Packaged rooftop unit / DOAS controller · BACnet points list

Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) BACnet points list

Updated 12 November 2026

Short answer

MAPS III and MAPS IV units with control options D15-D18 use the Reznor IQ system controller, which speaks BACnet over MS/TP as standard (BACnet over ARCNET and LonWorks are options). The network point list has about 230 objects: occupancy and BAS on/off commands, space, neutral air and discharge air setpoints, fan, damper and economizer settings for each control option, heating, cooling and reheat settings, alarm flags, output status and the energy recovery module interface.

This page lists 227 BACnet objects for the Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) — 87 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reznor’s own free documentation, linked below.

Manufacturer
Reznor
Model
MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list)
Equipment
Packaged rooftop unit / DOAS controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
227 (87 writable)
Transport
BACnet MS/TP, BACnet over ARCNET
Firmware
IQ controller software 2.01
Default device instance
2402
Also known as
MAPS III, MAPS IV, MAPSIII&IV-D15-D16-D17-D18-D19-D21, RCB, RDB, RDCB, RDDB, RECB, REDB, RCC, RDC, RDCC, RDDC, RECC, REDC, CP-MAPS-D15/D16/D17/D18, 254003R8, IQ Controller, IQ System Controller, D15, D16, D17, D18, MAPS ERM
Source document
Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) · MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A · rev. 2026-06
Download CSV 227 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Reznor’s current documentation and the live device before use. Not official Reznor information. Terms of use.

BMS integration notes: Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list)

Integration in brief

Set the IQ controller's MS/TP baud and address on its DIP and rotary switches and the network number and device instance in the BACnet menu. If the schedule is configured for BAS control, command occupancy with BV 50 and on/off with BV 51, then write the occupied space setpoints or the neutral air setpoint. Monitor unit mode, occupancy status, the system shutdown flag and the alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 51bas_on_off_cmd_1BAS on/off (schedule set for BAS)Write
BV 50bas_occ_unocc_cmd_1BAS occupied/unoccupied (schedule set for BAS)Write
AV 100occ_cool_sp_1Occupied space cooling setpointWrite
AV 101occ_heat_sp_1Occupied space heating setpointWrite
AV 150na_stpt_1Neutral air / discharge air setpointWrite
BV 178bas_reset_sys_shtdwn_1Reset a system shutdownWrite
AV 175unit_mode_1Current unit modeRead
BV 54occ_status_1Occupancy statusRead
BV 191shutdown_fail_1Unit shut down on alarmRead
BV 176sf_fail_1Supply fan failureRead

Enable & remote start

BV 50 bas_occ_unocc_cmd_1 and BV 51 bas_on_off_cmd_1 control occupancy and on/off, but only when BAS control is selected in the schedule configuration. AV 52 lets a BACnet schedule pass minutes-until-occupied for optimum start. BV 178 resets a system shutdown.

