Kitchen hood demand ventilation controller (exhaust and make-up air fans) · BACnet points list

Melink Intelli-Hood IH3 System Controller BACnet points list

Updated 12 November 2026

Short answer

The Intelli-Hood IH3 System Controller is the main BACnet IP device of the older Intelli-Hood 3 kitchen ventilation system and a virtual router for the fan and hood devices behind it. Its own object list is small and read-only: the state of three digital inputs, two dry-contact outputs, two 24 VDC outputs, and the analog input and output as a percentage. It differs from the IH4 System Controller (three inputs here instead of four, and only one analog input and output).

This page lists 9 BACnet objects for the Melink Intelli-Hood IH3 System Controller — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Melink’s own free documentation, linked below.

Manufacturer
Melink
Model
Intelli-Hood IH3 System Controller
Equipment
Kitchen hood demand ventilation controller (exhaust and make-up air fans)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
9 (0 writable)
Transport
BACnet IP
Firmware
Application 2.2, firmware 0.8.4
Default device instance
654000
Also known as
Intelli-Hood 3, IH3, IH3 SC, Melink IH3
Source document
Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS), Version 8.0 · IH-ENG-DTS-BAC-006 · rev. 2016-11-02
Download CSV 9 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Melink’s current documentation and the live device before use. Not official Melink information. Terms of use.

BMS integration notes: Melink Intelli-Hood IH3 System Controller

Integration in brief

Discover the System Controller (default Device ID 654000), then the fan and hood devices through its virtual router. This device only reports the state of its physical I/O; map the outputs set up as Fan On or alarms and the inputs wired for remote on/off or enable.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Digital Input 1 StatusPhysical input 1; function set in IH3 configRead
BV 1Digital Input 2 StatusPhysical input 2; function set in IH3 configRead
BV 2Digital Input 3 StatusPhysical input 3; function set in IH3 configRead
BV 3Digital Output 1 StatusRelay 1; e.g. Fan On or alarm per configRead
BV 4Digital Output 2 StatusRelay 2; function set in IH3 configRead
AV 0Analog Input StatusAnalog input value, 0-100 %Read
AV 1Analog Output StatusAnalog output to auxiliary airflows, 0-100 %Read

Enable & remote start

No BACnet enable or start/stop object on this device. Fans start from the Touchpad, schedules or digital inputs (physical, or the Virtual Input Module over BACnet).

Heartbeat & communication loss

The BACnet Watchdog (0-600 s, default 300 s, 0 = off) on the System Controller resets all Virtual Input Module inputs when no BACnet traffic addressed to the Intelli-Hood arrives in time.

Network setup

Watch out for

Melink Intelli-Hood IH3 System Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

9 of 9 shown
Type
AnalogBinary
Show
Melink Intelli-Hood IH3 System Controller BACnet Points List
DescriptionStates
BVmin0Digital Input 1 StatusPhysical digital input 1 on the System ControllerReadInactive = Open, Active = Closed
BVmin1Digital Input 2 StatusPhysical digital input 2ReadInactive = Open, Active = Closed
BVmin2Digital Input 3 StatusPhysical digital input 3ReadInactive = Open, Active = Closed
BVmin3Digital Output 1 StatusDry-contact output 1ReadInactive = De-Energized, Active = Energized
BVmin4Digital Output 2 StatusDry-contact output 2ReadInactive = De-Energized, Active = Energized
BV524VDC Out 1 Status24 VDC output 1ReadInactive = De-Energized, Active = Energized
BV624VDC Out 2 Status24 VDC output 2ReadInactive = De-Energized, Active = Energized
AVmin0Analog Input StatusPhysical analog input value%Read
AVmin1Analog Output StatusPhysical analog output value%Read
Object ID lookup: Melink Intelli-Hood IH3 System Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Intelli-Hood IH3 System Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Melink Intelli-Hood IH3 System Controller

How many BACnet points does the Melink Intelli-Hood IH3 System Controller have?

This list has 9 BACnet objects: 2 analog values, 7 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Melink Intelli-Hood IH3 System Controller BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Melink Intelli-Hood IH3 System Controller BACnet documentation?

The source is Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS), Version 8.0 (IH-ENG-DTS-BAC-006), revision 2016-11-02, published free by Melink at https://melinkcorp.com/wp-content/uploads/2018/09/IH3_BACnet_PICS.pdf.

What are the minimum BACnet points to integrate the Melink Intelli-Hood IH3 System Controller?

Start with BV 0 Digital Input 1 Status (Physical input 1; function set in IH3 config); BV 1 Digital Input 2 Status (Physical input 2; function set in IH3 config); BV 2 Digital Input 3 Status (Physical input 3; function set in IH3 config); BV 3 Digital Output 1 Status (Relay 1; e.g. Fan On or alarm per config); BV 4 Digital Output 2 Status (Relay 2; function set in IH3 config); AV 0 Analog Input Status (Analog input value, 0-100 %); AV 1 Analog Output Status (Analog output to auxiliary airflows, 0-100 %).

How do I enable BMS control of the Melink Intelli-Hood IH3 System Controller?

No BACnet enable or start/stop object on this device. Fans start from the Touchpad, schedules or digital inputs (physical, or the Virtual Input Module over BACnet).

Does the Melink Intelli-Hood IH3 System Controller need a BACnet heartbeat or have a communication timeout?

The BACnet Watchdog (0-600 s, default 300 s, 0 = off) on the System Controller resets all Virtual Input Module inputs when no BACnet traffic addressed to the Intelli-Hood arrives in time.

How do I check these points on the real Intelli-Hood IH3 System Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Melink BACnet points lists

Source: Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS), Version 8.0 · IH-ENG-DTS-BAC-006 · rev. 2016-11-02. Object names, instances and units are reproduced as published; descriptions are our own.