Room controller / thermostat (touchscreen) · BACnet points list

Produal TRC-P touchscreen room controller (BAC models) BACnet points list

Updated 12 November 2026

Short answer

TRC-P is a wall-mounted touchscreen room controller with temperature, optional humidity and CO2, and analog, relay or triac outputs depending on the variant. BAC models talk BACnet MS/TP (B-ASC) on the RS-485 terminals. The user guide lists 43 standard objects: measurements and control demands, setpoints and dead zones, output limits and values, mode/status flags and fan speed.

This page lists 43 BACnet objects for the Produal TRC-P touchscreen room controller (BAC models) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Produal’s own free documentation, linked below.

Manufacturer
Produal
Model
TRC-P touchscreen room controller (BAC models)
Equipment
Room controller / thermostat (touchscreen)
Equipment type
Thermostats, sensors & meters
BACnet objects
43 (32 writable)
Transport
BACnet MS/TP
Firmware
5.01 or newer
Also known as
TRC-P, TRC-P-3A-BAC, TRC-P-1A2T-BAC, TRC-P-H-3R2T-BAC, TRC-P-H-2A3R-BAC, TRC-P-H-1A2R-BAC, Produal TRC-P, 6001NM2000
Source document
TRC-P - Touchscreen room controller, User Guide (chapter 5 BACnet) · EN - 6001NM2000ug · rev. 16.05.2023
Download CSV 43 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.

BMS integration notes: Produal TRC-P touchscreen room controller (BAC models)

Integration in brief

Set the BAC model to BACnet MS/TP with a unique MAC address and baud rate, then write the mode (MSV 0) and the nominal setpoint (AV 9). Read the room temperature, the active target and the control demands; outputs set to Network follow AV 27-29 and BV 7-8.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 0Device ModeMode: 1 comfort, 2 eco, 3 off, 4 boostWrite
AV 9Nominal SPNominal temperature setpointWrite
MV 2FanFan speed: 1 = auto, 2-8 = speed 0-6Write
AV 0Built-In SensorRoom temperature, °CRead
AV 3TargetTarget temperature in useRead
AV 7Thermic 1 DemandHeating/cooling demand, stage 1, %Read
AV 6Fan DemandFan demand, %Read
MV 1AlarmSensor/DI alarm word + 1 (1 = no alarm)Read

Enable & remote start

No separate enable point is listed; the comfort, eco, off and boost modes can be selected over the network (MSV 0) as well as from the display or a digital input.

Sensors & values from the BMS

AV 24 Network Temp. takes a temperature value from the network; inputs configured as Network are read from the bus instead of the terminals.

Network setup

Watch out for

Produal TRC-P touchscreen room controller (BAC models) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

