Easy BACnet
  1. Home
  2. BACnet points lists
  3. Reznor
  4. R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)

Packaged rooftop unit controller · BACnet points list

Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet points list

Updated 12 November 2026

Short answer

R7DA and Y series packaged rooftop units with controls D19, D21, D22 or D23 use a programmable system controller that accepts a BACnet MS/TP card (option BHB8) or a BACnet IP/Ethernet card (option BHB9). The point list has 42 analog variables (AV 1-42), 19 integer variables (AV 1001-1019) and 47 digital variables (BV 1-48). The BMS can enable the unit, set occupancy and state, write discharge and space setpoints, send fan/heat/cool/dehumidify calls, share outdoor temperature and humidity, and command damper and fan outputs.

This page lists 108 BACnet objects for the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reznor’s own free documentation, linked below.

Manufacturer
Reznor
Model
R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)
Equipment
Packaged rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
108 (40 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
77000
Also known as
R7DA, Reznor Y series, R7DA-Y-D19-D21-D22-D23, 1024315-C, CP-P125-R7DA-D19-D21-D22-D23, 1024315-B, D19, D21, D22, D23, BHB8, BHB9, P125
Source document
Control System Guide for R7DA and Y Series, Options D19, D21, D22 and D23 · R7DA-Y-D19-D21-D22-D23 (05-26) 1024315-C · rev. 2026-05
Download CSV 108 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Reznor’s current documentation and the live device before use. Not official Reznor information. Terms of use.

BMS integration notes: Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)

Integration in brief

Fit the BHB8 MS/TP or BHB9 IP/Ethernet card and set the BACnet ID (default 77000), baud/MAC or IP settings from the controller's PCOWEB / NET CONFIG menu, then cycle power. Enable the unit with BV 39, set OccMode_Sel (AV 1007) to 2 and command occupancy with BV 26, pick the state with AV 1006 and write the setpoints. Monitor supply fan status, discharge temperature and the general alarm relay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 39Unit_EnableUnit enableWrite
BV 26Occupied_BMSOccupancy command (needs AV 1007 = 2)Write
AV 1007OccMode_SelOccupancy source: 0 schedule, 1 input, 2 BMSWrite
AV 1006State_SelUnit state: 2 auto, 3 cool, 4 heat, 5 offWrite
AV 28SpcTempSPSpace temperature setpoint, 65-85 °FWrite
AV 40DA_BMS_SPDischarge air setpoint from the BMS (D22)Write
BV 38BMS_Alm_RstAlarm resetWrite
BV 32SF_StsSupply fan statusRead
AV 9DA_TempDischarge air temperatureRead
BV 1Alm_Rly_CmdGeneral alarm relay onRead

Enable & remote start

BV 39 Unit_Enable enables the unit. Occupancy comes from the schedule, a digital input or the BMS, chosen with AV 1007 OccMode_Sel; with 2 = BMS, BV 26 Occupied_BMS sets occupancy. AV 1006 State_Sel picks auto, cool, heat or off. BV 44-47 are BMS fan, heat, cool and dehumidify calls, and on D22 AV 40 DA_BMS_SP is the BMS discharge air setpoint.

Sensors & values from the BMS

Set BV 24 OA_Temp_Sel or BV 23 OA_Hum_Sel to 1 (BMS) and write AV 20 OA_Temp_BMS or AV 18 OA_Hum_BMS.