Network setup

Watch out for

Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

227 of 227 shown
Type
AnalogBinaryMulti-state
Access
Show
Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) BACnet Points List
DescriptionStates
AV52bas_min_til_occ_1BAS Min Until OCC - Minutes until next occupied stateWrite
AV55min_til_occ_1Minutes Until Occupied - Minutes until next occupied stateRead
AVmin100occ_cool_sp_1Occupied Space Cool Setpoint - Occupied Space Cooling SetpointWrite
AVmin101occ_heat_sp_1Occupied Space Heat Setpoint - Occupied Space Heating SetpointWrite
AV102unocc_cool_sp_1Unoccupied Space Cool Setpoint - Unoccupied Space Cooling SetpointWrite
AV103unocc_heat_sp_1Unoccupied Space Heat Setpoint - Unoccupied Space Heating SetpointWrite
AV108mcd_temp_stpt_1Morning Cool-Down Space Temp Setpoint - Used when system is set to NA ControlWrite
AV109mwu_temp_stpt_1Morning Warm-Up Space Temp Setpoint - Used when system is set to NA ControlWrite
AVmin150na_stpt_1Neutral Air Setpoint - The Neutral Air Discharge Air SetpointWrite
AV151na_sp_gap_1NA Htg/Clg Offset - Used for offsetting the heating and cooling setpointsWrite
AV152na_reset_high_setpt_1NA High Reset Setpoint - Used for resetting Neutral Air Discharge Air Setpoint basedWrite
AV153na_reset_low_setpt_1NA Low Reset Setpoint - Used for resetting Neutral Air Discharge Air Setpoint basedWrite
AV154oat_high_setpt_1OAT High Reset Setpoint - Used for resetting Neutral Air Discharge Air Setpoint basedWrite
AV155oat_low_setpt_1OAT Low Reset Setpoint - Used for resetting Neutral Air Discharge Air Setpoint basedWrite
AVmin175unit_mode_1Current unit modeRead1=Test Mode, 2=Unoccupied, 4=BadSensor, 5=SysRestart, 6=SysShutdwn, 7=PhaseLoss, 8=SmokeAlrm, 9=No Flow, 10=Vent Mode, 11=Cooling, 12=Heating, 13=Free Cooling, 14=Morning Cool Down, 15=Morning Warm Up, 16=Dehumid+Clg, 17=Dehumid+Htg, 18=Dehumid+Vent, 19=Night Setback/Clg, 20=Night Setback/Htg, 21=Night Setback/Dehum
AV177man_off_mode_1Manual Mode Off ConditionRead
AV179vfd_minspd_param_1Minimum VFD Speed - Only available when VFD installedWrite
AV180stp_stpt_param_1Static Pressure SetpointWrite
AV181bpress_stpt_param_1Building Pressure SetpointWrite
AV182co2_setpt_1CO2 SetpointWrite
AV183ws3spd_low_sfvfd_1Low SF VFD SpeedWrite
AV184ws3spd_med_sfvfd_1Medium SF VFD SpeedWrite
AV185ws3spd_high_sfvfd_1High SF VFD SpeedWrite
AV186four_spd_opn_sfvfdmin_1Open SF VFD SpeedWrite
AV187four_spd_in1_sfvfdmin_1Input 1 SF VFD SpeedWrite
AV188four_spd_in2_sfvfdmin_1Input 2 SF VFD SpeedWrite
AV189four_spd_cls_sfvfdmin_1Closed SF VFD SpeedWrite
AV190vfd_speed_setpt_1VFD Constant Volume SpeedWrite
AV192dmp_2pos_cmd_1Damper 2 pos CmdWrite
AV193hi_oa_dmp_pos_1High OA Enth Damper PosWrite
AV194lo_oa_dmp_pos_1Low OA Enth Damper PosWrite
AV195oae_setpt_dmp_1OA Enth Damper Changeover SetptWrite
AV196mat_setpt_status_1Active MAT SetpointRead
AV197mat_setpt_offset_1MAT Setpt Offset - Only used in D15 ApplicationWrite
AV198mat_setpt_1MAT Setpt - Only used in D16 ApplicationWrite
AV200sp_adjust_range_1Setpt Adjust Range - Used to limit adjustable range of Wall Temperature SensorWrite
AV201sptsens_1Space TemperatureRead
AV202spt_adj_1Wall Temperature Sensor Setpoint Adjustment - Wall Temperature Sensor adjustment rangeRead
AV203ovrd_out_1Space Occupancy Override Time RemainingRead
AV205ws_mode_ao_1Wall Temperature Sensor Mode Request as AORead
AV207fan_lvl_out_1Wall Temperature Sensor Fan Speed Request as AORead
AV230effective_cool_sp_1Active Cool Setpoint - Active Space/Discharge Air Cooling SetpointRead
AV231effective_heat_sp_1Active Heat Setpoint - Active Space/Discharge Air Heating SetpointRead
