Packaged rooftop unit / DOAS controller · BACnet points list

Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) BACnet points list

Updated 12 November 2026

Short answer

MAPS III and MAPS IV units with control option D21 use a programmable system controller with an optional BMS card for BACnet MS/TP or BACnet IP/Ethernet. The D21 point list has 30 analog variables, 10 integer variables (AV 1001-1010) and 33 digital variables. Unlike D19 it adds space temperature and humidity setpoints, a state select and a BMS occupancy command.

This page lists 73 BACnet objects for the Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reznor’s own free documentation, linked below.

Manufacturer
Reznor
Model
MAPS III / MAPS IV Control Option D21 (BACnet point list)
Equipment
Packaged rooftop unit / DOAS controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
73 (19 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
77000
Also known as
MAPS III, MAPS IV, MAPSIII&IV-D15-D16-D17-D18-D19-D21, RCB, RDB, RDCB, RDDB, RECB, REDB, RCC, RDC, RDCC, RDDC, RECC, REDC, CP-MAPSIII-D21, D303070, Option D21, D21
Source document
Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) · MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A · rev. 2026-06
Download CSV 73 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Reznor’s current documentation and the live device before use. Not official Reznor information. Terms of use.

BMS integration notes: Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list)

Integration in brief

Set the BMS protocol, instance, baud and MAC in the controller's BMS Config screens. Set OccMode_Sel (AV 1007) to 2 and command occupancy with BV 23, choose the state with AV 1006 and write the space temperature setpoint. Monitor supply fan status, space and discharge temperatures and the general alarm relay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 23Occupied_BMSOccupancy command (needs AV 1007 = 2)Write
AV 1007OccMode_SelOccupancy source: 0 schedule, 1 input, 2 BMSWrite
AV 1006State_SelUnit state: 2 auto, 3 cool, 4 heat, 5 offWrite
AV 26SpcTempSPSpace temperature setpoint, 65-85 °FWrite
BV 22OccupiedOccupied mode statusRead
BV 25SF_StsSupply fan statusRead
AV 25Spc_TempSpace temperatureRead
AV 8DA_TempDischarge air temperatureRead
BV 1Alm_Rly_CmdGeneral alarm relay onRead

Enable & remote start

AV 1006 State_Sel picks auto, cool, heat or off. Occupancy comes from the schedule, a digital input or the BMS, chosen with AV 1007 OccMode_Sel; with 2 = BMS, BV 23 Occupied_BMS sets occupancy.

Sensors & values from the BMS

Set BV 19 OA_Temp_Sel or BV 18 OA_Hum_Sel to 1 (BMS) and write AV 18 OA_Temp_BMS or AV 16 OA_Hum_BMS.

