Differential pressure / airflow sensor (transmitter) · BACnet points list

Regin Presigo PDTN differential pressure transmitter (firmware 1.1) BACnet points list

Updated 6 November 2026

Short answer

PDTN measures one or two differential pressures and can calculate airflow from them (K-factor formulas). Over RS485 it speaks EXOline, Modbus or BACnet MS/TP. The variable list gives 91 BACnet objects: pressure and flow per channel, range/unit/formula settings, zero calibration, analogue output values with comm-loss defaults, and display settings.

This page lists 91 BACnet objects for the Regin Presigo PDTN differential pressure transmitter (firmware 1.1) — 79 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Regin’s own free documentation, linked below.

Manufacturer
Regin
Model
Presigo PDTN differential pressure transmitter (firmware 1.1)
Equipment
Differential pressure / airflow sensor (transmitter)
Equipment type
Thermostats, sensors & meters
BACnet objects
91 (79 writable)
Transport
BACnet MS/TP
Firmware
1.1-1-00
Also known as
PDTN, Presigo PDTN, PDTN 1.1-1-00, Regin PDTN
Source document
PDTN - 1.1-1-00 Variable list · variables_pdtn_1.1-1-00 (Revision A)
Download CSV 91 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Regin’s current documentation and the live device before use. Not official Regin information. Terms of use.

BMS integration notes: Regin Presigo PDTN differential pressure transmitter (firmware 1.1)

Integration in brief

Read AV 10002 PS_1_pressure (and AV 10003 for channel 2) or the calculated flows AV 10004 / AV 10005. Set the units, range and flow formula once at commissioning.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 10002PS_1_pressureChannel 1 pressure, unit per MV 10003Read
AV 10004PS_1_flowChannel 1 calculated flowRead
AV 10003PS_2_pressureChannel 2 pressure, unit per MV 10004Read
AV 10005PS_2_flowChannel 2 calculated flowRead

Network setup

Watch out for

Regin Presigo PDTN differential pressure transmitter (firmware 1.1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