AV240cool_mode_lockout_setpt_1Cooling Mode Lockout TempWrite
AV241mode_xover_1Mode Changeover Timer - Minimum time between heating and cooling modeWrite
AV244active_clg_stgs_1Active Clg Stages - Current number of cooling stages being requestedRead
AV245num_clg_stgs_1Number of stages Available - Number of available cooling stagesRead
AV246clg_ctrl_temp_1Active Clg Control TempRead
AV247clg_ctrlng_sp_1Active Clg Controlling Setpt - Active cooling control setpoint (Space clg SetpointRead
AV248na_clg_dbnd_1Neutral Air Cooling Temp DeadbandWrite
AV249sc_clg_dbnd_1Space override Cooling Temp DeadbandWrite
AV275heat_mode_lockout_setpt_1Heating Mode Lockout TempWrite
AV276active_htg_stgs_1Active Heating Stg Req - Current number of heating stages being requestedRead
AV277available_htg_stgs_1Available Heating Stages - Number of available heating stagesRead
AV278active_htg_ctr_sp_1Active heating DAT control Setpoint - Active Heating DAT setpointRead
AV279sc_delta_high_1Space deltaT High SetpointWrite
AV280sc_delta_low_1Space deltaT Low SetpointWrite
AV281sc_htdat_high_1Heating DAT High SetpointWrite
AV282sc_htdat_low_1Heating DAT Low SetpointWrite
AV283htg_enable_db_1Heating Enable DeadbandWrite
AV284ht_staging_dbnd_1Heat staging DeadbandWrite
AV300compa_runtime_1Comp A Runtime - Current runtime in Hours (Only used when compressor installed)Read
AV301compb_runtime_1Comp B Runtime - Current runtime in Hours (Only used when compressor installed)Read
AV302compc_runtime_1Comp C Runtime - Current runtime in Hours (Only used when compressor installed)Read
AV303compd_runtime_1Comp D Runtime - Current runtime in Hours (Only used when compressor installed)Read
AV304sf_runtime_1Supply Fan Runtime - Current runtime in HoursRead
AV305reheat_runtime_1Reheat Pump Runtime - Current runtime in Hours (Only used when ReHeat Pump installed)Read
AV312dat_1DATRead
AV313oat_1OA TempRead
AV314space_hum_1Space HumRead
AV315oa_hum_1OA HumRead
AV316mat_1MATRead
AV317cc_dat_1Clg Coil DATRead
AV318mod_heat_1Modulating HeatRead
AV319damper_ctrl_1Damper ControlRead
AV320oad_1OA DewpointRead
AV324pressure_1PressureRead
AV325sf_vfd_speed_1SF VFD SpeedRead
AV326mod_reheat_1Modulating ReheatRead
AV327mod_clg_out_1Modulating Cooling OutputRead
AV328ex_fan_vfd_1Exhaust Fan VFD SpeedRead
AV338ERM_dat_1ERM DATRead
AV339ERM_hum_1ERM HumRead
AV340var_fan_spd_manual_1AI VFD Manual Input 0- 10VdcRead
AV341co2_1CO2Read
AV344ERM_1ERM CommandRead
AV414compa_rt_alm_limit_1Comp A Runtime Alarm LimitWrite
AV416compb_rt_alm_limit_1Comp B Runtime Alarm LimitWrite
AV418compc_rt_alm_limit_1Comp C Runtime Alarm LimitWrite
AV420compd_rt_alm_limit_1Comp D Runtime Alarm LimitWrite
AV422saf_rt_alam_limit_1SAF Runtime Alarm limitWrite
AV424reht_rt_alm_limit_1Reheat Runtime Alarm LimitWrite
AV500na_rhlock_stpt_1Reheat Lockout Setpoint - When the OA dewpoint is below this setpoint the ReheatWrite
AV501spc_hum_stpt_1Space Humidity Setpoint - When the space humidity is below this setpoint the ReheatWrite
AV502sc_unocchum_stpt_1Unoccupied Humidity Setpoint - If space humidity is above this setpoint during unoccupied conditionsWrite
AV503sc_unocchum_dbnd_1Unocc Humidity Deadband - The system will remain in Unoccupied dehumidification mode untilWrite
AV504cc_dat_stpt_1Cooling Coil DA Temp SetpointWrite
AV505cc_dat_db_1Cooling Coil DA Temp DeadbandWrite
AV506dat_sp_4fc_1DAT Setpt for Fast CoolWrite
AV507dat_sp_4fh_1DAT Setpt for Fast HeatWrite
AV508sc_delta_high_dehum_1Space deltaT High Setpoint in DehumidWrite
AV509sc_delta_low_dehum_1Space deltaT Low Setpoint in DehumidWrite
