Packaged rooftop unit / DOAS controller · BACnet points list

Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) BACnet points list

Updated 12 November 2026

Short answer

MAPS III and MAPS IV units with control option D19 use a programmable system controller with an optional BMS card for BACnet MS/TP or BACnet IP/Ethernet. The D19 point list has 29 analog variables, 6 integer variables (AV 1001-1006) and 35 digital variables. The BMS can enable the unit, write discharge air, damper, economizer, pressure and CO2 setpoints and share outdoor temperature and humidity; it reads temperatures, mode flags, compressor and heat stage commands, fan, filter, safety and phase status.

This page lists 70 BACnet objects for the Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reznor’s own free documentation, linked below.

Manufacturer
Reznor
Model
MAPS III / MAPS IV Control Option D19 (BACnet point list)
Equipment
Packaged rooftop unit / DOAS controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
70 (18 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
77000
Also known as
MAPS III, MAPS IV, MAPSIII&IV-D15-D16-D17-D18-D19-D21, RCB, RDB, RDCB, RDDB, RECB, REDB, RCC, RDC, RDCC, RDDC, RECC, REDC, CP-MAPSIII-D19, D303069, Option D19, D19
Source document
Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) · MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A · rev. 2026-06
Download CSV 70 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Reznor’s current documentation and the live device before use. Not official Reznor information. Terms of use.

BMS integration notes: Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list)

Integration in brief

Set the BMS protocol, instance, baud and MAC in the controller's BMS Config screens. Enable the unit with BV 1, write the discharge air setpoints and pressure setpoints, and optionally share outdoor temperature and humidity. Monitor supply fan status, discharge temperature, safety status and the general alarm relay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Unit_EnableUnit enableWrite
AV 3DA_NAClg_SPNeutral discharge air cooling setpoint, °FWrite
AV 4DA_NAHtg_SPNeutral discharge air heating setpoint, °FWrite
AV 1002Duct_Press_SPDuct static pressure setpointWrite
BV 28SF_StsSupply fan statusRead
AV 8DA_TempDischarge air temperatureRead
BV 26Safety_StsSafety input: normal or alarmRead
BV 2Alm_Rly_CmdGeneral alarm relay onRead

Enable & remote start

BV 1 Unit_Enable enables the unit. Fan, heat, cool, dehumidify and occupied calls come from field inputs; BV 7-11 show their state.

Sensors & values from the BMS

Set BV 24 OA_Temp_Sel or BV 23 OA_Hum_Sel to 1 (BMS) and write AV 22 OA_Temp_BMS or AV 20 OA_Hum_BMS.

