Kitchen hood demand ventilation BMS inputs (exhaust and make-up air fans) · BACnet points list
Melink Intelli-Hood IH4 Virtual Input Module BACnet points list
Updated 28 October 2026
A Virtual Input Module is a virtual BACnet IP device behind the Intelli-Hood System Controller with four writable digital inputs and four writable analog inputs. They behave like the controller's physical inputs, so the BMS can start, stop, enable or set minimum fan speeds. What each input does is set in the Intelli-Hood configuration; every input defaults to unused.
This page lists 8 BACnet objects for the Melink Intelli-Hood IH4 Virtual Input Module — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Melink’s own free documentation, linked below.
- Manufacturer
- Melink
- Model
- Intelli-Hood IH4 Virtual Input Module
- Equipment
- Kitchen hood demand ventilation BMS inputs (exhaust and make-up air fans)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 8 (8 writable)
- Transport
- BACnet IP, BACnet IPv6
- Firmware
- Application 4.0, firmware 1.0.0
- Also known as
- Intelli-Hood, IH4, IH4-SC, Melink IH4, Intelli-Hood 4
BMS integration notes: Melink Intelli-Hood IH4 Virtual Input Module
Configure each virtual input's function and the fans it affects in the Intelli-Hood configuration first. Then write the BVs (e.g. Remote On/Off, Remote Enable/Disable) and AVs from the BMS. Keep BACnet traffic going to the Intelli-Hood, or the watchdog resets all virtual inputs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Digital Input 1 | Virtual input 1, e.g. Remote On/Off (per config) | Write |
| BV 1 | Digital Input 2 | Virtual input 2, e.g. Remote Enable/Disable | Write |
| BV 2 | Digital Input 3 | Virtual input 3 (function per IH4 config) | Write |
| BV 3 | Digital Input 4 | Virtual input 4 (function per IH4 config) | Write |
| AV 1 | Analog Input 1 | Speed input 1, 0-100 % (mode per IH4 config) | Write |
| AV 2 | Analog Input 2 | Speed input 2, 0-100 % (mode per IH4 config) | Write |
| AV 3 | Analog Input 3 | Speed input 3, 0-100 % (mode per IH4 config) | Write |
| AV 4 | Analog Input 4 | Speed input 4, 0-100 % (mode per IH4 config) | Write |
Enable & remote start
No separate enable. Each virtual input must be given a function and its affected fans in the Intelli-Hood configuration; unconfigured inputs (the default) do nothing. A Remote Enable/Disable input that is inactive keeps its hood groups' fans off (except on a high-temperature alarm).
Heartbeat & communication loss
BACnet Watchdog on the System Controller, 0-600 s, default 300 s (0 disables). If no BACnet traffic addressed to the Intelli-Hood arrives within that time, all digital and analog inputs on all Virtual Input Modules reset. Any request to the system, including reads, restarts the timer.
Network setup
- The System Controller is the main BACnet IP device (default Device ID 654000) and a virtual router (default DNET 654) for the fan, hood controller and virtual module devices; UDP port 47808.
- With BACnet Auto Number on (default), the virtual devices are numbered from 654001: exhaust fans and auxiliary airflows (sorted by name), then hood controllers, virtual output modules, virtual input modules.
- IP defaults to DHCP. BACnet runs on IPv4 or IPv6, not both; for IPv6 set IP Type to 'IPv4 & IPv6' and BACnet IP Type to IPv6 (multicast scope default ff05).
- Settings are on the Touchpad (System Controller configuration) or the web configurator at http://<controller IP>/ih4-configurator.
- Virtual Input Module Device IDs are shown on the Touchpad under Status > Virtual Input Modules.
Watch out for
- Front ends that send Who-Is without routing only find the System Controller; run a network/router discovery, select the router with the Intelli-Hood DNET, then discover devices again.
- The DNET must be unique; another router or BBMD using 654 breaks access to the virtual devices.
- An input set Out of Service is ignored: the system treats a digital input as inactive and an analog input as 0.
- If inputs keep resetting after a few minutes, the BACnet Watchdog expired; poll more often or lengthen it.
Melink Intelli-Hood IH4 Virtual Input Module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | Digital Input 1 | Virtual digital input 1; acts as its configured input type | Write | Inactive = Off, Active = On | |
| BVmin | 1 | Digital Input 2 | Virtual digital input 2; acts as its configured input type | Write | Inactive = Off, Active = On | |
| BVmin | 2 | Digital Input 3 | Virtual digital input 3; acts as its configured input type | Write | Inactive = Off, Active = On | |
| BVmin | 3 | Digital Input 4 | Virtual digital input 4; acts as its configured input type | Write | Inactive = Off, Active = On | |
| AVmin | 1 | Analog Input 1 | Virtual analog input 1, 0-100 %; acts per its configured mode | % | Write | |
| AVmin | 2 | Analog Input 2 | Virtual analog input 2, 0-100 %; acts per its configured mode | % | Write | |
| AVmin | 3 | Analog Input 3 | Virtual analog input 3, 0-100 %; acts per its configured mode | % | Write | |
| AVmin | 4 | Analog Input 4 | Virtual analog input 4, 0-100 %; acts per its configured mode | % | Write |
No points match these filters.