AV510sc_htdat_high_dehum_1Heating DAT High Setpoint in DehumidWrite
AV511sc_htdat_low_dehum_1Heating DAT Low Setpoint in DehumidWrite
AV601main_erv_rat_1ERV RATRead
AV602main_erv_rah_1Main ERV RA HumRead
AV603main_erv_saf_press_1Main ERV SAF PressRead
AV604main_erv_eaf_press_1Main ERV EAF PressRead
AV605main_erv_saf_spd_cmd_1Main ERV SAF SpeedRead
AV606main_erv_eaf_spd_cmd_1Main ERV EAF SpeedRead
AV614main_erv_mode_1Main ERV ModeRead
AV615main_erv_ra_enth_1ERV RA EnthalpyRead
AV616main_erv_ra_dewpt_1ERV RA DewpointRead
AV617main_erm_saf_vfd_speed_1ERM VFD Constant Volume SpeedWrite
AV618main_erm_savfd_press_setpt_1SA VFD Pressure Setpt - Energy Recovery Supply Air Fan VFD Pressure SetpointWrite
AV619main_erm_savfd_press_setpt_db_1SA VFD Pressure Setpt Deadband - Energy Recovery Supply Air Fan VFD Pressure DeadbandWrite
AV620main_erm_eaf_vfd_speed_1ERM EAF Constant Volume SpeedWrite
AV621main_erm_eavfd_press_setpt_1EA VFD Pressure Setpt - Energy Recovery Exhaust Air Fan VFD Pressure SetpointWrite
AV622main_erm_eavfd_press_setpt_db_1EA VFD Pressure Setpt Deadband - Energy Recovery Exhaust Air Fan VFD Pressure DeadbandWrite
AV623main_erm_eaf_vfd_offset_1ERM EAF VFD Offset - Energy Recovery Exhaust Air Fan VFD Offset SetpointWrite
AV625main_erv_dat_1ERV DATRead
AV626main_erv_oat_1ERV OATRead
BV6comm_loss_alarm_1COMM_LOSSRead
BVmin50bas_occ_unocc_cmd_1BAS Occ/Unocc Control - Binary value to control occupied and unoccupied modeWrite
BVmin51bas_on_off_cmd_1BAS On/Off - Binary value to control On and Off modeWrite
BV53schedule_1Bacnet Schedule Object - BACnet schedule object, Used only when selected in schedule configurationWrite
BVmin54occ_status_1Occupancy Status - Current occupancy StatusReadOn=Occupied
BV80erm_dat_bad_1ERM Wheel DAT- Sensor BadRead
BV82erm_rat_bad_1ERM Return Air Temp- Sensor BadRead
BV83er_wheel_fail_1ER Wheel FailRead
BV84erm_saf_fail_1ERM SAF FailRead
BV85erm_eaf_fail_1ERM EAF FailRead
BV86erm_filter_alm_1ERM Filter AlarmRead
BV87ermrahum_bad_1ERM RA Humidity- Sensor BadRead
BVmin176sf_fail_1Supply Fan FailureRead
BVmin178bas_reset_sys_shtdwn_1BAS Reset System ShutdownWrite
BVmin191shutdown_fail_1System Shutdown Mode - Active when unit is shutdown due to alarmRead
BV242allow_night_setbk_1Allow Night Setback - Allow the system to stage cooling at night to maintainWrite
BV243allow_optimal_start_1Allow Optimal Start - Allow the system to start fan based on an optimumWrite
BV306sa_fan_cmd_1Supply Fan CommandRead
BV307reheat_cmd_1Reheat CommandRead
BV308comp_a_cmd_1Comp A CommandRead
BV309comp_b_cmd_1Comp B CommandRead
BV310comp_c_cmd_1Comp C CommandRead
BV311comp_d_cmd_1Comp D CommandRead
BV322filter_status_1Filter StatusRead
BV323fan_status_1Fan StatusRead
BV329phase_loss_1Phase LossRead
BV330smoke_detector_1Smoke Detector Input StatusRead
BV331reheat_comp_stat_out_1Reheat Comp StatusRead
BV332comp_a_stat_out_1Comp A StatusRead
BV333comp_b_stat_out_1Comp B StatusRead
BV334comp_c_stat_out_1Comp C StatusRead
BV335comp_d_stat_out_1Comp D StatusRead
BV336status_input_1_out_1DI Status Input 1Read
BV337status_input_2_out_1DI Status Input 2Read
BV342start_stop_cmd_1DI Start/Stop Command Manual InputRead
BV343occ_cmd_manual_1DI Occupancy Command Manual InputRead
BV345exh_fan_1Exhaust Fan CommandRead
BV346oae_1OA EnthalpyRead
BV347clg_lck_state_1Cooling Stage Lockout StateRead
BV348rat_1Return Air TempRead
BV349rah_1Return Air HumidityRead
BV350rae_1RA EnthalpyRead
BV351rad_1Return Air DewpointRead
BV400reset_all_runtms_1Reset All RuntimesWrite
BV401reset_sf_rntm_1Reset Fan Runtime - Reset Supply Air Fan runtimeWrite
BV402reset_reheat_rntm_1Reset Reheat Pump RuntimeWrite
