Easy BACnet
  1. Home
  2. BACnet points lists
  3. Viconics
  4. VZ8250 VAV Zone Controller

VAV zone controller (room thermostat) · BACnet points list

Viconics VZ8250 VAV Zone Controller BACnet points list

Updated 28 October 2026

Short answer

The VZ8250 is the VAV version of the Viconics VT8000 room controller. It is a BACnet application-specific controller (B-ASC) on BACnet MS/TP, with BACnet IP and Wi-Fi status objects for units set up through the Wi-Fi configuration web page. Its VAV objects cover airflow (measured, setpoint, min/max limits and offsets), damper positions, PI zoning demand, box type (PD/PI), reheat and fan configuration, alongside the common VT8000 setpoint, display, Lua and ZigBee wireless sensor objects.

This page lists 440 BACnet objects for the Viconics VZ8250 VAV Zone Controller — 262 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Viconics’s own free documentation, linked below.

Manufacturer
Viconics
Model
VZ8250 VAV Zone Controller
Equipment
VAV zone controller (room thermostat)
Equipment type
VAV boxes & fan coils
BACnet objects
440 (262 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
2.6
Also known as
VZ8250, Viconics VZ8250, VT8000 VZ8250, Schneider Electric VZ8250
Source document
VZ8250 BACnet Integration Guide - Variable Air Volume (VAV) - Firmware Revision 2.6 · 028-0509-04_IG-VZ8250-BNET_A4_EN (Version 4) · rev. 2022-05
Download CSV 440 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Viconics VZ8250 VAV Zone Controller

Integration in brief

Command occupancy with MV 10 and on/off with MV 16 (Off/Auto), and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy, MV 112 control status and the airflow pair AV 110 / AI 350. Write at priorities 4-16 for live control; avoid 1-3.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10Occupancy CommandBMS occupancy: local, occupied or unoccupiedCommand
MV 16System ModeOff / autoCommand
AV 39Occupied Heat SetpointOccupied heating setpointCommand
AV 40Occupied Cool SetpointOccupied cooling setpointCommand
MV 112Control StatusCurrent state: off, cooling or heatingCommand
MI 33Effective OccupancyActual occupancy stateRead
AV 100Room TemperatureSpace temperature used for controlCommand
AV 110Airflow LevelMeasured airflow, CFMCommand
AI 350Airflow SetpointAirflow setpoint calculated by the controller, CFMRead
BV 37Service AlarmService alarm from an input set to ServiceCommand

Enable & remote start

No enable switch is needed. The BMS writes MV 10 Occupancy Command (1 = Loc. occ, the controller decides locally; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode (Off or Auto). MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.

Sensors & values from the BMS

The guide has no BMS-written room temperature object: MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.

