Air handling unit controller · BACnet points list

Regin Corrigo 5.0 ventilation (AHU) controller BACnet points list

Updated 6 November 2026

Short answer

Corrigo 5.0 is Regin's pre-programmed ventilation controller. Its EDE file lists 840 objects: run mode and manual/auto selectors for the unit, fans, dampers, pumps and sequences, supply/extract/room setpoints and outdoor compensation curve, fan pressure and flow setpoints, measured temperatures, pressures and flows, about 200 alarm BVs with A/B/C sum alarms, schedules, a holiday calendar and notification classes.

This page lists 840 BACnet objects for the Regin Corrigo 5.0 ventilation (AHU) controller — 330 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Regin’s own free documentation, linked below.

Manufacturer
Regin
Model
Corrigo 5.0 ventilation (AHU) controller
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
840 (330 writable)
Transport
—
Firmware
5.0
Also known as
Corrigo 5.0, Corrigo 5, Corrigo ventilation, Regin Corrigo, BACnet_Corrigo50
Source document
Corrigo 5.0 BACnet files (EDE) · BACnet_Corrigo50_EDE · rev. 2023-10
Download CSV 840 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Regin’s current documentation and the live device before use. Not official Regin information. Terms of use.

BMS integration notes: Regin Corrigo 5.0 ventilation (AHU) controller

Integration in brief

Use MV 30788 AirUnitAutoMode to run the unit (off, manual, auto or a forced speed) and AV 30811 SupplySetpoint for the supply air setpoint in constant supply air control. Read MV 40428 UnitMode and MV 40429 UnitModeControl for what is running and why, the supply and outdoor temperatures, and BV 20008/20009 for A- and B-alarms. BV 10000 acknowledges all alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 30788AirUnitAutoModeUnit run mode: off, manual, auto or fixed speedWrite
AV 30811SupplySetpointSupply air setpoint (constant supply control)Write
MV 40428UnitModeActual run mode: stop, start-up, low/normal/highRead
MV 40429UnitModeControlWhat triggers the current run modeRead
AV 40292AI_SupplyAirTempSupply air temperatureRead
AV 40290AI_OutDoorTempOutdoor temperatureRead
MV 40451SAFSpeedSupply fan speed stateRead
BV 20008SumAlarmASum A-alarmRead
BV 20009SumAlarmBSum B-alarmRead

Enable & remote start

MV 30788 AirUnitAutoMode sets the unit running mode (1 OFF, 2 Manual, 3 AUTO, 4-6 low/normal/high speed). MV 30796 ExternalControl selects extended-run speeds; MV 30797 AirUnitServiceStop stops the unit with top priority.

Network setup

Watch out for

Regin Corrigo 5.0 ventilation (AHU) controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

