?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Viconics BACnet points lists

Source: PIR Ready VT72xx & VT(R)73xx Series BACnet Integration Manual · 028-6009 R11 (ITG-VT(R) 72_73-BAC-E11) · rev. 2012-02-07. Object names, instances and units are reproduced as published; descriptions are our own.