Room controller / thermostat (touchscreen) · BACnet points list
Produal TRC-P touchscreen room controller (BAC models) BACnet points list
Updated 12 November 2026
TRC-P is a wall-mounted touchscreen room controller with temperature, optional humidity and CO2, and analog, relay or triac outputs depending on the variant. BAC models talk BACnet MS/TP (B-ASC) on the RS-485 terminals. The user guide lists 43 standard objects: measurements and control demands, setpoints and dead zones, output limits and values, mode/status flags and fan speed.
This page lists 43 BACnet objects for the Produal TRC-P touchscreen room controller (BAC models) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Produal’s own free documentation, linked below.
- Manufacturer
- Produal
- Model
- TRC-P touchscreen room controller (BAC models)
- Equipment
- Room controller / thermostat (touchscreen)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 43 (32 writable)
- Transport
- BACnet MS/TP
- Firmware
- 5.01 or newer
- Also known as
- TRC-P, TRC-P-3A-BAC, TRC-P-1A2T-BAC, TRC-P-H-3R2T-BAC, TRC-P-H-2A3R-BAC, TRC-P-H-1A2R-BAC, Produal TRC-P, 6001NM2000
Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.
BMS integration notes: Produal TRC-P touchscreen room controller (BAC models)
Set the BAC model to BACnet MS/TP with a unique MAC address and baud rate, then write the mode (MSV 0) and the nominal setpoint (AV 9). Read the room temperature, the active target and the control demands; outputs set to Network follow AV 27-29 and BV 7-8.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 0 | Device Mode | Mode: 1 comfort, 2 eco, 3 off, 4 boost | Write |
| AV 9 | Nominal SP | Nominal temperature setpoint | Write |
| MV 2 | Fan | Fan speed: 1 = auto, 2-8 = speed 0-6 | Write |
| AV 0 | Built-In Sensor | Room temperature, °C | Read |
| AV 3 | Target | Target temperature in use | Read |
| AV 7 | Thermic 1 Demand | Heating/cooling demand, stage 1, % | Read |
| AV 6 | Fan Demand | Fan demand, % | Read |
| MV 1 | Alarm | Sensor/DI alarm word + 1 (1 = no alarm) | Read |
Enable & remote start
No separate enable point is listed; the comfort, eco, off and boost modes can be selected over the network (MSV 0) as well as from the display or a digital input.
Sensors & values from the BMS
AV 24 Network Temp. takes a temperature value from the network; inputs configured as Network are read from the bus instead of the terminals.
Network setup
- BACnet is only in the BAC models; device profile B-ASC.
- MS/TP baud 9600 (factory), 19200, 38400, 56000 or 76800 bit/s.
Watch out for
- BV 6 Update Nonvol stores settings to non-volatile memory; do not write it cyclically.
- Most configuration is in proprietary objects that many BACnet front ends cannot read; set it on the display or with the Produal tool.
Produal TRC-P touchscreen room controller (BAC models) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Built-In Sensor | Built-in temperature sensor | °C | Read | |
| AV | 1 | RI1 | Resistive input 1 temperature | °C | Read | |
| AV | 2 | RI2 | Resistive input 2 temperature | °C | Read | |
| AVmin | 3 | Target | Current target temperature | °C | Read | |
| AV | 4 | Humidity | Relative humidity | %RH | Read | |
| AV | 5 | CO2 | CO2 concentration | ppm | Read | |
| AVmin | 6 | Fan Demand | Fan control demand | % | Read | |
| AVmin | 7 | Thermic 1 Demand | Control demand, thermic stage 1 | % | Read | |
| AV | 8 | Thermic 2 Demand | Control demand, thermic stage 2 | % | Read | |
| AVmin | 9 | Nominal SP | Nominal temperature setpoint | °C | Write | |
| AV | 10 | Heating DZ COMFORT | Heating dead zone, comfort mode | °C | Write | |
| AV | 11 | Cooling DZ COMFORT | Cooling dead zone, comfort mode | °C | Write | |
| AV | 12 | Heating DZ ECO | Heating dead zone, eco mode | °C | Write | |
| AV | 13 | Cooling DZ ECO | Cooling dead zone, eco mode | °C | Write | |