840 of 840 shown
Type
AnalogBinaryMulti-state
Access
Show
Regin Corrigo 5.0 ventilation (AHU) controller BACnet Points List
DescriptionStates
AV30503MinuteMinuteWrite
AV30504HourHourWrite
AV30505WDayDay of Week (1-7, 1=Monday)Write
AV30506WeekWeek numberWrite
AV30507DateDay of monthWrite
AV30508MonthMonthWrite
AV30509YearYearWrite
AV30760AirFlowK_22K-constant for air flow: SAF pressWrite
AV30761AirFlowX_22X-constant for air flow: SAF pressWrite
AV30762AirFlowK_23K-constant for air flow: EAF pressWrite
AV30763AirFlowX_23X-constant for air flow: EAF pressWrite
AV30764AirFlowK_24K-constant for air flow: SAF flowWrite
AV30765AirFlowX_24X-constant for air flow: SAF flowWrite
AV30766AirFlowK_25K-constant for air flow: EAF flowWrite
AV30767AirFlowX_25X-constant for air flow: EAF flowWrite
AV30768AirFlowK_26K-constant for air flow: Exch SAF pressWrite
AV30769AirFlowX_26X-constant for air flow: Exch SAF pressWrite
AV30770AirFlowK_27K-constant for air flow: Exch EAF pressWrite
AV30771AirFlowX_27X-constant for air flow: Exch EAF pressWrite
AV30791SAFManualSetpointManWrite
AV30792SAFManualOutputMan%Write
AV30794EAFManualSetpointManWrite
AV30795EAFManualOutputMan%Write
AV30798SeqPumpOutdLimitYx_1Pump outdWrite
AV30799SeqPumpOutdLimitYx_2Pump outdWrite
AV30800SeqPumpOutdLimitYx_3Pump outdWrite
AV30801SeqPumpOutdLimitYx_4Pump outdWrite
AV30802SeqPumpOutdLimitYx_5Pump outdWrite
AV30803SeqPumpOutdLimitYx_6Pump outdWrite
AV30804SeqPumpOutdLimitYx_7Pump outdWrite
AV30805SeqPumpOutdLimitYx_8Pump outdWrite
AV30806SeqPumpOutdLimitYx_9Pump outdWrite
AV30807SeqPumpOutdLimitYx_10Pump outdWrite
AVmin30811SupplySetpointSetpWrite
AV30812ExtractSetpointSetpWrite
AV30813SupplySetpointMaxMax limit of supply setpWrite
AV30814SupplySetpointMinMin limit of supply setpWrite
AV30815SupplySetpOffsetLowTempWrite
AV30816SupplySetpOffsetHighTempWrite
AV30817Curve1_X1OutdWrite
AV30818Curve1_X2OutdWrite
AV30819Curve1_X3OutdWrite
AV30820Curve1_X4OutdWrite
AV30821Curve1_X5OutdWrite
AV30822Curve1_X6OutdWrite
AV30823Curve1_X7OutdWrite
AV30824Curve1_X8OutdWrite
AV30825Curve1_Y1setpWrite
AV30826Curve1_Y2SetpWrite
AV30827Curve1_Y3SetpWrite
AV30828Curve1_Y4SetpWrite
AV30829Curve1_Y5SetpWrite
AV30830Curve1_Y6SetpWrite
AV30831Curve1_Y7SetpWrite
AV30832Curve1_Y8SetpWrite
AV30835SAFLowSpeedPressureSetpWrite
AV30836SAFNormalSpeedPressureSetpWrite
AV30837SAFHighSpeedPressureSetpWrite
AV30838EAFLowSpeedPressureSetpWrite
AV30839EAFNormalSpeedPressureSetpWrite
AV30840EAFHighSpeedPressureSetpWrite
AV30841SAFLowspeedAirFlowSetpWrite
AV30842SAFNormalspeedAirFlowSetpWrite
AV30843SAFHighspeedAirFlowSetpWrite
AV30844EAFLowspeedAirFlowSetpWrite
AV30845EAFNormalspeedAirFlowSetpWrite
AV30846EAFHighspeedAirFlowSetpWrite
AV30847SAFLowSpeedOutputOutput signal low speed SAF if Freq%Write
AV30848SAFNormalSpeedOutputOutput signal normal speed SAF if Freq%Write
AV30849SAFHighspeedOutputOutput signal high speed SAF if Freq%Write
AV30850EAFLowSpeedOutputOutput signal low speed EAF if Freq%Write
AV30851EAFNormalSpeedOutputOutput signal normal speed EAF if Freq%Write
AV30852EAFHighspeedOutputOutput signal high speed EAF if Freq%Write
AV30853SAFLowSpeedPressOffsetOffset SAF pressWrite
AV30854SAFHighSpeedPressOffsetOffset SAF pressWrite
AV30855SAFLowSpeedAirFlowOffsetOffset SAF air flow low speedWrite
AV30856SAFHighSpeedAirFlowOffsetOffset SAF air flow high speedWrite
AV30857SAFLowSpeedOutputOffsetOffset SAF output low speed%Write
AV30858SAFHighSpeedOutputOffsetOffset SAF output high speed%Write
AV30859EAFLowSpeedPressOffsetOffset EAF pressWrite
AV30860EAFHighSpeedPressOffsetOffset EAF pressWrite
AV30861EAFLowSpeedAirFlowOffsetOffset EAF air flow low speedWrite
AV30862EAFHighSpeedAirFlowOffsetOffset EAF air flow high speedWrite
AV30863EAFLowSpeedOutputOffsetOffset EAF output low speed%Write
AV30864EAFHighSpeedOutputOffsetOffset EAF output high speed%Write
AV30866SAFManSetpFreeCoolSAF setpWrite
AV30867SAFManOutFreeCoolSAF man%Write
AV30869SAFManSetpFireSAF setpWrite
AV30870SAFManOutFireSAF man%Write
AV30872SAFManSetpSmokeSAF setpWrite
AV30873SAFManOutSmokeSAF man%Write
AV30875SAFManSetpRecirculationSAF setpWrite
AV30876SAFManOutRecirculationSAF man%Write
AV30878EAFManSetpFreeCoolSAF setpWrite
AV30879EAFManOutFreeCoolEAF man%Write
AV30881EAFManSetpFireEAF setpWrite
AV30882EAFManOutFireEAF man%Write
AV30884EAFManSetpSmokeEAF setpWrite
AV30885EAFManOutSmokeEAF man%Write
AV30887EAFManSetpRecirculationEAF setpWrite
AV30888EAFManOutRecirculationEAF man%Write
AV30889EAFFrequencyFactFactor for controlling EAF if CAV fan contWrite
AV30890ExtractPID_PbandP-band Extract air contWrite
AV30891ExtractPID_ItimeI-time Extract air contWrite
AV30892SAFPID_PbandP-band pressWrite
AV30893SAFAirFlowPID_PbandP-band flow contWrite
AV30894SAFPID_ItimeI-time pressWrite
AV30895EAFPID_PbandP-band pressWrite
AV30896EAFAirFlowPID_PbandP-band flow contWrite
AV30897EAFPID_ItimeI-time pressWrite
AV30898FrostPID1_PBandP-band frost modeWrite
AV30899FrostPID1_ITimeI-time frost modeWrite
AV30900FrostPID2_PbandP-band frost modeWrite
AV30901FrostPID2_ITimeI-time frost modeWrite
AV30902FrostPID3_PbandP-band frost modeWrite
AV30903FrostPID3_ITimeI-time frost modeWrite
AV30904CO2PID_PbandP-band CO2 modeWrite
AV30905CO2PID_ItimeI-time CO2 modeWrite
AV30906RoomPID_PbandP-band room air contWrite
AV30907RoomPID_ItimeI-time room air contWrite
AV30908DeIcePID_PbandP-band de-icingWrite
AV30909DeIcePID_ItimeI-time de-icingWrite
AV30910HumidityPID_PbandP-band humidity contWrite
AV30911HumidityPID_ItimeI-time humidity contWrite
AV30912ExtraPID_PbandP-band extra pid contWrite
AV30913ExtraPID_ItimeI-time extra pid contWrite
AV30914SeqY1PID_PbandP-band Seq A air contWrite
AV30915SeqY1PID_ITimeI-time Seq A air contWrite
AV30916SeqY2PID_PbandP-band Seq B air contWrite
AV30917SeqY2PID_ITimeI-time Seq B air contWrite
AV30918SeqY3PID_PbandP-band Seq C air contWrite
AV30919SeqY3PID_ITimeI-time Seq C air contWrite
AV30920SeqY4PID_PbandP-band Seq D air contWrite
AV30921SeqY4PID_ITimeI-time Seq D air contWrite
AV30922SeqY5PID_PbandP-band Seq E air contWrite
AV30923SeqY5PID_ITimeI-time Seq E air contWrite
AV30924SeqY6PID_PbandP-band Seq F air contWrite
AV30925SeqY6PID_ITimeI-time Seq F air contWrite
AV30926SeqY7PID_PbandP-band Seq G air contWrite
AV30927SeqY7PID_ITimeI-time Seq G air contWrite
AV30928SeqY8PID_PbandP-band Seq H air contWrite
AV30929SeqY8PID_ITimeI-time Seq H air contWrite
AV30930SeqY9PID_PbandP-band Seq I air contWrite
AV30931SeqY9PID_ITimeI-time Seq I air contWrite
AV30932SeqY10PID_PbandP-band Seq J air contWrite
AV30933SeqY10PID_ITimeI-time Seq J air contWrite
AV30935AOManual_HumidityHumidification/Dehumidification cont%Write
AV30937AOManual_ExtraControllerExtra contr%Write
AV30939AOManual_SequenceY1Seq.A contr%Write
AV30941AOManual_SequenceY2Seq.B contr%Write
AV30943AOManual_SequenceY3Seq.C contr%Write
AV30945AOManual_SequenceY4Seq.D contr%Write
AV30947AOManual_SequenceY5Seq.E contr%Write
AV30949AOManual_SequenceY6Seq.F contr%Write
AV30951AOManual_SequenceY7Seq.G contr%Write
AV30953AOManual_SequenceY8Seq.H contr%Write
