- Home
- BACnet points lists
- LG
- MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)
Rooftop unit controller (room thermostat, rooftop, heat-pump and IAQ) · BACnet points list
LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ) BACnet points list
Updated 4 November 2026
The MS8650 is LG's MultiSITE touchscreen room controller for rooftop units, heat pumps and indoor air quality. It is a BACnet MS/TP application specific controller (B-ASC) with about 310 objects: room, outdoor and supply temperature, setpoints, system and fan mode, Y/W/G stage outputs, economizer and CO2 ventilation settings, alarms, Wi-Fi status and paired ZigBee wireless sensor objects.
This page lists 311 BACnet objects for the LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ) — 230 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from LG’s own free documentation, linked below.
- Manufacturer
- LG
- Model
- MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)
- Equipment
- Rooftop unit controller (room thermostat, rooftop, heat-pump and IAQ)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 311 (230 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- MS8650, VUCQMS8650, LG MS8650, MultiSITE MS8000
Reference only, provided as-is: verify against LG’s current documentation and the live device before use. Not official LG information. Terms of use.
BMS integration notes: LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)
Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy and MV 112 control status, plus the G fan output BO 25 and the fan lock alarm BV 39.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10 | Occupancy Command | BMS occupancy: local, occupied or unoccupied | Command |
| MV 16 | System Mode | Off / auto / cool / heat | Command |
| MV 17 | Fan Mode | Fan mode: on / auto / smart | Command |
| AV 39 | Occ. Heat | Occupied heating setpoint | Command |
| AV 40 | Occ. Cool | Occupied cooling setpoint | Command |
| MV 112 | Control Status | Current state: off, cooling or heating | Command |
| BO 25 | G Fan Status | Fan (G) output state | Command |
| MI 33 | Effective Occupancy | Actual occupancy state | Read |
| AV 100 | Room Temperature | Space temperature used for control | Command |
| BV 39 | Fan Lock Alarm | Fan lock alarm (1 = on) | Command |
Enable & remote start
The BMS writes MV 10 Occupancy Command (1 = Loc. occ; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 chooses whether local occupancy follows motion or the schedule.
Sensors & values from the BMS
The guide does not describe feeding room temperature from the BMS. MV 145 selects the wired, internal or a paired ZigBee wireless sensor, and MI 312 Effective Temperature Sensor shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.
Network setup
- BACnet MS/TP baud rate is MV 8 (9600, 19200, 38400, 57600, 76800, 115200 or Auto; default Auto). Max_Master is writable, 0-127, default 127.
- AV 10 COM Address holds the MS/TP address. Device Object_Identifier and Object_Name are writable; no default device instance is printed.
- MI 317 BACnet IP Status shows whether BACnet IP is enabled; separate Wi-Fi objects report the Wi-Fi module state.
- The controller is a B-ASC with COV, time synchronization and an internal schedule (SCHED-I-B); it does not support segmented requests or responses.
Watch out for
- For the MS8350 the guide says writes at some priority levels go to EEPROM (locked at the controller and kept through a power cycle until released at the same priority or by Restore Factory Default) and others to RAM (lost on a power cycle), but it does not print which priority numbers fall in each group.
- On the MS8350 the relinquish default is the value set at the thermostat and it survives power cycles; on the MS8650 the relinquish default of AV 100 and above is read-only.
- Keep Read Property Multiple requests small; segmentation is not supported.
LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Thermistor | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 2 | Light Sensor Level | Default 0; range 0 to 30000 | lx | Read | |
| AI | 3 | Thermistor Self Heat | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 4 | Relative Humidity Value | Default 0; range 20 to 80 | % | Read | |
| AI | 5 | UI20 Raw Value | Default 0; range 0 to 4095 | Read | ||
| AI | 7 | UI23 Raw Value | Default 0; range 0 to 4095 | Read | ||
| AI | 8 | UI22 Raw Value | Default 0; range 0 to 4095 | Read | ||
| AI | 9 | UI24 Raw Value | Default 0; range 0 to 4095 | Read | ||
| AI | 31 | UI19 Raw Value | Default 0; range 0 to 4095 | Read | ||
| AI | 210 | Wireless Device 1 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 220 | Wireless Device 2 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 230 | Wireless Device 3 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 240 | Wireless Device 4 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 250 | Wireless Device 5 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 260 | Wireless Device 6 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 270 | Wireless Device 7 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 280 | Wireless Device 8 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 290 | Wireless Device 9 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 300 | Wireless Device 10 - Address | ZigBee Pro; default 0; range -32768 to 32767 | Read | ||