91 of 91 shown
Type
AnalogBinaryMulti-state
Access
Show
Regin Presigo PDTN differential pressure transmitter (firmware 1.1) BACnet Points List
DescriptionStates
PIV9011WinkWink for this amount of time in secondsWrite
BV9001CommCommitCommit communication settings, set to 1 to commit port settingsWrite
MV9001Port1ModeCommWrite1=PORT_MODE_INACTIVE, 3=PORT_MODE_EXOLINE_SLAVE, 14=PORT_MODE_BACNET, 16=PORT_MODE_MODBUS_SLAVE, 22=PORT_MODE_EXOLINE_MODBUS_SLAVE
MV9101Port1BaudCommWrite1=UART_BAUD_9600, 3=UART_BAUD_2400, 4=UART_BAUD_1200, 16=UART_BAUD_19k2, 18=UART_BAUD_38k4, 19=UART_BAUD_57k6, 21=UART_BAUD_115k2, 22=UART_BAUD_230k4, 23=UART_BAUD_460k8, 26=UART_BAUD_921k6, 27=UART_BAUD_1M, 28=UART_BAUD_250k
MV9201Port1FormatCommWrite17=UART_FORMAT_8N1, 25=UART_FORMAT_8N2, 49=UART_FORMAT_8E1, 57=UART_FORMAT_8E2, 113=UART_FORMAT_8O1, 121=UART_FORMAT_8O2
AV1104Pressure_1_overrideOverride valueWrite
BV1004Pressure_1_override_enSet to 1 to enable overrideWrite
AV1105Pressure_2_overrideOverride valueWrite
BV1005Pressure_2_override_enSet to 1 to enable overrideWrite
AV1201Output_Channel_1_valueValue in % set for output%Write
AV1301Output_Channel_1_defaultDefault value if communication is lost%Write
AV1401Output_Channel_1_convertedActual value on the output pin in Volt or milliampereVRead
AV1501Output_Channel_1_overrideOverride value%Write
BV1401Output_Channel_1_override_enSet to 1 to enable overrideWrite
AV1202Output_Channel_2_valueValue in % set for output%Write
AV1302Output_Channel_2_defaultDefault value if communication is lost%Write
AV1402Output_Channel_2_convertedActual value on the output pin in Volt or milliampereVRead
AV1502Output_Channel_2_overrideOverride value%Write
BV1402Output_Channel_2_override_enSet to 1 to enable overrideWrite
AV8001Disp_BrightnessFullDisplay brightness, full (%)%Write
AV8011Disp_BrightnessDimDisplay brightness, dimmed (%)%Write
AV8021Disp_TimeFullDisplay time in full modesWrite
AV8031Disp_TimeDimDisplay time in dimmed modesWrite
PIV10004PS_display_value_time_msThis is the time in milliseconds (ms) that the value is shownmsWrite
PIV10005PS_display_unit_time_msThis is the time in milliseconds (ms) that the unit is shownmsWrite
PIV10006PS_display_split_time_msThis is the time in milliseconds (ms) that the display is offmsWrite
MV10000PS_display_modeUsed to set the display layoutWrite1=DUAL_ROW, 2=SINGLE_ROW
PIV10007PS_display_channel_time_msThis is the time in milliseconds (ms) that the channel is shownmsWrite
PIV10008PS_display_text_time_msTime the custom text is shown, msmsWrite
MV11000ps_text_fontWhat font to use for the display textWrite
MV11001PS_display_text_scroll_modeScroll modeWrite
BV10003PS_display_text_replace_chn_tagIn single row, replace the CHx tag with this textWrite
AV11000PS_display_text_scroll_speedTime in ms between scrolling one pixelmsWrite
AV10026ext_value_1Can be used as @15# or @16# in custom textWrite
AV10027ext_value_2Can be used as @15# or @16# in custom textWrite
AV10028ext_value_nonvolatile_3Can be used as @17# or @18# in custom textWrite
AV10029ext_value_nonvolatile_4Can be used as @17# or @18# in custom textWrite
BV10000Adaptive_Display_TimeAdaptive Time for Display: Activate the adaptive time display for single rowWrite
MV10001PS_1_rangeRange Selected by switchWrite1=Set Zero output, 2=Range 1, 3=Range 2, 4=Range 3, 5=Range 4, 6=Range 5, 7=Range 6, 8=Range 7, 9=Range 8, 10=Range 9, 11=Custom, 21=Disable Mapping
AVmin10002PS_1_pressureCurrent pressure in the selected unitRead
AVmin10004PS_1_flowCurrent flow in the selected unitRead
MV10003PS_1_unitUsed to convert the pressure sensor output value to the preferred unitWrite1=PA, 2=KPA, 3=PSI, 4=MBAR, 5=INCH_WC, 6=MM_WC
MV10005PS_1_flow_unitUsed to convert the pressure sensor output value to the preferred unitWrite1=M3_H, 2=M3_S, 3=L_S, 4=CFM
MV10007PS_1_flow_formulaThe formula used to calculate the flow from the measured pressureWrite1=COMMON_KfactorXsqrt(P), 2=ALT1_KfactorXsqrt(2xP)/Air, 3=ALT2_1/KfactorXsqrt(P)
AV10006PS_1_flow_k_factorThe K factor used in the flow calculationWrite
AV10008PS_1_flow_air_densityAir density used on some flow calculationsWrite
MV10009PS_1_display_unitUsed to set the displayed value in the displayWrite1=None, 2=PA, 3=KPA, 4=PSI, 5=MBAR, 6=INCH_WC, 7=MM_WC, 8=M3_H, 9=M3_S, 10=L_S, 11=CFM
AV10010PS_1_display_valueUsed to read the value currently displayedRead
AV10012PS_1_MaxPressureThis variable contains maximum measurable pressure in Pascal [Pa] for the selectedPaRead
AV10014PS_1_MinPressureThis variable contains minimum measurable pressure in Pascal [Pa] for the selectedPaRead
AV10016PS_1_display_resolutionShare of the sensor range used, %Write
AV10018PS_1_resolutionShare of the sensor range used, %Write
MV10011PS_1_display_extra_unitUsed to set an additional value to be displayed for this channelWrite1=None, 2=PA, 3=KPA, 4=PSI, 5=MBAR, 6=INCH_WC, 7=MM_WC, 8=M3_H, 9=M3_S, 10=L_S, 11=CFM