Network setup

Watch out for

Viconics VZ8250 VAV Zone Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

440 of 440 shown
Type
Access
Show
Viconics VZ8250 VAV Zone Controller BACnet Points List
DescriptionStates
AI2Light Sensor LevelRange 0 to 30000Read
AI4Relative Humidity Raw ValueRange 0 to 1000Read
AI5UI20 Raw ValueRange 0 to 4095Read
AI7UI23 Raw ValueRange 0 to 4095Read
AI8UI22 Raw ValueRange 0 to 4095Read
AI9UI24 Raw ValueRange 0 to 4095Read
AI31UI19 Raw ValueRange 0 to 4095Read
AI32Temperature Raw ValueRange -400 to 1220Read
AI33UI16 Raw ValueRange 0 to 4095Read
AI34UI17 Raw ValueRange 0 to 4095Read
AI315Wireless Device 1 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI316Wireless Device 2 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI317Wireless Device 3 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI318Wireless Device 4 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI319Wireless Device 5 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI320Wireless Device 6 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI321Wireless Device 7 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI322Wireless Device 8 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI323Wireless Device 9 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI324Wireless Device 10 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI329Effective SetpointRange 40°F (4°C) to 100°F (38°C)°F/°CRead
AI330Paired ZigBee DevicesRange 0 to 20Read
AI340Therm. Raw ValueRange -400 to 1220Read
AI341SH Therm. Raw ValueRange -400 to 1220Read
AI343Wi-Fi Module Boot CountRange 0 to 32767Read
AImin350Airflow SetpointRange 0 to 10000CFMRead
AI355Wireless Device 11 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI356Wireless Device 12 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI357Wireless Device 13 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI358Wireless Device 14 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI359Wireless Device 15 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI360Wireless Device 16 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI361Wireless Device 17 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI362Wireless Device 18 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI363Wireless Device 19 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI364Wireless Device 20 - TemperatureRange -40°F (-40°C) to 185°F (85°C)°F/°CRead
AI365Wireless Device 1 - HumidityRange 0 to 100%RHRead
AI366Wireless Device 2 - HumidityRange 0 to 100%RHRead
AI367Wireless Device 3 - HumidityRange 0 to 100%RHRead
AI368Wireless Device 4 - HumidityRange 0 to 100%RHRead
AI369Wireless Device 5 - HumidityRange 0 to 100%RHRead
AI370Wireless Device 6 - HumidityRange 0 to 100%RHRead
AI371Wireless Device 7 - HumidityRange 0 to 100%RHRead
AI372Wireless Device 8 - HumidityRange 0 to 100%RHRead
AI373Wireless Device 9 - HumidityRange 0 to 100%RHRead
AI374Wireless Device 10 - HumidityRange 0 to 100%RHRead
AI375Wireless Device 11 - HumidityRange 0 to 100%RHRead
AI376Wireless Device 12 - HumidityRange 0 to 100%RHRead
AI377Wireless Device 13 - HumidityRange 0 to 100%RHRead
AI378Wireless Device 14 - HumidityRange 0 to 100%RHRead
AI379Wireless Device 15 - HumidityRange 0 to 100%RHRead
AI380Wireless Device 16 - HumidityRange 0 to 100%RHRead
AI381Wireless Device 17 - HumidityRange 0 to 100%RHRead
AI382Wireless Device 18 - HumidityRange 0 to 100%RHRead
AI383Wireless Device 19 - HumidityRange 0 to 100%RHRead
AI384Wireless Device 20 - HumidityRange 0 to 100%RHRead
AI385Wireless Device 1 - CO2Range 0 to 5000ppmRead
AI386Wireless Device 2 - CO2Range 0 to 5000ppmRead
AI387Wireless Device 3 - CO2Range 0 to 5000ppmRead
AI388Wireless Device 4 - CO2Range 0 to 5000ppmRead
AI389Wireless Device 5 - CO2Range 0 to 5000ppmRead
AI390Wireless Device 6 - CO2Range 0 to 5000ppmRead
AI391Wireless Device 7 - CO2Range 0 to 5000ppmRead
AI392Wireless Device 8 - CO2Range 0 to 5000ppmRead
AI393Wireless Device 9 - CO2Range 0 to 5000ppmRead
AI394Wireless Device 10 - CO2Range 0 to 5000ppmRead
AI395Wireless Device 11 - CO2Range 0 to 5000ppmRead
AI396Wireless Device 12 - CO2Range 0 to 5000ppmRead
AI397Wireless Device 13 - CO2Range 0 to 5000ppmRead
AI398Wireless Device 14 - CO2Range 0 to 5000ppmRead
AI399Wireless Device 15 - CO2Range 0 to 5000ppmRead
AI400Wireless Device 16 - CO2Range 0 to 5000ppmRead
AI401Wireless Device 17 - CO2Range 0 to 5000ppmRead
AI402Wireless Device 18 - CO2Range 0 to 5000ppmRead
AI403Wireless Device 19 - CO2Range 0 to 5000ppmRead
AI404Wireless Device 20 - CO2Range 0 to 5000ppmRead
AO21PI Heating DemandDefault 0, range 0 to 100%Command
AO22PI Cooling DemandDefault 0, range 0 to 100%Command
AO25PI Zoning DemandDefault 0, range -100 to 100%Command
AO123UO11 Analog OutputDefault 0, range 0 to 10VCommand
AO124UO12 Analog OutputDefault 0, range 0 to 10VCommand
AO125UO9 Analog OutputDefault 0, range 0 to 10VCommand
