Energy recovery / DOAS heat pump ventilation unit controller · BACnet points list

Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) BACnet points list

Updated 6 November 2026

Short answer

ZQYRA is a discontinued Reznor ventilation unit with an energy recovery wheel and a heat pump. With option BHB8 its controller is reachable on BACnet MS/TP. The BMS can switch the unit on and off, shut it down, reset alarms and runtimes, and write dewpoint changeover and discharge, outdoor and zone changeover setpoints. It reads zone, outdoor, discharge and exhaust temperatures and dewpoints, unit mode, the on/off command source, compressor and heating output, runtimes, digital inputs, relays and alarms.

This page lists 78 BACnet objects for the Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reznor’s own free documentation, linked below.

Manufacturer
Reznor
Model
ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8)
Equipment
Energy recovery / DOAS heat pump ventilation unit controller
Equipment type
Heat pumps
BACnet objects
78 (22 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
77000
Also known as
ZQYRA, ZQYRA-IOM, 260414-A, BHB8, Reznor ZQYRA
Source document
ZQYRA Installation/Operation/Maintenance - Table 45 BACnet MSTP Points List · ZQYRA-IOM (05-26) 260414-A · rev. 2026-05
Download CSV 78 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Reznor’s current documentation and the live device before use. Not official Reznor information. Terms of use.

BMS integration notes: Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8)

Integration in brief

Fit option BHB8 and set the MS/TP address. Switch the unit with BV 1 BAS_OffOn, write the discharge setpoints, and read UnitMode (AV 1001) and UnitCmd (AV 1002) to see why the unit is on or off. Watch the fan pressure switches and the alarm BVs, and reset with BV 41.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1BAS_OffOnBAS on/off commandWrite
AV 3DatSpLoDpDischarge air setpoint, low dewpoint, 55-75 °FWrite
BV 41BAS_AlmRstAlarm resetWrite
AV 1001UnitModeUnit mode: 0 off, 1 starting, 2 running...Read
AV 1002UnitCmdSource of the current on/off commandRead
BV 2SafStatusSupply fan pressure switch statusRead
AV 20UnitDatUnit discharge air temperatureRead
BV 14AlarmLightAlarm output relay onRead
BV 28ShutdnAlmUnit shut down; manual restart neededRead

Enable & remote start

BV 1 BAS_OffOn turns the unit on or off from the BAS (default off); BV 40 BAS_Shtdwn shuts the unit down. AV 1002 shows which source (DI, BAS, schedule, CO2/VOC, test, alarm, manual) is driving on/off.

