Networked room thermostat · BACnet points list

Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats BACnet points list

Updated 28 October 2026

Short answer

Viconics VT76xx thermostats control single- and two-stage rooftop units and heat pumps and join a BACnet MS/TP trunk through a plug-in communication module. One object list covers all models; several instances hold a different object on different models (for example heat pump balance points versus discharge air limits). The thermostats do not support COV, so the BMS must poll them.

This page lists 109 BACnet objects for the Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats — 67 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Viconics’s own free documentation, linked below.

Manufacturer
Viconics
Model
VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats
Equipment
Networked room thermostat
Equipment type
Thermostats, sensors & meters
BACnet objects
109 (67 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
76000 + MAC
Also known as
VT7600, VT7605, VT7607, VT7652, VT7656, VT7657, VT7606, VT76xx
Source document
PIR Ready VT76xx Series BACnet Integration Manual · 028-6015 R2 (ITG-VT76xx-PIR-BAC-E02) · rev. 2011-01-23
Download CSV 109 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats

Integration in brief

Give each thermostat a MAC address from 0 to 127 (the factory 254 leaves BACnet off) and let it auto-baud. The BMS writes Occupancy Command (MV 12), the system mode for the unit type (MV 14 on rooftop units, MV 13 on heat pumps), Fan Mode (MV 15) and the setpoints, and reads Room Temperature (AV 7), Effective Occupancy (MV 34), the G/Y/W output status BIs and the alarms. Poll no faster than every 5 seconds, since there is no COV.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 12Occupancy CommandBMS occupancy: local, occupied or unoccupiedWrite
MV 14System Mode RTUOff / auto / cool / heat (rooftop models)Write
MV 13System Mode HPOff / auto / cool / heat / emergency (heat pump models)Write
MV 15Fan ModeFan mode: on / auto / smartWrite
AV 42Occupied Heat SetpointOccupied heating setpointWrite
AV 43Occupied Cool SetpointOccupied cooling setpointWrite
BI 25G FanFan (G) output stateRead
MV 34Effective OccupancyActual occupancy stateRead
AV 7Room TemperatureSpace temperature used for controlWrite
BI 40Fan Lock AlarmFan lock alarm (1 = on)Read

Enable & remote start

There is no separate enable point. Occupancy Command (MV 12) selects local occupancy, occupied or unoccupied; the system mode (MV 14 or MV 13) and Fan Mode (MV 15) act directly.

Heartbeat & communication loss

No heartbeat point. If the thermostat goes offline, the room temperature, outdoor temperature and occupancy values written over the network are released.

Sensors & values from the BMS

Room Temperature (AV 7) can be written only after Room Temp Override (BV 8) is set to Override. Outdoor Temperature (AV 9) has its own override (BV 10) and is one of the global values the guide shows a BMS sending to all thermostats.