AV30955AOManual_SequenceY9Seq.I contr%Write
AV30957AOManual_SequenceY10Seq.J contr%Write
AV30958FreeCoolDayLimitOutdoor temperature limit for night free coolingWrite
AV30959FreeCoolHighLimitIf outdWrite
AV30960FreeCoolLowLimitIf outdWrite
AV30961FreeCoolRoomLimitIf room temp is lower at night the free cool is stoppedWrite
AV30962FreeCoolStartTimeStart time free cool functionWrite
AV30963FreeCoolStopTimeStop time free cool functionWrite
AV30964FreeCoolHeatBlockTimeTime in minute to block heat output when start after free coolWrite
AV30965CO2StartLimitLevel to activate CO2 contppmWrite
AV30966CO2DemandDiffDiffppmWrite
AV30967CO2SetpointsetpppmWrite
AV30968CO2MinTimeMin time for CO2 contppmWrite
AV30969NeedControlEnable support control if the unit is shut downWrite
AV30970NeedHeatStartRoom temp for start the unit if intermittent heating contWrite
AV30971NeedHeatStopRoom temp for stop the unit if intermittent heating contWrite
AV30972NeedCoolStartRoom temp for start the unit if intermittent cooling contWrite
AV30973NeedCoolStopRoom temp for stop the unit if intermittent cooling contWrite
AV30974NeedMinTimeMinWrite
AV30976DeIcingSetpointSetpWrite
AV30977DeIcingHystHystWrite
AV30978DeIcingMinTimeMin time for de-icingWrite
AV30979DeIcingSAFTempStopIf lower outdWrite
AV30980HumiditySetpointsetpWrite
AV30981HumidityMaxDuctMax limit humidity ductWrite
AV30982HumidityHystHystWrite
AV30983HumidityMaxDiffMax allowed diff%Write
AV30984HumidityStartLimitStart limit in % to start DO signal%Write
AV30985HumidityStopLimitStop limit in % to stop DO signal%Write
AV30986RoomSetPRoom setpWrite
AV30987FrostProtSPRunAlarm limit frost protWrite
AV30988FrostProtSPStopSetpWrite
AV30989FrostProtPGainP-Gain frost protWrite
AV30990FrostProtSPRun_1Alarm limit frost protWrite
AV30991FrostProtSPStop_1SetpWrite
AV30992FrostProtPGain_1P-Gain frost protWrite
AV30993FrostProtSPRun_2Alarm limit frost protWrite
AV30994FrostProtSPStop_2SetpWrite
AV30995FrostProtPGain_2P-Gain frost protWrite
AV30996ExtraControllerSetPSetpWrite
AV31000AlarmOutputAlarm output of configured alarm numberWrite
AV31001SupplyMaxDiffMax contWrite
AV31002SupplyHighAlarmLimitHigh alarm limit supply air tempWrite
AV31003SupplyLowAlarmLimitLow alarm limit supply air tempWrite
AV31004EfficiencyLowLimitLow efficiency%Write
AV31005RoomHighLimitHigh alarm limit room air tempWrite
AV31006RoomLowLimitLow alarm limit room air tempWrite
AV31007ExtractAirTempHighHigh alarm limit Extract air tempWrite
AV31008ExtractAirTempLowLow alarm limit Extract air tempWrite
AV31009SAFMaxDiffPressureMax contWrite
AV31010EAFMaxDiffPressureMax contWrite
AV31011RecircSetPRecirculation setpWrite
AV31013RecircMaxRoomTempIf higher room temp when recircWrite
AV31014RecircFreeCoolEnable the free cool funcWrite
AV31015RecircSAFOffsetSetpWrite
AV31016RecircEAFOffsetSetpWrite
AV31017RecircSetPOffsetOffset for recirculation setpWrite
AV31018FilterAlarmTimeTime in month between filter exchange (Service Alarm)Write
AV31019ExtraSensor1HighLimitAlWrite
AV31020ExtraSensor2HighLimitAlWrite
AV31021ExtraSensor3HighLimitAlWrite
AV31022ExtraSensor4HighLimitAlWrite
AV31023ExtraSensor5HighLimitAlWrite
AV31024ExtraSensor1LowLimitAlWrite
AV31025ExtraSensor2LowLimitAlWrite
AV31026ExtraSensor3LowLimitAlWrite
AV31027ExtraSensor4LowLimitAlWrite
AV31028ExtraSensor5LowLimitAlWrite
AV31029SelectedSensor1Select sensor 1 for high low alarmWrite
AV31030SelectedSensor1HighLimitAlWrite
AV31031SelectedSensor1LowLimitAlWrite
AV31032SelectedSensor2Select sensor 2 for high low AlWrite
AV31033SelectedSensor2HighLimitAlWrite
AV31034SelectedSensor2LowLimitAlWrite
AV31036FanComp1X1OutdWrite
AV31037FanComp1Y1CompWrite
AV31038FanComp1X2OutdWrite
AV31039FanComp1Y2CompWrite
AV31040FanComp1X3OutdWrite
AV31041FanComp1Y3CompWrite
AV31042FanComp2X1OutdWrite
AV31043FanComp2Y1CompWrite
AV31044FanComp2X2OutdWrite
AV31045FanComp2Y2CompWrite
AV31046FanComp2X3OutdWrite
AV31047FanComp2Y3CompWrite
AV31048FanComp3X1OutdWrite
AV31049FanComp3Y1CompWrite
AV31050FanComp3X2OutdWrite
AV31051FanComp3Y2CompWrite
AV31052FanComp3X3OutdWrite
AV31053FanComp3Y3CompWrite
AV31054NeutralZoneNeutral zone around supply setpWrite
AV31055FreeCoolSAFOffsetSAF setpWrite
AV31056FreeCoolEAFOffsetEAF setpWrite
AV31057FilterGuard1Limit_X1AlWrite
AV31058FilterGuard1Limit_Y1AlWrite
AV31059FilterGuard1Limit_X2AlWrite
AV31060FilterGuard1Limit_Y2AlWrite
AV31061FilterGuard2Limit_X1AlWrite
AV31062FilterGuard2Limit_Y1AlWrite
AV31063FilterGuard2Limit_X2AlWrite
AV31064FilterGuard2Limit_Y2AlWrite
AV31065SummerModeSupplySetpointSupply temp setpWrite
AV31066SummerModeOutdoortempOutdWrite
AV31071PowerFactorSupplyAirFanPower factor supply air fanWrite
AV31072PowerFactorExtractAirFanPower factor extract air fanWrite
AV31073OutdoorAirTempHighAlarm limit high outdoor air tempWrite
AV31074OutdoorAirTempLowAlarm limit low outdoor air tempWrite
AV31090ExtDisp_SetpOffsetSetpoint offsetWrite
AV31091ExtendedRunTimeExtended operation in minutes when activating digital input (min)Write
AV31092SummerModeExtractSetpointExtract air summer setpoint if extract air controlWrite
AV40250AI_1AI1Read
AV40251AI_2AI2Read
AV40252AI_3AI3Read
AV40253AI_4AI4Read
AV40254AI_5UAI1Read
AV40255AI_6UAI2Read
AV40256AI_7UAI3Read
AV40257AI_8UAI4Read
AV40258AIExp1_1AI1 ExpRead
AV40259AIExp1_2AI2 ExpRead
AV40260AIExp1_3AI3 ExpRead
AV40261AIExp1_4AI4 ExpRead
AV40262AIExp1_5UAI1 ExpRead
AV40263AIExp1_6UAI2 ExpRead
AV40264AIExp1_7UAI3 ExpRead
AV40265AIExp1_8UAI3 ExpRead
AV40266AIExp2_1AI1 ExpRead
AV40267AIExp2_2AI2 ExpRead
AV40268AIExp2_3AI3 ExpRead
AV40269AIExp2_4AI4 ExpRead
AV40270AIExp2_5UAI1 ExpRead
AV40271AIExp2_6UAI2 ExpRead
AV40272AIExp2_7UAI3 ExpRead
AV40273AIExp2_8UAI3 ExpRead
AVmin40290AI_OutDoorTempOutdoor tempRead
AV40291AI_IntakeAirTempIntake air tempRead
AVmin40292AI_SupplyAirTempSupply air tempRead
AV40293AI_ExhaustAirTempExhaust air tempRead
AV40294AI_ExtractAirTempExtract air tempRead
AV40295AI_RoomTemp1Room tempRead
AV40296AI_RoomTemp2Room tempRead
AV40297AI_RoomTemp3Room tempRead
AV40298AI_RoomTemp4Room tempRead
AV40299AI_RoomTemp5Room tempRead
AV40300AI_RoomTemp6Room tempRead
AV40301AI_RoomTemp7Room tempRead
AV40302AI_RoomTemp8Room tempRead
AV40303AI_RoomTemp9Room tempRead
AV40304AI_RoomTemp10Room tempRead
AV40305AI_RoomTemp11Room tempRead
AV40306AI_RoomTemp12Room tempRead
AV40307AI_RoomTemp13Room tempRead
AV40308AI_RoomTemp14Room tempRead
AV40309AI_RoomTemp15Room tempRead
AV40310AI_RoomTemp16Room tempRead
AV40311AI_SAFPressureSupply air fan pressRead
AV40312AI_EAFPressureExtract air fan pressRead
AV40313AI_SAFFlowSupply air fan flowRead
AV40314AI_EAFFlowExtract air fan flowRead
AV40315ExchPressureSAFExchRead
AV40316AI_ExchPressureEAFExchRead
AV40317AI_DeIcingTempDe-icing temp exchangerRead
AV40318AI_FrostprotTemp1Frost protRead
AV40319AI_FrostprotTemp2Frost protRead
AV40320AI_FrostprotTemp3Frost protRead
AV40321AI_CO2CO2 (ppm)ppmRead
AV40322AI_HumidityRoomHumidity roomRead
AV40323AI_HumidityDuctHumidity ductRead
AV40324AI_HumidityOutDoorHumidity outdoorRead
AV40325AI_ExtraControllerTempExtra cont.ler tempRead
