Fan coil room controller · BACnet points list

Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) BACnet points list

Updated 4 November 2026

Short answer

The RCF is a wall-mounted fan coil controller for heating, cooling and change-over with a three-speed or EC fan. Models with a C in the name have an RS485 port that runs EXOline, Modbus or BACnet MS/TP; BACnet is selected with parameter 57. All communicating models share one object list; objects for functions a model lacks stay unused.

This page lists 48 BACnet objects for the Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Regin’s own free documentation, linked below.

Manufacturer
Regin
Model
RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC)
Equipment
Fan coil room controller
Equipment type
VAV boxes & fan coils
BACnet objects
48 (23 writable)
Transport
BACnet MS/TP
Firmware
1.4-1-00 or later (BTL listed from 1.2-1-00)
Also known as
RCF, Regio RCF, RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC
Source document
RCF manual · rev. Rev. 3.2, May 2021
Download CSV 48 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Regin’s current documentation and the live device before use. Not official Regin information. Terms of use.

BMS integration notes: Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC)

Integration in brief

Set parameter 57 to BACnet MS/TP, then the MAC address and device ID (parameters 58-60). Command the unit state with RegioRemoteState (MV 5), adjust the basic setpoint (AV 33) and fan mode, and read room temperature, running mode, control mode and fan speed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 5RC_Setp_X.RegioRemoteStateUnit state command: off, economy/standby or comfortWrite
BV 10RC_Setp_L.RegioShutDownForce the unit into shutdownWrite
AV 33RC_SetpExt_R.RegioRCFSetPointBasic room setpointWrite
MV 2RC_Setp_X.RegioFanSelectFan mode: off, manual speed 1-3 or autoWrite
MI 1RC_Actual_X.RegioUnitStateCurrent running modeRead
MI 2RC_Actual_X.RegioControllerStateOff, heating or coolingRead
MI 3RC_Actual_X.RegioFanSpeedCurrent fan speedRead
AI 0RC_Actual_R.RegioRoomTempRoom temperatureRead
AV 3RC_Actual_R.RegioPIDSetPActive controller setpointRead

Enable & remote start

RegioRemoteState (MV 5) forces off, economy/standby or comfort; 6 = no remote control returns control to the buttons. RegioShutDown (BV 10) forces shutdown, and RegioFireAlarmStop (BV 9) blocks the unit until it is written back to 0.

Sensors & values from the BMS

RegioRoomTempRemote (AV 15) takes the room temperature from the network when the controller is configured for remote room temperature.