Network setup

Watch out for

Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

109 of 109 shown
Type
Multi-state
Access
Show
Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats BACnet Points List
DescriptionStates
AVmin7Room TemperatureRoom temperature; writable only when BV 8 = Override°FWrite
BV8Room Temp OverrideEnables writing AV 7 from the networkWrite0=Normal, 1=Override
AV9Outdoor TemperatureOutdoor temperature; can be written from the BMS°FWrite
BV10Outdoor Temp OverrideWrite0=Normal, 1=Override
AV11Room HumidityRoom relative humidity (humidity models)%Read
MVmin12Occupancy CommandWrite1=Local Occupancy, 2=Occupied, 3=Unoccupied
BV13Room Humidity OverrideWrite0=Normal, 1=Override
MVmin13System Mode HPSystem mode on heat pump modelsWrite1=Off, 2=Auto, 3=Cool, 4=Heat, 5=Emergency
MVmin14System Mode RTUSystem mode on rooftop unit modelsWrite1=Off, 2=Auto, 3=Cool, 4=Heat
MVmin15Fan ModeDefault SmartWrite1=On, 2=Auto, 3=Smart
AI16Supply TempSupply air temperature, if a sensor is fitted°FRead
AV17Supply RH / Water Temp.Supply RH (0-100 %) or water temperature (°F), by modelRead
MV18Keypad LockoutWrite1=Level 0, 2=Level 1, 3=Level 2
Other19Control OutputGroup object (bundle of related points) (printed GR 19)Read
AV20PI Heating Demand%Read
AV21PI Cooling Demand%Read
AV22Economizer OutputEconomizer models%Read
AI23AI1 ValueAnalog input 1, 0 to 10 VDCVRead
Other23Controller StatusGroup object (bundle of related points)Read
BI24AUXAuxiliary output statusRead0=Off, 1=On
BImin25G FanFan (G) output statusRead0=Off, 1=On
BI26Y1 CoolCooling stage 1 (Y1) outputRead0=Off, 1=On
BI27Y2 CoolCooling stage 2 (Y2) outputRead0=Off, 1=On
BI28W1 HeatHeating stage 1 (W1) outputRead0=Off, 1=On
BI29W2 HeatHeating stage 2 (W2) outputRead0=Off, 1=On
BI30Reversing ValveReversing valve output (heat pump models)Read0=Off, 1=On
BI31DI 1 StatusRead0=Not Activated, 1=Activated
BI32DI 2 StatusRead0=Not Activated, 1=Activated
BI33Local MotionPIR motion detectedRead0=No Motion, 1=Motion
MVmin34Effective OccupancyRead1=Occupied, 2=Unoccupied, 3=Temporary Occupied
AV35Analog Heat OutputModulating heat output (some models)%Read
Other35Controller AlarmsGroup object (bundle of related points)Read
BI36Frost AlarmRead0=Off, 1=On
BI37Clock AlarmScheduling modelsRead0=Off, 1=On
BI38Filter AlarmRead0=Off, 1=On
BI39Service AlarmRead0=Off, 1=On
BImin40Fan Lock AlarmRead0=Off, 1=On
Other41Temperature SetpointsGroup object (bundle of related points)Read
AVmin42Occupied Heat SetpointRange 40 to 90 °F, default 72 °F.°FWrite
AVmin43Occupied Cool SetpointRange 54 to 100 °F, default 75 °F.°FWrite
AV44Unoccupied Heat SetpointRange 40 to 90 °F, default 62 °F.°FWrite
AV45Unoccupied Cool SetpointRange 54 to 100 °F, default 80 °F.°FWrite
AI46Fresh Air LevelRange 0 to 20000 cfmcfmRead
Other46General Options 1Group object (bundle of related points)Read
BV47Temperature ScaleWrite0=°C, 1=°F
AV48Heating Setpoint LimitRange 40 to 90 °F, default 90 °F.°FWrite
AV49Cooling Setpoint LimitRange 54 to 100 °F, default 54 °F.°FWrite
AV50Heating Lockout TemperatureRange -15 to 120 °F, default 120 °F.°FWrite
AV51Cooling Lockout TemperatureRange -40 to 95 °F, default -40 °F.°FWrite
AV52DeadbandRange 2 to 4 °F, default 2 °F.°FWrite
MV53Heating CPHWrite1=3 CPH, 2=4 CPH, 3=5 CPH, 4=6 CPH, 5=7 CPH, 6=8 CPH
MV54Cooling CPHWrite1=3 CPH, 2=4 CPH
BV55Frost ProtectionWrite0=Off, 1=On
BV56Aux ContactWrite0=N.O., 1=N.C.
BV57Menu ScrollWrite0=No Scroll, 1=Scroll Active
BV58Supply Heat Lockout StatusListed as BI 58 in the state tableRead0=Off, 1=On
Other58General Options 2Group object (bundle of related points)Read
AV59Password ValueRange 0 to 1000Write
AV60Power-up DelayRange 10 to 120 s, default 10 s.sWrite
MV61Temporary Occ. TimeDefault 3 hoursWrite1=0 hour ... 13=12 hours (1-hour steps)
BV62Fan ControlWrite0=Off, 1=On
MV63AnticycleWrite1=0 minute, 2=1 minute, 3=2 minutes, 4=3 minutes, 5=4 minutes, 6=5 minutes
BV64Fan Purge DelayWrite0=Off, 1=On
MV65DI 1 ConfigurationWrite1=None, 2=RemNSB, 3=RemOVR, 4=Filter, 5=Service, 6=Fan lock
MV66DI 2 ConfigurationWrite1=None, 2=RemNSB, 3=RemOVR, 4=Filter, 5=Service, 6=Fan lock
MV67Proportional BandWrite1=2 °F, 2=3 °F, 3=4 °F, 4=5 °F, 5=6 °F, 6=7 °F, 7=8 °F
AV68Unoccupied TimeRange 0.5 to 24 h, default 0.5 h.hWrite
AI69CO2 LevelRange 0 to 2000 ppmppmRead
Other69With schedule Model Configuration OptionsGroup object (bundle of related points)Read
BV70Progressive RecoveryScheduling modelsWrite0=Off, 1=Active
MV71Event DisplayScheduling modelsWrite1=2 Events, 2=4 Events
Other72Stages Configuration OptionsGroup object (bundle of related points)Read
BI72Discharge Air AlarmRead0=Off, 1=On
MV73Heating StagesWrite1=Analog Heat, 2=1 Stage, 3=2 Stages
MV74Cooling StagesWrite1=1 Stage, 2=2 Stages
MV75Heatpump StagesWrite1=1 Stage, 2=2 Stages
Other76Economizer Model Configuration OptionsGroup object (bundle of related points)Read
AV76Fresh Air Max RangeRange 0 to 20000 cfmcfmWrite
AV77Economizer Changeover SetpointRange 14 to 70 °F, default 55 °F.°FWrite
AV78Economizer Minimum PositionRange 0 to 100 %, default 0 %.%Write
BV79Mechanical Cooling EnabledWrite0=Off, 1=On
AV80Mixed Air SetpointRange 50 to 90 °F, default 55 °F.°FWrite
Other81Heatpump Model Configuration OptionsGroup object (bundle of related points)Read
AV81Economizer Max PositionRange 0 to 100 %%Write
AV82High Balance Point / Discharge High Limit SetpointBalance point 34-90 °F, or discharge high limit 70-150 °F, by model°FWrite
AV83Low Balance Point / Discharge Low Limit SetpointBalance point -40 to 30 °F, or discharge low limit 35-65 °F, by model°FWrite
BV84Comfort ModeWrite0=Comfort, 1=Economy
BI84High CO2 AlarmWrite0=Off, 1=On
BV85Reversing Valve ConfigurationWhether the reversing valve is energized in heating or coolingWrite0=Normally Cool Energized in Heating, 1=Normally Heat Energized in Cooling
BV86Compressor InterlockWrite0=Off, 1=On
BI86Fresh Air AlarmRead0=Off, 1=On
Other87Dehumidification Model Configuration OptionsGroup object (bundle of related points)Read
BV88RH DisplayWrite0=Disabled, 1=Enabled
AV89Dehumidification RH SetpointRange 30-95 % or 20-100 % by model, default 50 %%Write
AV90Dehumidification HysterisysRange 2 to 20 %, default 5 %.%Write
AV91Dehumidification Low OA LockoutRange -40 to 122 °F, default 32 °F.°FWrite
BV92Dehumidification Lockout FunctionsWrite0=Disabled, 1=Enabled
MV92Dehumidification Lockout FunctionsWrite1=Disabled, 2=Restricted, 3=Enabled
BI93Dehumidification Output StatusRead0=Off, 1=On
Other94Humidification Model Configuration OptionsGroup object (bundle of related points)Read
BV94AI1 ConfigWrite0=None, 1=CO2
AV95Humidification RH Setpoint / Minimum Supply Heat SetpointRH setpoint 10-90 % or minimum supply heat 50-72 °F, by modelWrite
AV96Eff Reset Humidification RH Spt / Supply Heat Lockout TemperatureEffective RH setpoint (read-only) or supply heat lockout (°F), by modelWrite
AV97Humidification High Limit Spt / Supply PI Heat DemandRH high limit 50-90 % or supply heat demand (read-only, %), by modelWrite
AV98Low RH Setpoint / Minimum Fresh AirLow RH setpoint 10-90 % or minimum fresh air (cfm), by modelWrite
AV99Low Temp Reset RH Setpoint / Maximum Fresh AirReset outdoor temp -40 to 15 °F or maximum fresh air (cfm), by modelWrite
AV100High Temp Reset RH Setpoint / Minimum CO2 LevelReset outdoor temp 20-55 °F or minimum CO2 0-2000 ppm, by modelWrite
AV101Humidifier Output / Maximum CO2 LevelHumidifier output (read-only, %) or maximum CO2 (ppm), by modelWrite
SCH102Local ScheduleInternal weekly schedule (scheduling models)Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats

How many BACnet points does the Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats have?

This list has 109 BACnet objects: 4 analog inputs, 37 analog values, 19 binary inputs, 18 binary values, 1 schedule, 18 multi-state values, 12 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats BACnet points are writable?

67 of the 109 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats BACnet documentation?

The source is PIR Ready VT76xx Series BACnet Integration Manual (028-6015 R2 (ITG-VT76xx-PIR-BAC-E02)), revision 2011-01-23, published free by Viconics at https://www.veris.com/ASSETS/DOCUMENTS/CMS/EN/Static_Documents/DownloadCenter/028-6015-R2-ITG-VT76xx-PIR-BAC-E02.pdf.

What are the minimum BACnet points to integrate the Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats?

Start with MV 12 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 14 System Mode RTU (Off / auto / cool / heat (rooftop models)); MV 13 System Mode HP (Off / auto / cool / heat / emergency (heat pump models)); MV 15 Fan Mode (Fan mode: on / auto / smart); AV 42 Occupied Heat Setpoint (Occupied heating setpoint); AV 43 Occupied Cool Setpoint (Occupied cooling setpoint); BI 25 G Fan (Fan (G) output state); MV 34 Effective Occupancy (Actual occupancy state); AV 7 Room Temperature (Space temperature used for control); BI 40 Fan Lock Alarm (Fan lock alarm (1 = on)).

How do I enable BMS control of the Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats?

There is no separate enable point. Occupancy Command (MV 12) selects local occupancy, occupied or unoccupied; the system mode (MV 14 or MV 13) and Fan Mode (MV 15) act directly.

Does the Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats need a BACnet heartbeat or have a communication timeout?

No heartbeat point. If the thermostat goes offline, the room temperature, outdoor temperature and occupancy values written over the network are released.

Can the BMS supply sensor values to the Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats?

Room Temperature (AV 7) can be written only after Room Temp Override (BV 8) is set to Override. Outdoor Temperature (AV 9) has its own override (BV 10) and is one of the global values the guide shows a BMS sending to all thermostats.

How do I check these points on the real VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.