AV40326AI_ExtSAFControlExt%Read
AV40327AI_ExtEAFControlExt%Read
AV40328AI_ExtraSensor1Extra sensor 1Read
AV40329AI_ExtraSensor2Extra sensor 2Read
AV40330AI_ExtraSensor3Extra sensor 3Read
AV40331AI_ExtraSensor4Extra sensor 4Read
AV40332AI_ExtraSensor5Extra sensor 5Read
AV40333AI_ExternalSupplySetPExtRead
AV40334AI_ExternalFlowSetPExtRead
AV40335AI_FilterGuard1AnaRead
AV40336AI_FilterGuard2AnaRead
AV40337AI_EfficiencyTemptempRead
AV40358RoomTempRoom tempRead
AV40359SAFAirFlowCounted air flow m3/h supply airRead
AV40360EAFAirFlowCounted air flow m3/h extract airRead
AV40361AI_ExchAirFlowSAFCounted air flow m3/h over exch, SAFRead
AV40362ExchAirFlowEAFCounted air flow m3/h over exch, EAFRead
AV40363AO_SeqY1Seq A output%Read
AV40364AO_SeqY2Seq B output%Read
AV40365AO_SeqY3Seq C output%Read
AV40366AO_SeqY4Seq D output%Read
AV40367AO_SeqY5Seq E output%Read
AV40368AO_SeqY6Seq F output%Read
AV40369AO_SeqY7Seq G output%Read
AV40370AO_SeqY8Seq H output%Read
AV40371AO_SeqY9Seq I output%Read
AV40372AO_SeqY10Seq J output%Read
AV40373AO_ChangeOver1Cont%Read
AV40374AO_ChangeOver2Cont%Read
AV40375AO_SAFSupply air fan cont%Read
AV40376AO_EAFExtract air fan cont%Read
AV40377AO_HumidityCont%Read
AV40378AO_StepController1Step cont%Read
AV40379AO_StepController2Step cont%Read
AV40380AO_ExtraControllerExtra cont.ler%Read
AV40381AO_AISignalOutputAI Signal output%Read
AV40402AO_1AO1VRead
AV40403AO_2AO2VRead
AV40404AO_3AO3VRead
AV40405AO_4AO4VRead
AV40406AO_5AO5VRead
AV40407AOExp1_1AO1 ExpVRead
AV40408AOExp1_2AO2 ExpVRead
AV40409AOExp1_3AO3 ExpVRead
AV40410AOExp1_4AO4 ExpVRead
AV40411AOExp1_5AO5 ExpVRead
AV40412AOExp2_1AO1 ExpVRead
AV40413AOExp2_2AO2 ExpVRead
AV40414AOExp2_3AO3 ExpVRead
AV40415AOExp2_4AO4 ExpVRead
AV40416AOExp2_5AO5 ExpVRead
AV40427EfficiencyEfficiency for exchanger%Read
AV40431ActiveHeatSeqStepCurrRead
AV40432ActiveCoolSeqStepCurrRead
AV40433ActiveYSeqCurrRead
AV40434SAFRunTimeRunhRead
AV40435EAFRunTimeRunhRead
AV40436DeIcingTimeNumber of min for ongoing de-icingminRead
AV40437NeedRunTimeNo of min in ongoing support heat/coolminRead
AV40438CO2RunTimeNo of min support run time CO2minRead
AV40439Y1SeqCont%Read
AV40440Y2SeqCont%Read
AV40441Y3SeqCont%Read
AV40442Y4SeqCont%Read
AV40443Y5SeqCont%Read
AV40444Y6SeqCont%Read
AV40445Y7SeqCont%Read
AV40446Y8SeqCont%Read
AV40447Y9SeqCont%Read
AV40448Y10SeqCont%Read
AV40449SAFCont%Read
AV40450EAFCont%Read
AV40453CompLowSpeedSAFTotal compRead
AV40454CompNormalSpeedSAFTotal compRead
AV40455CompHighSpeedSAFTotal compRead
AV40456CompLowSpeedEAFTotal compRead
AV40457CompNormalSpeedEAFTotal compRead
AV40458CompHighSpeedEAFTotal compRead
AV40459AlarmACountNo of A alarmsRead
AV40460AlarmBCountNo of B alarmsRead
AV40461AlarmCCountNo of C alarmsRead
AV40462SumAlarm1CountNo of SumAlarm1 alarmsRead
AV40463SumAlarm2CountNo of SumAlarm2 alarmsRead
AV40464SupplyPID_SetPCalcRead
AV40465SAFPID_SetPActual setpRead
AV40466EAFPID_SetPActual setpRead
AV40467FrostPID1_OutputFrost prot%Read
AV40468FrostPID2_OutputFrost prot%Read
AV40469FrostPID3_OutputFrost prot%Read
AV40470CO2PID_OutputCO2 cont.ler output%Read
AV40471DeIcePID_OutputDe-icing cont.ler output%Read
AV40472HumidityPID_OutputHum%Read
AV40473SFPActual SFPRead
AV40474SFPDayDay averRead
AV40475SFPMonthMonth averRead
AV40476MotSpHzSAF_1SAF Mot spHzRead
AV40477MotSpHzSAF_2SAF Mot spHzRead
AV40478MotSpHzSAF_3SAF Mot spHzRead
AV40479MotSpHzSAF_4SAF Mot spHzRead
AV40480MotSpHzSAF_5SAF Mot spHzRead
AV40481MotSpHzEAF_1EAF Mot spHzRead
AV40482MotSpHzEAF_2EAF Mot spHzRead
AV40483MotSpHzEAF_3EAF Mot spHzRead
AV40484MotSpHzEAF_4EAF Mot spHzRead
AV40485MotSpHzEAF_5EAF Mot spHzRead
AV40486MotSpRpmSAF_1SAF Mot sprpmRead
AV40487MotSpRpmSAF_2SAF Mot sprpmRead
AV40488MotSpRpmSAF_3SAF Mot sprpmRead
AV40489MotSpRpmSAF_4SAF Mot sprpmRead
AV40490MotSpRpmSAF_5SAF Mot sprpmRead
AV40491MotSpRpmEAF_1EAF Mot sprpmRead
AV40492MotSpRpmEAF_2EAF Mot sprpmRead
AV40493MotSpRpmEAF_3EAF Mot sprpmRead
AV40494MotSpRpmEAF_4EAF Mot sprpmRead
AV40495MotSpRpmEAF_5EAF Mot sprpmRead
AV40496MotCurrSAF_1SAF Mot currARead
AV40497MotCurrSAF_2SAF Mot currARead
AV40498MotCurrSAF_3SAF Mot currARead
AV40499MotCurrSAF_4SAF Mot currARead
AV40500MotCurrSAF_5SAF Mot currARead
AV40501MotCurrEAF_1EAF Mot currARead
AV40502MotCurrEAF_2EAF Mot currARead
AV40503MotCurrEAF_3EAF Mot currARead
AV40504MotCurrEAF_4EAF Mot currARead
AV40505MotCurrEAF_5EAF Mot currARead
AV40506MotPowSAF_1SAF Mot power%Read
AV40507MotPowSAF_2SAF Mot power%Read
AV40508MotPowSAF_3SAF Mot power%Read
AV40509MotPowSAF_4SAF Mot power%Read
AV40510MotPowSAF_5SAF Mot power%Read
AV40511MotPowEAF_1EAF Mot power%Read
AV40512MotPowEAF_2EAF Mot power%Read
AV40513MotPowEAF_3EAF Mot power%Read
AV40514MotPowEAF_4EAF Mot power%Read
AV40515MotPowEAF_5EAF Mot power%Read
AV40516ActFaultSAF_1SAF fault (bit masked)Read
AV40517ActFaultSAF_2SAF fault (bit masked)Read
AV40518ActFaultSAF_3SAF fault (bit masked)Read
AV40519ActFaultSAF_4SAF fault (bit masked)Read
AV40520ActFaultSAF_5SAF fault (bit masked)Read
AV40521ActFaultEAF_1EAF fault (bit masked)Read
AV40522ActFaultEAF_2EAF fault (bit masked)Read
AV40523ActFaultEAF_3EAF fault (bit masked)Read
AV40524ActFaultEAF_4EAF fault (bit masked)Read
AV40525ActFaultEAF_5EAF fault (bit masked)Read
AV40526ActualSpeedSAF_1SAF ActRead
AV40527ActualSpeedSAF_2SAF ActRead
AV40528ActualSpeedSAF_3SAF ActRead
AV40529ActualSpeedSAF_4SAF ActRead
AV40530ActualSpeedSAF_5SAF ActRead
AV40531ActualSpeedEAF_1EAF ActRead
AV40532ActualSpeedEAF_2EAF ActRead
AV40533ActualSpeedEAF_3EAF ActRead
AV40534ActualSpeedEAF_4EAF ActRead
AV40535ActualSpeedEAF_5EAF ActRead
AV40536AccumPowSAF_1SAF AccumRead
AV40537AccumPowSAF_2SAF AccumRead
AV40538AccumPowSAF_3SAF AccumRead
AV40539AccumPowSAF_4SAF AccumRead
AV40540AccumPowSAF_5SAF AccumRead
AV40541AccumPowEAF_1EAF AccumRead
AV40542AccumPowEAF_2EAF AccumRead
AV40543AccumPowEAF_3EAF AccumRead
AV40544AccumPowEAF_4EAF AccumRead
AV40545AccumPowEAF_5EAF AccumRead
AV40546VVXFaultVVX Fault (bit masked)Read
AV40547DampActPos_1Damper act%Read
AV40548DampActPos_2Damper act%Read
AV40549DampActPos_3Damper act%Read
AV40550DampActPos_4Damper act%Read
AV40551DampActPos_5Damper act%Read
AV40552DampFault_1Damper fault (bit masked)Read
AV40553DampFault_2Damper fault (bit masked)Read
AV40554DampFault_3Damper fault (bit masked)Read
AV40555DampFault_4Damper fault (bit masked)Read
AV40556DampFault_5Damper fault (bit masked)Read
AV40557EnergyFanDay_0Sum of today and last 7 days total energy (kWh)Read
AV40559EnergyFanDay_1Sum of today and last 7 days total energy (kWh)Read
AV40561EnergyFanDay_2Sum of today and last 7 days total energy (kWh)Read
AV40563EnergyFanDay_3Sum of today and last 7 days total energy (kWh)Read
AV40565EnergyFanDay_4Sum of today and last 7 days total energy (kWh)Read
AV40567EnergyFanDay_5Sum of today and last 7 days total energy (kWh)Read
AV40569EnergyFanDay_6Sum of today and last 7 days total energy (kWh)Read
AV40571EnergyFanDay_7Sum of today and last 7 days total energy (kWh)Read
AV40573EnergyFanMonth_1Sum of month total energy used (kWh)Read