Network setup

Watch out for

Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

108 of 108 shown
Type
AnalogBinary
Access
Show
Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet Points List
DescriptionStates
AV1CC_TempCooling coil Discharge Air Temp°FRead
AV2Comp_A_CmdCompressor A modulation command; range 0 to 100%Read
AV3DA_NAClg_SPDischarge Air Temp neutral cooling setpoint; range 50 to 100; default 70°FWrite
AV4DA_NAHtg_SPDischarge Air Temp neutral heating setpoint; range 50 to 140; default 70°FWrite
AV5DA_SPDischarge Air Temp active setpoint°FRead
AV6DA_SpcClg_SPDischarge Air Temp space cooling setpoint; range 50 to 100; default 55°FWrite
AV7DA_SpcHtCl_SPDischarge Air Temp space heat mode cooling setpoint; range 50 to 100; default 55°FWrite
AV8DA_SpcHtg_SPDischarge Air Temp space heating setpoint; range 50 to 140; default 90°FWrite
AVmin9DA_TempDischarge Air Temp°FRead
AV10Damper_CmdDamper output command; range 0 to 100%Read
AV11DhOADP_SPDehumidification outside air dew point setpoint; range 50 to 100; default 58°FWrite
AV12EF_Spd_CmdExhaust fan speed command; range 15 to 100%Read
AV13ERV_DA_TempEnergy recovery wheel Discharge Air Temp°FRead
AV14Damper_BMSDamper output BMS command; range 0 to 100%Write
AV15HX_Mod_CmdHeating modulation command; range 0 to 100%Read
AV16MA_TempMixed air temperature°FRead
AV17OA_Dew_PointOutside air dew point°FRead
AV18OA_Hum_BMSOutside air humidity from BMS; used when OA_Hum_Sel = 1%RHWrite
AV19OA_Hum_RawOutside air humidity%RHRead
AV20OA_Temp_BMSOutside air temp from BMS; used when OA_Temp_Sel = 1°FWrite
AV21OA_Temp_RawOutside Air Temp°FRead
AV22OAChgOv_SPOutside air change over setpoint; range 45 to 80; default 65°FWrite
AV23RH_A_CmdReheat A modulation command; range 0 to 100%Read
AV24SF_Spd_CmdSupply fan speed command; range 0 to 100%Read
AV25Spc_TempSpace temperature°FRead
AV26SpcEffClgSPSpace effective cooling setpoint°FRead
AV27SpcEffHtgSPSpace effective heating setpoint°FRead
AVmin28SpcTempSPSpace temperature setpoint; range 65 to 85; default 72°FWrite
AV29RA_TempReturn air temperature°FRead
AV30RA_HumidityReturn air humidity%RHRead
AV31EA_TempExhaust air temperature°FRead
AV32EA_HumidityExhaust air humidity%RHRead
AV33SF_BMSSupply fan output BMS command; range 0 to 100%Write
AV34EF_BMSExhaust fan output BMS command; range 0 to 100%Write
AV35DA_Dh_SPDischarge Air Temp dehumidification setpoint; range 50 to 100; default 70°FWrite
AV36MinDmprSpMinimum damper setpoint; range 0 to 100; default 10%Write
AV37EC_OADPLO_SPEconomizer outside air dew point lockout setpoint; range 0 to 120; default 58°FWrite
AV38EC_OALO_SPEconomizer OAT lockout setpoint; range 0 to 120; default 60°FWrite
AV39CO2DmprOsSPCO2 minimum damper offset setpoint 2; range 0 to 100; default 10%Write
AVmin40DA_BMS_SPDischarge Air Temp BMS setpoint; range 50 to 140°FWrite
AV41RH_B_CmdReheat B modulation command%Read
AV42Comp_B_MCmdCompressor B modulation command%Read
AV1001Bldg_PressureBuilding static pressurein. w.c.Read
AV1002Bldg_Press_SPBuilding static pressure setpoint; range −500 to 500; default 100in. w.c.Write
AV1003Duct_Press_SPDuct static pressure setpoint; range 0 to 2500; default 500in. w.c.Write
AV1004Spc_HumSpace humidity%RHRead
AV1005SpcHumSPSpace humidity setpoint; range 35 to 75; default 55%RHWrite
AVmin1006State_SelState select; default 5Write2=AUTO, 3=COOL, 4=HEAT, 5=OFF
AVmin1007OccMode_SelOccupied mode select; default 1Write0=Schedule, 1=Digital Input, 2=BMS
