- Home
- BACnet points lists
- Produal
- RTX-D room transmitter with display (BACnet MS/TP)
Room sensor / transmitter (display) · BACnet points list
Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
RTX-D is a room transmitter/controller with display that measures temperature, humidity, CO2, VOC and light, and has external inputs, four outputs and configurable buttons. It is a BACnet MS/TP B-ASC device. The PICS gives 65 objects: measurements, calculated values (dew point, enthalpy and so on), BMS-written controller inputs, setpoints and output values, button states and timers.
This page lists 65 BACnet objects for the Produal RTX-D room transmitter with display (BACnet MS/TP) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Produal’s documentation hosted by BACnet International, not by Produal itself, so treat it as unofficial.
- Manufacturer
- Produal
- Model
- RTX-D room transmitter with display (BACnet MS/TP)
- Equipment
- Room sensor / transmitter (display)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 65 (22 writable)
- Transport
- BACnet MS/TP
- Firmware
- 2.1.9.7
- Also known as
- RTX-D, Produal RTX-D, RTX-D room transmitter, 53011WD0B0
- Source document
- BACnet protocol implementation conformance statement, RTX-D (published 02.02.2026) · EN - 53011WD0B0PICS · rev. 02.02.2026 (unofficial copy, hosted by BACnet International)
Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.
BMS integration notes: Produal RTX-D room transmitter with display (BACnet MS/TP)
Give the transmitter a unique MS/TP address, then read temperature, humidity, CO2 and VOC. When the RTX-D acts as a controller, write the setpoints (AV 19200-19203) or feed BUS-CONTROLLER inputs; outputs set to bus control follow the BUS-OUTPUTn-POWER values.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 19200 | SETPOINT-TEMPERATURE | Temperature setpoint | Write |
| AV 19202 | SETPOINT-CO2 | CO2 setpoint, ppm | Write |
| AI 0 | TEMPERATURE | Room temperature | Read |
| AI 1 | HUMIDITY | Room relative humidity | Read |
| AI 2 | CO2 | Room CO2, ppm | Read |
| AI 3 | TVOC | Total VOC, µg/m³ | Read |
| MV 72 | VOC-DETAILED-STATUS | VOC sensor status (1 = normal) | Read |
Sensors & values from the BMS
BUS-CONTROLLER-INPUT-T/-RH/-CO2/-CO2-VOC (AV 1003-1006) and OUTDOOR-TEMPERATURE-BUS-VALUE (AV 19100) take values from the BMS.
Network setup
- BACnet MS/TP only; baud 9600-115200 bit/s.
Watch out for
- Many objects only matter for the variant and configuration in use (outputs, external inputs, buttons).
Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | TEMPERATURE | Room temperature | °C/°F | Read | |
| AImin | 1 | HUMIDITY | Room relative humidity | %RH | Read | |
| AImin | 2 | CO2 | Room CO2 | ppm | Read | |
| AImin | 3 | TVOC | Total VOC | µg/m³ | Read | |
| AI | 5 | EXTERNAL-INPUT-1-VOLTAGE | External input measurement | V | Read | |
| AI | 6 | EXTERNAL-INPUT-1-RESISTANCE | External input measurement | Ω | Read | |
| AI | 8 | EXTERNAL-INPUT-1-TEMPERATURE | External input measurement | °C/°F | Read | |
| AI | 9 | EXTERNAL-INPUT-1-HUMIDITY | External input measurement | %RH | Read | |
| AI | 10 | EXTERNAL-INPUT-1-CO2 | External input measurement | ppm | Read | |
| AI | 11 | EXTERNAL-INPUT-1-VOC | External input measurement | µg/m³ | Read | |
| AI | 85 | EXTERNAL-INPUT-2-RESISTANCE | External input measurement | Ω | Read | |
| AI | 86 | EXTERNAL-INPUT-2-TEMPERATURE | External input measurement | °C/°F | Read | |
| AV | 13 | OUTPUT1-VOLTAGE | Analog output 1 voltage | V | Read | |
| AV | 14 | OUTPUT2-VOLTAGE | Analog output 2 voltage | V | Read | |
| AV | 15 | OUTPUT3-VOLTAGE | Analog output 3 voltage | V | Read | |
| AV | 16 | OUTPUT4-VOLTAGE | Analog output 4 voltage | V | Read | |
| AV | 17 | AVERAGE TEMPERATURE | °C/°F | Read | ||
| AV | 18 | DEW-POINT | Calculated dew point | °C/°F | Read | |
| AV | 21 | ABSOLUTE-HUMIDITY | Calculated absolute humidity | g/m³ | Read | |
