Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

RTX-D is a room transmitter/controller with display that measures temperature, humidity, CO2, VOC and light, and has external inputs, four outputs and configurable buttons. It is a BACnet MS/TP B-ASC device. The PICS gives 65 objects: measurements, calculated values (dew point, enthalpy and so on), BMS-written controller inputs, setpoints and output values, button states and timers.

This page lists 65 BACnet objects for the Produal RTX-D room transmitter with display (BACnet MS/TP) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Produal’s documentation hosted by BACnet International, not by Produal itself, so treat it as unofficial.

Manufacturer
Produal
Model
RTX-D room transmitter with display (BACnet MS/TP)
Equipment
Room sensor / transmitter (display)
Equipment type
Thermostats, sensors & meters
BACnet objects
65 (22 writable)
Transport
BACnet MS/TP
Firmware
2.1.9.7
Also known as
RTX-D, Produal RTX-D, RTX-D room transmitter, 53011WD0B0
Source document
BACnet protocol implementation conformance statement, RTX-D (published 02.02.2026) · EN - 53011WD0B0PICS · rev. 02.02.2026 (unofficial copy, hosted by BACnet International)
Download CSV 65 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.

BMS integration notes: Produal RTX-D room transmitter with display (BACnet MS/TP)

Integration in brief

Give the transmitter a unique MS/TP address, then read temperature, humidity, CO2 and VOC. When the RTX-D acts as a controller, write the setpoints (AV 19200-19203) or feed BUS-CONTROLLER inputs; outputs set to bus control follow the BUS-OUTPUTn-POWER values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 19200SETPOINT-TEMPERATURETemperature setpointWrite
AV 19202SETPOINT-CO2CO2 setpoint, ppmWrite
AI 0TEMPERATURERoom temperatureRead
AI 1HUMIDITYRoom relative humidityRead
AI 2CO2Room CO2, ppmRead
AI 3TVOCTotal VOC, µg/m³Read
MV 72VOC-DETAILED-STATUSVOC sensor status (1 = normal)Read

Sensors & values from the BMS

BUS-CONTROLLER-INPUT-T/-RH/-CO2/-CO2-VOC (AV 1003-1006) and OUTDOOR-TEMPERATURE-BUS-VALUE (AV 19100) take values from the BMS.