BV403reset_compa_rntm_1Reset Comp A Runtime - Reset Comp A runtime (Only used when compressor installed)Write
BV404reset_compb_rntm_1Reset Comp B Runtime - Reset Comp B runtime (Only used when compressor installed)Write
BV405reset_compc_rntm_1Reset Comp C Runtime - Reset Comp C runtime (Only used when compressor installed)Write
BV406reset_compd_rntm_1Reset Comp D Runtime - Reset Comp D runtime (Only used when compressor installed)Write
BV407compa_runtime_alm_1Comp A Runtime Alarm - Compressor runtime AlarmRead
BV408compb_runtime_alm_1Comp B Runtime Alarm - Compressor runtime AlarmRead
BV409compc_runtime_alm_1Comp C Runtime Alarm - Compressor runtime AlarmRead
BV410comp4_runtime_alm_1Comp D Runtime Alarm - Compressor runtime AlarmRead
BV411smoke_detect_alm_1Smoke AlarmRead
BV412phase_loss_alarm_1Phase Loss AlarmRead
BV413compa_rt_alm_en_1Comp A Runtime Alarm EnabledWrite
BV415compb_rt_alm_en_1Comp B Runtime Alarm EnabledWrite
BV417compc_rt_alm_en_1Comp C Runtime Alarm EnabledWrite
BV419compd_rt_alm_en_1Comp D Runtime Alarm EnabledWrite
BV421saf_rt_alarm_en_1SAF Runtime Alarm EnabledWrite
BV423reht_rt_alm_en_1Reheat Runtime Alarm EnabledWrite
BV425locked_input_1Locked InputRead
BV426saf_runtime_alm_1SAF Runtime AlarmRead
BV427reht_runtime_alm_1Reheat Runtime AlarmRead
BV428ht_failure_1Heating General Failure AlarmRead
BV429hi_datsp_alarm_1High DAT SP Limit AlarmRead
BV430filt_fail_1Filter AlarmRead
BV431ll_fail_1Freeze Stat AlarmRead
BV432space_bad_1Space Temp - Bad SensorRead
BV433oat_bad_1Outside Air Temp - Sensor BadRead
BV434cc_dat_bad_1Cooling Coil Discharge Air Temp - Sensor BadRead
BV435dat_bad_1Discharge Air Temp - Bad SensorRead
BV436oarh_bad_1Outdoor Relative Humidity - Sensor BadRead
BV437mat_bad_1Mixed Air Temp - Sensor BadRead
BV438htg_alm_fia_1Heating - Failed Ignition Attempt (A01)Read
BV439htg_alm_lf_1Heating - Lost Flame (A02)Read
BV440htg_alm_ica_1Heating - Insufficient Combustion Air (A03)Read
BV441htg_alm_llf_1Heating - Limited Low Fire (A04)Read
BV442htg_alm_wfs_1Heating - Weak Flame Signal (A05)Read
BV443htg_alm_ces_1Heating - Com Error (Slave) (A99)Read
BV444htg_alm_fi_1Heating - Failed Ignition (E01)Read
BV445htg_alm_plf_1Heating - Primary Limit Failure (E02)Read
BV446htg_alm_mvf_1Heating - Modulation Valve Failure (E03)Read
BV447htg_alm_asfl_1Heating - Air Sensor Failure (Low) (E04)Read
BV448htg_alm_asfh_1Heating - Air Sensor Failure (High) (E05)Read
BV449htg_alm_gsfl_1Heating - Gas Sensor Failure (Low) (E06)Read
BV450htg_alm_gsfh_1Heating - Gas Sensor Failure (High) (E07)Read
BV451htg_alm_ifs_1Heating - Improper Flame Signal (E08)Read
BV452htg_alm_nfri_1Heating - No Firing Rate Input (E09)Read
BV453htg_alm_iidp_1Heating - Invalid I.DRead
BV454htg_alm_sfcm_1Heating - Slave Furnace COM Missing (E20)Read
BV455htg_alm_sfl_1Heating - Slave Furnace Lockout (E21)Read
BV456htg_alm_comm_1Heating - Board Comm Output FailureRead
BV606main_erv_start_cmd_stat_1Main ERV Cmd Input StatusRead
BV607main_erv_saf_stat_1Main ERV SAF StatusRead
BV608main_erv_eaf_stat_1Main ERV EAF StatusRead
BV609main_erv_wheel_stat_1Main ERV Wheel StatusRead
BV610main_erv_saf_cmd_1Main ERV SAF CmdRead
BV611main_erv_eaf_cmd_1Main ERV EAF CmdRead
BV612main_erv_wheel_cmd_1Main ERV Wheel CmdRead
BV613main_erv_filte_stat_1Main ERV Filter StatusRead
BV618erv_comm_avail_1ERV Comm AvailableRead
MV204ws_mode_1Wall Temperature Sensor Mode Request - Requested mode from Wall Temperature Sensor: AutoRead
MV206fan_lvl_out_msv_1Wall Temperature Sensor Fan Speed RequestRead
Object ID lookup: Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list)