Network setup

Watch out for

Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

78 of 78 shown
Type
AnalogBinary
Access
Show
Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) BACnet Points List
DescriptionStates
AV1DpCngOvrLtWheel Dewpoint Changeover Limit; range 55–65°F, default 59°FWrite
AV2DatSpHiDpDischarge Air Temperature Setpoint with High Dewpoint; default 58°FWrite
AVmin3DatSpLoDpDA setpoint, low dewpoint (TempCntrl = 0); range 55-75°F, default 70°FWrite
AV4ActDatSpActive DA setpoint°FRead
AV5DatHtgLoDpDischarge Air Temperature Heating Setpoint with Low Dewpoint,; range 55–75°F, default 70°FWrite
AV6DatClgLoDpDischarge Air Temperature Cooling Setpoint with Low Dewpoint,; default 60°FWrite
AV7OaLoSpLoDpOutside Air Temperature Low Setpoint with Low Dewpoint; range 55–80°F, default 65°FWrite
AV8OaHiSpLoDpOutside Air Temperature High Setpoint with Low Dewpoint; default 70°FWrite
AV9DaLoSpLoDpDischarge Air Temperature Low Setpoint with Low Dewpoint; range 55–75°F, default 58°FWrite
AV10DaHiSpLoDpDischarge Air Temperature High Setpoint with Low Dewpoint; default 70°FWrite
AV11ZoneZone temperature (AI_1)°FRead
AV12ZnCngOvHeating/Cooling Zone Temperature Changeover Setpoint; range 55–80°F°FWrite
AV13ZnCngOvDbHeating/Cooling Zone Temperature Changeover Deadband Setpoint°FWrite
AV14OaCngOvrHeating/Cooling OA Temperature Changeover Setpoint; range 55–80°F, default 65°FWrite
AV15OaCngOvrDbHeating/Cooling OA Temperature Changeover Deadband Setpoint°FWrite
AV16OatOutside air temperature (AI_3)°FRead
AV17ErDatEnergy Recovery DAT (AI_4)°FRead
AV19ErDaDpEnergy Recovery DA dewpoint°FRead
AVmin20UnitDatUnit DAT (AI_2)°FRead
AV21Suction_TempSuction Line Temperature°FRead
AV22ErEatEnergy Recovery Exhaust Air Temperature°FRead
AV23ErEahEnergy Recovery Exhaust Air Humidty%RHRead
AV24ErEadpEnergy Recovery Exhaust Air Dewpoint°FRead
AVmin1001UnitModeUnit Operation ModeRead0=Off, 1=Starting, 2=Running, 3=Test, 4=Cripple, 5=SysRestart, 6=SysShutdwn
AVmin1002UnitCmdUnit On/Off Command StatusRead0=DI Off, 1= DI On, 2=BAS On, 3=BAS OFF, 4=Local Sch On, 5=Local Sch Off, 6=VOC/CO2 On, 7=VOC/CO2 Off, 8=Test On, 9=Test Off, 10=Alarm Off, 11=Shtdwn DI Off, 12=Manual On, 13=Manual Off, 14=BAS Shutdown
AV1003CompPercModulation Compressor Output Percentage%Read
AV1004VocCo2VOC or CO2 Sensor OutputRead
AV1005FanRunTmFan RuntimeRead
AV1006CompRunTmCompressor RuntimeRead
AV1007ErwRunTmEnergy Recovery Wheel RuntimeRead
AV1008PreHtRunTmPreheat Runtime TimeRead
AV1009FiltrRunTmFilter RuntimeRead
AV1010TempCntrlTemp Control TypeRead0=Dewpoint (Default), 1=Dewpoint with OA changeover of Htg/Clg Setpoint, 2=Dewpoint with OA reset of Htg/Clg Setpoint, 3=Dewpoint with Space changeover of Htg/Clg Setpoint
AV1011HP_StatusHeatpump StatusRead0=Off, 1=Heating, 2=Cooling
AV1012HOA_StatHOA StatusRead0=Off, 1=Auto, 2=Hand, 3=Off
AV1013Supp_Htg_PercSupplemental Heating Percentage%Read
BVmin1BAS_OffOnBAS OffOn command; default OffWriteOn/Off
BVmin2SafStatusSupply Fan Pressure Switch Status (DI_1)Read
BV3EafStatusExhaust Fan Pressure Switch Status (DI_2)Read
BV4DiOffOnDI On/Off Switch Status (DI_3)Read
BV5CompAlmDiDigital Compressor General Alarm DI Status (DI_4)Read
BV6SafetyDISafety Input DI Status (DI_5)Read
BV7FanGenAlDiFan General Alarm DI Status (DI_6)Read
BV8FilterDiFilter DI Status (DI_7)Read
BV9FanCmdFan Relay (DO-1)Read
BV10ErwCmdEnergy Recovery Wheel Relay (DO-3)Read
BV11CompCmdCompressor CommandRead
BV12RevVlvCmdReversing Valve Cmd Relay (DO-2)Read
BV13PreHtCmdAuxiliary heat stage output Relay (DO-4)Read
BVmin14AlarmLightAlarm output Relay (DO-5)Read
BV15SafFailAlmSupply Air Fan Failure Alarm (critical alarm)Read
BV16EafFailAlmExhaust Air Fan Failure Alarm (critical alarm)Read
BV17SafetyAlmSafety Input Alarm (critical alarm)Read
BV18OatAlmOutside air temperature sensor failure Alarm (cripple)Read
BV19UnitDatAlmUnit discharge air temperature sensor failure Alarm (critical alarm)Read
BV20ErDatAlmEnergy Recovery DAT sensor failure (cripple)Read
BV21ErDahAlmER DA Humidity failure (cripple)%RHRead
BV22RevVlvAlmReversing Valve Failure Alarm (cripple)Read
BV23DirtyFiltrDirty Filter Alarm (General)Read
BV24FanGenAlmFan General Alarm (critical alarm)Read
BV25CompGenAlmDigital Compressor General Alarm (cripple)Read
BV26TestModeUnit in Test Mode (General)Read
BV27RestartAlmSystem in Restart Mode (system will auto-restart after 60 minutes)Read
BVmin28ShutdnAlmSystem in Shutdown Mode (manual restart required)Read
BV29RstAllRtsReset All RuntimesWrite
BV30RstPhtRtsReset PreHt RuntimesWrite
BV31RstFanRtsReset Fan RuntimesWrite
BV32RstCompRtsReset Comp RuntimesWrite
BV33RstFltrRtsReset Filter RuntmWrite
BV34RstErwRtsReset ERW RuntimesWrite
BV35FanHrsAlmFan Run Hours Alarm (general)Read
BV36CompHrsAlmCompressor Run Hours Alarm (general)Read
BV37ErwHrsAlmWheel Run Hours Alarm (general)Read
BV38PhtHrsAlmPreheat Run Hours Alarm (general)Read
BV39FiltHrsAlmFilter Run Hours Alarm (general)Read
BV40BAS_ShtdwnBAS Unit ShutdownWrite
BVmin41BAS_AlmRstBAS Alarm ResetWrite
BV42Supp_Htg_CmdSupplemental Heating CommandRead
Object ID lookup: Reznor ZQYRA Energy Recovery Ventilation Unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8)