Network setup

Watch out for

Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

73 of 73 shown
Type
AnalogBinary
Access
Show
Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) BACnet Points List
DescriptionStates
AV1CC_TempCooling Coil Discharge Air Temp°FRead
AV2DA_NAClg_SPDischarge Air Temp Neutral Cooling SP; range 50 to 100; default 70°FWrite
AV3DA_NAHtg_SPDischarge Air Temp Neutral Heating SP; range 50 to 140; default 70°FWrite
AV4DA_SPDischarge Air Temp Active SP°FRead
AV5DA_SpcClg_SPDischarge Air Temp Space Cooling SP; range 50 to 100; default 55°FWrite
AV6DA_SpcHtCl_SPDischarge Air Temp Space Heat Mode Cooling SP; range 50 to 100; default 55°FWrite
AV7DA_SpcHtg_SPDischarge Air Temp Space Heating Sp; range 50 to 140; default 90°FWrite
AVmin8DA_TempDischarge Air Temp°FRead
AV9Damper_CmdDamper Output Command; range 0 to 100%Read
AV10DhOADP_SPDehum OA Dew Point SP; range 50 to 100; default 58°FWrite
AV11Ext_Dmpr_CmdExternal Unit Damper Command; range 0 to 100%Read
AV12HX1_Mod_CmdHeating 1 Modulation Command; range 0 to 100%Read
AV13HX2_Mod_CmdHeating 2 Modulation Command; range 0 to 100%Read
AV14MA_TempMixed Air Temp°FRead
AV15OA_Dew_PointOutside Air Dew Point°FRead
AV16OA_Hum_BMSOutside air humidity from BMS; used when OA_Hum_Sel = 1 (BMS)%RHWrite
AV17OA_Hum_RawOutside Air Humidity%RHRead
AV18OA_Temp_BMSOutside air temp from BMS; used when OA_Temp_Sel = 1 (BMS)°FWrite
AV19OA_Temp_RawOutside Air Temp°FRead
AV20OAChgOv_SPOA Change Over SP; range 45 to 80; default 65°FWrite
AV21RH_Mod_OutReheat Modulation Output %; range 0 to 100%Read
AV22SF_VFD_CmdSupply Fan VFD Command; range 0 to 100%Read
AV23SpcEffClgSPSpace Effective Cooling SP°FRead
AV24SpcEffHtgSPSpace Effective Heating SP°FRead
AVmin25Spc_TempSpace Temp°FRead
AVmin26SpcTempSPSpace Temp SP; range 65 to 85; default 72°FWrite
AV27RA_TempReturn Air Temperature°FRead
AV28RA_HumidityReturn Air Humidity%RHRead
AV29EA_TempExhaust Air Temperature°FRead
AV30EA_HumidityExhaust Air Humidity%RHRead
AV1001Bldg_PressureBuilding Static Pressurein. w.c.Read
AV1002Bldg_Press_SPBuilding Static Pressure SP; range -500 to 500; default 100in. w.c.Write
AV1003Duct_Press_SPDuct Static Pressure SP; range 0 to 2500; default 500in. w.c.Write
AV1004Spc_HumSpace Humidity%RHRead
AV1005SpcHumSPSpace Humidity SP; range 35 to 75; default 55%RHWrite
AVmin1006State_SelState select; default 5Write2=AUTO, 3=COOL, 4=HEAT, 5=OFF
AVmin1007OccMode_SelOccupied mode select; default 1Write0=Schedule, 1=Digital Input, 2=BMS
AV1008Spc_CO2Space CO2ppmRead
AV1009SpcCO2SPSpace CO2 SP; range 0 to 2,000; default 1,000ppmWrite
AV1010Duct_PressureDuct Static Pressurein. w.c.Read
BVmin1Alm_Rly_CmdUnit General Alarm Relay CommandRead0=Off, 1=On
BV2Comp_Stg1_CmdCompressor Stage 1 CommandRead0=Off, 1=On
BV3Comp_Stg2_CmdCompressor Stage 2 CommandRead0=Off, 1=On
BV4Comp_Stg3_CmdCompressor Stage 3 CommandRead0=Off, 1=On
BV5Comp_Stg4_CmdCompressor Stage 4 CommandRead0=Off, 1=On
BV6Ext_OCCOccupied Mode InputRead0=Off, 1=On
BV7Ext_Switch_1External Damper Position Sw 1Read0=Off, 1=On
BV8Ext_Switch_2External Damper Position Sw 2Read0=Off, 1=On
BV9HX_Stg1_CmdHeating Stage 1 CommandRead0=Off, 1=On
BV10HX_Stg2_CmdHeating Stage 2 CommandRead0=Off, 1=On
BV11HX_Stg3_CmdHeating Stage 3 CommandRead0=Off, 1=On
BV12HX_Stg4_CmdHeating Stage 4 CommandRead0=Off, 1=On
BV13HX_Stg5_CmdHeating Stage 5 CommandRead0=Off, 1=On
BV14HX_Stg6_CmdHeating Stage 6 CommandRead0=Off, 1=On
BV15NA_Clg_MdNeutral Air Cooling ModeRead0=Off, 1=On
BV16NA_Dehum_MdNeutral Air Dehum ModeRead0=Off, 1=On
BV17NA_Htg_MdNeutral Air Heating ModeRead0=Off, 1=On
BV18OA_Hum_SelShare OA Humidity from BMS (0=Probe 1=BMS); default OffWrite0=Off, 1=On
BV19OA_Temp_SelShare OA Temp from BMS (0=Probe 1=BMS); default OffWrite0=Off, 1=On
BV20Phase_AlarmPhase Protection AlarmRead0=Off, 1=On
BV21Safety_StsSafety Input StatusRead0=Normal, 1=Alarm
BVmin22OccupiedOccupied Mode StatusRead0=Off, 1=On
BVmin23Occupied_BMSOccupied mode from BMS; used when OccMode_Sel = 2; default OffWrite0=Off, 1=On
BV24SF_CmdSupply Fan CommandRead0=Off, 1=On
BVmin25SF_StsSupply Fan StatusRead0=Off, 1=On
BV26Spc_Clg_MdSpace Cooling ModeRead0=Off, 1=On
BV27Spc_Dehum_MdSpace Dehum ModeRead0=Off, 1=On
BV28Spc_Htg_MdSpace Heating ModeRead0=Off, 1=On
BV29Filter_StsMain or ERV Dirty Filter StatusRead0=Off, 1=On
BV30RH_CmdReheat Compressor CommandRead0=Off, 1=On
BV31Spc_HtgClg_MdSpace Heating Cooling ModeRead0=Off, 1=On
BV32Htr_1_StsGas Heater 1 StatusRead0=Off, 1=On
BV33Htr_2_StsGas Heater 2 StatusRead0=Off, 1=On
Object ID lookup: Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MAPS III / MAPS IV Control Option D21 (BACnet point list) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list)