AO126UO10 Analog OutputDefault 0, range 0 to 10VCommand
AV2User HMIDefault 2, range 0 to 12Command
AV3Low BacklightDefault 60, range 0 to 100%Command
AV4Night BacklightDefault 5, range 0 to 100%Command
AV7Calibrate Room Temperature SensorDefault 0°F (0.0°C), range -5°F (-2.5°C) to 5°F (2.5°C)Δ°F/Δ°CCommand
AV8Calibrate Humidity SensorDefault 0, range -15 to 15%RHCommand
AV10COM AddressDefault 254, range 0 to 254Command
AV16BACnet Stack Poll RateDefault 4, range 1 to 5Command
AV23Minimum CO2Default 800, range 0 to 4800ppmCommand
AV24Maximum CO2Default 1200, range 200 to 5000ppmCommand
AV25Lua Parameter A (AV25)Default 0, range -32768 to 32767Command
AV26Lua Parameter B (AV26)Default 0, range -32768 to 32767Command
AV27Lua Parameter C (AV27)Default 0, range -32768 to 32767Command
AV28Lua Parameter D (AV28)Default 0, range -32768 to 32767Command
AV29Lua Parameter E (AV29)Default 0, range -32768 to 32767Command
AV30Lua Parameter F (AV30)Default 0, range -32768 to 32767Command
AVmin39Occupied Heat SetpointDefault 72°F (22°C), range 40°F (4°C) to 90°F (32°C)°F/°CCommand
AVmin40Occupied Cool SetpointDefault 75°F (24°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV41Standby Heat SetpointDefault 69°F (21°C), range 40°F (4°C) to 90°F (32°C)°F/°CCommand
AV42Standby Cool SetpointDefault 78°F (26°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV43Unoccupied Heat SetpointDefault 62°F (17°C), range 40°F (4°C) to 90°F (32°C)°F/°CCommand
AV44Unoccupied Cool SetpointDefault 80°F (27°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV45Default Heating SetpointDefault 72°F (22°C), range 65°F (18°C) to 80°F (27°C)°F/°CCommand
AV46Standby Temperature DifferentialDefault 4°F (2.0°C), range 1°F (0.5°C) to 5°F (2.5°C)Δ°F/Δ°CCommand
AV56Main PasswordDefault 0, range 0 to 9999Command
AV57User PasswordDefault 0, range 0 to 9999Command
AV58Heating Setpoint LimitDefault 90°F (32°C), range 40°F (4°C) to 90°F (32°C)°F/°CCommand
AV59Cooling Setpoint LimitDefault 54°F (12°C), range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV62Temporary Occupancy TimeDefault 2, range 0 to 24hCommand
AV63DeadbandDefault 3°F (1.5°C), range 2°F (1.0°C) to 5°F (2.5°C)Δ°F/Δ°CCommand
AV65Proportional BandDefault 3, range 3 to 10Command
AV67Standby TimeDefault 0.5, range 0.5 to 24hCommand
AV68Unoccupied TimeDefault 0, range 0 to 24hCommand
AV88Heating Demand LimitDefault 0, range 0 to 100%Command
AV89Cooling Demand LimitDefault 0, range 0 to 100%Command
AV92Keyboard ValueDefault 0, range 0 to 35Command
AVmin100Room TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 122°F (50°C)°F/°CCommand
AV101Outdoor TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV102UI22 Supply TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV103Room HumidityDefault 0, range 0 to 100%RHCommand
AV104UI19 Changeover TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV105UI20 Remote TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV106CO2 LevelDefault 0, range 0 to 5000ppmCommand
AV107UI24 Analog InputDefault 0, range 0 to 10VCommand
AV108UI19 Analog InputDefault 0, range 0 to 10VCommand
AV109UI24 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AVmin110Airflow LevelDefault 0, range 0 to 20000CFMCommand
AV111UI16 Analog InputDefault 0, range 0 to 10VCommand
AV112UI17 Analog InputDefault 0, range 0 to 10VCommand
AV113UI20 Analog InputDefault 0, range 0 to 10VCommand
AV114UI22 Analog InputDefault 0, range 0 to 10VCommand
AV115UI23 Analog InputDefault 0, range 0 to 10VCommand
AV117UI16 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV118UI17 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV119UI19 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV120UI20 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV121UI22 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV122UI23 TemperatureDefault -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C)°F/°CCommand
AV202UI19 LuaDefault 0, range -3276.8 to 3276.7Command
AV203UI20 LuaDefault 0, range -3276.8 to 3276.7Command
AV204UI22 LuaDefault 0, range -3276.8 to 3276.7Command
AV205UI23 LuaDefault 0, range -3276.8 to 3276.7Command
AV206UI24 LuaDefault 0, range -3276.8 to 3276.7Command
AV209Ambient Low Temperature ThresholdDefault 40°F (4°C), range 32°F (0°C) to 50°F (10°C)°F/°CCommand
AV210Temperature Alarm HysteresisDefault 2°F (1°C), range 0°F (0°C) to 10°F (5.5°C)Δ°F/Δ°CCommand
AV211Load Shedding OffsetDefault 4°F (2°C), range 4°F (2°C) to 10°F (5.5°C)Δ°F/Δ°CCommand
AV212ECM Fan Low VoltageDefault 2.2, range 2 to 4VCommand
AV214ECM Fan High VoltageDefault 8.6, range 7.1 to 10VCommand
AV220Zone Heating PI WeightDefault 100, range 0 to 100%Command
AV221Zone Cooling PI WeightDefault 100, range 0 to 100%Command
AV222Flow @ 1 inch wc (K)Default 800, range 150 to 7500CFMCommand
AV223Pressure Sensor RangeDefault 1, range 0.5 to 5Command
AV225Lua Parameter G (AV225)Default 0, range -32768 to 32767Command
AV226Lua Parameter H (AV226)Default 0, range -32768 to 32767Command