AV10020PS_1_display_extra_valueUsed to read the value currently displayed extra valueWrite
AV10022PS_1_MapMaxPressureUsed for custom Mapping och analog output rangeWrite
AV10024PS_1_MapMinPressureUsed for custom Mapping och analog output rangeWrite
BV10001PS_1_set_zeroWrite 1 to start a zero calibrationWrite
CSV11000PS_1_text_rowString to show on row 1 in the displayWrite
MV10002PS_2_rangeRange Selected by switchWrite1=Set Zero output, 2=Range 1, 3=Range 2, 4=Range 3, 5=Range 4, 6=Range 5, 7=Range 6, 8=Range 7, 9=Range 8, 10=Range 9, 11=Custom, 21=Disable Mapping
AVmin10003PS_2_pressureCurrent pressure in the selected unitRead
AVmin10005PS_2_flowCurrent flow in the selected unitRead
MV10004PS_2_unitUsed to convert the pressure sensor output value to the preferred unitWrite1=PA, 2=KPA, 3=PSI, 4=MBAR, 5=INCH_WC, 6=MM_WC
MV10006PS_2_flow_unitUsed to convert the pressure sensor output value to the preferred unitWrite1=M3_H, 2=M3_S, 3=L_S, 4=CFM
MV10008PS_2_flow_formulaThe formula used to calculate the flow from the measured pressureWrite1=COMMON_KfactorXsqrt(P), 2=ALT1_KfactorXsqrt(2xP)/Air, 3=ALT2_1/KfactorXsqrt(P)
AV10007PS_2_flow_k_factorThe K factor used in the flow calculationWrite
AV10009PS_2_flow_air_densityAir density used on some flow calculationsWrite
MV10010PS_2_display_unitUsed to set the displayed value in the displayWrite1=None, 2=PA, 3=KPA, 4=PSI, 5=MBAR, 6=INCH_WC, 7=MM_WC, 8=M3_H, 9=M3_S, 10=L_S, 11=CFM
AV10011PS_2_display_valueUsed to read the value currently displayedRead
AV10013PS_2_MaxPressureThis variable contains maximum measurable pressure in Pascal [Pa] for the selectedPaRead
AV10015PS_2_MinPressureThis variable contains minimum measurable pressure in Pascal [Pa] for the selectedPaRead
AV10017PS_2_display_resolutionShare of the sensor range used, %Write
AV10019PS_2_resolutionShare of the sensor range used, %Write
MV10012PS_2_display_extra_unitUsed to set an additional value to be displayed for this channelWrite1=None, 2=PA, 3=KPA, 4=PSI, 5=MBAR, 6=INCH_WC, 7=MM_WC, 8=M3_H, 9=M3_S, 10=L_S, 11=CFM
AV10021PS_2_display_extra_valueUsed to read the value currently displayed extra valueWrite
AV10023PS_2_MapMaxPressureUsed for custom Mapping och analog output rangeWrite
AV10025PS_2_MapMinPressureUsed for custom Mapping och analog output rangeWrite
BV10002PS_2_set_zeroWrite 1 to start a zero calibrationWrite
CSV11001PS_2_text_rowString to show on row 2 in the displayWrite
MV11002rt_fb_visabilityWhen to show the custom frame bufferWrite
AV11001rt_fb_timeleftTime to show the custom frame buffersWrite
AV11002rt_fb_row0Frame buffer data for row 0 on the displayWrite
AV11003rt_fb_row1Frame buffer data for row 1 on the displayWrite
AV11004rt_fb_row2Frame buffer data for row 2 on the displayWrite
AV11005rt_fb_row3Frame buffer data for row 3 on the displayWrite
AV11006rt_fb_row4Frame buffer data for row 4 on the displayWrite
AV11007rt_fb_row5Frame buffer data for row 5 on the displayWrite
AV11008rt_fb_row6Frame buffer data for row 6 on the displayWrite
AV11009rt_fb_row7Frame buffer data for row 7 on the displayWrite
AV11010rt_fb_row8Frame buffer data for row 8 on the displayWrite
AV11011rt_fb_row9Frame buffer data for row 9 on the displayWrite
AV11012rt_fb_row10Frame buffer data for row 10 on the displayWrite
Object ID lookup: Regin Presigo PDTN differential pressure transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Presigo PDTN differential pressure transmitter (firmware 1.1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Regin Presigo PDTN differential pressure transmitter (firmware 1.1)

How many BACnet points does the Regin Presigo PDTN differential pressure transmitter (firmware 1.1) have?

This list has 91 BACnet objects: 55 analog values, 9 binary values, 19 multi-state values, 2 characterstring values, 6 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Regin Presigo PDTN differential pressure transmitter (firmware 1.1) BACnet points are writable?

79 of the 91 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Regin Presigo PDTN differential pressure transmitter (firmware 1.1) BACnet documentation?

The source is PDTN - 1.1-1-00 Variable list (variables_pdtn_1.1-1-00 (Revision A)), published free by Regin at https://www.regincontrols.com/globalassets/pimmediafiles/documents/variables_pdtn_1.1-1-00.xlsx.

What are the minimum BACnet points to integrate the Regin Presigo PDTN differential pressure transmitter (firmware 1.1)?

Start with AV 10002 PS_1_pressure (Channel 1 pressure, unit per MV 10003); AV 10004 PS_1_flow (Channel 1 calculated flow); AV 10003 PS_2_pressure (Channel 2 pressure, unit per MV 10004); AV 10005 PS_2_flow (Channel 2 calculated flow).

How do I check these points on the real Presigo PDTN differential pressure transmitter (firmware 1.1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Regin BACnet points lists