Network setup

Watch out for

Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

70 of 70 shown
Type
AnalogBinary
Access
Show
Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) BACnet Points List
DescriptionStates
AV1CC_TempCooling Coil Discharge Air Temp°FRead
AV2CO2DmprOsSPCO2 Minimum Damper Offset SP; range 0 to 100; default 10%Write
AVmin3DA_NAClg_SPDischarge Air Temp Neutral Cooling SP; range 50 to 100; default 75°FWrite
AVmin4DA_NAHtg_SPDischarge Air Temp Neutral Heating SP; range 50 to 140; default 65°FWrite
AV5DA_SPDischarge Air Temp Active SP°FRead
AV6DA_SpcClg_SPDischarge Air Temp Space Cooling SP; range 50 to 100; default 55°FWrite
AV7DA_SpcHtg_SPDischarge Air Temp Space Heating Sp; range 50 to 140; default 90°FWrite
AVmin8DA_TempDischarge Air Temp°FRead
AV9Damper_CmdDamper Output Command; range 0 to 100%Read
AV10DhOADP_SPDehum OA Dew Point SP; range 50 to 100; default 58°FWrite
AV11Ec_OADPLO_SPEconomizer OA Dew Point Lockout SP; range 0 to 120; default 58°FWrite
AV12Ec_OALO_SPEconomizer OA Temp Lockout SP; range 0 to 120; default 60°FWrite
AV13Ext_Dmpr_CmdExternal Unit Damper Command; range 0 to 100%Read
AV14HX1_Mod_CmdHeating 1 Modulation Command; range 0 to 100%Read
AV15HX2_Mod_CmdHeating 2 Modulation Command; range 0 to 100%Read
AV16MA_ChgOvr_SPMixed Air Temp Auto Change Over SP; range 45 to 80; default 65°FWrite
AV17MA_TempMixed Air Temp°FRead
AV18MinDmprSPMinimum Damper SP; range 0 to 100; default 10%Write
AV19OA_Dew_PointOutside Air Dew Point°FRead
AV20OA_Hum_BMSOutside air humidity from BMS; used when OA_Hum_Sel = 1 (BMS)%RHWrite
AV21OA_Hum_RawOutside Air Humidity%RHRead
AV22OA_Temp_BMSOutside air temp from BMS; used when OA_Temp_Sel = 1 (BMS)°FWrite
AV23OA_Temp_RawOutside Air Temp°FRead
AV24RH_Mod_OutReheat Modulation Output %; range 0 to 100%Read
AV25SF_VFD_CmdSupply Fan VFD Command; range 0 to 100%Read
AV26RA_TempReturn Air Temperature°FRead
AV27RA_HumidityReturn Air Humidity%RHRead
AV28EA_TempExhaust Air Temperature°FRead
AV29EA_HumidityExhaust Air Humidity%RHRead
AV1001Bldg_Press_SPBuilding Static Pressure SP; range -500 to 500; default 100in. w.c.Write
AVmin1002Duct_Press_SPDuct Static Pressure SP; range 0 to 2500; default 500in. w.c.Write
AV1003Bldg_PressureBuilding Static Pressurein. w.c.Read
AV1004Spc_CO2Space CO2ppmRead
AV1005SpcCO2SPSpace CO2 SP; range 0 to 2,000; default 1,000ppmWrite
AV1006Duct_PressureDuct Static Pressurein. w.c.Read
BVmin1Unit_EnableUnit Enable; default OffWrite0=Off, 1=On
BVmin2Alm_Rly_CmdUnit General Alarm Relay CommandRead0=Off, 1=On
BV3Comp_Stg1_CmdCompressor Stage 1 CommandRead0=Off, 1=On
BV4Comp_Stg2_CmdCompressor Stage 2 CommandRead0=Off, 1=On
BV5Comp_Stg3_CmdCompressor Stage 3 CommandRead0=Off, 1=On
BV6Comp_Stg4_CmdCompressor Stage 4 CommandRead0=Off, 1=On
BV7Ext_Call_CoolExternal Cool Call Input (Y1)Read0=Off, 1=On
BV8Ext_Call_DhExternal Call Dehum InputRead0=Off, 1=On
BV9Ext_Call_FanExternal Fan Call Input (G)Read0=Off, 1=On
BV10Ext_Call_HeatExternal Heat Call Input (W1)Read0=Off, 1=On
BV11Ext_OCCOccupied Mode InputRead0=Off, 1=On
BV12Ext_Switch_1External Damper Position Sw 1Read0=Off, 1=On
BV13Ext_Switch_2External Damper Position Sw 2Read0=Off, 1=On
BV14HX_Stg1_CmdHeating Stage 1 CommandRead0=Off, 1=On
BV15HX_Stg2_CmdHeating Stage 2 CommandRead0=Off, 1=On
BV16HX_Stg3_CmdHeating Stage 3 CommandRead0=Off, 1=On
BV17HX_Stg4_CmdHeating Stage 4 CommandRead0=Off, 1=On
BV18HX_Stg5_CmdHeating Stage 5 CommandRead0=Off, 1=On
BV19HX_Stg6_CmdHeating Stage 6 CommandRead0=Off, 1=On
BV20NA_Clg_MdNeutral Air Cooling ModeRead0=Off, 1=On
BV21NA_Dehum_MdNeutral Air Dehum ModeRead0=Off, 1=On
BV22NA_Htg_MdNeutral Air Heating ModeRead0=Off, 1=On
BV23OA_Hum_SelShare OA Humidity from BMS (0=Probe 1=BMS); default OffWrite0=Off, 1=On
BV24OA_Temp_SelShare OA Temp from BMS (0=Probe 1=BMS); default OffWrite0=Off, 1=On
BV25Phase_AlarmPhase Protection AlarmRead0=Off, 1=On
BVmin26Safety_StsSafety Input StatusRead0=Normal, 1=Alarm
BV27SF_CmdSupply Fan CommandRead0=Off, 1=On
BVmin28SF_StsSupply Fan StatusRead0=Off, 1=On
BV29Spc_Clg_MdSpace Cooling ModeRead0=Off, 1=On
BV30Spc_Dehum_MdSpace Dehum ModeRead0=Off, 1=On
BV31Spc_Htg_MdSpace Heating ModeRead0=Off, 1=On
BV32Filter_StsMain or ERV Dirty Filter StatusRead0=Off, 1=On
BV33RH_CmdReheat Compressor CommandRead0=Off, 1=On
BV34Htr_1_StsGas Heater 1 StatusRead0=Off, 1=On
BV35Htr_2_StsGas Heater 2 StatusRead0=Off, 1=On
Object ID lookup: Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MAPS III / MAPS IV Control Option D19 (BACnet point list) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list)

How many BACnet points does the Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) have?

This list has 70 BACnet objects: 35 analog values, 35 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) BACnet points are writable?

18 of the 70 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list) BACnet documentation?

The source is Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) (MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A), revision 2026-06, published free by Reznor at https://assets.reznorhvac.com/download/bcd1b330-3a4f-11f1-ae67-0016e1e579b9/MAPSIII%26IV-D15-D16-D17-D18-D19-D21%20%2806-26%29%20REV-A.pdf.

What are the minimum BACnet points to integrate the Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list)?

Start with BV 1 Unit_Enable (Unit enable); AV 3 DA_NAClg_SP (Neutral discharge air cooling setpoint, °F); AV 4 DA_NAHtg_SP (Neutral discharge air heating setpoint, °F); AV 1002 Duct_Press_SP (Duct static pressure setpoint); BV 28 SF_Sts (Supply fan status); AV 8 DA_Temp (Discharge air temperature); BV 26 Safety_Sts (Safety input: normal or alarm); BV 2 Alm_Rly_Cmd (General alarm relay on).

How do I enable BMS control of the Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list)?

BV 1 Unit_Enable enables the unit. Fan, heat, cool, dehumidify and occupied calls come from field inputs; BV 7-11 show their state.

Can the BMS supply sensor values to the Reznor MAPS III / MAPS IV Control Option D19 (BACnet point list)?

Set BV 24 OA_Temp_Sel or BV 23 OA_Hum_Sel to 1 (BMS) and write AV 22 OA_Temp_BMS or AV 20 OA_Hum_BMS.

How do I check these points on the real MAPS III / MAPS IV Control Option D19 (BACnet point list)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Reznor BACnet points lists

Source: Control System Guide for Modular Air Processing System Units, Options D15, D16, D17, D18, D19 and D21 (MAPS III and MAPS IV) · MAPSIII&IV-D15-D16-D17-D18-D19-D21 (06-26) REV-A · rev. 2026-06. Object names, instances and units are reproduced as published; descriptions are our own.