AV227Lua Parameter I (AV227)Default 0, range -32768 to 32767Command
AV228Lua Parameter J (AV228)Default 0, range -32768 to 32767Command
AV229Lua Parameter K (AV229)Default 0, range -32768 to 32767Command
AV230Lua Parameter L (AV230)Default 0, range -32768 to 32767Command
AV240Actuator TimingDefault 1.5, range 0.5 to 9minCommand
AV241Floating Reheat TimingDefault 1.5, range 0.5 to 9minCommand
AV242Outside Air Temperature Duct Heater LockoutDefault 60°F (16°C), range 30°F (-1°C) to 90°F (32°C)°F/°CCommand
AV243Outside Air Temperature Baseboard LockoutDefault 60°F (16°C), range 30°F (-1°C) to 90°F (32°C)°F/°CCommand
AV250Damper Minimum PositionDefault 10, range 0 to 100%Command
AV251Damper Maximum Cooling PositionDefault 100, range 0 to 100%Command
AV252Damper Maximum Heating PositionDefault 100, range 0 to 100%Command
AV253Damper Maximum Reheat PositionDefault 30, range 0 to 100%Command
AV254Minimum AirflowDefault 50, range 0 to 10000CFMCommand
AV255Maximum Cooling AirflowDefault 200, range 0 to 10000CFMCommand
AV256Maximum Heating AirflowDefault 200, range 0 to 10000CFMCommand
AV257Maximum Reheat AirflowDefault 50, range 0 to 10000CFMCommand
AV258Minimum Airflow OffsetDefault 0, range -5000 to 5000CFMCommand
AV259Maximum Airflow OffsetDefault 0, range -5000 to 5000CFMCommand
AV270Standby Screen DelayDefault 150, range 5 to 300sCommand
AV275Ambient High Temperature ThresholdDefault 86°F (30°C), range 32°F (0°C) to 122°F (50°C)°F/°CCommand
AV276Refrigeration High Temperature ThresholdDefault 40°F (4°C), range 32°F (0°C) to 60°F (16°C)°F/°CCommand
AV277Refrigeration Low Temperature ThresholdDefault 32°F (0°C), range 32°F (0°C) to 50°F (10°C)°F/°CCommand
AV278Freezer High Temperature ThresholdDefault 0°F (-18°C), range -40°F (-40°C) to 32°F (0°C)°F/°CCommand
BI29UI16 Binary InputRead0=Activated, 1=Not activ.
BI30UI17 Binary InputRead0=Activated, 1=Not activ.
BI91UI19 Binary InputRead0=Activated, 1=Not activ.
BI94UI20 Binary InputRead0=Activated, 1=Not activ.
BI95UI22 Binary InputRead0=Activated, 1=Not activ.
BI96UI23 Binary InputRead0=Activated, 1=Not activ.
BI97UI24 Binary InputRead0=Activated, 1=Not activ.
BO93UO9 Binary OutputDefault 0Command0=Off, 1=On
BO94UO10 Binary OutputDefault 0Command0=Off, 1=On
BO95BO4 High Speed Fan OutputDefault 0Command0=Off, 1=On
BO98BO8 Auxiliary Binary OutputDefault 0Command0=Off, 1=On
BO101UO11 Binary OutputDefault 0Command0=Off, 1=On
BO102UO12 Binary OutputDefault 0Command0=Off, 1=On
BV1Door Contact StatusDefault 0Command0=Closed, 1=Opened
BV2Door Contact InstalledDefault 0Command0=No, 1=Yes
BV3Window Contact StatusDefault 0Command0=Closed, 1=Opened
BV4Window Contact InstalledDefault 0Command0=No, 1=Yes
BV5Low Battery AlarmDefault 0Command0=Off, 1=On
BV6Force High BacklightDefault 0Command0=Off, 1=On
BV7Display Long Screen MessageDefault 0Command0=Off, 1=On
BV8Clock AlarmDefault 0Command0=Off, 1=On
BV10Exception StatusDefault 0Command0=Off, 1=On
BV32PIR Local MotionDefault 0Command0=No motion, 1=Motion
BV35Window AlarmDefault 0Command0=Off, 1=On
BV36Filter AlarmDefault 0Command0=Off, 1=On
BVmin37Service AlarmDefault 0Command0=Off, 1=On
BV40Smart Recovery StatusDefault 0Command0=Off, 1=On
BV41CO2 AlarmDefault 0Command0=Off, 1=On
BV44Water LeakDefault 0Command0=Off, 1=On
BV45Water Leak Sensor InstalledDefault 0Command0=No, 1=Yes
BV46Water leak sensor statusDefault 0Command0=Normal, 1=Leak
BV47Low TemperatureDefault 0Command0=Off, 1=On
BV48Load Shedding DemandDefault 0Command0=Off, 1=On
BV49Load Shedding StatusDefault 0Command0=Off, 1=On
BV50Load Shedding OverrideDefault 0Command0=Off, 1=On
BV53High TemperatureDefault 0Command0=Off, 1=On
BV200ZigBee PIR Sensor InstalledDefault 0Command0=Off, 1=On
BV201ZigBee Sensor MotionDefault 0Command0=No motion, 1=Motion
CSV1Short Screen Message TextText, up to 26 charactersWrite
CSV2Long Screen Message TextText, up to 480 charactersWrite
CSV3External Memory RevisionTextWrite
CSV4Wi-Fi Device NameTextWrite
CSV5Wi-Fi Firmware VersionTextWrite
CSV6MAC AddressTextWrite
CSV7Wi-Fi Network SSIDTextWrite
CSV8Wi-Fi Network IP AddressTextWrite
CSV9Zigbee Firmware RevisionTextWrite
CSV10Zigbee IEEE AddressTextWrite
CSV11Wireless Device 1 - AddressTextWrite
CSV12Wireless Device 2 - AddressTextWrite
CSV13Wireless Device 3 - AddressTextWrite
CSV14Wireless Device 4 - AddressTextWrite
CSV15Wireless Device 5 - AddressTextWrite
CSV16Wireless Device 6 - AddressTextWrite
CSV17Wireless Device 7 - AddressTextWrite
CSV18Wireless Device 8 - AddressTextWrite
CSV19Wireless Device 9 - AddressTextWrite
CSV20Wireless Device 10 - AddressTextWrite
CSV21Wireless Device 11 - AddressTextWrite
CSV22Wireless Device 12 - AddressTextWrite
CSV23Wireless Device 13 - AddressTextWrite
CSV24Wireless Device 14 - AddressTextWrite
CSV25Wireless Device 15 - AddressTextWrite
CSV26Wireless Device 16 - AddressTextWrite
CSV27Wireless Device 17 - AddressTextWrite
CSV28Wireless Device 18 - AddressTextWrite