| AV | 22 | MIXING-RATIO | Calculated mixing ratio | g/kg | Read | |
| AV | 23 | ENTHALPY | Calculated enthalpy | kJ/kg | Read | |
| AV | 24 | VOC-TVOC-PPB | ppb | Read | ||
| AV | 25 | VOC-CO2-EQV-PPM | ppm | Read | ||
| AV | 26 | VOC-AQI | VOC air quality index 1-5 | Read | ||
| AV | 28 | EXTERNAL-INPUT-1-PULSE-COUNTER | External input measurement | Read | ||
| AV | 36 | INSTALLATION-QUALITY-SCORE | Installation quality score 1-4 | Read | ||
| AV | 73 | COMBINED-VOC-CO2 | Combined VOC/CO2 value | ppm | Read | |
| AV | 88 | AMBIENT-LIGHT-SENSOR-VALUE | Ambient light level | lx | Read | |
| AV | 89 | EXTERNAL-INPUT-2-PULSE-COUNTER | External input measurement | Read | ||
| AV | 115 | FORCE-VENTILATION-TIMER-VALUE | min | Read | ||
| AV | 206 | CONFIGURABLE-BUTTON-1-TIMER | Configurable button timer | s | Read | |
| AV | 207 | CONFIGURABLE-BUTTON-2-TIMER | Configurable button timer | s | Read | |
| AV | 208 | CONFIGURABLE-BUTTON-3-TIMER | Configurable button timer | s | Read | |
| AV | 209 | CONFIGURABLE-BUTTON-4-TIMER | Configurable button timer | s | Read | |
| AV | 210 | CONFIGURABLE-BUTTON-5-TIMER | Configurable button timer | s | Read | |
| AV | 211 | CONFIGURABLE-BUTTON-6-TIMER | Configurable button timer | s | Read | |
| AV | 1000 | BUS-TEMPORARY-OVERDRIVE-TIMER | Temporary override time written by BMS | min | Write | |
| AV | 1001 | BUS-TEMPORARY-OVERDRIVE-SELECTION | Temporary override selection written by BMS | Write | ||
| AV | 1002 | BUS-EXTERNAL-INPUT-1-POWER | External input value written by BMS | % | Write | |
| AV | 1003 | BUS-CONTROLLER-INPUT-T | Controller input written by BMS | °C/°F | Write | |
| AV | 1004 | BUS-CONTROLLER-INPUT-RH | Controller input written by BMS | %RH | Write | |
| AV | 1005 | BUS-CONTROLLER-INPUT-CO2 | Controller input written by BMS | ppm | Write | |
| AV | 1006 | BUS-CONTROLLER-INPUT-CO2-VOC | Controller input written by BMS | µg/m³ | Write | |
| AV | 1007 | BUS-CONTROLLER-SETPOINT-T | Controller setpoint written by BMS | °C/°F | Write | |
| AV | 1008 | BUS-CONTROLLER-SETPOINT-RH | Controller setpoint written by BMS | %RH | Write | |
| AV | 1009 | BUS-CONTROLLER-SETPOINT-CO2 | Controller setpoint written by BMS | ppm | Write | |
| AV | 1010 | BUS-CONTROLLER-SETPOINT-VOC | Controller setpoint written by BMS | µg/m³ | Write | |
| AV | 1012 | BUS-OUTPUT1-POWER | Output 1 value written by BMS | % | Write | |
| AV | 1013 | BUS-OUTPUT2-POWER | Output 2 value written by BMS | % | Write | |
| AV | 1014 | BUS-OUTPUT3-POWER | Output 3 value written by BMS | % | Write | |
| AV | 1015 | BUS-OUTPUT4-POWER | Output 4 value written by BMS | % | Write | |
| AV | 1035 | BUS-EXTERNAL-INPUT-2-POWER | External input value written by BMS | % | Write | |
| AV | 19100 | OUTDOOR-TEMPERATURE-BUS-VALUE | Outdoor temperature written by BMS | °C/°F | Write | |
| AVmin | 19200 | SETPOINT-TEMPERATURE | Setpoint | °C/°F | Write | |
| AV | 19201 | SETPOINT-RH | Setpoint | %RH | Write | |
| AVmin | 19202 | SETPOINT-CO2 | Setpoint | ppm | Write | |
| AV | 19203 | SETPOINT-VOC | Setpoint | µg/m³ | Write | |
| AV | 19800 | CONFIGURABLE-BUTTON-1-STATE | Configurable button state | Read | ||
| AV | 19801 | CONFIGURABLE-BUTTON-2-STATE | Configurable button state | Read | ||
| AV | 19802 | CONFIGURABLE-BUTTON-3-STATE | Configurable button state | Read | ||
| AV | 19803 | CONFIGURABLE-BUTTON-4-STATE | Configurable button state | Read | ||
| AV | 19804 | CONFIGURABLE-BUTTON-5-STATE | Configurable button state | Read | ||
| AV | 19805 | CONFIGURABLE-BUTTON-6-STATE | Configurable button state | Read | ||
| MVmin | 72 | VOC-DETAILED-STATUS | VOC sensor status | Read | 1=Operating normally, 2=Warm-up sequence, 3=Initial start-up, 4=No valid output | |
| MV | 1017 | BUS-LED-COLOR | LED colour written by BMS | Write | 1=Off, 2=Red, 3=Green, 4=Blue, 5=Yellow, 6=Cyan, 7=Purple, 8=White |
No points match these filters.
