Kitchen hood demand ventilation BMS inputs (exhaust and make-up air fans) · BACnet points list

Melink Intelli-Hood IH4 Virtual Input Module BACnet points list

Updated 28 October 2026

Short answer

A Virtual Input Module is a virtual BACnet IP device behind the Intelli-Hood System Controller with four writable digital inputs and four writable analog inputs. They behave like the controller's physical inputs, so the BMS can start, stop, enable or set minimum fan speeds. What each input does is set in the Intelli-Hood configuration; every input defaults to unused.

This page lists 8 BACnet objects for the Melink Intelli-Hood IH4 Virtual Input Module — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Melink’s own free documentation, linked below.

Manufacturer
Melink
Model
Intelli-Hood IH4 Virtual Input Module
Equipment
Kitchen hood demand ventilation BMS inputs (exhaust and make-up air fans)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
8 (8 writable)
Transport
BACnet IP, BACnet IPv6
Firmware
Application 4.0, firmware 1.0.0
Also known as
Intelli-Hood, IH4, IH4-SC, Melink IH4, Intelli-Hood 4
Source document
Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS) · rev. Revision 250723 (PICS dated 07-18-2025)
Download CSV 8 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Melink Intelli-Hood IH4 Virtual Input Module

Integration in brief

Configure each virtual input's function and the fans it affects in the Intelli-Hood configuration first. Then write the BVs (e.g. Remote On/Off, Remote Enable/Disable) and AVs from the BMS. Keep BACnet traffic going to the Intelli-Hood, or the watchdog resets all virtual inputs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Digital Input 1Virtual input 1, e.g. Remote On/Off (per config)Write
BV 1Digital Input 2Virtual input 2, e.g. Remote Enable/DisableWrite
BV 2Digital Input 3Virtual input 3 (function per IH4 config)Write
BV 3Digital Input 4Virtual input 4 (function per IH4 config)Write
AV 1Analog Input 1Speed input 1, 0-100 % (mode per IH4 config)Write
AV 2Analog Input 2Speed input 2, 0-100 % (mode per IH4 config)Write
AV 3Analog Input 3Speed input 3, 0-100 % (mode per IH4 config)Write
AV 4Analog Input 4Speed input 4, 0-100 % (mode per IH4 config)Write

Enable & remote start

No separate enable. Each virtual input must be given a function and its affected fans in the Intelli-Hood configuration; unconfigured inputs (the default) do nothing. A Remote Enable/Disable input that is inactive keeps its hood groups' fans off (except on a high-temperature alarm).

Heartbeat & communication loss

BACnet Watchdog on the System Controller, 0-600 s, default 300 s (0 disables). If no BACnet traffic addressed to the Intelli-Hood arrives within that time, all digital and analog inputs on all Virtual Input Modules reset. Any request to the system, including reads, restarts the timer.

Network setup

Watch out for

Melink Intelli-Hood IH4 Virtual Input Module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

8 of 8 shown
Type
AnalogBinary
Show
Melink Intelli-Hood IH4 Virtual Input Module BACnet Points List
DescriptionStates
BVmin0Digital Input 1Virtual digital input 1; acts as its configured input typeWriteInactive = Off, Active = On
BVmin1Digital Input 2Virtual digital input 2; acts as its configured input typeWriteInactive = Off, Active = On
BVmin2Digital Input 3Virtual digital input 3; acts as its configured input typeWriteInactive = Off, Active = On
BVmin3Digital Input 4Virtual digital input 4; acts as its configured input typeWriteInactive = Off, Active = On
AVmin1Analog Input 1Virtual analog input 1, 0-100 %; acts per its configured mode%Write
AVmin2Analog Input 2Virtual analog input 2, 0-100 %; acts per its configured mode%Write
AVmin3Analog Input 3Virtual analog input 3, 0-100 %; acts per its configured mode%Write
AVmin4Analog Input 4Virtual analog input 4, 0-100 %; acts per its configured mode%Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Intelli-Hood IH4 Virtual Input Module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Melink Intelli-Hood IH4 Virtual Input Module

How many BACnet points does the Melink Intelli-Hood IH4 Virtual Input Module have?

This list has 8 BACnet objects: 4 analog values, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Melink Intelli-Hood IH4 Virtual Input Module BACnet points are writable?

8 of the 8 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Melink Intelli-Hood IH4 Virtual Input Module BACnet documentation?

The source is Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS), revision Revision 250723 (PICS dated 07-18-2025), published free by Melink at https://melinkcorp.com/wp-content/uploads/2021/10/IH4_BACnet_PICS.pdf.

What are the minimum BACnet points to integrate the Melink Intelli-Hood IH4 Virtual Input Module?

Start with BV 0 Digital Input 1 (Virtual input 1, e.g. Remote On/Off (per config)); BV 1 Digital Input 2 (Virtual input 2, e.g. Remote Enable/Disable); BV 2 Digital Input 3 (Virtual input 3 (function per IH4 config)); BV 3 Digital Input 4 (Virtual input 4 (function per IH4 config)); AV 1 Analog Input 1 (Speed input 1, 0-100 % (mode per IH4 config)); AV 2 Analog Input 2 (Speed input 2, 0-100 % (mode per IH4 config)); AV 3 Analog Input 3 (Speed input 3, 0-100 % (mode per IH4 config)); AV 4 Analog Input 4 (Speed input 4, 0-100 % (mode per IH4 config)).

How do I enable BMS control of the Melink Intelli-Hood IH4 Virtual Input Module?

No separate enable. Each virtual input must be given a function and its affected fans in the Intelli-Hood configuration; unconfigured inputs (the default) do nothing. A Remote Enable/Disable input that is inactive keeps its hood groups' fans off (except on a high-temperature alarm).

Does the Melink Intelli-Hood IH4 Virtual Input Module need a BACnet heartbeat or have a communication timeout?

BACnet Watchdog on the System Controller, 0-600 s, default 300 s (0 disables). If no BACnet traffic addressed to the Intelli-Hood arrives within that time, all digital and analog inputs on all Virtual Input Modules reset. Any request to the system, including reads, restarts the timer.

How do I check these points on the real Intelli-Hood IH4 Virtual Input Module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Melink BACnet points lists

Source: Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS) · rev. Revision 250723 (PICS dated 07-18-2025). Object names, instances and units are reproduced as published; descriptions are our own.