CSV29Wireless Device 19 - AddressTextWrite
CSV30Wireless Device 20 - AddressTextWrite
MI2ZigBee Network StatusRead1=Not det., 2=Pwr on, 3=No NWK, 4=Joined, 5=Online
MImin33Effective OccupancyRead1=Occupied, 2=Unoccupied, 3=Override, 4=Standby
MI180Wireless Device 1 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI181Wireless Device 2 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI182Wireless Device 3 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI183Wireless Device 4 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI184Wireless Device 5 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI185Wireless Device 6 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI186Wireless Device 7 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI187Wireless Device 8 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI188Wireless Device 9 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI189Wireless Device 10 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI190Wireless Device 11 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI191Wireless Device 12 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI192Wireless Device 13 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI193Wireless Device 14 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI194Wireless Device 15 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI195Wireless Device 16 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI196Wireless Device 17 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI197Wireless Device 18 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI198Wireless Device 19 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI199Wireless Device 20 - Sensor TypeRead1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2
MI210Wireless Device 1 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI211Wireless Device 1 - BatteryRead1=None, 2=Normal, 3=Low
MI212Wireless Device 1 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI220Wireless Device 2 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI221Wireless Device 2 - BatteryRead1=None, 2=Normal, 3=Low
MI222Wireless Device 2 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI230Wireless Device 3 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI231Wireless Device 3 - BatteryRead1=None, 2=Normal, 3=Low
MI232Wireless Device 3 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI240Wireless Device 4 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI241Wireless Device 4 - BatteryRead1=None, 2=Normal, 3=Low
MI242Wireless Device 4 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI250Wireless Device 5 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI251Wireless Device 5 - BatteryRead1=None, 2=Normal, 3=Low
MI252Wireless Device 5 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI260Wireless Device 6 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI261Wireless Device 6 - BatteryRead1=None, 2=Normal, 3=Low
MI262Wireless Device 6 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI270Wireless Device 7 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI271Wireless Device 7 - BatteryRead1=None, 2=Normal, 3=Low
MI272Wireless Device 7 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI280Wireless Device 8 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI281Wireless Device 8 - BatteryRead1=None, 2=Normal, 3=Low
MI282Wireless Device 8 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI290Wireless Device 9 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI291Wireless Device 9 - BatteryRead1=None, 2=Normal, 3=Low
MI292Wireless Device 9 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI300Wireless Device 10 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI301Wireless Device 10 - BatteryRead1=None, 2=Normal, 3=Low
MI302Wireless Device 10 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI309Effective temperature sensorRead1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20
MI310Wireless Device 11 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI311Wireless Device 11 - BatteryRead1=None, 2=Normal, 3=Low
MI312Wireless Device 11 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI313Effective Relative Humidity sensorRead1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20
MI314Effective System ModeRead1=Cool, 2=Heat
MI315Wi-Fi Module StatusRead1=Offline, 2=Initializing, 3=Ready, 4=Booting, 5=Resetting, 6=Fail, 7=Testing
MI316Wi-Fi StatusRead1=Idle, 2=Associate, 3=Config., 4=Ready, 5=Online, 6=Disconn., 7=Failure
MI317BACnet IP StatusRead1=Disabled, 2=Enabled
MI318SMTP Server StatusRead1=Unknown, 2=Disabled, 3=Offline, 4=Online
MI319Facility Expert EnabledRead1=Disabled, 2=Enabled
MI320Wireless Device 12 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI321Wireless Device 12 - BatteryRead1=None, 2=Normal, 3=Low
MI322Wireless Device 12 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI323Facility Expert StatusRead1=Disabled, 2=Offline, 3=Connect., 4=Online, 5=Failure, 6=Unknown