Integration notes
- The analog inputs are numbered AV 1-AV 4 in the PICS (there is no AV 0).
- Digital input functions include Remote On/Off, Remote On, Remote On 100%, Remote Enable/Disable, Remote On/Off with Enable, 50-100% Minimum Speed, External Fault, Lights On/Off and External Alert.
- Remote On/Off and Lights On/Off are edge-triggered; Enable/Disable and Minimum Speed inputs are level-based.
- Analog input modes are Highest, Add or Average with the calculated fan speed, or the Aux. versions that affect auxiliary airflows only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Intelli-Hood IH4 Virtual Input Module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Melink Intelli-Hood IH4 Virtual Input Module
How many BACnet points does the Melink Intelli-Hood IH4 Virtual Input Module have?
This list has 8 BACnet objects: 4 analog values, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Melink Intelli-Hood IH4 Virtual Input Module BACnet points are writable?
8 of the 8 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Melink Intelli-Hood IH4 Virtual Input Module BACnet documentation?
The source is Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS), revision Revision 250723 (PICS dated 07-18-2025), published free by Melink at https://melinkcorp.com/wp-content/uploads/2021/10/IH4_BACnet_PICS.pdf.
What are the minimum BACnet points to integrate the Melink Intelli-Hood IH4 Virtual Input Module?
Start with BV 0 Digital Input 1 (Virtual input 1, e.g. Remote On/Off (per config)); BV 1 Digital Input 2 (Virtual input 2, e.g. Remote Enable/Disable); BV 2 Digital Input 3 (Virtual input 3 (function per IH4 config)); BV 3 Digital Input 4 (Virtual input 4 (function per IH4 config)); AV 1 Analog Input 1 (Speed input 1, 0-100 % (mode per IH4 config)); AV 2 Analog Input 2 (Speed input 2, 0-100 % (mode per IH4 config)); AV 3 Analog Input 3 (Speed input 3, 0-100 % (mode per IH4 config)); AV 4 Analog Input 4 (Speed input 4, 0-100 % (mode per IH4 config)).
How do I enable BMS control of the Melink Intelli-Hood IH4 Virtual Input Module?
No separate enable. Each virtual input must be given a function and its affected fans in the Intelli-Hood configuration; unconfigured inputs (the default) do nothing. A Remote Enable/Disable input that is inactive keeps its hood groups' fans off (except on a high-temperature alarm).
Does the Melink Intelli-Hood IH4 Virtual Input Module need a BACnet heartbeat or have a communication timeout?
BACnet Watchdog on the System Controller, 0-600 s, default 300 s (0 disables). If no BACnet traffic addressed to the Intelli-Hood arrives within that time, all digital and analog inputs on all Virtual Input Modules reset. Any request to the system, including reads, restarts the timer.
How do I check these points on the real Intelli-Hood IH4 Virtual Input Module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Melink BACnet points lists
- Kitchen exhaust / make-up air fan VFD device (Intelli-Hood demand ventilation)
Melink Intelli-Hood IH4 Exhaust Fan / Auxiliary Airflow
Each exhaust fan and auxiliary airflow (make-up air fan) VFD run by a Melink Intelli-Hood 4 system.
Also known as: Intelli-Hood, IH4, IH4-SC, Melink IH4, Intelli-Hood 4 - Kitchen hood sensor controller (demand ventilation for exhaust and make-up air fans)
Melink Intelli-Hood IH4 Hood Controller
Each Hood Controller (temperature probes and optic smoke sensor) in a Melink Intelli-Hood 4 system.
Also known as: Intelli-Hood, IH4, IH4-SC, Melink IH4, Intelli-Hood 4 - Kitchen hood demand ventilation controller (exhaust and make-up air fans)
Melink Intelli-Hood IH4 System Controller
The main BACnet device of a Melink Intelli-Hood 4 (IH4-SC) kitchen demand-control ventilation system.
Also known as: Intelli-Hood, IH4, IH4-SC, Melink IH4, Intelli-Hood 4 - Kitchen hood demand ventilation status outputs (exhaust and make-up air fans)
Melink Intelli-Hood IH4 Virtual Output Module
Virtual Output Modules of a Melink Intelli-Hood 4 system, which give a BMS extra status outputs over BACnet.
Also known as: Intelli-Hood, IH4, IH4-SC, Melink IH4, Intelli-Hood 4
Source: Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS) · rev. Revision 250723 (PICS dated 07-18-2025). Object names, instances and units are reproduced as published; descriptions are our own.