Easy BACnet
  1. Home
  2. BACnet points lists
  3. Regin
  4. Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)

Room controller (fan coil, radiator, VAV) · BACnet points list

Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) BACnet points list

Updated 4 November 2026

Short answer

Regio Midi is a wall-mounted room controller for heating, cooling, change-over, fan coil and VAV applications. The RS485 port runs EXOline, Modbus or BACnet MS/TP; BACnet is only offered on the display models and is switched on from the parameter menu or Application tool. All Midi models share one fixed object list, so objects for hardware a model lacks (CO2, fan, VAV, extra zone) simply stay unused.

This page lists 74 BACnet objects for the Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) — 38 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Regin’s own free documentation, linked below.

Manufacturer
Regin
Model
Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)
Equipment
Room controller (fan coil, radiator, VAV)
Equipment type
VAV boxes & fan coils
BACnet objects
74 (38 writable)
Transport
BACnet MS/TP
Firmware
1.7 or later (AV 35, AV 36 and AV 42 need 1.7-1-04 or newer)
Also known as
Regio Midi, RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS, RC-C
Source document
Regio Midi manual · MA30008 · rev. Rev. F, 2026-06-29
Download CSV 74 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Regin’s current documentation and the live device before use. Not official Regin information. Terms of use.

BMS integration notes: Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)

Integration in brief

Switch the controller's protocol to BACnet MS/TP in the parameter menu (or Application tool), then set the MAC address and device ID. Command occupancy with RegioRemoteState (MV 5), adjust the comfort setpoints and offset, and read room temperature, unit state, controller state and the alarm objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 5RC_Setp_X.RegioRemoteStateOccupancy command: off, unoccupied, standby, occupiedWrite
BV 10RC_Setp_L.RegioShutDownForce the unit into shutdownWrite
AV 7RC_Setp_R.RegioOccSetPHeatOccupied heating setpointWrite
AV 8RC_Setp_R.RegioOccSetPCoolOccupied cooling setpointWrite
MV 2RC_Setp_X.RegioFanSelectFan mode: off, manual speed 1-3 or autoWrite
MI 1RC_Actual_X.RegioUnitStateCurrent unit stateRead
MI 2RC_Actual_X.RegioControllerStateOff, heating or coolingRead
AI 0RC_Actual_R.RegioRoomTempRoom temperatureRead
AV 3RC_Actual_R.RegioPIDSetPActive controller setpointRead
BV 8RC_Actual_L.RegioRoomTempSensorAlarmRoom sensor faultRead

Enable & remote start

RegioRemoteState (MV 5) lets the BMS force the unit state (off, unoccupied, standby, occupied); 6 = no remote control hands control back to the local logic. RegioShutDown (BV 10) forces the shutdown state and RegioBypass (BV 9) starts a timed bypass.

Sensors & values from the BMS

RegioRoomTempRemote (AV 15) lets the BMS supply the room temperature when the controller is configured for an external room sensor; the manual gives -255 as the 'disabled' value.