MI324CO2 Effective SourceRead1=None, 2=Internal, 3=Error, 4=Wired, 5=WL 1, 6=WL 2, 7=WL 3, 8=WL 4, 9=WL 5, 10=WL 6, 11=WL 7, 12=WL 8, 13=WL 9, 14=WL 10, 15=WL 11, 16=WL 12, 17=WL 13, 18=WL 14, 19=WL 15, 20=WL 16, 21=WL 17, 22=WL 18, 23=WL 19, 24=WL 20
MI325Time sourceRead1=None, 2=Local, 3=BACnet, 4=NTP, 5=Cloud
MI326Fan Speed StatusRead1=Off, 2=Low, 3=Medium, 4=High
MI327Wi-Fi Network Signal StrengthRead1=Unknown, 2=Weak, 3=Fair, 4=Good, 5=Excellent
MI330Wireless Device 13 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI331Wireless Device 13 - BatteryRead1=None, 2=Normal, 3=Low
MI332Wireless Device 13 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI340Wireless Device 14 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI341Wireless Device 14 - BatteryRead1=None, 2=Normal, 3=Low
MI342Wireless Device 14 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI350Wireless Device 15 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI351Wireless Device 15 - BatteryRead1=None, 2=Normal, 3=Low
MI352Wireless Device 15 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI360Wireless Device 16 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI361Wireless Device 16 - BatteryRead1=None, 2=Normal, 3=Low
MI362Wireless Device 16 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI370Wireless Device 17 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI371Wireless Device 17 - BatteryRead1=None, 2=Normal, 3=Low
MI372Wireless Device 17 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI380Wireless Device 18 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI381Wireless Device 18 - BatteryRead1=None, 2=Normal, 3=Low
MI382Wireless Device 18 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI390Wireless Device 19 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI391Wireless Device 19 - BatteryRead1=None, 2=Normal, 3=Low
MI392Wireless Device 19 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI400Wireless Device 20 - StatusRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI401Wireless Device 20 - BatteryRead1=None, 2=Normal, 3=Low
MI402Wireless Device 20 - Communication StatusRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MV1Long Message Background ColourDefault 1Command1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black, 11=Default
MV2HMI ColorDefault 1Command1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black
MV3Main DisplayDefault 3Command1=Temp., 2=Setpoint, 3=T. + set.
MV4Display LanguageDefault 1Command1=English, 2=French, 3=Spanish, 4=Chinese, 5=Russian, 6=Arabic, 7=Bulgarian, 8=Czech, 9=Danish, 10=Dutch, 11=Finnish, 12=German, 13=Hungarian, 14=Indones., 15=Italian, 16=Norwegian, 17=Polish, 18=Portug., 19=Slovak, 20=Swedish, 21=Turkish, 22=Japanese, 23=Hebrew
MV5Time FormatDefault 1Command1=AM-PM, 2=24 Hours
MV6Network UnitsDefault 2Command1=SI, 2=Imperial
MV7Network LanguageDefault 1Command1=English, 2=French, 3=Spanish
MV8BACnet Baud RateDefault 7Command1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto
MV9No Activity Sleep Mode TimeDefault 1Command1=Disabled, 2=Enabled
MVmin10Occupancy CommandDefault 2Command1=Loc occ., 2=Occupied, 3=Unocc.
MV11Standby Mode ConfigurationDefault 1Command1=Absolute, 2=Offset
MVmin16System ModeDefault 2Command1=Off, 2=Auto
MV32Use Standby ScreenDefault 1Command1=No, 2=Yes, 3=Occ. only, 4=Screen sav
MV46UI16 ConfigurationDefault 1Command1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window
MV47UI17 ConfigurationDefault 1Command1=None, 2=Door dry, 3=Override, 4=Filter, 5=Service
MV49UI19 ConfigurationDefault 1Command1=None, 2=COC/NH, 3=COC/NC, 4=COS
MV51Temperature ScaleDefault 2Command1=°C, 2=°F
MV70Room Humidity DisplayDefault 1Command1=Disabled, 2=Enabled
MV71Enable Smart RecoveryDefault 1Command1=Off, 2=On
MV73Schedule MenuDefault 3Command1=Disabled, 2=Enabled, 3=Dis.no.clk, 4=En.no.clk
MV81Actuator TypeDefault 1Command1=0-10V DA, 2=0-10V RA, 3=2-10V DA, 4=2-10V RA, 5=Floating
MV92Baseboard ConfigurationDefault 1Command1=Relay, 2=PWM Vac, 3=Valve NC, 4=Valve NO
MV96UO9 ConfigurationDefault 2Command1=Analog, 2=Binary, 3=Relay RC, 4=Relay RH
MV97UO10 ConfigurationDefault 2Command1=Analog, 2=Binary, 3=Relay RC
MV98UO11 ConfigurationDefault 2Command1=Analog, 2=Binary
MV99UO12 ConfigurationDefault 2Command1=Analog, 2=Binary
MV101FrenchDefault 2Command1=Disabled, 2=Enabled
MV102SpanishDefault 2Command1=Disabled, 2=Enabled
MV103ChineseDefault 2Command1=Disabled, 2=Enabled
MV104RussianDefault 2Command1=Disabled, 2=Enabled
MV110Occupancy SourceDefault 1Command1=Motion, 2=Schedule, 3=Mot. occ., 4=Mot. unoc.
MVmin112Control StatusDefault 1Command1=Off, 2=Cool, 3=Heat
MV114Custom button iconDefault 1Command1=Default Button, 2=No Button, 3=System Mode Heat/Cool, 4=System Mode On/Off, 5=Fan Mode, 6=Override Button, 7=Units Button, 8=Help Button, 9=Language Button, 10=Schedule Button, 11=Lighting Button, 12=Blind Button, 13=Lamp Button, 14=Energy Button, 15=Make Room Button, 16=Setting Button, 17=Timer Button