AV40575EnergyFanMonth_2Sum of month total energy used (kWh)Read
AV40577EnergyFanMonth_3Sum of month total energy used (kWh)Read
AV40579EnergyFanMonth_4Sum of month total energy used (kWh)Read
AV40581EnergyFanMonth_5Sum of month total energy used (kWh)Read
AV40583EnergyFanMonth_6Sum of month total energy used (kWh)Read
AV40585EnergyFanMonth_7Sum of month total energy used (kWh)Read
AV40587EnergyFanMonth_8Sum of month total energy used (kWh)Read
AV40589EnergyFanMonth_9Sum of month total energy used (kWh)Read
AV40591EnergyFanMonth_10Sum of month total energy used (kWh)Read
AV40593EnergyFanMonth_11Sum of month total energy used (kWh)Read
AV40595EnergyFanMonth_12Sum of month total energy used (kWh)Read
AV40597EnergyFanMonth_13Sum of month total energy used (kWh)Read
AV40599EnergyFanMonth_14Sum of month total energy used (kWh)Read
AV40601EnergyFanMonth_15Sum of month total energy used (kWh)Read
AV40603EnergyFanMonth_16Sum of month total energy used (kWh)Read
AV40605EnergyFanMonth_17Sum of month total energy used (kWh)Read
AV40607EnergyFanMonth_18Sum of month total energy used (kWh)Read
AV40609EnergyFanMonth_19Sum of month total energy used (kWh)Read
AV40611EnergyFanMonth_20Sum of month total energy used (kWh)Read
AV40613EnergyFanMonth_21Sum of month total energy used (kWh)Read
AV40615EnergyFanMonth_22Sum of month total energy used (kWh)Read
AV40617EnergyFanMonth_23Sum of month total energy used (kWh)Read
AV40619EnergyFanMonth_24Sum of month total energy used (kWh)Read
AV40621EnergyFanMonth_25Sum of month total energy used (kWh)Read
AV40623EnergyFanMonth_26Sum of month total energy used (kWh)Read
AV40625EnergyFanMonth_27Sum of month total energy used (kWh)Read
AV40627EnergyFanMonth_28Sum of month total energy used (kWh)Read
AV40629EnergyFanMonth_29Sum of month total energy used (kWh)Read
AV40631EnergyFanMonth_30Sum of month total energy used (kWh)Read
AV40633EnergyFanMonth_31Sum of month total energy used (kWh)Read
AV40635EnergyFanMonth_32Sum of month total energy used (kWh)Read
AV40637EnergyFanMonth_33Sum of month total energy used (kWh)Read
AV40639EnergyFanMonth_34Sum of month total energy used (kWh)Read
AV40641EnergyFanMonth_35Sum of month total energy used (kWh)Read
AV40643EnergyFanMonth_36Sum of month total energy used (kWh)Read
AV40645EnergyFanYear_0Sum of year total energu used (MWh)Read
AV40647EnergyFanYear_1Sum of year total energu used (MWh)Read
AV40649EnergyFanYear_2Sum of year total energu used (MWh)Read
AV40651EnergyFanPwrCurrent fans total power (kW)Read
BV10000AlaAcknowAllCommand to acknowledge all alarmsWrite0=NORMAL, 1=ACKNOWLEDGE
BV10001FilterAlarmResetResets the filter alarm counterWrite0=Inactive, 1=Active
BV20000TC_FanLowSpeedActualTC low speedRead0=INACTIVE, 1=ACTIVE
BV20001TC_FanNormalSpeedActualTC normal speedRead0=INACTIVE, 1=ACTIVE
BV20002TC_FanHighSpeedActualTC high speedRead0=INACTIVE, 1=ACTIVE
BV20003TC_Extra1ActualTC timer 1Read0=INACTIVE, 1=ACTIVE
BV20004TC_Extra2ActualTC timer 2Read0=INACTIVE, 1=ACTIVE
BV20005TC_Extra3ActualTC timer 3Read0=INACTIVE, 1=ACTIVE
BV20006TC_Extra4ActualTC timer 4Read0=INACTIVE, 1=ACTIVE
BV20007SumAlarmSumalarmRead0=NORMAL, 1=ALARM
BVmin20008SumAlarmAA-alarmRead0=NORMAL, 1=ALARM
BVmin20009SumAlarmBB-alarmRead0=NORMAL, 1=ALARM
BV20010SumAlarmCC-alarmRead0=NORMAL, 1=ALARM
BV20011Malf_SAF1MalfRead0=NORMAL, 1=ALARM
BV20012Malf_SAF2MalfRead0=NORMAL, 1=ALARM
BV20013Malf_SAF3MalfRead0=NORMAL, 1=ALARM
BV20014Malf_SAF4MalfRead0=NORMAL, 1=ALARM
BV20015Malf_SAF5MalfRead0=NORMAL, 1=ALARM
BV20016Malf_EAF1MalfRead0=NORMAL, 1=ALARM
BV20017Malf_EAF2MalfRead0=NORMAL, 1=ALARM
BV20018Malf_EAF3MalfRead0=NORMAL, 1=ALARM
BV20019Malf_EAF4MalfRead0=NORMAL, 1=ALARM
BV20020Malf_EAF5MalfRead0=NORMAL, 1=ALARM
BV20021Ala_freq_conv_SAF1Alarm freqRead0=NORMAL, 1=ALARM
BV20022Ala_freq_conv_SAF2Alarm freqRead0=NORMAL, 1=ALARM
BV20023Ala_freq_conv_SAF3Alarm freqRead0=NORMAL, 1=ALARM
BV20024Ala_freq_conv_SAF4Alarm freqRead0=NORMAL, 1=ALARM
BV20025Ala_freq_conv_SAF5Alarm freqRead0=NORMAL, 1=ALARM
BV20026Ala_freq_conv_EAF1Alarm freqRead0=NORMAL, 1=ALARM
BV20027Ala_freq_conv_EAF2Alarm freqRead0=NORMAL, 1=ALARM
BV20028Ala_freq_conv_EAF3Alarm freqRead0=NORMAL, 1=ALARM
BV20029Ala_freq_conv_EAF4Alarm freqRead0=NORMAL, 1=ALARM
BV20030Ala_freq_conv_EAF5Alarm freqRead0=NORMAL, 1=ALARM
BV20031Warn_freq_conv_SAF1WarnRead0=NORMAL, 1=ALARM
BV20032Warn_freq_conv_SAF2WarnRead0=NORMAL, 1=ALARM
BV20033Warn_freq_conv_SAF3WarnRead0=NORMAL, 1=ALARM
BV20034Warn_freq_conv_SAF4WarnRead0=NORMAL, 1=ALARM
BV20035Warn_freq_conv_SAF5WarnRead0=NORMAL, 1=ALARM
BV20036Warn_freq_conv_EAF1WarnRead0=NORMAL, 1=ALARM
BV20037Warn_freq_conv_EAF2WarnRead0=NORMAL, 1=ALARM
BV20038Warn_freq_conv_EAF3WarnRead0=NORMAL, 1=ALARM
BV20039Warn_freq_conv_EAF4WarnRead0=NORMAL, 1=ALARM
BV20040Warn_freq_conv_EAF5WarnRead0=NORMAL, 1=ALARM
BV20041ExternaloperationSAFExternal operation SAFRead0=NORMAL, 1=ALARM
BV20042ExternaloperationEAFExternal operation EAFRead0=NORMAL, 1=ALARM
BV20043MotorCont1extOperationMotor contRead0=NORMAL, 1=ALARM
BV20044MotorCont2extOperationMotor contRead0=NORMAL, 1=ALARM
BV20045Malf_pumpheaterMalfRead0=NORMAL, 1=ALARM
BV20046Malf_pumpcoolerMalfRead0=NORMAL, 1=ALARM
BV20047Malf_pumpexchangerMalfRead0=NORMAL, 1=ALARM
BV20048Malf_firedamperMalfRead0=NORMAL, 1=ALARM
BV20049Malf_damperMalfRead0=NORMAL, 1=ALARM
BV20050Malf_motorcont_1MalfRead0=NORMAL, 1=ALARM
BV20051Malf_motorcont_2MalfRead0=NORMAL, 1=ALARM
BV20052FireDamperExStopFire damper exercise stopRead0=NORMAL, 1=ALARM
BV20053Malf_pumpseq_1MalfRead0=NORMAL, 1=ALARM
BV20054Malf_pumpseq_2MalfRead0=NORMAL, 1=ALARM
BV20055Malf_pumpseq_3MalfRead0=NORMAL, 1=ALARM
BV20056Malf_pumpseq_4MalfRead0=NORMAL, 1=ALARM
BV20057Malf_pumpseq_5MalfRead0=NORMAL, 1=ALARM
BV20058Malf_pumpseq_6MalfRead0=NORMAL, 1=ALARM
BV20059Malf_pumpseq_7MalfRead0=NORMAL, 1=ALARM
BV20060Malf_pumpseq_8MalfRead0=NORMAL, 1=ALARM
BV20061Malf_pumpseq_9MalfRead0=NORMAL, 1=ALARM
BV20062Malf_pumpseq_10MalfRead0=NORMAL, 1=ALARM
BV20063Filterguard1Filter guard 1Read0=NORMAL, 1=ALARM
BV20064Filterguard2Filter guard 2Read0=NORMAL, 1=ALARM
BV20065FlowguardFlow guardRead0=NORMAL, 1=ALARM
BV20066ExternalfrostguardExternal frost guardRead0=NORMAL, 1=ALARM
BV20067DeicingpressGuardDeicing pressRead0=NORMAL, 1=ALARM
BV20068FirealarmFire alarmRead0=NORMAL, 1=ALARM
BV20069SmokedetectoralarmSmoke detector alarmRead0=NORMAL, 1=ALARM
BV20070Ext_switchExtRead0=NORMAL, 1=ALARM
BV20071Ext_alarmExtRead0=NORMAL, 1=ALARM
BV20072ServicestopService stopRead0=NORMAL, 1=ALARM
BV20073Elec_heatingisoverheatedElecRead0=NORMAL, 1=ALARM
BV20074FrostriskFrost riskRead0=NORMAL, 1=ALARM
BV20075LowefficiencyLow efficiencyRead0=NORMAL, 1=ALARM
BV20076AnaloguedeicingAnalogue deicingRead0=NORMAL, 1=ALARM
BV20077RotationguardexchangerRotation guard exchangerRead0=NORMAL, 1=ALARM
BV20078Ex_alarm1Extra alarm 1Read0=NORMAL, 1=ALARM
BV20079Ex_alarm2Extra alarm 2Read0=NORMAL, 1=ALARM
BV20080Ex_alarm3Extra alarm 3Read0=NORMAL, 1=ALARM
BV20081Ex_alarm4Extra alarm 4Read0=NORMAL, 1=ALARM
BV20082Ex_alarm5Extra alarm 5Read0=NORMAL, 1=ALARM
BV20083Ex_alarm6Extra alarm 6Read0=NORMAL, 1=ALARM