How many BACnet points does the Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) have?

This list has 227 BACnet objects: 122 analog values, 103 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) BACnet points are writable?

87 of the 227 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list) BACnet documentation?

The source is Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) (MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A), revision 2026-06, published free by Reznor at https://assets.reznorhvac.com/download/bcd1b330-3a4f-11f1-ae67-0016e1e579b9/MAPSIII%26IV-D15-D16-D17-D18-D19-D21%20%2806-26%29%20REV-A.pdf.

What are the minimum BACnet points to integrate the Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list)?

Start with BV 51 bas_on_off_cmd_1 (BAS on/off (schedule set for BAS)); BV 50 bas_occ_unocc_cmd_1 (BAS occupied/unoccupied (schedule set for BAS)); AV 100 occ_cool_sp_1 (Occupied space cooling setpoint); AV 101 occ_heat_sp_1 (Occupied space heating setpoint); AV 150 na_stpt_1 (Neutral air / discharge air setpoint); BV 178 bas_reset_sys_shtdwn_1 (Reset a system shutdown); AV 175 unit_mode_1 (Current unit mode); BV 54 occ_status_1 (Occupancy status); BV 191 shutdown_fail_1 (Unit shut down on alarm); BV 176 sf_fail_1 (Supply fan failure).

How do I enable BMS control of the Reznor MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list)?

BV 50 bas_occ_unocc_cmd_1 and BV 51 bas_on_off_cmd_1 control occupancy and on/off, but only when BAS control is selected in the schedule configuration. AV 52 lets a BACnet schedule pass minutes-until-occupied for optimum start. BV 178 resets a system shutdown.

How do I check these points on the real MAPS / MAPS III / MAPS IV IQ Controller, Options D15 / D16 / D17 / D18 (BACnet point list)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Reznor BACnet points lists

Source: Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) · MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A · rev. 2026-06. Object names, instances and units are reproduced as published; descriptions are our own.