Network setup

Watch out for

Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

65 of 65 shown
Type
Multi-state
Access
Show
Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0TEMPERATURERoom temperature°C/°FRead
AImin1HUMIDITYRoom relative humidity%RHRead
AImin2CO2Room CO2ppmRead
AImin3TVOCTotal VOCµg/m³Read
AI5EXTERNAL-INPUT-1-VOLTAGEExternal input measurementVRead
AI6EXTERNAL-INPUT-1-RESISTANCEExternal input measurementΩRead
AI8EXTERNAL-INPUT-1-TEMPERATUREExternal input measurement°C/°FRead
AI9EXTERNAL-INPUT-1-HUMIDITYExternal input measurement%RHRead
AI10EXTERNAL-INPUT-1-CO2External input measurementppmRead
AI11EXTERNAL-INPUT-1-VOCExternal input measurementµg/m³Read
AI85EXTERNAL-INPUT-2-RESISTANCEExternal input measurementΩRead
AI86EXTERNAL-INPUT-2-TEMPERATUREExternal input measurement°C/°FRead
AV13OUTPUT1-VOLTAGEAnalog output 1 voltageVRead
AV14OUTPUT2-VOLTAGEAnalog output 2 voltageVRead
AV15OUTPUT3-VOLTAGEAnalog output 3 voltageVRead
AV16OUTPUT4-VOLTAGEAnalog output 4 voltageVRead
AV17AVERAGE TEMPERATURE°C/°FRead
AV18DEW-POINTCalculated dew point°C/°FRead
AV21ABSOLUTE-HUMIDITYCalculated absolute humidityg/m³Read
AV22MIXING-RATIOCalculated mixing ratiog/kgRead
AV23ENTHALPYCalculated enthalpykJ/kgRead
AV24VOC-TVOC-PPBppbRead
AV25VOC-CO2-EQV-PPMppmRead
AV26VOC-AQIVOC air quality index 1-5Read
AV28EXTERNAL-INPUT-1-PULSE-COUNTERExternal input measurementRead
AV36INSTALLATION-QUALITY-SCOREInstallation quality score 1-4Read
AV73COMBINED-VOC-CO2Combined VOC/CO2 valueppmRead
AV88AMBIENT-LIGHT-SENSOR-VALUEAmbient light levellxRead
AV89EXTERNAL-INPUT-2-PULSE-COUNTERExternal input measurementRead
AV115FORCE-VENTILATION-TIMER-VALUEminRead
AV206CONFIGURABLE-BUTTON-1-TIMERConfigurable button timersRead
AV207CONFIGURABLE-BUTTON-2-TIMERConfigurable button timersRead
AV208CONFIGURABLE-BUTTON-3-TIMERConfigurable button timersRead
AV209CONFIGURABLE-BUTTON-4-TIMERConfigurable button timersRead
AV210CONFIGURABLE-BUTTON-5-TIMERConfigurable button timersRead
AV211CONFIGURABLE-BUTTON-6-TIMERConfigurable button timersRead
AV1000BUS-TEMPORARY-OVERDRIVE-TIMERTemporary override time written by BMSminWrite
AV1001BUS-TEMPORARY-OVERDRIVE-SELECTIONTemporary override selection written by BMSWrite
AV1002BUS-EXTERNAL-INPUT-1-POWERExternal input value written by BMS%Write
AV1003BUS-CONTROLLER-INPUT-TController input written by BMS°C/°FWrite
AV1004BUS-CONTROLLER-INPUT-RHController input written by BMS%RHWrite
AV1005BUS-CONTROLLER-INPUT-CO2Controller input written by BMSppmWrite
AV1006BUS-CONTROLLER-INPUT-CO2-VOCController input written by BMSµg/m³Write
AV1007BUS-CONTROLLER-SETPOINT-TController setpoint written by BMS°C/°FWrite
AV1008BUS-CONTROLLER-SETPOINT-RHController setpoint written by BMS%RHWrite
AV1009BUS-CONTROLLER-SETPOINT-CO2Controller setpoint written by BMSppmWrite
AV1010BUS-CONTROLLER-SETPOINT-VOCController setpoint written by BMSµg/m³Write
AV1012BUS-OUTPUT1-POWEROutput 1 value written by BMS%Write
AV1013BUS-OUTPUT2-POWEROutput 2 value written by BMS%Write
AV1014BUS-OUTPUT3-POWEROutput 3 value written by BMS%Write
AV1015BUS-OUTPUT4-POWEROutput 4 value written by BMS%Write
AV1035BUS-EXTERNAL-INPUT-2-POWERExternal input value written by BMS%Write
AV19100OUTDOOR-TEMPERATURE-BUS-VALUEOutdoor temperature written by BMS°C/°FWrite
AVmin19200SETPOINT-TEMPERATURESetpoint°C/°FWrite
AV19201SETPOINT-RHSetpoint%RHWrite
AVmin19202SETPOINT-CO2SetpointppmWrite
AV19203SETPOINT-VOCSetpointµg/m³Write
AV19800CONFIGURABLE-BUTTON-1-STATEConfigurable button stateRead
AV19801CONFIGURABLE-BUTTON-2-STATEConfigurable button stateRead
AV19802CONFIGURABLE-BUTTON-3-STATEConfigurable button stateRead
AV19803CONFIGURABLE-BUTTON-4-STATEConfigurable button stateRead
AV19804CONFIGURABLE-BUTTON-5-STATEConfigurable button stateRead
AV19805CONFIGURABLE-BUTTON-6-STATEConfigurable button stateRead
MVmin72VOC-DETAILED-STATUSVOC sensor statusRead1=Operating normally, 2=Warm-up sequence, 3=Initial start-up, 4=No valid output
MV1017BUS-LED-COLORLED colour written by BMSWrite1=Off, 2=Red, 3=Green, 4=Blue, 5=Yellow, 6=Cyan, 7=Purple, 8=White
Object ID lookup: Produal RTX-D room transmitter with display point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RTX-D room transmitter with display (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Produal RTX-D room transmitter with display (BACnet MS/TP)

How many BACnet points does the Produal RTX-D room transmitter with display (BACnet MS/TP) have?

This list has 65 BACnet objects: 12 analog inputs, 51 analog values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet points are writable?

22 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet documentation?

Produal does not publish it on its own website. This list comes from BACnet protocol implementation conformance statement, RTX-D (published 02.02.2026) (EN - 53011WD0B0PICS), revision 02.02.2026, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/produal%20oy/PICS%20rtx-d_260202_pics_en.pdf. Ask Produal or its representative for the current revision.

What are the minimum BACnet points to integrate the Produal RTX-D room transmitter with display (BACnet MS/TP)?

Start with AV 19200 SETPOINT-TEMPERATURE (Temperature setpoint); AV 19202 SETPOINT-CO2 (CO2 setpoint, ppm); AI 0 TEMPERATURE (Room temperature); AI 1 HUMIDITY (Room relative humidity); AI 2 CO2 (Room CO2, ppm); AI 3 TVOC (Total VOC, µg/m³); MV 72 VOC-DETAILED-STATUS (VOC sensor status (1 = normal)).

Can the BMS supply sensor values to the Produal RTX-D room transmitter with display (BACnet MS/TP)?

BUS-CONTROLLER-INPUT-T/-RH/-CO2/-CO2-VOC (AV 1003-1006) and OUTDOOR-TEMPERATURE-BUS-VALUE (AV 19100) take values from the BMS.

How do I check these points on the real RTX-D room transmitter with display (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Produal BACnet points lists

Source: BACnet protocol implementation conformance statement, RTX-D (published 02.02.2026) · EN - 53011WD0B0PICS · rev. 02.02.2026. Object names, instances and units are reproduced as published; descriptions are our own.