BV20084Ex_alarm7Extra alarm 7Read0=NORMAL, 1=ALARM
BV20085Ex_alarm8Extra alarm 8Read0=NORMAL, 1=ALARM
BV20086Ex_alarm9Extra alarm 9Read0=NORMAL, 1=ALARM
BV20087Ex_alarm10Extra alarm 10Read0=NORMAL, 1=ALARM
BV20088InternalbatteryerrorInternal battery errorRead0=NORMAL, 1=ALARM
BV20089TimeforserviceTime for serviceRead0=NORMAL, 1=ALARM
BV20090RestartblockedafterpoweronRestart blocked after power onRead0=NORMAL, 1=ALARM
BV20091SupplyairtempcontErrorSupply air temp contRead0=NORMAL, 1=ALARM
BV20092SAFcontErrorSAF contRead0=NORMAL, 1=ALARM
BV20093EAFcontErrorEAF contRead0=NORMAL, 1=ALARM
BV20094HumiditycontErrorHumidity contRead0=NORMAL, 1=ALARM
BV20095ExtraControllercontollErrorExtra cont.ler contRead0=NORMAL, 1=ALARM
BV20096HighsupplyairtempHigh supply air tempRead0=NORMAL, 1=ALARM
BV20097LowsupplyairtempLow supply air tempRead0=NORMAL, 1=ALARM
BV20119Hightempsel_sensor1High temp selRead0=NORMAL, 1=ALARM
BV20120Lowtempsel_sensor1Low temp selRead0=NORMAL, 1=ALARM
BV20121Hightempsel_sensor2High temp selRead0=NORMAL, 1=ALARM
BV20122Lowtempsel_sensor2Low temp selRead0=NORMAL, 1=ALARM
BV20123ManCont_airunitManRead0=NORMAL, 1=ALARM
BV20124ManCont_supplyairManRead0=NORMAL, 1=ALARM
BV20125ManCont_SAFManRead0=NORMAL, 1=ALARM
BV20126ManCont_EAFManRead0=NORMAL, 1=ALARM
BV20127ManCont_heaterManRead0=NORMAL, 1=ALARM
BV20128ManCont_exchangerManRead0=NORMAL, 1=ALARM
BV20129ManCont_coolerManRead0=NORMAL, 1=ALARM
BV20130ManCont_damperManRead0=NORMAL, 1=ALARM
BV20131ManCont_heaterpumpManRead0=NORMAL, 1=ALARM
BV20132ManCont_exchangerpumpManRead0=NORMAL, 1=ALARM
BV20133ManCont_coolerpumpManRead0=NORMAL, 1=ALARM
BV20134ManCont_recirculationairdamperManRead0=NORMAL, 1=ALARM
BV20135ManCont_freshairdamperManRead0=NORMAL, 1=ALARM
BV20136ManCont_exhaustairdamperManRead0=NORMAL, 1=ALARM
BV20137ManCont_firedamperManRead0=NORMAL, 1=ALARM
BV20138ManCont_seq_1ManRead0=NORMAL, 1=ALARM
BV20139ManCont_seq_2ManRead0=NORMAL, 1=ALARM
BV20140ManCont_seq_3ManRead0=NORMAL, 1=ALARM
BV20141ManCont_seq_4ManRead0=NORMAL, 1=ALARM
BV20142ManCont_seq_5ManRead0=NORMAL, 1=ALARM
BV20143ManCont_seq_6ManRead0=NORMAL, 1=ALARM
BV20144ManCont_seq_7ManRead0=NORMAL, 1=ALARM
BV20145ManCont_seq_8ManRead0=NORMAL, 1=ALARM
BV20146ManCont_seq_9ManRead0=NORMAL, 1=ALARM
BV20147ManCont_seq_10ManRead0=NORMAL, 1=ALARM
BV20148OutputinManCont_Output in ManRead0=NORMAL, 1=ALARM
BV20149InputinManCont_Input in ManRead0=NORMAL, 1=ALARM
BV20150ManCont_extracont_lerManRead0=NORMAL, 1=ALARM
BV20151ManCont_motorcont_1ManRead0=NORMAL, 1=ALARM
BV20152ManCont_motorcont_2ManRead0=NORMAL, 1=ALARM
BV20153ManCont_pretreatmentManRead0=NORMAL, 1=ALARM
BV20202CommErrorDeviceFault communication deviceRead0=NORMAL, 1=ALARM
BV20203MalfunctionExtraControllerMalfunction Extra ControllerRead0=NORMAL, 1=ALARM
BV20204InternalErrorInternal errorRead0=NORMAL, 1=ALARM
BV20261DI_1DI1Read0=Inactive, 1=Active
BV20262DI_2DI2Read0=Inactive, 1=Active
BV20263DI_3DI3Read0=Inactive, 1=Active
BV20264DI_4DI4Read0=Inactive, 1=Active
BV20265DI_5DI5Read0=Inactive, 1=Active
BV20266DI_6DI6Read0=Inactive, 1=Active
BV20267DI_7DI7Read0=Inactive, 1=Active
BV20268DI_8DI8Read0=Inactive, 1=Active
BV20269DI_9UDI1Read0=Inactive, 1=Active
BV20270DI_10UDI2Read0=Inactive, 1=Active
BV20271DI_11UDI3Read0=Inactive, 1=Active
BV20272DI_12UDI4Read0=Inactive, 1=Active
BV20273DIExp1_1DI1 expRead0=Inactive, 1=Active
BV20274DIExp1_2DI2 expRead0=Inactive, 1=Active
BV20275DIExp1_3DI3 expRead0=Inactive, 1=Active
BV20276DIExp1_4DI4 expRead0=Inactive, 1=Active
BV20277DIExp1_5DI5 expRead0=Inactive, 1=Active
BV20278DIExp1_6DI6 expRead0=Inactive, 1=Active
BV20279DIExp1_7DI7 expRead0=Inactive, 1=Active
BV20280DIExp1_8DI8 expRead0=Inactive, 1=Active
BV20281DIExp1_9UDI1 expRead0=Inactive, 1=Active
BV20282DIExp1_10UDI2 expRead0=Inactive, 1=Active
BV20283DIExp1_11UDI3 expRead0=Inactive, 1=Active
BV20284DIExp1_12UDI4 expRead0=Inactive, 1=Active
BV20285DIExp2_1DI1 expRead0=Inactive, 1=Active
BV20286DIExp2_2DI2 expRead0=Inactive, 1=Active
BV20287DIExp2_3DI3 expRead0=Inactive, 1=Active
BV20288DIExp2_4DI4 expRead0=Inactive, 1=Active
BV20289DIExp2_5DI5 expRead0=Inactive, 1=Active
BV20290DIExp2_6DI6 expRead0=Inactive, 1=Active
BV20291DIExp2_7DI7 expRead0=Inactive, 1=Active
BV20292DIExp2_8DI8 expRead0=Inactive, 1=Active
BV20293DIExp2_9UDI1 expRead0=Inactive, 1=Active
BV20294DIExp2_10UDI2 expRead0=Inactive, 1=Active
BV20295DIExp2_11UDI3 expRead0=Inactive, 1=Active
BV20296DIExp2_12UDI4 expRead0=Inactive, 1=Active
BV20321DO_SeqPumpY1Start sigRead0=Inactive, 1=Active
BV20322DO_SeqPumpY2Start sigRead0=Inactive, 1=Active
BV20323DO_SeqPumpY3Start sigRead0=Inactive, 1=Active
BV20324DO_SeqPumpY4Start sigRead0=Inactive, 1=Active
BV20325DO_SeqPumpY5Start sigRead0=Inactive, 1=Active
BV20326DO_SeqPumpY6Start sigRead0=Inactive, 1=Active
BV20327DO_SeqPumpY7Start sigRead0=Inactive, 1=Active
BV20328DO_SeqPumpY8Start sigRead0=Inactive, 1=Active
BV20329DO_SeqPumpY9Start sigRead0=Inactive, 1=Active
BV20330DO_SeqPumpY10Start sigRead0=Inactive, 1=Active
BV20331DO_SAFStartStart sigRead0=Inactive, 1=Active
BV20332DO_EAFStartStart sigRead0=Inactive, 1=Active
BV20333DO_1DO1Read0=Inactive, 1=Active
BV20334DO_2DO2Read0=Inactive, 1=Active
BV20335DO_3DO3Read0=Inactive, 1=Active
BV20336DO_4DO4Read0=Inactive, 1=Active
BV20337DO_5DO5Read0=Inactive, 1=Active
BV20338DO_6DO6Read0=Inactive, 1=Active
BV20339DO_7DO7Read0=Inactive, 1=Active
BV20340DOExp1_1DO1 ExpRead0=Inactive, 1=Active
BV20341DOExp1_2DO2 ExpRead0=Inactive, 1=Active
BV20342DOExp1_3DO3 ExpRead0=Inactive, 1=Active
BV20343DOExp1_4DO4 ExpRead0=Inactive, 1=Active
BV20344DOExp1_5DO5 ExpRead0=Inactive, 1=Active
BV20345DOExp1_6DO6 ExpRead0=Inactive, 1=Active
BV20346DOExp1_7DO7 ExpRead0=Inactive, 1=Active
BV20347DOExp2_1DO1 ExpRead0=Inactive, 1=Active
BV20348DOExp2_2DO2 ExpRead0=Inactive, 1=Active
BV20349DOExp2_3DO3 ExpRead0=Inactive, 1=Active
BV20350DOExp2_4DO4 ExpRead0=Inactive, 1=Active
BV20351DOExp2_5DO5 ExpRead0=Inactive, 1=Active
BV20352DOExp2_6DO6 ExpRead0=Inactive, 1=Active
BV20353DOExp2_7DO7 ExpRead0=Inactive, 1=Active
BV20368NeedHeatActiveSupport heatingRead0=INACTIVE, 1=ACTIVE
BV20369NeedCoolActiveSupport coolingRead0=INACTIVE, 1=ACTIVE
BV20370DemandCO2ActiveSupport CO2Read0=INACTIVE, 1=ACTIVE
BV20371RecirculationRunActiveRecycle runRead0=INACTIVE, 1=ACTIVE
BV20372DeIcingActiveDe-icingRead0=INACTIVE, 1=ACTIVE
CAL1HolidayPlanThe holiday plan for time channelsRead
NC1AlarmClassANotification class for alarms of class ARead
NC2AlarmClassBNotification class for alarms of class BRead
NC3AlarmClassCNotification class for events of class CRead
SCH1TC_FanLowSpeedThe start/stop times for Fan low speedRead
SCH2TC_FanNormalSpeedThe start/stop times for Fan normal speedRead
SCH3TC_FanHighSpeedThe start/stop times for Fan high speedRead
SCH4TC_Extra1The start/stop times for extra time channel 1Read
SCH5TC_Extra2The start/stop times for extra time channel 2Read
SCH6TC_Extra3The start/stop times for extra time channel 3Read
SCH7TC_Extra4The start/stop times for extra time channel 4Read
