Produal TRC-A-3A touchscreen apartment controller (BAC model) BACnet points list
Updated 12 November 2026
TRC-A-3A is a touchscreen apartment controller for ventilation and room temperature, with home/away/boost modes, three analog outputs and digital inputs. The BAC model speaks BACnet MS/TP (B-ASC). Its object map differs from the TRC-P: measurements are AIs, settings AVs, digital inputs BIs and mode flags BOs (40 objects).
This page lists 40 BACnet objects for the Produal TRC-A-3A touchscreen apartment controller (BAC model) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Produal’s own free documentation, linked below.
- Manufacturer
- Produal
- Model
- TRC-A-3A touchscreen apartment controller (BAC model)
- Equipment
- Room controller (apartment ventilation, touchscreen)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 40 (27 writable)
- Transport
- BACnet MS/TP
- Firmware
- 5.02 or newer
- Also known as
- TRC-A-3A, TRC-A-3A-BAC, TRC-A, Produal TRC-A, 6001CBM2000
Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.
BMS integration notes: Produal TRC-A-3A touchscreen apartment controller (BAC model)
Give the BAC model a unique MS/TP MAC address and baud rate, then write the home/away/boost mode (MSV 0) and the nominal setpoint (AV 0), and read temperature, humidity, CO2 and the fan demand.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 0 | Device Mode | Mode: 1 home, 2 away, 3 boost | Write |
| AV 0 | Nominal SP | Nominal temperature setpoint | Write |
| AV 15 | CO2 SP | CO2 setpoint, ppm | Write |
| AI 0 | Built-In Sensor | Room temperature, °C | Read |
| AI 4 | Humidity | Room relative humidity | Read |
| AI 5 | CO2 | Room CO2, ppm | Read |
| AI 6 | Fan Demand | Ventilation demand, % | Read |
| MV 1 | Alarm | Alarm word + 1 (1 = no alarm) | Read |
Enable & remote start
No separate enable point is listed; home, away and boost can be selected over the network (MSV 0), from the display or by a digital input.
Sensors & values from the BMS
AV 14 Network Temp. takes a temperature value from the network.
Network setup
- BACnet is only in the BAC model; device profile B-ASC.
- MS/TP baud 9600 (factory), 19200, 38400, 56000 or 76800 bit/s.
Watch out for
- BO 3 Update Nonvol stores settings to non-volatile memory; do not write it cyclically.
Produal TRC-A-3A touchscreen apartment controller (BAC model) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Built-In Sensor | Built-in temperature sensor | °C | Read | |
| AI | 1 | RI1 | Resistive input 1 temperature | °C | Read | |
| AI | 2 | RI2 | Resistive input 2 temperature | °C | Read | |
| AI | 3 | Target | Current target temperature | °C | Read | |
| AImin | 4 | Humidity | Relative humidity | %RH | Read | |
| AImin | 5 | CO2 | CO2 concentration | ppm | Read | |
| AImin | 6 | Fan Demand | Fan (ventilation) demand | % | Read | |
| AI | 7 | Lights Demand | Lighting demand | % | Read | |
| AVmin | 0 | Nominal SP | Nominal temperature setpoint | °C | Write | |
| AV | 1 | Heating DZ COMFORT | Heating dead zone, home mode | °C | Write | |
| AV | 2 | Cooling DZ COMFORT | Cooling dead zone, home mode | °C | Write | |
| AV | 3 | Heating DZ ECO | Heating dead zone, away mode | °C | Write | |
| AV | 4 | Cooling DZ ECO | Cooling dead zone, away mode | °C | Write | |
| AV | 5 | Y1 Min. | Output Y1 minimum | % | Write | |
| AV | 6 | Y1 Max. | Output Y1 maximum | % | Write | |
| AV | 7 | Y2 Min. | Output Y2 minimum | % | Write | |
| AV | 8 | Y2 Max. | Output Y2 maximum | % | Write | |
| AV | 9 | Y3 Min. | Output Y3 minimum | % | Write | |