MV115Custom button behaviorDefault 1Command1=Default function, 2=No function, 3=System mode function, 4=Fan function, 5=Override function, 6=Schedule function, 7=Units function, 8=Help function, 9=Language function, 10=Configuration function, 11=Custom function, 12=Standby function
MV120ArabicDefault 1Command1=Disabled, 2=Enabled
MV122CzechDefault 1Command1=Disabled, 2=Enabled
MV123DanishDefault 1Command1=Disabled, 2=Enabled
MV124DutchDefault 1Command1=Disabled, 2=Enabled
MV125FinnishDefault 1Command1=Disabled, 2=Enabled
MV126GermanDefault 1Command1=Disabled, 2=Enabled
MV127HungarianDefault 1Command1=Disabled, 2=Enabled
MV128IndonesianDefault 1Command1=Disabled, 2=Enabled
MV129ItalianDefault 1Command1=Disabled, 2=Enabled
MV130NorwegianDefault 1Command1=Disabled, 2=Enabled
MV131PolishDefault 1Command1=Disabled, 2=Enabled
MV132PortugueseDefault 1Command1=Disabled, 2=Enabled
MV133SlovakDefault 1Command1=Disabled, 2=Enabled
MV134SwedishDefault 1Command1=Disabled, 2=Enabled
MV135TurkishDefault 1Command1=Disabled, 2=Enabled
MV136Schedule TypeDefault 1Command1=7 days, 2=5+2 days, 3=5+1+1 day
MV138UI16 Input TypeDefault 2Command1=Therm., 2=Binary, 3=Voltage
MV139UI17 Input TypeDefault 2Command1=Therm., 2=Binary, 3=Voltage
MV140UI19 Input TypeDefault 1Command1=Therm., 2=Binary, 3=Voltage
MV141UI20 Input TypeDefault 1Command1=Therm., 2=Binary, 3=Voltage
MV142UI22 Input TypeDefault 1Command1=Therm., 2=Binary, 3=Voltage
MV143UI23 Input TypeDefault 1Command1=Therm., 2=Binary, 3=Voltage
MV144UI24 Input TypeDefault 3Command1=Therm., 2=Binary, 3=Voltage
MV145Room Temperature SensorDefault 1Command1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20
MV146CO2 DisplayDefault 2Command1=Disabled, 2=Enabled
MV147CO2 AutocalibrationDefault 2Command1=Disabled, 2=Enabled
MV148Lock ScreenDefault 1Command1=No, 2=Yes
MV149Relative humidity sensorDefault 2Command1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20
MV150CO2 sourceDefault 2Command1=None, 2=Local, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20
MV151Temperature Alarm EnabledDefault 1Command1=Off, 2=On
MV152ADR PermissionDefault 1Command1=Off, 2=On
MV154Fan TypeDefault 1Command1=None, 2=Par. on/off, 3=Ser. on/off, 4=Par. ECM, 5=Ser. ECM
MV155JapaneseDefault 1Command1=Disabled, 2=Enabled
MV156HebrewDefault 1Command1=Disabled, 2=Enabled
MV160Duct Heater ConfigurationDefault 1Command1=0-10V DA, 2=0-10V RA, 3=2-10V DA, 4=2-10V RA, 5=Floating, 6=On/Off, 7=PWM Vac, 8=Valve NC, 9=Valve NO
MV170VAV Box TypeDefault 2Command1=PD, 2=PI
MV171Reheat ConfigurationDefault 1Command1=None, 2=Duct only, 3=Base only, 4=Duct+base, 5=Base+duct
MV172Damper OverrideDefault 1Command1=None, 2=Minimum, 3=Max. cool, 4=Close, 5=Reheat, 6=Open
MV173Zone Control ModeDefault 1Command1=Cool, 2=Heat
MV180Display the Fan Status iconDefault 2Command1=Disabled, 2=Enabled
MV181Display the System Status iconDefault 2Command1=Disabled, 2=Enabled
MV182Display the Help buttonDefault 2Command1=Disabled, 2=Enabled
MV210Wireless Device 1 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV220Wireless Device 2 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV230Wireless Device 3 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV240Wireless Device 4 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV250Wireless Device 5 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV260Wireless Device 6 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV270Wireless Device 7 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV280Wireless Device 8 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV290Wireless Device 9 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV300Wireless Device 10 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV310Wireless Device 11 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV320Wireless Device 12 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV330Wireless Device 13 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV340Wireless Device 14 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV350Wireless Device 15 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV360Wireless Device 16 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV370Wireless Device 17 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV380Wireless Device 18 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV390Wireless Device 19 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV400Wireless Device 20 - FunctionDefault 1Command1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
FILE1Custom Lua FileLua script file (read/write the custom script)Write
Other1Lua Program 1Monitors and controls the Lua script programWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VZ8250 VAV Zone Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Viconics VZ8250 VAV Zone Controller

