Room sensor / transmitter · BACnet points list

Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP BACnet points list

Updated 12 November 2026

Short answer

The RXX-BAC sensors are wall room sensors with a built-in BACnet MS/TP interface, three 0-10 V outputs, resistive and digital inputs and two triac outputs; they can also run simple control loops. All four models use one fixed object map: sensor AIs, Y1-Y3 AOs, setpoint and pulse-count AVs, input and push-button BIs, output and LED BOs, and an alarm-level MSI. Objects for sensors a model does not have are printed as Not Assigned. This list is the full RCD-BAC set.

This page lists 35 BACnet objects for the Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Produal’s own free documentation, linked below.

Manufacturer
Produal
Model
RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP
Equipment
Room sensor / transmitter
Equipment type
Thermostats, sensors & meters
BACnet objects
35 (20 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC, RCD, RRH, RTE, RLL, Produal RCD-BAC, Produal RRH-BAC, Produal RTE-BAC, Produal RLL-BAC, PS 6041-RCD-BAC, PS 6041-RRH-BAC, PS 6041-RTE-BAC, PS 6041-RLL-BAC, Produal RXX-BAC
Source document
RCD-BAC Room CO2 and Temperature Sensors with BACnet, product sheet · PS 6041-RCD-BAC · rev. 07/2024
Download CSV 35 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.

BMS integration notes: Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP

Integration in brief

Set the MS/TP MAC address and baud rate on the DIP switches, then read the measurements. When the sensor runs its own control, write the setpoints (AV 0-3); outputs set to network value follow the AOs. Settings written over BACnet are kept only after BO 8 NonVol Update is set.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2CO2 SetpointCO2 setpoint, ppmWrite
AV 0Temperature SetpointTemperature setpointWrite
AI 0Temperature SensorRoom temperatureRead
AI 5C02 SensorRoom CO2, ppmRead
AI 2Humidity SensorRoom relative humidityRead
AI 1Setpoint AdjustUser setpoint adjustmentRead
BI 2OccupancyOccupancy inputRead
MI 0Alarm LevelAlarm level: 1 green, 2 amber, 3 redRead

Network setup

Watch out for

Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

35 of 35 shown
Type
Multi-state
Access
Show
Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP BACnet Points List
DescriptionStates
AImin0Temperature SensorRoom temperature°CRead
AImin1Setpoint AdjustSetpoint adjustment knob value°CRead
AImin2Humidity SensorRoom relative humidity%Read
AI3RI1 / AI1Resistive input 1ΩRead
AI4RI2 / AI2Resistive input 2ΩRead
AImin5C02 SensorRoom CO2 concentrationppmRead
AI6LUX SensorLight levellxRead
AO0Y1Analog output Y1 (when set to network value)%Write
AO1Y2Analog output Y2 (when set to network value)%Write
AO2Y3Analog output Y3 (when set to network value)%Write
AVmin0Temperature SetpointTemperature setpoint°CWrite
AV1Humidity SetpointHumidity Setpoint%Write
AVmin2CO2 SetpointCO2 SetpointppmWrite
AV3LUX SetpointLight level setpointlxWrite
AV4DI1 Pulse CountPulse count on DI1Write
AV5DI2 Pulse CountPulse count on DI2Write
AV6LCD Backlight BrightnessDisplay backlight 0-10Write
AV7Amber Alarm ThresholdThreshold for amber alarm levelWrite
AV8Red Alarm ThresholdThreshold for red alarm levelWrite
BI0DI1Digital input 1Read0=off, 1=on
BI1DI2Digital input 2Read0=off, 1=on
BImin2OccupancyOccupancyRead0=off, 1=on
BI3Push Button 1Push button 1 (button options)Read0=off, 1=on
BI4Push Button 2Push button 2 (button options)Read0=off, 1=on
BI5Push Button 3Push button 3 (button options)Read0=off, 1=on
BI6Push Button 4Push button 4 (button options)Read0=off, 1=on
BO0DO1Digital (triac) output 1Command0=off, 1=on
BO1DO2Digital (triac) output 2Command0=off, 1=on
BO2SPA Reset1 disables the user setpoint adjustment (SPB option)Command0=off, 1=on
BO3PB1_LEDPush button 1 LEDCommand0=off, 1=on
BO4PB2_LEDPush button 2 LEDCommand0=off, 1=on
BO5PB3_LEDPush button 3 LEDCommand0=off, 1=on
BO6PB4_LEDPush button 4 LEDCommand0=off, 1=on
BO8NonVol UpdateStore BACnet-written settingsCommand0=off, 1=on
MImin0Alarm LevelAlarm level indicationRead1=Green, 2=Amber, 3=Red
Object ID lookup: Produal RXX-BAC room sensors with BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP

How many BACnet points does the Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP have?

This list has 35 BACnet objects: 7 analog inputs, 3 analog outputs, 9 analog values, 7 binary inputs, 8 binary outputs, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP BACnet points are writable?

20 of the 35 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP BACnet documentation?

The source is RCD-BAC Room CO2 and Temperature Sensors with BACnet, product sheet (PS 6041-RCD-BAC), revision 07/2024, published free by Produal at https://produal-pim.rockon.io/rockon/api/v1/int/extmedia/openFile/01TGWJBKEKIBLBX64BNRBLTZJF3OTRO3OZ.

What are the minimum BACnet points to integrate the Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP?

Start with AV 2 CO2 Setpoint (CO2 setpoint, ppm); AV 0 Temperature Setpoint (Temperature setpoint); AI 0 Temperature Sensor (Room temperature); AI 5 C02 Sensor (Room CO2, ppm); AI 2 Humidity Sensor (Room relative humidity); AI 1 Setpoint Adjust (User setpoint adjustment); BI 2 Occupancy (Occupancy input); MI 0 Alarm Level (Alarm level: 1 green, 2 amber, 3 red).

How do I check these points on the real RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Produal BACnet points lists

Source: RCD-BAC Room CO2 and Temperature Sensors with BACnet, product sheet · PS 6041-RCD-BAC · rev. 07/2024. Object names, instances and units are reproduced as published; descriptions are our own.