- R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)
Packaged rooftop unit controller · BACnet points list
Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet points list
Updated 12 November 2026
R7DA and Y series packaged rooftop units with controls D19, D21, D22 or D23 use a programmable system controller that accepts a BACnet MS/TP card (option BHB8) or a BACnet IP/Ethernet card (option BHB9). The point list has 42 analog variables (AV 1-42), 19 integer variables (AV 1001-1019) and 47 digital variables (BV 1-48). The BMS can enable the unit, set occupancy and state, write discharge and space setpoints, send fan/heat/cool/dehumidify calls, share outdoor temperature and humidity, and command damper and fan outputs.
This page lists 108 BACnet objects for the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reznor’s own free documentation, linked below.
- Manufacturer
- Reznor
- Model
- R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)
- Equipment
- Packaged rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 108 (40 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 77000
- Also known as
- R7DA, Reznor Y series, R7DA-Y-D19-D21-D22-D23, 1024315-C, CP-P125-R7DA-D19-D21-D22-D23, 1024315-B, D19, D21, D22, D23, BHB8, BHB9, P125
Reference only, provided as-is: verify against Reznor’s current documentation and the live device before use. Not official Reznor information. Terms of use.
BMS integration notes: Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)
Fit the BHB8 MS/TP or BHB9 IP/Ethernet card and set the BACnet ID (default 77000), baud/MAC or IP settings from the controller's PCOWEB / NET CONFIG menu, then cycle power. Enable the unit with BV 39, set OccMode_Sel (AV 1007) to 2 and command occupancy with BV 26, pick the state with AV 1006 and write the setpoints. Monitor supply fan status, discharge temperature and the general alarm relay.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 39 | Unit_Enable | Unit enable | Write |
| BV 26 | Occupied_BMS | Occupancy command (needs AV 1007 = 2) | Write |
| AV 1007 | OccMode_Sel | Occupancy source: 0 schedule, 1 input, 2 BMS | Write |
| AV 1006 | State_Sel | Unit state: 2 auto, 3 cool, 4 heat, 5 off | Write |
| AV 28 | SpcTempSP | Space temperature setpoint, 65-85 °F | Write |
| AV 40 | DA_BMS_SP | Discharge air setpoint from the BMS (D22) | Write |
| BV 38 | BMS_Alm_Rst | Alarm reset | Write |
| BV 32 | SF_Sts | Supply fan status | Read |
| AV 9 | DA_Temp | Discharge air temperature | Read |
| BV 1 | Alm_Rly_Cmd | General alarm relay on | Read |
Enable & remote start
BV 39 Unit_Enable enables the unit. Occupancy comes from the schedule, a digital input or the BMS, chosen with AV 1007 OccMode_Sel; with 2 = BMS, BV 26 Occupied_BMS sets occupancy. AV 1006 State_Sel picks auto, cool, heat or off. BV 44-47 are BMS fan, heat, cool and dehumidify calls, and on D22 AV 40 DA_BMS_SP is the BMS discharge air setpoint.
Sensors & values from the BMS
Set BV 24 OA_Temp_Sel or BV 23 OA_Hum_Sel to 1 (BMS) and write AV 20 OA_Temp_BMS or AV 18 OA_Hum_BMS.
Network setup
- Default BACnet ID 77000; MS/TP default 38400 baud, Max Masters 127, Max Frames 20.
- Settings: hold Alarm and Enter > OTHER INFORMATION > PCOWEB / NET CONFIG > PCONET Settings (MS/TP) or PCOWEB Settings (IP/Ethernet).
- Save with Update pCOnet/pCOWeb = Yes, then cycle power to the controller.
Watch out for
- Static pressure integers are scaled x1000.
- BV 26 has no effect unless AV 1007 is set to 2 (BMS).
Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | CC_Temp | Cooling coil Discharge Air Temp | °F | Read | |
| AV | 2 | Comp_A_Cmd | Compressor A modulation command; range 0 to 100 | % | Read | |
| AV | 3 | DA_NAClg_SP | Discharge Air Temp neutral cooling setpoint; range 50 to 100; default 70 | °F | Write | |
| AV | 4 | DA_NAHtg_SP | Discharge Air Temp neutral heating setpoint; range 50 to 140; default 70 | °F | Write | |
| AV | 5 | DA_SP | Discharge Air Temp active setpoint | °F | Read | |
| AV | 6 | DA_SpcClg_SP | Discharge Air Temp space cooling setpoint; range 50 to 100; default 55 | °F | Write | |
| AV | 7 | DA_SpcHtCl_SP | Discharge Air Temp space heat mode cooling setpoint; range 50 to 100; default 55 | °F | Write | |
| AV | 8 | DA_SpcHtg_SP | Discharge Air Temp space heating setpoint; range 50 to 140; default 90 | °F | Write | |
| AVmin | 9 | DA_Temp | Discharge Air Temp | °F | Read | |
| AV | 10 | Damper_Cmd | Damper output command; range 0 to 100 | % | Read | |
| AV | 11 | DhOADP_SP | Dehumidification outside air dew point setpoint; range 50 to 100; default 58 | °F | Write | |
| AV | 12 | EF_Spd_Cmd | Exhaust fan speed command; range 15 to 100 | % | Read | |
| AV | 13 | ERV_DA_Temp | Energy recovery wheel Discharge Air Temp | °F | Read | |
| AV | 14 | Damper_BMS | Damper output BMS command; range 0 to 100 | % | Write | |
| AV | 15 | HX_Mod_Cmd | Heating modulation command; range 0 to 100 | % | Read | |
| AV | 16 | MA_Temp | Mixed air temperature | °F | Read | |
| AV | 17 | OA_Dew_Point | Outside air dew point | °F | Read | |
| AV | 18 | OA_Hum_BMS | Outside air humidity from BMS; used when OA_Hum_Sel = 1 | %RH | Write | |
| AV | 19 | OA_Hum_Raw | Outside air humidity | %RH | Read | |
| AV | 20 | OA_Temp_BMS | Outside air temp from BMS; used when OA_Temp_Sel = 1 | °F | Write | |
| AV | 21 | OA_Temp_Raw | Outside Air Temp | °F | Read | |
| AV | 22 | OAChgOv_SP | Outside air change over setpoint; range 45 to 80; default 65 | °F | Write | |
| AV | 23 | RH_A_Cmd | Reheat A modulation command; range 0 to 100 | % | Read | |
| AV | 24 | SF_Spd_Cmd | Supply fan speed command; range 0 to 100 | % | Read | |
| AV | 25 | Spc_Temp | Space temperature | °F | Read | |
| AV | 26 | SpcEffClgSP | Space effective cooling setpoint | °F | Read | |
| AV | 27 | SpcEffHtgSP | Space effective heating setpoint | °F | Read | |
| AVmin | 28 | SpcTempSP | Space temperature setpoint; range 65 to 85; default 72 | °F | Write | |
| AV | 29 | RA_Temp | Return air temperature | °F | Read | |
| AV | 30 | RA_Humidity | Return air humidity | %RH | Read | |
| AV | 31 | EA_Temp | Exhaust air temperature | °F | Read | |
| AV | 32 | EA_Humidity | Exhaust air humidity | %RH | Read | |
| AV | 33 | SF_BMS | Supply fan output BMS command; range 0 to 100 | % | Write | |
| AV | 34 | EF_BMS | Exhaust fan output BMS command; range 0 to 100 | % | Write | |
| AV | 35 | DA_Dh_SP | Discharge Air Temp dehumidification setpoint; range 50 to 100; default 70 | °F | Write | |
