Room controller / thermostat (hotel, two zones) · BACnet points list

Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) BACnet points list

Updated 12 November 2026

Short answer

The TRT-H-2R2T controls a main room zone and a second zone (such as a bathroom) and can enable lighting and ventilation, for example from a door-card contact. BAC models talk BACnet MS/TP. The product sheet lists 32 objects: zone temperatures and setpoints, eco/frost setpoints, output levels, relay and triac outputs, mode flags and an alarm word.

This page lists 32 BACnet objects for the Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Produal’s own free documentation, linked below.

Manufacturer
Produal
Model
TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)
Equipment
Room controller / thermostat (hotel, two zones)
Equipment type
Thermostats, sensors & meters
BACnet objects
32 (20 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
TRT-H-2R2T, TRT-H-2R2T-BAC, TRT-H-2R2T-RH-BAC, Produal TRT-H, 6001TRT-H-2R2T
Source document
TRT-H-2R2T Slimline Touchscreen Hotel Thermostatic Controller, product sheet (BACnet object instance assignments) · PS 6001TRT-H-2R2T V4.05 · rev. 02/2020
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.

BMS integration notes: Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)

Integration in brief

Set the BACnet MAC address and baud rate on the controller, then write the zone setpoints (AV 0 / AV 5) and switch off/eco with BO 4 / BO 5. Read the zone temperatures, the setpoint in use and the door-card input.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 4OFF StatusOff mode (1 = off)Write
BO 5ECO StatusEco mode (1 = eco)Write
AV 0Zone 1 SetpointMain room setpointWrite
AV 5Zone 2 SetpointSecond zone (bathroom) setpointWrite
AI 0Zone 1 TempMain room temperatureRead
AI 2Zone 2 TempSecond zone temperatureRead
AI 3Setpoint (Calculated)Setpoint in useRead
BI 0DI_1 (Digital Input 1)Door card / occupancy contactRead
MI 1AlarmAlarm word + 1 (1 = no alarm)Read

Sensors & values from the BMS

AV 8 Network Temp. takes a temperature value from the network.

Network setup

Watch out for

Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

32 of 32 shown
Type
Multi-state
Access
Show
Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) BACnet Points List
DescriptionStates
AImin0Zone 1 TempZone 1 (main room) temperature°CRead
AI1Zone 3 Temp (Outside)Outside temperature°CRead
AImin2Zone 2 TempZone 2 (e.g. bathroom) temperature°CRead
AImin3Setpoint (Calculated)Setpoint in use°CRead
AI4HumidityRelative humidity%RHRead
AI5RI_1Resistive input 1°CRead
AI6Zone 1 PWM LevelZone 1 output level%Read
AI7Zone 2 PWM LevelZone 2 output level%Read
AVmin0Zone 1 Setpoint°CWrite
AV1ECO Heating Setpoint°CWrite
AV2ECO Cooling Setpoint°CWrite
AV3Frost Setpoint°CWrite
AV4Zone 1 P-BandZone 1 proportional band°CWrite
AVmin5Zone 2 Setpoint°CWrite
AV6Zone 2 P-BandZone 2 proportional band°CWrite
AV7Brightness (LCD)Display brightnessWrite
AV8Network Temp.Temperature value written over the network°CWrite
BImin0DI_1 (Digital Input 1)Digital input (e.g. door card)Read0=Off, 1=On
BI1Boost StatusBoost mode activeRead0=Off, 1=On
BO0Relay1 (Output)Write0=Off, 1=On
BO1Relay2 (Output)Write0=Off, 1=On
BO2Triac 1 (Output)Write0=Off, 1=On
BO3Triac 2 (Output)Write0=Off, 1=On
BOmin4OFF StatusOff modeWrite0=Off, 1=On
BOmin5ECO StatusEco modeWrite0=Off, 1=On
BO6LightsLighting enableWrite0=Off, 1=On
BO7A/CVentilation / A/C enableWrite0=Off, 1=On
BO8Lock ScreenWrite0=Off, 1=On
BO9Heating/Cooling ModeHeating/cooling change-overWrite0=Off, 1=On
BO10Non Volatile UpdateStore setpoints/configurationWrite0=Off, 1=On
MI0Device ModeOperating modeRead1=Comfort, 2=ECO, 3=OFF
MImin1AlarmAlarm bits + 1Read
Object ID lookup: Produal TRT-H-2R2T hotel touchscreen thermostatic controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)

How many BACnet points does the Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) have?

This list has 32 BACnet objects: 8 analog inputs, 9 analog values, 2 binary inputs, 11 binary outputs, 2 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) BACnet points are writable?

20 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models) BACnet documentation?

The source is TRT-H-2R2T Slimline Touchscreen Hotel Thermostatic Controller, product sheet (BACnet object instance assignments) (PS 6001TRT-H-2R2T V4.05), revision 02/2020, published free by Produal at https://produal-pim.rockon.io/rockon/api/v1/int/extmedia/openFile/01TGWJBKAML4CD2ANFONH2KMTBS36ATEMT.

What are the minimum BACnet points to integrate the Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)?

Start with BO 4 OFF Status (Off mode (1 = off)); BO 5 ECO Status (Eco mode (1 = eco)); AV 0 Zone 1 Setpoint (Main room setpoint); AV 5 Zone 2 Setpoint (Second zone (bathroom) setpoint); AI 0 Zone 1 Temp (Main room temperature); AI 2 Zone 2 Temp (Second zone temperature); AI 3 Setpoint (Calculated) (Setpoint in use); BI 0 DI_1 (Digital Input 1) (Door card / occupancy contact); MI 1 Alarm (Alarm word + 1 (1 = no alarm)).

Can the BMS supply sensor values to the Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)?

AV 8 Network Temp. takes a temperature value from the network.

How do I check these points on the real TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Produal BACnet points lists

Source: TRT-H-2R2T Slimline Touchscreen Hotel Thermostatic Controller, product sheet (BACnet object instance assignments) · PS 6001TRT-H-2R2T V4.05 · rev. 02/2020. Object names, instances and units are reproduced as published; descriptions are our own.