| AV | 10 | Y3 Max. | Output Y3 maximum | % | Write | |
| AV | 11 | PB | Proportional band | °C | Write | |
| AV | 12 | IA | Integration time | s | Write | |
| AV | 13 | Brightness | Display brightness | Write | ||
| AV | 14 | Network Temp. | Temperature value written over the network | °C | Write | |
| AVmin | 15 | CO2 SP | CO2 setpoint | ppm | Write | |
| AV | 16 | Humidity SP | Humidity setpoint | %RH | Write | |
| AV | 17 | Y1 | Output Y1 value | % | Write | |
| AV | 18 | Y2 | Output Y2 value | % | Write | |
| AV | 19 | Y3 | Output Y3 value | % | Write | |
| MVmin | 0 | Device Mode | Operating mode | Write | 1=Home mode, 2=Away mode, 3=Boost mode | |
| MVmin | 1 | Alarm | Alarm bits + 1 | Read | Value = 7-bit alarm word + 1; bits: 0=internal sensor, 1=RI1, 2=RI2, 3=humidity sensor, 4=DI1, 5=supply air flow, 6=extract air flow | |
| MV | 2 | Lights | Lighting level | Write | 1=Off, 2=Level 1, 3=Level 2, 4=Level 3 | |
| BI | 0 | DI1 | Digital input 1 | Read | 0=Off, 1=On | |
| BI | 1 | Boost Status | Boost mode active | Read | 0=Off, 1=On | |
| BI | 2 | DI2 | Digital input 2 | Read | 0=Off, 1=On | |
| BI | 3 | DI3 | Digital input 3 | Read | 0=Off, 1=On | |
| BO | 0 | ECO Status | Eco (away) mode | Write | 0=Off, 1=On | |
| BO | 1 | Lock | Display lock | Write | 0=Off, 1=On | |
| BO | 2 | Change-Over | Heating/cooling change-over | Write | 0=Off, 1=On | |
| BO | 3 | Update Nonvol | Store settings to non-volatile memory | Write | 0=Off, 1=On | |
| BO | 4 | TestMode | Test mode | Write | 0=Off, 1=On |
No points match these filters.
Object ID lookup: Produal TRC-A-3A touchscreen apartment controller point IDs by name
AI0Built-In SensorAI1RI1AI2RI2AI3TargetAI4HumidityAI5CO2AI6Fan DemandAI7Lights DemandAV0Nominal SPAV1Heating DZ COMFORTAV2Cooling DZ COMFORTAV3Heating DZ ECOAV4Cooling DZ ECOAV5Y1 Min.AV6Y1 Max.AV7Y2 Min.AV8Y2 Max.AV9Y3 Min.AV10Y3 Max.AV11PBAV12IAAV13BrightnessAV14Network Temp.AV15CO2 SPAV16Humidity SPAV17Y1AV18Y2AV19Y3MV0Device ModeMV1AlarmMV2LightsBI0DI1BI1Boost StatusBI2DI2BI3DI3BO0ECO StatusBO1LockBO2Change-OverBO3Update NonvolBO4TestMode
Integration notes
- Object names, ranges and units are from the user guide, chapter 5 (software 5.02 or newer); the guide has no read/write column, so access is inferred from what each object does.
- Configuration parameters sit in proprietary objects (type proprietary-128) and are not listed.
- The Alarm MSV carries a 7-bit alarm word plus 1 (sensors, DI1, supply and extract air flow).
- MS/TP 9600 (default), 19200, 38400, 56000 or 76800 bit/s.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TRC-A-3A touchscreen apartment controller (BAC model) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Produal TRC-A-3A touchscreen apartment controller (BAC model)
How many BACnet points does the Produal TRC-A-3A touchscreen apartment controller (BAC model) have?
This list has 40 BACnet objects: 8 analog inputs, 20 analog values, 4 binary inputs, 5 binary outputs, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Produal TRC-A-3A touchscreen apartment controller (BAC model) BACnet points are writable?
27 of the 40 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Produal TRC-A-3A touchscreen apartment controller (BAC model) BACnet documentation?
The source is TRC-A-3A - Touchscreen apartment controller, User Guide (chapter 5 BACnet) (EN - 6001CBM2000ug), revision 14.09.2023, published free by Produal at https://produal-pim.rockon.io/rockon/api/v1/int/extmedia/openFile/01TGWJBKCSDMEWJVUDQNGKE26DEI5JQNNU.