Object ID lookup: Produal RTX-D room transmitter with display point IDs by name
AI0TEMPERATUREAI1HUMIDITYAI2CO2AI3TVOCAI5EXTERNAL-INPUT-1-VOLTAGEAI6EXTERNAL-INPUT-1-RESISTANCEAI8EXTERNAL-INPUT-1-TEMPERATUREAI9EXTERNAL-INPUT-1-HUMIDITYAI10EXTERNAL-INPUT-1-CO2AI11EXTERNAL-INPUT-1-VOCAI85EXTERNAL-INPUT-2-RESISTANCEAI86EXTERNAL-INPUT-2-TEMPERATUREAV13OUTPUT1-VOLTAGEAV14OUTPUT2-VOLTAGEAV15OUTPUT3-VOLTAGEAV16OUTPUT4-VOLTAGEAV17AVERAGE TEMPERATUREAV18DEW-POINTAV21ABSOLUTE-HUMIDITYAV22MIXING-RATIOAV23ENTHALPYAV24VOC-TVOC-PPBAV25VOC-CO2-EQV-PPMAV26VOC-AQIAV28EXTERNAL-INPUT-1-PULSE-COUNTERAV36INSTALLATION-QUALITY-SCOREAV73COMBINED-VOC-CO2AV88AMBIENT-LIGHT-SENSOR-VALUEAV89EXTERNAL-INPUT-2-PULSE-COUNTERAV115FORCE-VENTILATION-TIMER-VALUEAV206CONFIGURABLE-BUTTON-1-TIMERAV207CONFIGURABLE-BUTTON-2-TIMERAV208CONFIGURABLE-BUTTON-3-TIMERAV209CONFIGURABLE-BUTTON-4-TIMERAV210CONFIGURABLE-BUTTON-5-TIMERAV211CONFIGURABLE-BUTTON-6-TIMERAV1000BUS-TEMPORARY-OVERDRIVE-TIMERAV1001BUS-TEMPORARY-OVERDRIVE-SELECTIONAV1002BUS-EXTERNAL-INPUT-1-POWERAV1003BUS-CONTROLLER-INPUT-TAV1004BUS-CONTROLLER-INPUT-RHAV1005BUS-CONTROLLER-INPUT-CO2AV1006BUS-CONTROLLER-INPUT-CO2-VOCAV1007BUS-CONTROLLER-SETPOINT-TAV1008BUS-CONTROLLER-SETPOINT-RHAV1009BUS-CONTROLLER-SETPOINT-CO2AV1010BUS-CONTROLLER-SETPOINT-VOCAV1012BUS-OUTPUT1-POWERAV1013BUS-OUTPUT2-POWERAV1014BUS-OUTPUT3-POWERAV1015BUS-OUTPUT4-POWERAV1035BUS-EXTERNAL-INPUT-2-POWERAV19100OUTDOOR-TEMPERATURE-BUS-VALUEAV19200SETPOINT-TEMPERATUREAV19201SETPOINT-RHAV19202SETPOINT-CO2AV19203SETPOINT-VOCAV19800CONFIGURABLE-BUTTON-1-STATEAV19801CONFIGURABLE-BUTTON-2-STATEAV19802CONFIGURABLE-BUTTON-3-STATEAV19803CONFIGURABLE-BUTTON-4-STATEAV19804CONFIGURABLE-BUTTON-5-STATEAV19805CONFIGURABLE-BUTTON-6-STATEMV72VOC-DETAILED-STATUSMV1017BUS-LED-COLOR
Integration notes
- Taken from the PICS value-range tables (ID, object name, values, resolution, units, default). The PICS has no read/write column; objects named BUS-... and SETPOINT-... are taken as BMS-writable, the rest as read-only.
- Temperature objects report in °C or °F depending on the unit setting.
- Binary input and binary value objects are supported by type but none are listed in the PICS.
- MS/TP baud rates 9600 to 115200 bit/s.
- Shares many names and IDs with the older RT/RTX map (for example OUTPUT1-VOLTAGE = AV 13) but adds external input 2, light, button and outdoor/setpoint objects.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RTX-D room transmitter with display (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Produal RTX-D room transmitter with display (BACnet MS/TP)
How many BACnet points does the Produal RTX-D room transmitter with display (BACnet MS/TP) have?
This list has 65 BACnet objects: 12 analog inputs, 51 analog values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet points are writable?
