Kitchen hood demand ventilation status outputs (exhaust and make-up air fans) · BACnet points list

Melink Intelli-Hood IH4 Virtual Output Module BACnet points list

Updated 28 October 2026

Short answer

A Virtual Output Module is a virtual BACnet IP device behind the Intelli-Hood System Controller with four read-only digital outputs. They work like the controller's relay outputs: each is given a function in the configuration (Fan On, Temperature Alarm, Smoke, System Fault, VFD Fault...) and the BMS reads its state.

This page lists 4 BACnet objects for the Melink Intelli-Hood IH4 Virtual Output Module — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Melink’s own free documentation, linked below.

Manufacturer
Melink
Model
Intelli-Hood IH4 Virtual Output Module
Equipment
Kitchen hood demand ventilation status outputs (exhaust and make-up air fans)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
4 (0 writable)
Transport
BACnet IP, BACnet IPv6
Firmware
Application 4.0, firmware 1.0.0
Also known as
Intelli-Hood, IH4, IH4-SC, Melink IH4, Intelli-Hood 4
Source document
Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS) · rev. Revision 250723 (PICS dated 07-18-2025)
Download CSV 4 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Melink Intelli-Hood IH4 Virtual Output Module

Integration in brief

Assign each virtual output a function (for example Fan On and System Fault) and its hood groups in the Intelli-Hood configuration, then read the four BVs from the BMS.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Digital Output 1 StatusVirtual output 1, e.g. Fan On (per config)Read
BV 1Digital Output 2 StatusVirtual output 2, e.g. System Fault (per config)Read
BV 2Digital Output 3 StatusVirtual output 3 (function per IH4 config)Read
BV 3Digital Output 4 StatusVirtual output 4 (function per IH4 config)Read

Network setup

Watch out for

Melink Intelli-Hood IH4 Virtual Output Module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

4 of 4 shown
Type
Binary
Show
Melink Intelli-Hood IH4 Virtual Output Module BACnet Points List
DescriptionStates
BVmin0Digital Output 1 StatusVirtual digital output 1; follows its configured functionReadInactive = De-Energized, Active = Energized
BVmin1Digital Output 2 StatusVirtual digital output 2; follows its configured functionReadInactive = De-Energized, Active = Energized
BVmin2Digital Output 3 StatusVirtual digital output 3; follows its configured functionReadInactive = De-Energized, Active = Energized
BVmin3Digital Output 4 StatusVirtual digital output 4; follows its configured functionReadInactive = De-Energized, Active = Energized

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Intelli-Hood IH4 Virtual Output Module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Melink Intelli-Hood IH4 Virtual Output Module

How many BACnet points does the Melink Intelli-Hood IH4 Virtual Output Module have?

This list has 4 BACnet objects: 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Melink Intelli-Hood IH4 Virtual Output Module BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Melink Intelli-Hood IH4 Virtual Output Module BACnet documentation?

The source is Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS), revision Revision 250723 (PICS dated 07-18-2025), published free by Melink at https://melinkcorp.com/wp-content/uploads/2021/10/IH4_BACnet_PICS.pdf.

What are the minimum BACnet points to integrate the Melink Intelli-Hood IH4 Virtual Output Module?

Start with BV 0 Digital Output 1 Status (Virtual output 1, e.g. Fan On (per config)); BV 1 Digital Output 2 Status (Virtual output 2, e.g. System Fault (per config)); BV 2 Digital Output 3 Status (Virtual output 3 (function per IH4 config)); BV 3 Digital Output 4 Status (Virtual output 4 (function per IH4 config)).

How do I check these points on the real Intelli-Hood IH4 Virtual Output Module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Melink BACnet points lists

Source: Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS) · rev. Revision 250723 (PICS dated 07-18-2025). Object names, instances and units are reproduced as published; descriptions are our own.