43 of 43 shown
Type
AnalogBinaryMulti-state
Access
Show
Produal TRC-P touchscreen room controller (BAC models) BACnet Points List
DescriptionStates
AVmin0Built-In SensorBuilt-in temperature sensor°CRead
AV1RI1Resistive input 1 temperature°CRead
AV2RI2Resistive input 2 temperature°CRead
AVmin3TargetCurrent target temperature°CRead
AV4HumidityRelative humidity%RHRead
AV5CO2CO2 concentrationppmRead
AVmin6Fan DemandFan control demand%Read
AVmin7Thermic 1 DemandControl demand, thermic stage 1%Read
AV8Thermic 2 DemandControl demand, thermic stage 2%Read
AVmin9Nominal SPNominal temperature setpoint°CWrite
AV10Heating DZ COMFORTHeating dead zone, comfort mode°CWrite
AV11Cooling DZ COMFORTCooling dead zone, comfort mode°CWrite
AV12Heating DZ ECOHeating dead zone, eco mode°CWrite
AV13Cooling DZ ECOCooling dead zone, eco mode°CWrite
AV14Frost SPFrost protection setpoint°CWrite
AV15Y1 Min.Output Y1 minimum%Write
AV16Y1 Max.Output Y1 maximum%Write
AV17Y2 Min.Output Y2 minimum%Write
AV18Y2 Max.Output Y2 maximum%Write
AV19Y3 Min.Output Y3 minimum%Write
AV20Y3 Max.Output Y3 maximum%Write
AV21PBProportional band°CWrite
AV22IAIntegration timesWrite
AV23BrightnessDisplay brightness, 0-20Write
AV24Network Temp.Temperature value written over the network°CWrite
AV25CO2 SPCO2 setpointppmWrite
AV26Humidity SPHumidity setpoint%RHWrite
AV27Y1Output Y1 value%Write
AV28Y2Output Y2 value%Write
AV29Y3Output Y3 value%Write
AV30Aux. SPAuxiliary heating setpoint°CWrite
BV0DI1Digital input 1Read0=Off, 1=On
BV1Boost StatusBoost mode activeWrite0=Off, 1=On
BV2Off StatusOff mode activeWrite0=Off, 1=On
BV3ECO StatusEco mode activeWrite0=Off, 1=On
BV4LockDisplay lockWrite0=Off, 1=On
BV5Change-OverHeating/cooling change-overWrite0=Off, 1=On
BV6Update NonvolStore settings to non-volatile memoryWrite0=Off, 1=On
BV7DO1Digital output 1Write0=Off, 1=On
BV8DO2Digital output 2Write0=Off, 1=On
MVmin0Device ModeOperating modeWrite1=Comfort mode, 2=Eco mode, 3=Off mode, 4=Boost mode
MVmin1AlarmAlarm bits + 1 (sensor and DI1 alarms)ReadValue = 5-bit alarm word + 1; bits: 0=internal sensor, 1=RI1, 2=RI2, 3=humidity sensor, 4=DI1
MVmin2FanFan speed selectionWrite1=Automatic, 2=Speed 0, 3=Speed 1, 4=Speed 2, 5=Speed 3, 6=Speed 4, 7=Speed 5, 8=Speed 6
Object ID lookup: Produal TRC-P touchscreen room controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TRC-P touchscreen room controller (BAC models) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Produal TRC-P touchscreen room controller (BAC models)

How many BACnet points does the Produal TRC-P touchscreen room controller (BAC models) have?

This list has 43 BACnet objects: 31 analog values, 9 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Produal TRC-P touchscreen room controller (BAC models) BACnet points are writable?

32 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Produal TRC-P touchscreen room controller (BAC models) BACnet documentation?

The source is TRC-P - Touchscreen room controller, User Guide (chapter 5 BACnet) (EN - 6001NM2000ug), revision 16.05.2023, published free by Produal at https://produal-pim.rockon.io/rockon/api/v1/int/extmedia/openFile/01TGWJBKBRVW3XVAI6UBGLA4VEFWEAT22V.

What are the minimum BACnet points to integrate the Produal TRC-P touchscreen room controller (BAC models)?

Start with MV 0 Device Mode (Mode: 1 comfort, 2 eco, 3 off, 4 boost); AV 9 Nominal SP (Nominal temperature setpoint); MV 2 Fan (Fan speed: 1 = auto, 2-8 = speed 0-6); AV 0 Built-In Sensor (Room temperature, °C); AV 3 Target (Target temperature in use); AV 7 Thermic 1 Demand (Heating/cooling demand, stage 1, %); AV 6 Fan Demand (Fan demand, %); MV 1 Alarm (Sensor/DI alarm word + 1 (1 = no alarm)).

How do I enable BMS control of the Produal TRC-P touchscreen room controller (BAC models)?

No separate enable point is listed; the comfort, eco, off and boost modes can be selected over the network (MSV 0) as well as from the display or a digital input.

Can the BMS supply sensor values to the Produal TRC-P touchscreen room controller (BAC models)?

AV 24 Network Temp. takes a temperature value from the network; inputs configured as Network are read from the bus instead of the terminals.

How do I check these points on the real TRC-P touchscreen room controller (BAC models)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Produal BACnet points lists

Source: TRC-P - Touchscreen room controller, User Guide (chapter 5 BACnet) · EN - 6001NM2000ug · rev. 16.05.2023. Object names, instances and units are reproduced as published; descriptions are our own.