| AV | 36 | MinDmprSp | Minimum damper setpoint; range 0 to 100; default 10 | % | Write | |
| AV | 37 | EC_OADPLO_SP | Economizer outside air dew point lockout setpoint; range 0 to 120; default 58 | °F | Write | |
| AV | 38 | EC_OALO_SP | Economizer OAT lockout setpoint; range 0 to 120; default 60 | °F | Write | |
| AV | 39 | CO2DmprOsSP | CO2 minimum damper offset setpoint 2; range 0 to 100; default 10 | % | Write | |
| AVmin | 40 | DA_BMS_SP | Discharge Air Temp BMS setpoint; range 50 to 140 | °F | Write | |
| AV | 41 | RH_B_Cmd | Reheat B modulation command | % | Read | |
| AV | 42 | Comp_B_MCmd | Compressor B modulation command | % | Read | |
| AV | 1001 | Bldg_Pressure | Building static pressure | in. w.c. | Read | |
| AV | 1002 | Bldg_Press_SP | Building static pressure setpoint; range −500 to 500; default 100 | in. w.c. | Write | |
| AV | 1003 | Duct_Press_SP | Duct static pressure setpoint; range 0 to 2500; default 500 | in. w.c. | Write | |
| AV | 1004 | Spc_Hum | Space humidity | %RH | Read | |
| AV | 1005 | SpcHumSP | Space humidity setpoint; range 35 to 75; default 55 | %RH | Write | |
| AVmin | 1006 | State_Sel | State select; default 5 | Write | 2=AUTO, 3=COOL, 4=HEAT, 5=OFF | |
| AVmin | 1007 | OccMode_Sel | Occupied mode select; default 1 | Write | 0=Schedule, 1=Digital Input, 2=BMS | |
| AV | 1008 | Spc_CO2 | Space CO2 | ppm | Read | |
| AV | 1009 | SpcCO2SP | Space CO2 setpoint; range 0 to 2000; default 1000 | ppm | Write | |
| AV | 1010 | Duct_Pressure | Duct static pressure | in. w.c. | Read | |
| AV | 1011 | SF_CFM | Supply fan cfm | cfm | Read | |
| AV | 1012 | SF_CFM_SP | Supply fan cfm setpoint; default 3000 | cfm | Write | |
| AV | 1013 | EF_CFM | Exhaust fan cfm | cfm | Read | |
| AV | 1014 | EF_CFM_SP | Exhaust fan cfm setpoint; default 3000 | cfm | Write | |
| AV | 1015 | EF_CFMOs_SP | Exhaust fan cfm tracking offset setpoint; default 0 | cfm | Write | |
| AV | 1016 | OA_CFM | Outside air cfm | cfm | Read | |
| AV | 1017 | OA_CFM_SP | Outside air cfm setpoint; default 3000 | cfm | Write | |
| AV | 1018 | MIN_CFM_SP | Minimum outside air cfm setpoint; default 500 | cfm | Write | |
| AV | 1019 | MIN_CFMOsSP | Minimum outside air cfm offset setpoint; default 500 | cfm | Write | |
| BVmin | 1 | Alm_Rly_Cmd | Unit general alarm relay command | Read | 0=Off, 1=On | |
| BV | 2 | Comp_A_Alarm | Modulating compressor A alarm | Read | 0=Off, 1=On | |
| BV | 3 | Comp_B_Cmd | Compressor B command | Read | 0=Off, 1=On | |
| BV | 4 | Comp_C_Cmd | Compressor C command | Read | 0=Off, 1=On | |
| BV | 5 | Comp_D_Cmd | Compressor D command | Read | 0=Off, 1=On | |
| BV | 6 | EF_Cmd | Exhaust fan command | Read | 0=Off, 1=On | |
| BV | 7 | EF_Sts | Exhaust fan status | Read | 0=Off, 1=On | |
| BV | 8 | ERV_Cmd | Energy recovery wheel command | Read | 0=Off, 1=On | |
| BV | 10 | Ext_Switch_1 | External position switch 1 | Read | 0=Off, 1=On | |
| BV | 11 | Ext_Switch_2 | External position switch 2 | Read | 0=Off, 1=On | |