MV30496TC_FanLowSpeed_StatusManual/Auto Low Speed time channelWrite1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30497TC_FanNormalSpeed_StatusMan/Auto Normal Speed time channelWrite1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30498TC_FanHighSpeed_StatusMan/Auto High Speed time channelWrite1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30499TC_Extra1_StatusMan/Auto Timer 1Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30500TC_Extra2_StatusMan/Auto Timer 2Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30501TC_Extra3_StatusMan/Auto Timer 3Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30502TC_Extra4_StatusMan/Auto Timer 4Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30772DOSelect_SeqPumpY1Run mode pump seq AWrite1=Man off, 2=Man on, 3=Auto
MV30773DOSelect_SeqPumpY2Run mode pump seq BWrite1=Man off, 2=Man on, 3=Auto
MV30774DOSelect_SeqPumpY3Run mode pump seq CWrite1=Man off, 2=Man on, 3=Auto
MV30775DOSelect_SeqPumpY4Run mode pump seq DWrite1=Man off, 2=Man on, 3=Auto
MV30776DOSelect_SeqPumpY5Run mode pump seq EWrite1=Man off, 2=Man on, 3=Auto
MV30777DOSelect_SeqPumpY6Run mode pump seq FWrite1=Man off, 2=Man on, 3=Auto
MV30778DOSelect_SeqPumpY7Run mode pump seq GWrite1=Man off, 2=Man on, 3=Auto
MV30779DOSelect_SeqPumpY8Run mode pump seq HWrite1=Man off, 2=Man on, 3=Auto
MV30780DOSelect_SeqPumpY9Run mode pump seq IWrite1=Man off, 2=Man on, 3=Auto
MV30781DOSelect_SeqPumpY10Run mode pump seq JWrite1=Man off, 2=Man on, 3=Auto
MV30782DOSelect_RecirculationAirDamperRun mode recircWrite1=Close, 2=Open, 3=Auto
MV30783DOSelect_OutdoorAirDamperRun mode fresh air damperWrite1=Close, 2=Open, 3=Auto
MV30784DOSelect_ExhaustAirDamperRun mode exhaust airWrite1=Close, 2=Open, 3=Auto
MV30785DOSelect_HumidityStartRun mode humidity start signalWrite1=Off, 2=On, 3=Auto
MV30786DOSelect_ChangeOver1Select changeOver ExternalWrite1=Heating, 2=Cooling, 3=Auto
MV30787DOSelect_ChangeOver2Select changeOver ExternalWrite1=Heating, 2=Cooling, 3=Auto
MVmin30788AirUnitAutoModeRunning mode air unitWrite1=OFF, 2=Manual, 3=AUTO, 4=Low speed, 5=Normal speed, 6=High speed
MV30789AirUnitManualManWrite1=Stop, 2=Starting up, 3=Low speed run, 4=Normal speed run, 5=High speed run, 6=Heat support run, 7=Cool support run, 8=CO2 Run, 9=Free cool run, 10=Fan stop run, 11=Fire run, 12=Smoke run, 13=Recirculation run,DeIcing run
MV30790SAFAutoModeRunning mode SAFWrite1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed
MV30793EAFAutoModeRunning mode EAFWrite1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed
MV30796ExternalControlExternal contWrite1=No External control, 2=Extended run speed 1, 3=Extended run speed 2, 4=Extended run speed 3, 5=External stop, 6=External stop with support control, 7=Start Free cooling, 8=Recirculation
MV30797AirUnitServiceStopStop the air unit with No 1 prioWrite1=No, 2=Yes
MV30808VentControlSelect tempWrite1=Const.supply air, 2=Outdoor comp. supply air, 3=Cascade room temp cont., 4=Extract temp cont., 5=Outdoor dep. supply or room temp, 6=Outdoor dep. supply or extract temp, 7=Cascade outdoor comp. room temp cont., 8=Cascade outdoor comp. extract temp cont., 9=Extract air dep. supply air temp.
MV30809FanTypeSelect fan contWrite1=Freq. cont. pressure, 2=Freq. cont. air flow, 3=Freq. cont. manually, 4=Direct Freq. cont., 5=Freq. cont. with slave cont. EAF, 6=Freq. cont. with slave cont. EAF air flow dep., 7=Freq. cont. with slave cont. SAF, 8=Freq. cont. with slave cont. SAF air flow dep.
MV30833SAFSetpointSelectSAF setpWrite1=Constant setpoints, 2=Offset of normal speed setpoint
MV30834EAFSetpointSelectEAF setpWrite1=Constant setpoints, 2=Offset of normal speed setpoint
MV30865SAFModeFreeCoolSAF speed in freecool modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30868SAFModeFireSAF speed in fire modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30871SAFModeSmokeSAF speed in smoke modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30874SAFModeRecirculationSAF speed in recircWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30877EAFModeFreeCoolEAF speed in freecool modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30880EAFModeFireEAF speed in fire modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30883EAFModeSmokeEAF speed in smoke modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30886EAFModeRecirculationEAF speed in recircWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30934AOSelect_HumidityRunning mode Humidification/DehumidificationWrite1=Manual off, 2=Manual on, 3=Auto
MV30936AOSelect_ExtraControllerManual/Auto Extra contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30938AOSelect_SequenceY1Seq.A contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30940AOSelect_SequenceY2Seq.B contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30942AOSelect_SequenceY3Seq.C contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30944AOSelect_SequenceY4Seq.D contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30946AOSelect_SequenceY5Seq.E contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30948AOSelect_SequenceY6Seq.F contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30950AOSelect_SequenceY7Seq.G contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30952AOSelect_SequenceY8Seq.H contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30954AOSelect_SequenceY9Seq.I contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30956AOSelect_SequenceY10Seq.J contrWrite1=Manual off, 2=Manual on, 3=Auto
MV30975FireDampersAutoModeRunWrite1=Close, 2=Open, 3=Auto
MV30997ExtraControllerModeControl mode exWrite1=Heating, 2=Cooling
MV30998SumAlarm1Selects which alarms go to sum alarm 1Write1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C
MV30999SumAlarm2Selects which alarms go to sum alarm 2Write1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C
MV31012RecircTempControlEnable supply air temp contWrite1=No temp control, 2=Heating/cooling, 3=Only heating, 4=Only cooling
MV31035SupplyPIDFreezeFreeze supply PID controlWrite1=Off, 2=On
MV36916SummerWinterModeManualManual setting for summer/winter modeWrite1=Auto, 2=Summer, 3=Winter
MVmin40428UnitModeRun modeRead1=Stop, 2=Starting up, 3=Low speed run, 4=Normal speed run, 5=High speed run, 6=Heating support run, 7=Cooling support run, 8=CO2 Run, 9=Free cool run, 10=Fan stop run, 11=Fire run, 12=Smoke run, 13=Recirculation run, 14=DeIcing run
MVmin40429UnitModeControlIndicates what is triggering the currRead1=Nothing, 2=Time schedule, 3=Manual run, 4=Digital Input, 5=Alarm, 6=External control, 7=Service stop
MV40430ActiveSeqTypeActive seqRead1=Heating, 2=Cooling
MVmin40451SAFSpeedSAF speedRead1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Special
MV40452EAFSpeedEAF speedRead1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Special
Object ID lookup: Regin Corrigo 5.0 ventilation controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Corrigo 5.0 ventilation (AHU) controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Regin Corrigo 5.0 ventilation (AHU) controller