How many BACnet points does the Viconics VZ8250 VAV Zone Controller have?

This list has 440 BACnet objects: 76 analog inputs, 7 analog outputs, 96 analog values, 7 binary inputs, 6 binary outputs, 25 binary values, 1 file, 95 multi-state inputs, 96 multi-state values, 30 characterstring values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Viconics VZ8250 VAV Zone Controller BACnet points are writable?

262 of the 440 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Viconics VZ8250 VAV Zone Controller BACnet documentation?

The source is VZ8250 BACnet Integration Guide - Variable Air Volume (VAV) - Firmware Revision 2.6 (028-0509-04_IG-VZ8250-BNET_A4_EN (Version 4)), revision 2022-05, published free by Viconics at https://www.veris.com/ASSETS/DOCUMENTS/CMS/EN/Static_Documents/DownloadCenter/028-0509-04_IG-VZ8250-2.6-BNET_A4_EN_RH20220530.pdf.

What are the minimum BACnet points to integrate the Viconics VZ8250 VAV Zone Controller?

Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); AV 110 Airflow Level (Measured airflow, CFM); AI 350 Airflow Setpoint (Airflow setpoint calculated by the controller, CFM); BV 37 Service Alarm (Service alarm from an input set to Service).

How do I enable BMS control of the Viconics VZ8250 VAV Zone Controller?

No enable switch is needed. The BMS writes MV 10 Occupancy Command (1 = Loc. occ, the controller decides locally; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode (Off or Auto). MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.

Can the BMS supply sensor values to the Viconics VZ8250 VAV Zone Controller?

The guide has no BMS-written room temperature object: MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.

How do I check these points on the real VZ8250 VAV Zone Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Viconics BACnet points lists

Source: VZ8250 BACnet Integration Guide - Variable Air Volume (VAV) - Firmware Revision 2.6 · 028-0509-04_IG-VZ8250-BNET_A4_EN (Version 4) · rev. 2022-05. Object names, instances and units are reproduced as published; descriptions are our own.