| BV | 12 | Htr_1_Sts | Gas heater 1 status | Read | 0=Off, 1=On | |
| BV | 13 | Htr_2_Sts | Gas heater 2 status | Read | 0=Off, 1=On | |
| BV | 14 | HX_Stg1_Cmd | Heating stage 1 command | Read | 0=Off, 1=On | |
| BV | 15 | HX_Stg2_Cmd | Heating stage 2 command | Read | 0=Off, 1=On | |
| BV | 16 | HX_Stg3_Cmd | Heating stage 3 command | Read | 0=Off, 1=On | |
| BV | 17 | HX_Stg4_Cmd | Heating stage 4 command | Read | 0=Off, 1=On | |
| BV | 18 | HX_Stg5_Cmd | Heating stage 5 command | Read | 0=Off, 1=On | |
| BV | 19 | HX_Stg6_Cmd | Heating stage 6 command | Read | 0=Off, 1=On | |
| BV | 20 | NA_Clg_Md | Neutral air cooling mode | Read | 0=Off, 1=On | |
| BV | 21 | NA_Dehum_Md | Neutral air dehumidification mode | Read | 0=Off, 1=On | |
| BV | 22 | NA_Htg_Md | Neutral air heating mode | Read | 0=Off, 1=On | |
| BV | 23 | OA_Hum_Sel | Share outside air humidity from BMS (0 = Probe, 1 = BMS); default Off | Write | 0=Off, 1=On | |
| BV | 24 | OA_Temp_Sel | Share OAT from BMS (0 = Probe, 1 = BMS); default Off | Write | 0=Off, 1=On | |
| BV | 25 | Occupied | Occupied mode status | Read | 0=Off, 1=On | |
| BVmin | 26 | Occupied_BMS | Occupied mode from BMS; used when OccMode_Sel = 2; default Off | Write | 0=Off, 1=On | |
| BV | 27 | Phase_Alarm | Phase protection alarm | Read | 0=Off, 1=On | |
| BV | 28 | Preheat_Cmd | Electric preheat command | Read | 0=Off, 1=On | |
| BV | 29 | RH_A_Alarm | Modulating reheat compressor A alarm | Read | 0=Off, 1=On | |
| BV | 30 | Safety_Sts | Safety input status | Read | 0=Normal, 1=Alarm | |
| BV | 31 | SF_Cmd | Supply fan command | Read | 0=Off, 1=On | |
| BVmin | 32 | SF_Sts | Supply fan status | Read | 0=Off, 1=On | |
| BV | 33 | Spc_Clg_Md | Space cooling mode | Read | 0=Off, 1=On | |
| BV | 34 | Spc_Dehum_Md | Space dehumidification mode | Read | 0=Off, 1=On | |
| BV | 35 | Spc_Htg_Md | Space heating mode | Read | 0=Off, 1=On | |
| BV | 36 | Spc_HtgClg_Md | Space heating cooling mode | Read | 0=Off, 1=On | |
| BV | 37 | Filter_Sts | Main or ERV dirty filter status | Read | 0=Off, 1=On | |
| BVmin | 38 | BMS_Alm_Rst | BMS alarm reset; default Off | Write | 0=Off, 1=On | |
| BVmin | 39 | Unit_Enable | Unit enable; default Off | Write | 0=Off, 1=On | |
| BV | 40 | Ext_Call_Fan | External call fan input (G) | Read | 0=Off, 1=On | |
| BV | 41 | Ext_Call_Heat | External call heat input (W1) | Read | 0=Off, 1=On | |
| BV | 42 | Ext_Call_Cool | External call cool input (Y1) | Read | 0=Off, 1=On | |
| BV | 43 | Ext_Call_Dh | External call dehumidification input | Read | 0=Off, 1=On | |
| BV | 44 | BMS_Call_Fan | BMS call fan input (G) | Write | 0=Off, 1=On | |
| BV | 45 | BMS_Call_Heat | BMS call heat input (W1) | Write | 0=Off, 1=On | |
| BV | 46 | BMS_Call_Cool | BMS call cool input (Y1) | Write | 0=Off, 1=On | |
| BV | 47 | BMS_Call_Dh | BMS call dehumidification input | Write | 0=Off, 1=On | |
| BV | 48 | Comp_B_Alarm | Modulating compressor B alarm | Read | 0=Off, 1=On |
No points match these filters.