Network setup

Watch out for

Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

74 of 74 shown
Type
Other
Access
Show
Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) BACnet Points List
DescriptionStates
AImin0RC_Actual_R.RegioRoomTempRoom temperature°CRead
AI1RC_Actual_R.RegioAIChangeOverChange over temperature°CRead
AI2RC_Actual_R.RegioAnaIn1Value of analogue input 1°CRead
AI3RC_Actual_R.RegioUAnaIn1Value of universal analogue input 1VRead
AI4RC_Actual_R.RegioRoomCO2CO2 input valueppmRead
AI5RC_Actual_R.RegioSupplyAirTempSupply air temperature°CRead
AI6RC_Actual_R.RegioRoomFlowAir flowl/sRead
AI7RC_Actual_R.RegioVoltInputValue on analogue input 2VRead
AI8RC_Actual_R.Regio2ndZoneTemperatureZone 2 Temperature°CRead
AV0RC_Actual_R.RegioUAnaOut1Value of universal analogue output 1VRead
AV1RC_Actual_R.RegioUAnaOut2Value of universal analogue output 2VRead
AVmin3RC_Actual_R.RegioPIDSetPController setpoint°CRead
AV4RC_Actual_R.RegioPIDOutputController output%Read
AV5RC_Actual_R.RegioHeatOutputHeat output%Read
AV6RC_Actual_R.RegioCoolOutputCool output%Read
AVmin7RC_Setp_R.RegioOccSetPHeatRoom base setpoint heating°CWrite
AVmin8RC_Setp_R.RegioOccSetPCoolRoom base setpoint cooling°CWrite
AV9RC_Setp_R.RegioUnOccSetPHeatRoom heat setpoint in unoccupied mode°CWrite
AV10RC_Setp_R.RegioUnOccSetPCoolRoom cool setpoint in unoccupied mode°CWrite
AV11RC_Setp_R.RegioFrostSetPFrost protection setpoint°CWrite
AV12RC_Setp_R.RegioSetPOffsetSetpoint adjustment°CWrite
AV13RC_Setp_R.RegioHeatOutputManualManual value heating output%Write
AV14RC_Setp_R.RegioCoolOutputManualManual value cooling output%Write
AV15RC_Setp_R.RegioRoomTempRemoteRemote control of room temperature°CWrite
AV16RC_Setp_R.RegioStandbySetPDeadBandDeadband in Standby mode°CWrite
AV17RC_Setp_R.RegioCVDeadbandDeadband control valve%Write
AV22RC_Setp_R.RegioFlow_0VFlow at 0 V input signal at AI2l/sWrite
AV23RC_Setp_R.RegioFlow_10VFlow at 10 V input signal at AI2l/sWrite
AV26RC_Setp_R.RegioMinHeatMinimum heat output at Heat control%Write
AV27RC_Setp_R.RegioMinECFanSpeedMinimum speed for the EC fan%Write
AV28RC_Setp_R.RegioMaxECFanSpeedMaximum speed for the EC fan%Write
AV29RC_Actual_R.RegioUAnaOut3Value on universal analogue output 3VRead
AV30RC_Actual_R.RegioUO3OutputUO3 output, 0-100 %%Read
AV31RC_Actual_R.RegioPID2SetpCalculated supply air setpoint°CRead
AV35CO2LimitLowCO2 level where the damper starts to open (fw 1.7-1-04+)ppmWrite
AV36CO2LimitHighCO2 level where the damper is fully open (fw 1.7-1-04+)ppmWrite
AV37RC_Setp_R.Regio2ndZoneSetpointRoom setpoint for Extra zone°CWrite
AV38RC_Setp_R.RegioRoomCO2HighLimitCO2 high alarm limitppmWrite
AV39RC_Setp_R.RegioHeat2OutputManualManual value heat output 2%Write
AV40RC_Setp_R.RegioCool2OutputManualManual value cool output 2%Write
AV41RC_Setp_R.RegioVAV2OutputManualManual value vav output 2%Write
AV42RC_Setp_R.RegioUo3OutputManualManual value for the VAV output (fw 1.7-1-04+)%Write
BI0RC_Actual_L.RegioDIOpenWindowIndicate open windowRead
BI1RC_Actual_L.RegioDICondenseAlarmIndicate condense alarm from digital inputReadYES/NO
BI2RC_Actual_L.RegioDIPresencesIndicate presence from digital inputRead
BI3RC_Actual_L.RegioDIChangeOverIndicate change over from digital inputRead
BI4RC_Actual_L.RegioRoomTempHighTempAlarmRoom high temperature alarmRead
BI5RC_Actual_L.RegioRoomTempLowTempAlarmRoom low temperature alarmRead
BI7RC_Actual_L.RegioDIindacationRun indication when DI2 is configured for itRead
BI8RC_Actual_L.RegioRoomCO2HighAlarmHigh CO2 alarm (clears when CO2 drops below the limit)Read
BV0RC_Actual_L.RegioForcedVentilationIndicate forced ventilationReadON/OFF
BV1RC_Actual_L.RegioCVHeatPulsPropIndicate pulse prop heatingRead
BV2RC_Actual_L.RegioCVCoolPulsPropIndicate pulse prop coolingRead
BV7RC_Actual_L.RegioChangeOverStateChange-over state from digital or analogue inputRead
BVmin8RC_Actual_L.RegioRoomTempSensorAlarmIndicate sensor alarm on room sensorRead
BV9RC_Setp_L.RegioBypassForce Bypass mode; returns after the Bypass time (default 120 min)Write
BVmin10RC_Setp_L.RegioShutDownForce the unit in ShutDown stateWrite
BV11RC_Setp_L.RegioComFactoryDefaultsResets communication settings to default valuesWrite
BV12RC_Setp_L.RegioBlockConfigBlock the configuration menu on the controller buttonsWrite
BV13RC_Setp_L.RegioChangeOverAdvancedUse advanced analog change-over functionWrite
LO0RegulatorRoom temperature control loopRead
MI0RC_Actual_X.RegioFanSwitchFan switch stateRead1=OFF, 2=LOW, 3=MEDIUM, 4=HIGH, 5=AUTO
MImin1RC_Actual_X.RegioUnitStateCurrent unit stateRead1=Off, 2=Unoccupied, 3=Stand-by, 4=Occupied, 5=Bypass
MImin2RC_Actual_X.RegioControllerStateCurrent controller stateRead1=Off, 2=Heating, 3=Cooling
MI3RC_Actual_X.RegioFanSpeedCurrent fan speedRead1=Off, 2=Fan speed 1, 3=Fan speed 2, 4=Fan speed 3
MV0RC_Setp_X.RegioHeatOutputSelectManual/Auto heat outputWrite1=Off, 2=Manual output, 3=Automatic output
MV1RC_Setp_X.RegioCoolOutputSelectManual/Auto cool outputWrite1=Off, 2=Manual output, 3=Automatic output
MVmin2RC_Setp_X.RegioFanSelectFan mode selectWrite1=Off, 2=Manual speed 1, 3=Manual speed 2, 4=Manual speed 3, 5=Auto, 6=Auto 2, 7=Auto 1
MV3RC_Setp_X.RegioForcedVentSelectManual/Auto forced ventilation and VAV outputWrite1=Off, 2=Manual On, 3=Auto
MV4RC_Setp_X.RegioChangeOverSelectManual/Auto change-overWrite1=Heating, 2=Cooling, 3=Auto
MVmin5RC_Setp_X.RegioRemoteStateRemote control unit stateWrite1=Off, 2=Unoccupied, 3=Stand-by, 4=Occupied, 6=No remote control
MV7RC_Setp_X.RegioHeatOutput2SelectManual/Auto for heat output 2Write0=Off, 1=Manual, 2=Auto
MV8RC_Setp_X.RegioCoolOutput2SelectManual/Auto for cool output 2Write0=Off, 1=Manual, 2=Auto
MV9RC_Setp_X.RegioVAVOuput2SelectManual/Auto for VAV output 2Write0=Off, 1=Manual, 2=Auto
Object ID lookup: Regin Regio Midi RC-C point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)