How many BACnet points does the Regin Corrigo 5.0 ventilation (AHU) controller have?

This list has 840 BACnet objects: 552 analog values, 212 binary values, 1 calendar, 3 notification classs, 7 schedules, 65 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Regin Corrigo 5.0 ventilation (AHU) controller BACnet points are writable?

330 of the 840 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Regin Corrigo 5.0 ventilation (AHU) controller BACnet documentation?

The source is Corrigo 5.0 BACnet files (EDE) (BACnet_Corrigo50_EDE), revision 2023-10, published free by Regin at https://www.regincontrols.com/globalassets/pimmediafiles/documents/corrigo-5.0-bacnet-files.zip.

What are the minimum BACnet points to integrate the Regin Corrigo 5.0 ventilation (AHU) controller?

Start with MV 30788 AirUnitAutoMode (Unit run mode: off, manual, auto or fixed speed); AV 30811 SupplySetpoint (Supply air setpoint (constant supply control)); MV 40428 UnitMode (Actual run mode: stop, start-up, low/normal/high); MV 40429 UnitModeControl (What triggers the current run mode); AV 40292 AI_SupplyAirTemp (Supply air temperature); AV 40290 AI_OutDoorTemp (Outdoor temperature); MV 40451 SAFSpeed (Supply fan speed state); BV 20008 SumAlarmA (Sum A-alarm); BV 20009 SumAlarmB (Sum B-alarm).

How do I enable BMS control of the Regin Corrigo 5.0 ventilation (AHU) controller?

MV 30788 AirUnitAutoMode sets the unit running mode (1 OFF, 2 Manual, 3 AUTO, 4-6 low/normal/high speed). MV 30796 ExternalControl selects extended-run speeds; MV 30797 AirUnitServiceStop stops the unit with top priority.

How do I check these points on the real Corrigo 5.0 ventilation (AHU) controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Regin BACnet points lists

Source: Corrigo 5.0 BACnet files (EDE) · BACnet_Corrigo50_EDE · rev. 2023-10. Object names, instances and units are reproduced as published; descriptions are our own.