Object ID lookup: Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 point IDs by name
AV1CC_TempAV2Comp_A_CmdAV3DA_NAClg_SPAV4DA_NAHtg_SPAV5DA_SPAV6DA_SpcClg_SPAV7DA_SpcHtCl_SPAV8DA_SpcHtg_SPAV9DA_TempAV10Damper_CmdAV11DhOADP_SPAV12EF_Spd_CmdAV13ERV_DA_TempAV14Damper_BMSAV15HX_Mod_CmdAV16MA_TempAV17OA_Dew_PointAV18OA_Hum_BMSAV19OA_Hum_RawAV20OA_Temp_BMSAV21OA_Temp_RawAV22OAChgOv_SPAV23RH_A_CmdAV24SF_Spd_CmdAV25Spc_TempAV26SpcEffClgSPAV27SpcEffHtgSPAV28SpcTempSPAV29RA_TempAV30RA_HumidityAV31EA_TempAV32EA_HumidityAV33SF_BMSAV34EF_BMSAV35DA_Dh_SPAV36MinDmprSpAV37EC_OADPLO_SPAV38EC_OALO_SPAV39CO2DmprOsSPAV40DA_BMS_SPAV41RH_B_CmdAV42Comp_B_MCmdAV1001Bldg_PressureAV1002Bldg_Press_SPAV1003Duct_Press_SPAV1004Spc_HumAV1005SpcHumSPAV1006State_SelAV1007OccMode_SelAV1008Spc_CO2AV1009SpcCO2SPAV1010Duct_PressureAV1011SF_CFMAV1012SF_CFM_SPAV1013EF_CFMAV1014EF_CFM_SPAV1015EF_CFMOs_SPAV1016OA_CFMAV1017OA_CFM_SPAV1018MIN_CFM_SPAV1019MIN_CFMOsSPBV1Alm_Rly_CmdBV2Comp_A_AlarmBV3Comp_B_CmdBV4Comp_C_CmdBV5Comp_D_CmdBV6EF_CmdBV7EF_StsBV8ERV_CmdBV10Ext_Switch_1BV11Ext_Switch_2BV12Htr_1_StsBV13Htr_2_StsBV14HX_Stg1_CmdBV15HX_Stg2_CmdBV16HX_Stg3_CmdBV17HX_Stg4_CmdBV18HX_Stg5_CmdBV19HX_Stg6_CmdBV20NA_Clg_MdBV21NA_Dehum_MdBV22NA_Htg_MdBV23OA_Hum_SelBV24OA_Temp_SelBV25OccupiedBV26Occupied_BMSBV27Phase_AlarmBV28Preheat_CmdBV29RH_A_AlarmBV30Safety_StsBV31SF_CmdBV32SF_StsBV33Spc_Clg_MdBV34Spc_Dehum_MdBV35Spc_Htg_MdBV36Spc_HtgClg_MdBV37Filter_StsBV38BMS_Alm_RstBV39Unit_EnableBV40Ext_Call_FanBV41Ext_Call_HeatBV42Ext_Call_CoolBV43Ext_Call_DhBV44BMS_Call_FanBV45BMS_Call_HeatBV46BMS_Call_CoolBV47BMS_Call_DhBV48Comp_B_Alarm
Integration notes
- Analog variables are AV 1-42, integer variables AV 1001-1019 and digital variables BV 1-48; BV 9 is not listed.
- Building and duct static pressure (AV 1001-1003, AV 1010) must be divided by 1000 in the BMS.
- Defaults and min/max are shown as printed; binary min/max columns give the off/on state text.
- Source: Table 30 BACnet Points List, guide pages 50-52.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)
How many BACnet points does the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) have?
This list has 108 BACnet objects: 61 analog values, 47 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet points are writable?
40 of the 108 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet documentation?
The source is Control System Guide for R7DA and Y Series, Options D19, D21, D22 and D23 (R7DA-Y-D19-D21-D22-D23 (05-26) 1024315-C), revision 2026-05, published free by Reznor at https://assets.reznorhvac.com/download/DA4B0977-C1A0-4675-A665-3DCFC911F756/R7DA-Y-D19-D21-D22-D23%20%2805-26%29%201024315-C.pdf.
What are the minimum BACnet points to integrate the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?