How many BACnet points does the Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) have?

This list has 74 BACnet objects: 9 analog inputs, 33 analog values, 8 binary inputs, 10 binary values, 1 loop, 4 multi-state inputs, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) BACnet points are writable?

38 of the 74 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS) BACnet documentation?

The source is Regio Midi manual (MA30008), revision Rev. F, 2026-06-29, published free by Regin at https://www.regincontrols.com/globalassets/pimmediafiles/documents/regio_midi_ma30008_en.pdf.

What are the minimum BACnet points to integrate the Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)?

Start with MV 5 RC_Setp_X.RegioRemoteState (Occupancy command: off, unoccupied, standby, occupied); BV 10 RC_Setp_L.RegioShutDown (Force the unit into shutdown); AV 7 RC_Setp_R.RegioOccSetPHeat (Occupied heating setpoint); AV 8 RC_Setp_R.RegioOccSetPCool (Occupied cooling setpoint); MV 2 RC_Setp_X.RegioFanSelect (Fan mode: off, manual speed 1-3 or auto); MI 1 RC_Actual_X.RegioUnitState (Current unit state); MI 2 RC_Actual_X.RegioControllerState (Off, heating or cooling); AI 0 RC_Actual_R.RegioRoomTemp (Room temperature); AV 3 RC_Actual_R.RegioPIDSetP (Active controller setpoint); BV 8 RC_Actual_L.RegioRoomTempSensorAlarm (Room sensor fault).

How do I enable BMS control of the Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)?

RegioRemoteState (MV 5) lets the BMS force the unit state (off, unoccupied, standby, occupied); 6 = no remote control hands control back to the local logic. RegioShutDown (BV 10) forces the shutdown state and RegioBypass (BV 9) starts a timed bypass.

Can the BMS supply sensor values to the Regin Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)?

RegioRoomTempRemote (AV 15) lets the BMS supply the room temperature when the controller is configured for an external room sensor; the manual gives -255 as the 'disabled' value.

How do I check these points on the real Regio Midi room controllers (RC-CDFO, RC-CDTO, RC-C3DOC, RC-C3DFOC, RCC-C3DOCS)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Regin BACnet points lists

Source: Regio Midi manual · MA30008 · rev. Rev. F, 2026-06-29. Object names, instances and units are reproduced as published; descriptions are our own.