What are the minimum BACnet points to integrate the Produal TRC-A-3A touchscreen apartment controller (BAC model)?
Start with MV 0 Device Mode (Mode: 1 home, 2 away, 3 boost); AV 0 Nominal SP (Nominal temperature setpoint); AV 15 CO2 SP (CO2 setpoint, ppm); AI 0 Built-In Sensor (Room temperature, °C); AI 4 Humidity (Room relative humidity); AI 5 CO2 (Room CO2, ppm); AI 6 Fan Demand (Ventilation demand, %); MV 1 Alarm (Alarm word + 1 (1 = no alarm)).
How do I enable BMS control of the Produal TRC-A-3A touchscreen apartment controller (BAC model)?
No separate enable point is listed; home, away and boost can be selected over the network (MSV 0), from the display or by a digital input.
Can the BMS supply sensor values to the Produal TRC-A-3A touchscreen apartment controller (BAC model)?
AV 14 Network Temp. takes a temperature value from the network.
How do I check these points on the real TRC-A-3A touchscreen apartment controller (BAC model)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Produal BACnet points lists
- Room sensor / transmitter
Produal RT / RTX room transmitter (BACnet MS/TP)
Produal RT and RTX room transmitters with BACnet MS/TP, application software 1.1.0.51.
Also known as: RT, RTX, Produal RT, Produal RTX, RT room transmitter, RTX room transmitter - Room sensor / transmitter (display)
Produal RTX-D room transmitter with display (BACnet MS/TP)
Produal RTX-D room transmitters with display (temperature, humidity, CO2, VOC, light; outputs and configurable buttons), application software 2.1.9.7.
Also known as: RTX-D, Produal RTX-D, RTX-D room transmitter, 53011WD0B0 - Room sensor / transmitter
Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP
Produal RXX-BAC wall sensors: RCD-BAC (CO2 and temperature, optional humidity), RRH-BAC (temperature and humidity), RTE-BAC (temperature) and RLL-BAC (light level and occupancy), with 0-10 V outputs, digital inputs and optional push buttons.
Also known as: RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC, RCD, RRH, RTE, RLL, Produal RCD-BAC, Produal RRH-BAC, Produal RTE-BAC, Produal RLL-BAC, PS 6041-RCD-BAC, PS 6041-RRH-BAC, PS 6041-RTE-BAC, PS 6041-RLL-BAC, Produal RXX-BAC - Room controller / thermostat (touchscreen)
Produal TRC-P touchscreen room controller (BAC models)
Produal TRC-P touchscreen room controllers (fan coil, chilled beam, radiator and auxiliary heat applications), BAC models.
Also known as: TRC-P, TRC-P-3A-BAC, TRC-P-1A2T-BAC, TRC-P-H-3R2T-BAC, TRC-P-H-2A3R-BAC, TRC-P-H-1A2R-BAC, Produal TRC-P, 6001NM2000 - Thermostat (touchscreen, relay output)
Produal TRT-1R slimline touchscreen thermostat (BAC models)
Produal TRT-1R series touchscreen thermostats with one switched relay output (no time program), BAC models.
Also known as: TRT-1R, TRT-1R-BAC, TRT-1R-RH-BAC, Produal TRT-1R, 6001TRT-1R - Room controller / thermostat (hotel, two zones)
Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)
Produal TRT-H-2R2T touchscreen controllers for hotel rooms: two temperature zones (room and bathroom), two relays and two triacs, BAC models.
Also known as: TRT-H-2R2T, TRT-H-2R2T-BAC, TRT-H-2R2T-RH-BAC, Produal TRT-H, 6001TRT-H-2R2T - Thermostat (programmable touchscreen, relay output)
Produal TRT-P-1R programmable touchscreen thermostat (BAC models)
Produal TRT-P-1R series 7-day programmable touchscreen thermostats with one switched relay output, BAC models.
Also known as: TRT-P-1R, TRT-P-1R-BAC, TRT-P-1R-RH-BAC, Produal TRT-P, 6001TRT-P-1R
Source: TRC-A-3A - Touchscreen apartment controller, User Guide (chapter 5 BACnet) · EN - 6001CBM2000ug · rev. 14.09.2023. Object names, instances and units are reproduced as published; descriptions are our own.