| AV | 14 | Frost SP | Frost protection setpoint | °C | Write | |
| AV | 15 | Y1 Min. | Output Y1 minimum | % | Write | |
| AV | 16 | Y1 Max. | Output Y1 maximum | % | Write | |
| AV | 17 | Y2 Min. | Output Y2 minimum | % | Write | |
| AV | 18 | Y2 Max. | Output Y2 maximum | % | Write | |
| AV | 19 | Y3 Min. | Output Y3 minimum | % | Write | |
| AV | 20 | Y3 Max. | Output Y3 maximum | % | Write | |
| AV | 21 | PB | Proportional band | °C | Write | |
| AV | 22 | IA | Integration time | s | Write | |
| AV | 23 | Brightness | Display brightness, 0-20 | Write | ||
| AV | 24 | Network Temp. | Temperature value written over the network | °C | Write | |
| AV | 25 | CO2 SP | CO2 setpoint | ppm | Write | |
| AV | 26 | Humidity SP | Humidity setpoint | %RH | Write | |
| AV | 27 | Y1 | Output Y1 value | % | Write | |
| AV | 28 | Y2 | Output Y2 value | % | Write | |
| AV | 29 | Y3 | Output Y3 value | % | Write | |
| AV | 30 | Aux. SP | Auxiliary heating setpoint | °C | Write | |
| BV | 0 | DI1 | Digital input 1 | Read | 0=Off, 1=On | |
| BV | 1 | Boost Status | Boost mode active | Write | 0=Off, 1=On | |
| BV | 2 | Off Status | Off mode active | Write | 0=Off, 1=On | |
| BV | 3 | ECO Status | Eco mode active | Write | 0=Off, 1=On | |
| BV | 4 | Lock | Display lock | Write | 0=Off, 1=On | |
| BV | 5 | Change-Over | Heating/cooling change-over | Write | 0=Off, 1=On | |
| BV | 6 | Update Nonvol | Store settings to non-volatile memory | Write | 0=Off, 1=On | |
| BV | 7 | DO1 | Digital output 1 | Write | 0=Off, 1=On | |
| BV | 8 | DO2 | Digital output 2 | Write | 0=Off, 1=On | |
| MVmin | 0 | Device Mode | Operating mode | Write | 1=Comfort mode, 2=Eco mode, 3=Off mode, 4=Boost mode | |
| MVmin | 1 | Alarm | Alarm bits + 1 (sensor and DI1 alarms) | Read | Value = 5-bit alarm word + 1; bits: 0=internal sensor, 1=RI1, 2=RI2, 3=humidity sensor, 4=DI1 | |
| MVmin | 2 | Fan | Fan speed selection | Write | 1=Automatic, 2=Speed 0, 3=Speed 1, 4=Speed 2, 5=Speed 3, 6=Speed 4, 7=Speed 5, 8=Speed 6 |
No points match these filters.
Object ID lookup: Produal TRC-P touchscreen room controller point IDs by name
AV0Built-In SensorAV1RI1AV2RI2AV3TargetAV4HumidityAV5CO2AV6Fan DemandAV7Thermic 1 DemandAV8Thermic 2 DemandAV9Nominal SPAV10Heating DZ COMFORTAV11Cooling DZ COMFORTAV12Heating DZ ECOAV13Cooling DZ ECOAV14Frost SPAV15Y1 Min.AV16Y1 Max.AV17Y2 Min.AV18Y2 Max.AV19Y3 Min.AV20Y3 Max.AV21PBAV22IAAV23BrightnessAV24Network Temp.AV25CO2 SPAV26Humidity SPAV27Y1AV28Y2AV29Y3AV30Aux. SPBV0DI1BV1Boost StatusBV2Off StatusBV3ECO StatusBV4LockBV5Change-OverBV6Update NonvolBV7DO1BV8DO2MV0Device ModeMV1AlarmMV2Fan
Integration notes
- Object names, value ranges and units are from the user guide, chapter 5 (software 5.01 or newer); the guide has no read/write column, so access is inferred from what each object does.
- Configuration parameters sit in proprietary objects (Config1 etc., type proprietary-128) and are not listed here.
- The Alarm MSV carries a 5-bit alarm word plus 1 (internal sensor, RI1, RI2, humidity sensor, DI1).
- MS/TP 9600 (default), 19200, 38400, 56000 or 76800 bit/s, 1 stop bit, 1/2 unit load.
- Which inputs and outputs exist depends on the TRC-P variant; Y1-Y3 and DO1-DO2 follow the BMS only when the output is set to Network.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TRC-P touchscreen room controller (BAC models) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Produal TRC-P touchscreen room controller (BAC models)
How many BACnet points does the Produal TRC-P touchscreen room controller (BAC models) have?
This list has 43 BACnet objects: 31 analog values, 9 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Produal TRC-P touchscreen room controller (BAC models) BACnet points are writable?
32 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Produal TRC-P touchscreen room controller (BAC models) BACnet documentation?