AV1008Spc_CO2Space CO2ppmRead
AV1009SpcCO2SPSpace CO2 setpoint; range 0 to 2000; default 1000ppmWrite
AV1010Duct_PressureDuct static pressurein. w.c.Read
AV1011SF_CFMSupply fan cfmcfmRead
AV1012SF_CFM_SPSupply fan cfm setpoint; default 3000cfmWrite
AV1013EF_CFMExhaust fan cfmcfmRead
AV1014EF_CFM_SPExhaust fan cfm setpoint; default 3000cfmWrite
AV1015EF_CFMOs_SPExhaust fan cfm tracking offset setpoint; default 0cfmWrite
AV1016OA_CFMOutside air cfmcfmRead
AV1017OA_CFM_SPOutside air cfm setpoint; default 3000cfmWrite
AV1018MIN_CFM_SPMinimum outside air cfm setpoint; default 500cfmWrite
AV1019MIN_CFMOsSPMinimum outside air cfm offset setpoint; default 500cfmWrite
BVmin1Alm_Rly_CmdUnit general alarm relay commandRead0=Off, 1=On
BV2Comp_A_AlarmModulating compressor A alarmRead0=Off, 1=On
BV3Comp_B_CmdCompressor B commandRead0=Off, 1=On
BV4Comp_C_CmdCompressor C commandRead0=Off, 1=On
BV5Comp_D_CmdCompressor D commandRead0=Off, 1=On
BV6EF_CmdExhaust fan commandRead0=Off, 1=On
BV7EF_StsExhaust fan statusRead0=Off, 1=On
BV8ERV_CmdEnergy recovery wheel commandRead0=Off, 1=On
BV10Ext_Switch_1External position switch 1Read0=Off, 1=On
BV11Ext_Switch_2External position switch 2Read0=Off, 1=On
BV12Htr_1_StsGas heater 1 statusRead0=Off, 1=On
BV13Htr_2_StsGas heater 2 statusRead0=Off, 1=On
BV14HX_Stg1_CmdHeating stage 1 commandRead0=Off, 1=On
BV15HX_Stg2_CmdHeating stage 2 commandRead0=Off, 1=On
BV16HX_Stg3_CmdHeating stage 3 commandRead0=Off, 1=On
BV17HX_Stg4_CmdHeating stage 4 commandRead0=Off, 1=On
BV18HX_Stg5_CmdHeating stage 5 commandRead0=Off, 1=On
BV19HX_Stg6_CmdHeating stage 6 commandRead0=Off, 1=On
BV20NA_Clg_MdNeutral air cooling modeRead0=Off, 1=On
BV21NA_Dehum_MdNeutral air dehumidification modeRead0=Off, 1=On
BV22NA_Htg_MdNeutral air heating modeRead0=Off, 1=On
BV23OA_Hum_SelShare outside air humidity from BMS (0 = Probe, 1 = BMS); default OffWrite0=Off, 1=On
BV24OA_Temp_SelShare OAT from BMS (0 = Probe, 1 = BMS); default OffWrite0=Off, 1=On
BV25OccupiedOccupied mode statusRead0=Off, 1=On
BVmin26Occupied_BMSOccupied mode from BMS; used when OccMode_Sel = 2; default OffWrite0=Off, 1=On
BV27Phase_AlarmPhase protection alarmRead0=Off, 1=On
BV28Preheat_CmdElectric preheat commandRead0=Off, 1=On
BV29RH_A_AlarmModulating reheat compressor A alarmRead0=Off, 1=On
BV30Safety_StsSafety input statusRead0=Normal, 1=Alarm
BV31SF_CmdSupply fan commandRead0=Off, 1=On
BVmin32SF_StsSupply fan statusRead0=Off, 1=On
BV33Spc_Clg_MdSpace cooling modeRead0=Off, 1=On
BV34Spc_Dehum_MdSpace dehumidification modeRead0=Off, 1=On
BV35Spc_Htg_MdSpace heating modeRead0=Off, 1=On
BV36Spc_HtgClg_MdSpace heating cooling modeRead0=Off, 1=On
BV37Filter_StsMain or ERV dirty filter statusRead0=Off, 1=On
BVmin38BMS_Alm_RstBMS alarm reset; default OffWrite0=Off, 1=On
BVmin39Unit_EnableUnit enable; default OffWrite0=Off, 1=On
BV40Ext_Call_FanExternal call fan input (G)Read0=Off, 1=On
BV41Ext_Call_HeatExternal call heat input (W1)Read0=Off, 1=On
BV42Ext_Call_CoolExternal call cool input (Y1)Read0=Off, 1=On
BV43Ext_Call_DhExternal call dehumidification inputRead0=Off, 1=On
BV44BMS_Call_FanBMS call fan input (G)Write0=Off, 1=On
BV45BMS_Call_HeatBMS call heat input (W1)Write0=Off, 1=On
BV46BMS_Call_CoolBMS call cool input (Y1)Write0=Off, 1=On
BV47BMS_Call_DhBMS call dehumidification inputWrite0=Off, 1=On
BV48Comp_B_AlarmModulating compressor B alarmRead0=Off, 1=On
Object ID lookup: Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)