22 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Produal RTX-D room transmitter with display (BACnet MS/TP) BACnet documentation?
Produal does not publish it on its own website. This list comes from BACnet protocol implementation conformance statement, RTX-D (published 02.02.2026) (EN - 53011WD0B0PICS), revision 02.02.2026, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/produal%20oy/PICS%20rtx-d_260202_pics_en.pdf. Ask Produal or its representative for the current revision.
What are the minimum BACnet points to integrate the Produal RTX-D room transmitter with display (BACnet MS/TP)?
Start with AV 19200 SETPOINT-TEMPERATURE (Temperature setpoint); AV 19202 SETPOINT-CO2 (CO2 setpoint, ppm); AI 0 TEMPERATURE (Room temperature); AI 1 HUMIDITY (Room relative humidity); AI 2 CO2 (Room CO2, ppm); AI 3 TVOC (Total VOC, µg/m³); MV 72 VOC-DETAILED-STATUS (VOC sensor status (1 = normal)).
Can the BMS supply sensor values to the Produal RTX-D room transmitter with display (BACnet MS/TP)?
BUS-CONTROLLER-INPUT-T/-RH/-CO2/-CO2-VOC (AV 1003-1006) and OUTDOOR-TEMPERATURE-BUS-VALUE (AV 19100) take values from the BMS.
How do I check these points on the real RTX-D room transmitter with display (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Produal BACnet points lists
- Room sensor / transmitter
Produal RT / RTX room transmitter (BACnet MS/TP)
Produal RT and RTX room transmitters with BACnet MS/TP, application software 1.1.0.51.
Also known as: RT, RTX, Produal RT, Produal RTX, RT room transmitter, RTX room transmitter - Room sensor / transmitter
Produal RXX-BAC room sensors (RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC) with BACnet MS/TP
Produal RXX-BAC wall sensors: RCD-BAC (CO2 and temperature, optional humidity), RRH-BAC (temperature and humidity), RTE-BAC (temperature) and RLL-BAC (light level and occupancy), with 0-10 V outputs, digital inputs and optional push buttons.
Also known as: RCD-BAC, RRH-BAC, RTE-BAC, RLL-BAC, RCD, RRH, RTE, RLL, Produal RCD-BAC, Produal RRH-BAC, Produal RTE-BAC, Produal RLL-BAC, PS 6041-RCD-BAC, PS 6041-RRH-BAC, PS 6041-RTE-BAC, PS 6041-RLL-BAC, Produal RXX-BAC - Room controller (apartment ventilation, touchscreen)
Produal TRC-A-3A touchscreen apartment controller (BAC model)
Produal TRC-A-3A touchscreen apartment controller with temperature, humidity and CO2 measurement and three 0-10 V outputs (ventilation, heating/cooling, lighting), BAC model.
Also known as: TRC-A-3A, TRC-A-3A-BAC, TRC-A, Produal TRC-A, 6001CBM2000 - Room controller / thermostat (touchscreen)
Produal TRC-P touchscreen room controller (BAC models)
Produal TRC-P touchscreen room controllers (fan coil, chilled beam, radiator and auxiliary heat applications), BAC models.
Also known as: TRC-P, TRC-P-3A-BAC, TRC-P-1A2T-BAC, TRC-P-H-3R2T-BAC, TRC-P-H-2A3R-BAC, TRC-P-H-1A2R-BAC, Produal TRC-P, 6001NM2000 - Thermostat (touchscreen, relay output)
Produal TRT-1R slimline touchscreen thermostat (BAC models)
Produal TRT-1R series touchscreen thermostats with one switched relay output (no time program), BAC models.
Also known as: TRT-1R, TRT-1R-BAC, TRT-1R-RH-BAC, Produal TRT-1R, 6001TRT-1R - Room controller / thermostat (hotel, two zones)
Produal TRT-H-2R2T hotel touchscreen thermostatic controller (BAC models)
Produal TRT-H-2R2T touchscreen controllers for hotel rooms: two temperature zones (room and bathroom), two relays and two triacs, BAC models.
Also known as: TRT-H-2R2T, TRT-H-2R2T-BAC, TRT-H-2R2T-RH-BAC, Produal TRT-H, 6001TRT-H-2R2T - Thermostat (programmable touchscreen, relay output)
Produal TRT-P-1R programmable touchscreen thermostat (BAC models)
Produal TRT-P-1R series 7-day programmable touchscreen thermostats with one switched relay output, BAC models.
Also known as: TRT-P-1R, TRT-P-1R-BAC, TRT-P-1R-RH-BAC, Produal TRT-P, 6001TRT-P-1R
Source: BACnet protocol implementation conformance statement, RTX-D (published 02.02.2026) · EN - 53011WD0B0PICS · rev. 02.02.2026. Object names, instances and units are reproduced as published; descriptions are our own.