The source is TRC-P - Touchscreen room controller, User Guide (chapter 5 BACnet) (EN - 6001NM2000ug), revision 16.05.2023, published free by Produal at https://produal-pim.rockon.io/rockon/api/v1/int/extmedia/openFile/01TGWJBKBRVW3XVAI6UBGLA4VEFWEAT22V.
What are the minimum BACnet points to integrate the Produal TRC-P touchscreen room controller (BAC models)?
Start with MV 0 Device Mode (Mode: 1 comfort, 2 eco, 3 off, 4 boost); AV 9 Nominal SP (Nominal temperature setpoint); MV 2 Fan (Fan speed: 1 = auto, 2-8 = speed 0-6); AV 0 Built-In Sensor (Room temperature, °C); AV 3 Target (Target temperature in use); AV 7 Thermic 1 Demand (Heating/cooling demand, stage 1, %); AV 6 Fan Demand (Fan demand, %); MV 1 Alarm (Sensor/DI alarm word + 1 (1 = no alarm)).
How do I enable BMS control of the Produal TRC-P touchscreen room controller (BAC models)?
No separate enable point is listed; the comfort, eco, off and boost modes can be selected over the network (MSV 0) as well as from the display or a digital input.
Can the BMS supply sensor values to the Produal TRC-P touchscreen room controller (BAC models)?
AV 24 Network Temp. takes a temperature value from the network; inputs configured as Network are read from the bus instead of the terminals.
How do I check these points on the real TRC-P touchscreen room controller (BAC models)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Produal BACnet points lists
- Room sensor / transmitter
Produal RT / RTX room transmitter (BACnet MS/TP)
Produal RT and RTX room transmitters with BACnet MS/TP, application software 1.1.0.51.
Also known as: RT, RTX, Produal RT, Produal RTX, RT room transmitter, RTX room transmitter - Room sensor / transmitter (display)
Produal RTX-D room transmitter with display (BACnet MS/TP)
Produal RTX-D room transmitters with display (temperature, humidity, CO2, VOC, light; outputs and configurable buttons), application software 2.1.9.7.
Also known as: RTX-D, Produal RTX-D, RTX-D room transmitter, 53011WD0B0 - Room sensor / transmitter
Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP
Produal RXX-BAC wall sensors: RCD-BAC (CO2 and temperature, optional humidity), RRH-BAC (temperature and humidity), RTE-BAC (temperature) and RLL-BAC (light level and occupancy), with 0-10 V outputs, digital inputs and optional push buttons.
Also known as: RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC, RCD, RRH, RTE, RLL, Produal RCD-BAC, Produal RRH-BAC, Produal RTE-BAC, Produal RLL-BAC, PS 6041-RCD-BAC, PS 6041-RRH-BAC, PS 6041-RTE-BAC, PS 6041-RLL-BAC, Produal RXX-BAC - Room controller (apartment ventilation, touchscreen)
Produal TRC-A-3A touchscreen apartment controller (BAC model)
Produal TRC-A-3A touchscreen apartment controller with temperature, humidity and CO2 measurement and three 0-10 V outputs (ventilation, heating/cooling, lighting), BAC model.
Also known as: TRC-A-3A, TRC-A-3A-BAC, TRC-A, Produal TRC-A, 6001CBM2000 - Thermostat (touchscreen, relay output)
Produal TRT-1R slimline touchscreen thermostat (BAC models)
Produal TRT-1R series touchscreen thermostats with one switched relay output (no time program), BAC models.
Also known as: TRT-1R, TRT-1R-BAC, TRT-1R-RH-BAC, Produal TRT-1R, 6001TRT-1R - Room controller / thermostat (hotel, two zones)
Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)
Produal TRT-H-2R2T touchscreen controllers for hotel rooms: two temperature zones (room and bathroom), two relays and two triacs, BAC models.
Also known as: TRT-H-2R2T, TRT-H-2R2T-BAC, TRT-H-2R2T-RH-BAC, Produal TRT-H, 6001TRT-H-2R2T - Thermostat (programmable touchscreen, relay output)
Produal TRT-P-1R programmable touchscreen thermostat (BAC models)
Produal TRT-P-1R series 7-day programmable touchscreen thermostats with one switched relay output, BAC models.
Also known as: TRT-P-1R, TRT-P-1R-BAC, TRT-P-1R-RH-BAC, Produal TRT-P, 6001TRT-P-1R
Source: TRC-P - Touchscreen room controller, User Guide (chapter 5 BACnet) · EN - 6001NM2000ug · rev. 16.05.2023. Object names, instances and units are reproduced as published; descriptions are our own.