How many BACnet points does the Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) have?

This list has 78 BACnet objects: 36 analog values, 42 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) BACnet points are writable?

22 of the 78 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8) BACnet documentation?

The source is ZQYRA Installation/Operation/Maintenance - Table 45 BACnet MSTP Points List (ZQYRA-IOM (05-26) 260414-A), revision 2026-05, published free by Reznor at https://assets.reznorhvac.com/download/509BCA8A-35FC-409F-AC22-E9A172ED80CB.

What are the minimum BACnet points to integrate the Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8)?

Start with BV 1 BAS_OffOn (BAS on/off command); AV 3 DatSpLoDp (Discharge air setpoint, low dewpoint, 55-75 °F); BV 41 BAS_AlmRst (Alarm reset); AV 1001 UnitMode (Unit mode: 0 off, 1 starting, 2 running); AV 1002 UnitCmd (Source of the current on/off command); BV 2 SafStatus (Supply fan pressure switch status); AV 20 UnitDat (Unit discharge air temperature); BV 14 AlarmLight (Alarm output relay on); BV 28 ShutdnAlm (Unit shut down; manual restart needed).

How do I enable BMS control of the Reznor ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8)?

BV 1 BAS_OffOn turns the unit on or off from the BAS (default off); BV 40 BAS_Shtdwn shuts the unit down. AV 1002 shows which source (DI, BAS, schedule, CO2/VOC, test, alarm, manual) is driving on/off.

How do I check these points on the real ZQYRA Energy Recovery Ventilation Unit (BACnet MS/TP Option BHB8)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Reznor BACnet points lists

Source: ZQYRA Installation/Operation/Maintenance - Table 45 BACnet MSTP Points List · ZQYRA-IOM (05-26) 260414-A · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.