Network setup

Watch out for

Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

48 of 48 shown
Type
Other
Access
Show
Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) BACnet Points List
DescriptionStates
AImin0RC_Actual_R.RegioRoomTempRoom temperature°CRead
AI1RC_Actual_R.RegioAIChangeOverChange-over temperature°CRead
AI2RC_Actual_R.RegioAnaIn1Value on analogue input 1°CRead
AI3RC_Actual_R.RegioUAnaIn1Value on universal analogue input 1VRead
AI4RC_Actual_R.RegioSupplyAirTempSupply air temperature°CRead
AV0RC_Actual_R.RegioUAnaOut1Value on universal analogue output 1VRead
AV1RC_Actual_R.RegioUAnaOut2Value on universal analogue output 2VRead
AV2RC_Actual_R.RegioSetPAdjustmentSetpoint displacement from internal unit°CRead
AVmin3RC_Actual_R.RegioPIDSetPController setpoint°CRead
AV4RC_Actual_R.RegioPIDOutputController output%Read
AV5RC_Actual_R.RegioHeatOutputHeating control%Read
AV6RC_Actual_R.RegioCoolOutputCooling control%Read
AV9RC_Setp_R.RegioUnOccSetPHeatRoom heating setpoint in Economy mode°CWrite
AV10RC_Setp_R.RegioUnOccSetPCoolRoom cooling setpoint in Economy mode°CWrite
AV12RC_Setp_R.RegioSetPOffsetSetpoint displacement during presence°CWrite
AV13RC_Setp_R.RegioHeatOutputManualManual value heating output%Write
AV14RC_Setp_R.RegioCoolOutputManualManual value cooling output%Write
AV15RC_Setp_R.RegioRoomTempRemoteRoom temperature written from the network°CWrite
AV16RC_Setp_R.RegioStandbySetPDeadBandDeadband for Standby mode°CWrite
AV27RC_Setp_R.RegioMinECFanSpeedLowest possible speed for the EC fan%Write
AV28RC_Setp_R.RegioMaxFanSpeedHighest possible speed for the EC fan%Write
AV29RC_Setp_R.RegioAIChangeOverLimitLowCool when change-over temperature is below this°CWrite
AV30RC_Setp_R.RegioAIChangeOverLimitHighHeat when change-over temperature is above this°CWrite
AV31RC_Setp_R.RegioThermostatHystRoom temperature hysteresis°CWrite
AV32RC_Setp_R.RegioComfortSetPDeadbandDeadband for comfort mode°CWrite
AVmin33RC_SetpExt_R.RegioRCFSetPointBasic setpoint for the controller°CWrite
AV34RC_Actual_R.RegioPID2SetpCalculated supply air setpoint°CRead
BI0RC_Actual_L.RegioDIOpenWindowIndicates open windowRead
BI2RC_Actual_L.RegioDIPresencesIndicates presence from digital inputRead
BI3RC_Actual_L.RegioDIChangeOverIndicates change-over from digital inputRead
BV1RC_Actual_L.RegioCVHeatPulsPropIndicates pulse prop. heatingRead
BV2RC_Actual_L.RegioCVCoolPulsPropIndicates pulse prop. coolingRead
BV3RC_Actual_L.RegioCVHeatIncIndicates heating increaseRead
BV4RC_Actual_L.RegioCVHeatDecIndicates heating decreaseRead
BV7RC_Actual_L.RegioChangeOverStateChange-over state from digital or analogue inputRead
BV9RC_Actual_L.RegioFireAlarmStopFire alarm stop: shutdown and block restart until reset to 0Write
BVmin10RC_Setp_L.RegioShutDownPlaces the unit in Shutdown modeWrite
BV12RC_Setp_L.RegioBlockConfigPrevents parameter menu access via displayWrite
LO0ControllerRoom temperature control loopRead
MImin1RC_Actual_X.RegioUnitStateCurrent running modeRead1=Off, 2=Economy/Standby, 3=Not used, 4=Not used, 5=Comfort
MImin2RC_Actual_X.RegioControllerStateCurrent control modeRead1=Off, 2=Heating, 3=Cooling
MImin3RC_Actual_X.RegioFanSpeedCurrent fan speedRead1=Off, 2=Fan speed 1, 3=Fan speed 2, 4=Fan speed 3
MV0RC_Setp_X.RegioHeatOutputSelectManual/Auto heat outputWrite1=Off, 2=Manual output, 3=Automatic output
MV1RC_Setp_X.RegioCoolOutputSelectManual/Auto cool outputWrite1=Off, 2=Manual output, 3=Automatic output
MVmin2RC_Setp_X.RegioFanSelectFan mode selectWrite1=Off, 2=Manual speed 1, 3=Manual speed 2, 4=Manual speed 3, 5=Auto, 6=Auto 2, 7=Auto 1
MV4RC_Setp_X.RegioChangeOverSelectManual/Auto change-overWrite1=Heating, 2=Cooling, 3=Auto
MVmin5RC_Setp_X.RegioRemoteStateRemote control unit stateWrite1=Off, 2=Economy/Standby, 3=Not used, 4=Not used, 5=Comfort, 6=No remote control
MV6RC_Non_Modbus.RegioButtonActiveConfButtons activeWrite1=No buttons, 2=Occupancy button only, 3=INCREASE/DECREASE only, 4=Occupancy button and INCREASE/DECREASE, 5=Fan button only, 6=Occupancy button and fan button, 7=INCREASE/DECREASE and fan button, 8=All buttons
Object ID lookup: Regin Regio RCF point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC)

How many BACnet points does the Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) have?

This list has 48 BACnet objects: 5 analog inputs, 22 analog values, 3 binary inputs, 8 binary values, 1 loop, 3 multi-state inputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) BACnet points are writable?

23 of the 48 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC) BACnet documentation?

The source is RCF manual, revision Rev. 3.2, May 2021, published free by Regin at https://www.regincontrols.com/globalassets/pimmediafiles/documents/rcf_manu_en.pdf.

What are the minimum BACnet points to integrate the Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC)?

Start with MV 5 RC_Setp_X.RegioRemoteState (Unit state command: off, economy/standby or comfort); BV 10 RC_Setp_L.RegioShutDown (Force the unit into shutdown); AV 33 RC_SetpExt_R.RegioRCFSetPoint (Basic room setpoint); MV 2 RC_Setp_X.RegioFanSelect (Fan mode: off, manual speed 1-3 or auto); MI 1 RC_Actual_X.RegioUnitState (Current running mode); MI 2 RC_Actual_X.RegioControllerState (Off, heating or cooling); MI 3 RC_Actual_X.RegioFanSpeed (Current fan speed); AI 0 RC_Actual_R.RegioRoomTemp (Room temperature); AV 3 RC_Actual_R.RegioPIDSetP (Active controller setpoint).

How do I enable BMS control of the Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC)?

RegioRemoteState (MV 5) forces off, economy/standby or comfort; 6 = no remote control returns control to the buttons. RegioShutDown (BV 10) forces shutdown, and RegioFireAlarmStop (BV 9) blocks the unit until it is written back to 0.

Can the BMS supply sensor values to the Regin RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC)?

RegioRoomTempRemote (AV 15) takes the room temperature from the network when the controller is configured for remote room temperature.

How do I check these points on the real RCF fan coil room controllers (RCF-230CD, RCF-230CAD, RCF-230CTD, RCF-230CTD-EC)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Regin BACnet points lists