How many BACnet points does the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) have?

This list has 108 BACnet objects: 61 analog values, 47 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet points are writable?

40 of the 108 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9) BACnet documentation?

The source is Control System Guide for R7DA and Y Series, Options D19, D21, D22 and D23 (R7DA-Y-D19-D21-D22-D23 (05-26) 1024315-C), revision 2026-05, published free by Reznor at https://assets.reznorhvac.com/download/DA4B0977-C1A0-4675-A665-3DCFC911F756/R7DA-Y-D19-D21-D22-D23%20%2805-26%29%201024315-C.pdf.

What are the minimum BACnet points to integrate the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?

Start with BV 39 Unit_Enable (Unit enable); BV 26 Occupied_BMS (Occupancy command (needs AV 1007 = 2)); AV 1007 OccMode_Sel (Occupancy source: 0 schedule, 1 input, 2 BMS); AV 1006 State_Sel (Unit state: 2 auto, 3 cool, 4 heat, 5 off); AV 28 SpcTempSP (Space temperature setpoint, 65-85 °F); AV 40 DA_BMS_SP (Discharge air setpoint from the BMS (D22)); BV 38 BMS_Alm_Rst (Alarm reset); BV 32 SF_Sts (Supply fan status); AV 9 DA_Temp (Discharge air temperature); BV 1 Alm_Rly_Cmd (General alarm relay on).

How do I enable BMS control of the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?

BV 39 Unit_Enable enables the unit. Occupancy comes from the schedule, a digital input or the BMS, chosen with AV 1007 OccMode_Sel; with 2 = BMS, BV 26 Occupied_BMS sets occupancy. AV 1006 State_Sel picks auto, cool, heat or off. BV 44-47 are BMS fan, heat, cool and dehumidify calls, and on D22 AV 40 DA_BMS_SP is the BMS discharge air setpoint.

Can the BMS supply sensor values to the Reznor R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?

Set BV 24 OA_Temp_Sel or BV 23 OA_Hum_Sel to 1 (BMS) and write AV 20 OA_Temp_BMS or AV 18 OA_Hum_BMS.

How do I check these points on the real R7DA and Y Series Rooftop Controls, Options D19 / D21 / D22 / D23 (BACnet card BHB8 / BHB9)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Reznor BACnet points lists

Source: Control System Guide for R7DA and Y Series, Options D19, D21, D22 and D23 · R7DA-Y-D19-D21-D22-D23 (05-26) 1024315-C · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.