How many BACnet points does the Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) have?

This list has 73 BACnet objects: 40 analog values, 33 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) BACnet points are writable?

19 of the 73 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list) BACnet documentation?

The source is Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) (MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A), revision 2026-06, published free by Reznor at https://assets.reznorhvac.com/download/bcd1b330-3a4f-11f1-ae67-0016e1e579b9/MAPSIII%26IV-D15-D16-D17-D18-D19-D21%20%2806-26%29%20REV-A.pdf.

What are the minimum BACnet points to integrate the Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list)?

Start with BV 23 Occupied_BMS (Occupancy command (needs AV 1007 = 2)); AV 1007 OccMode_Sel (Occupancy source: 0 schedule, 1 input, 2 BMS); AV 1006 State_Sel (Unit state: 2 auto, 3 cool, 4 heat, 5 off); AV 26 SpcTempSP (Space temperature setpoint, 65-85 °F); BV 22 Occupied (Occupied mode status); BV 25 SF_Sts (Supply fan status); AV 25 Spc_Temp (Space temperature); AV 8 DA_Temp (Discharge air temperature); BV 1 Alm_Rly_Cmd (General alarm relay on).

How do I enable BMS control of the Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list)?

AV 1006 State_Sel picks auto, cool, heat or off. Occupancy comes from the schedule, a digital input or the BMS, chosen with AV 1007 OccMode_Sel; with 2 = BMS, BV 23 Occupied_BMS sets occupancy.

Can the BMS supply sensor values to the Reznor MAPS III / MAPS IV Control Option D21 (BACnet point list)?

Set BV 19 OA_Temp_Sel or BV 18 OA_Hum_Sel to 1 (BMS) and write AV 18 OA_Temp_BMS or AV 16 OA_Hum_BMS.

How do I check these points on the real MAPS III / MAPS IV Control Option D21 (BACnet point list)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Reznor BACnet points lists

Source: Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) · MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A · rev. 2026-06. Object names, instances and units are reproduced as published; descriptions are our own.