Start with BV 39 Unit_Enable (Unit enable); BV 26 Occupied_BMS (Occupancy command (needs AV 1007 = 2)); AV 1007 OccMode_Sel (Occupancy source: 0 schedule, 1 input, 2 BMS); AV 1006 State_Sel (Unit state: 2 auto, 3 cool, 4 heat, 5 off); AV 28 SpcTempSP (Space temperature setpoint, 65-85 °F); AV 40 DA_BMS_SP (Discharge air setpoint from the BMS (D22)); BV 38 BMS_Alm_Rst (Alarm reset); BV 32 SF_Sts (Supply fan status); AV 9 DA_Temp (Discharge air temperature); BV 1 Alm_Rly_Cmd (General alarm relay on).
How do I enable BMS control of the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?
BV 39 Unit_Enable enables the unit. Occupancy comes from the schedule, a digital input or the BMS, chosen with AV 1007 OccMode_Sel; with 2 = BMS, BV 26 Occupied_BMS sets occupancy. AV 1006 State_Sel picks auto, cool, heat or off. BV 44-47 are BMS fan, heat, cool and dehumidify calls, and on D22 AV 40 DA_BMS_SP is the BMS discharge air setpoint.
Can the BMS supply sensor values to the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?
Set BV 24 OA_Temp_Sel or BV 23 OA_Hum_Sel to 1 (BMS) and write AV 20 OA_Temp_BMS or AV 18 OA_Hum_BMS.
How do I check these points on the real R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Reznor BACnet points lists
- Packaged rooftop unit / DOAS controller
Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list)
Reznor MAPS III units (from March 2010) and MAPS IV units with control option D15, D16, D17 or D18 and the IQ system controller (software 2.01), including the optional energy recovery module (ERM).
Also known as: MAPS III, MAPS IV, MAPSIII&IV-D15-D16-D17-D18-D19-D21, RCB, RDB, RDCB, RDDB, RECB, REDB, RCC, RDC, RDCC, RDDC, RECC, REDC, CP-MAPS-D15/D16/D17/D18, 254003R8, IQ Controller, IQ System Controller, D15, D16, D17, D18, MAPS ERM - Packaged rooftop unit / DOAS controller
Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list)
Reznor MAPS III and MAPS IV modular air processing units (packaged DX rooftop units for high outside air) with control option D19.
Also known as: MAPS III, MAPS IV, MAPSIII&IV-D15-D16-D17-D18-D19-D21, RCB, RDB, RDCB, RDDB, RECB, REDB, RCC, RDC, RDCC, RDDC, RECC, REDC, CP-MAPSIII-D19, D303069, Option D19, D19 - Packaged rooftop unit / DOAS controller
Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list)
Reznor MAPS III and MAPS IV modular air processing units (packaged DX rooftop units) with control option D21 (space temperature control).
Also known as: MAPS III, MAPS IV, MAPSIII&IV-D15-D16-D17-D18-D19-D21, RCB, RDB, RDCB, RDDB, RECB, REDB, RCC, RDC, RDCC, RDDC, RECC, REDC, CP-MAPSIII-D21, D303070, Option D21, D21 - Air handling unit / make-up air controller
Reznor PREEVA Air Handler Controls CP-AHU D19 / D21 / D22 (BACnet MS/TP Option BHB8)
Discontinued Reznor PREEVA air handlers (PDH, PEH, PXH, RDH, REH, RHH, RXH, SDH, SHH) with control option D19, D21 or D22 and the BACnet MS/TP communication card (option BHB8).
Also known as: CP-AHU D19_D21_D22, D303072-A, PREEVA-CONTROLS, D19, D21, D22, BHB8, PDH, PEH, PXH, RDH, REH, RHH, RXH, SDH, SHH, Preeva - Energy recovery / DOAS heat pump ventilation unit controller
Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8)
Discontinued Reznor ZQYRA ventilation units (energy recovery wheel with heat pump) fitted with the BACnet MS/TP option BHB8.
Also known as: ZQYRA, ZQYRA-IOM, 260414-A, BHB8, Reznor ZQYRA
Source: Control System Guide for R7DA and Y Series, Options D19, D21, D22 and D23 · R7DA-Y-D19-D21-D22-D23 (05-26) 1024315-C · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.