Short answer

The TRT-1R is a flush-mounted touchscreen thermostat with a built-in sensor, two remote NTC10 inputs, an optional humidity sensor and one relay. BAC models talk BACnet MS/TP. Unlike the programmable TRT-P-1R it uses a single nominal setpoint (AV 12) instead of four target setpoints; 31 usable objects are listed.

This page lists 31 BACnet objects for the Produal TRT-1R slimline touchscreen thermostat (BAC models) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Produal’s own free documentation, linked below.

Manufacturer
Produal
Model
TRT-1R slimline touchscreen thermostat (BAC models)
Equipment
Thermostat (touchscreen, relay output)
Equipment type
Thermostats, sensors & meters
BACnet objects
31 (17 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
TRT-1R, TRT-1R-BAC, TRT-1R-RH-BAC, Produal TRT-1R, 6001TRT-1R
Source document
TRT-1R Slimline Touchscreen Thermostats, product sheet (BACnet object instance assignments) · PS 6001TRT-1R V5.02 · rev. 11/2022
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Produal’s current documentation and the live device before use. Not official Produal information. Terms of use.

BMS integration notes: Produal TRT-1R slimline touchscreen thermostat (BAC models)

Integration in brief

Set the BACnet MAC address and baud rate on the thermostat, then write the nominal setpoint (AV 12) and switch off/eco mode with BO 1 / BO 2. Read the room temperature, the setpoint in use and the relay state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1OFF ModeOff mode (1 = off)Write
BO 2ECO ModeEco mode (1 = eco)Write
AV 12Nominal SetpointComfort setpointWrite
AI 0Room TemperatureRoom temperatureRead
AI 3Current Active SetpointSetpoint in useRead
MI 0Device ModeMode: 1 comfort, 2 eco, 3 offRead
BO 0Relay OutputRelay output stateWrite
MI 1AlarmAlarm word + 1 (1 = no alarm)Read

Sensors & values from the BMS

AV 11 Network Temp takes a temperature value from the network.

Network setup

Watch out for

Produal TRT-1R slimline touchscreen thermostat (BAC models) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

31 of 31 shown
Type
Multi-state
Access
Show
Produal TRT-1R slimline touchscreen thermostat (BAC models) BACnet Points List
DescriptionStates
AImin0Room TemperatureBuilt-in room temperature°CRead
AI1Outside TemperatureOutside temperature (remote sensor)°CRead
AI2Floor TemperatureFloor temperature (remote sensor)°CRead
AImin3Current Active SetpointSetpoint in use°CRead
AI4Humidity MeasurementRelative humidity (RH models)%RHRead
AI5RI1 External Sensor 1Resistive input 1°CRead
AI6RI2 External Sensor 2Resistive input 2°CRead
AV4ECO Heating Setpoint°CWrite
AV5ECO Cooling Setpoint°CWrite
AV6Frost Setpoint°CWrite
AV7Min Floor LimitFloor temperature low limit°CWrite
AV8Max Floor LimitFloor temperature high limit°CWrite
AV9LCD BrightnessDisplay brightnessWrite
AV10Control HysteresisRelay control hysteresis°CWrite
AV11Network TempTemperature value written over the network°CWrite
AVmin12Nominal SetpointNominal (comfort) setpoint°CWrite
BI0Digital Input (DI1)Read0=Off, 1=On
BI1Cleaning Mode StatusRead0=Off, 1=On
BI2Boost Mode StatusRead0=Off, 1=On
BI3DI2 (RI1 Input)RI1 used as digital inputRead0=Off, 1=On
BI4DI3 (RI2 Input)RI2 used as digital inputRead0=Off, 1=On
BOmin0Relay OutputRelay outputWrite0=Off, 1=On
BOmin1OFF ModeOff modeWrite0=Off, 1=On
BOmin2ECO ModeEco modeWrite0=Off, 1=On
BO3Light Switch StatusWrite0=Off, 1=On
BO4AC Switch StatusWrite0=Off, 1=On
BO5Lock ScreenWrite0=Off, 1=On
BO6Heating/Cooling Change-OverWrite0=Off, 1=On
BO7Non Volatile UpdateStore setpoints/configurationWrite0=Off, 1=On
MImin0Device ModeOperating modeRead1=Comfort, 2=ECO, 3=OFF
MImin1AlarmAlarm bits + 1Read
Object ID lookup: Produal TRT-1R slimline touchscreen thermostat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TRT-1R slimline touchscreen thermostat (BAC models) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Produal TRT-1R slimline touchscreen thermostat (BAC models)

How many BACnet points does the Produal TRT-1R slimline touchscreen thermostat (BAC models) have?

This list has 31 BACnet objects: 7 analog inputs, 9 analog values, 5 binary inputs, 8 binary outputs, 2 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Produal TRT-1R slimline touchscreen thermostat (BAC models) BACnet points are writable?

17 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Produal TRT-1R slimline touchscreen thermostat (BAC models) BACnet documentation?

The source is TRT-1R Slimline Touchscreen Thermostats, product sheet (BACnet object instance assignments) (PS 6001TRT-1R V5.02), revision 11/2022, published free by Produal at https://produal-pim.rockon.io/rockon/api/v1/int/extmedia/openFile/01TGWJBKATT4IA2BJP6NGKJWG7XFZR55GG.

What are the minimum BACnet points to integrate the Produal TRT-1R slimline touchscreen thermostat (BAC models)?

Start with BO 1 OFF Mode (Off mode (1 = off)); BO 2 ECO Mode (Eco mode (1 = eco)); AV 12 Nominal Setpoint (Comfort setpoint); AI 0 Room Temperature (Room temperature); AI 3 Current Active Setpoint (Setpoint in use); MI 0 Device Mode (Mode: 1 comfort, 2 eco, 3 off); BO 0 Relay Output (Relay output state); MI 1 Alarm (Alarm word + 1 (1 = no alarm)).

Can the BMS supply sensor values to the Produal TRT-1R slimline touchscreen thermostat (BAC models)?

AV 11 Network Temp takes a temperature value from the network.

How do I check these points on the real TRT-1R slimline touchscreen thermostat (BAC models)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Produal BACnet points lists

Source: TRT-1R Slimline Touchscreen Thermostats, product sheet (BACnet object instance assignments) · PS 6001TRT-1R V5.02 · rev. 11/2022. Object names, instances and units are reproduced as published; descriptions are our own.