| AI | 315 | Wireless Device 1 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 316 | Wireless Device 2 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 317 | Wireless Device 3 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 318 | Wireless Device 4 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 319 | Wireless Device 5 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 320 | Wireless Device 6 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 321 | Wireless Device 7 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 322 | Wireless Device 8 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 323 | Wireless Device 9 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 324 | Wireless Device 10 - Temperature | Default 0; range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 327 | Remote Relative Humidity | Default 0; range 0 to 100 | % | Read | |
| AI | 328 | Permit Timeout | Default 0; range 0 to 180 | min | Read | |
| AI | 329 | Effective Setpoint | Default 0; range 40°F (4.5°C) to 100°F (38°C) | °F/°C | Read | |
| AI | 330 | Paired ZigBee Devices | Number of paired devices; default 0; range 0 to 11 | Read | ||
| AI | 342 | Wi-Fi Network Signal Strength | Default 0; range 0 to 100 | % | Read | |
| AO | 21 | PI Heat Demand | Default 0; range 0 to 100 | % | Command | |
| AO | 22 | PI Cool Demand | Default 0; range 0 to 100 | % | Command | |
| AO | 23 | Economizer Demand | Default 0; range 0 to 100 | % | Command | |
| AO | 24 | AO Heat Demand | Default 0; range 0 to 100 | % | Command | |
| AO | 123 | UO11 Analog Output | Default 0; range 0 to 10 | V | Command | |
| AO | 124 | UO12 Analog Output | Default 0; range 0 to 10 | V | Command | |
| AO | 125 | UO9 Analog Output | Default 0; range 0 to 10 | V | Command | |
| AO | 126 | UO10 Analog Output | Default 0; range 0 to 10 | V | Command | |
| AV | 2 | User HMI Icons | Show/Hide screen icons; default 0; range 0 to 12 | Command | ||
| AV | 3 | Low Backlight | Default 60; range 0 to 100 | % | Command | |
| AV | 4 | Night Backlight | Default 5; range 0 to 100 | % | Command | |
| AV | 7 | Calibrate Temperature | Default 0; range -5°F (-20°C) to 5°F (10°C) | °F/°C | Command | |
| AV | 8 | Calibrate Humidity | Default 0; range -15 to 15 | % | Command | |
| AV | 10 | COM Address | COM address; default 254; range 0 to 254 | Command | ||
| AV | 11 | PAN ID | PAN ID; default 0; range 0 to 32767 | Command | ||
| AV | 12 | Channel | Channel; default 10; range 10 to 25 | Command | ||
| AV | 13 | Short Address | Short address; default 0; range -32768 to 32767 | Command | ||
| AV | 14 | IEEE Address | IEEE address; default 0; range -32768 to 32767 | Command | ||
| AV | 15 | Get from COM | Default 0; range 0 to 254 | Command | ||
| AV | 16 | BACnet Stack Poll Rate | Default 4; range 1 to 5 | Command | ||
| AV | 20 | Discharge Low Limit | Default 45°F (7°C); range 35°F (2°C) to 65°F (18°C) | °F/°C | Command | |
| AV | 21 | Minimum Fresh Air | Default 0; range 0 to 20000 | cfm | Command | |
| AV | 22 | Maximum Fresh Air | Default 0; range 0 to 20000 | cfm | Command | |
| AV | 23 | Minimum CO2 | Default 800; range 0 to 5000 | ppm | Command | |
| AV | 24 | Maximum CO2 | Default 1200; range 0 to 5000 | ppm | Command | |
| AV | 25 | Param. A (AV25) | Default 0; range -32768 to 32767 | Command | ||
| AV | 26 | Param. B (AV26) | Default 0; range -32768 to 32767 | Command | ||
| AV | 27 | Param. C (AV27) | Default 0; range -32768 to 32767 | Command | ||
| AV | 28 | Param. D (AV28) | Default 0; range -32768 to 32767 | Command | ||
| AV | 29 | Param. E (AV29) | Default 0; range -32768 to 32767 | Command | ||
| AV | 30 | Param. F (AV30) | Default 0; range -32768 to 32767 | Command | ||
| AVmin | 39 | Occ. Heat | Default 72°F (22°C); range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AVmin | 40 | Occ. Cool | Default 75°F (24°C); range 54°F (12°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 41 | Standby Heat | Default 69°F (21°C); range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 42 | Standby Cool | Default 78°F (21°C); range 54°F (26°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 43 | Unocc. Heat | Default 62°F (17°C); range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 44 | Unocc. Cool | Default 80°F (27°C); range 54°F (26°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 45 | Default Heat | Default 72°F (22°C); range 65°F (18°C) to 80°F (27°C) | °F/°C | Command | |
| AV | 46 | Standby Differential | Default 4°F (1.5°C); range 1°F (0.5°C) to 5°F (2.5°C) | °F/°C | Command | |
| AV | 56 | Main Password | Installer password; default 0; range 0 to 9999 | Command | ||
| AV | 57 | User Password | User password; default 0; range 0 to 999 | Command | ||
| AV | 58 | Maximum Heating | Default 90°F (32°C); range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 59 | Maximum Cooling | Default 54°F (26°C); range 54°F (26°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 62 | Temp Occ. Time | Default 2; range 0 to 24 | h | Command | |
| AV | 63 | Minimum Deadband | Default 3°F (1.5°C); range 2°F (1°C) to 5°F (2.5°C) | °F/°C | Command | |
| AV | 65 | Proportional Band | Default 3; range 3 to 10 | Command | ||
| AV | 67 | Standby Time | Default 0.5; range 0.5 to 24 | h | Command | |
| AV | 68 | Unoccupied Time | Default 0.5; range 0.5 to 24 | h | Command | |
| AV | 71 | Dehumidification Setpoint | Default 50; range 30 to 95 | %RH | Command | |
| AV | 72 | Dehumidification Hysteresis | Default 50; range 30 to 95 | %RH | Command | |
| AV | 74 | Calibrate Outside Temperature | Default 0°F (0°C); range -5°F (-2.5°C) to 5°F (2.5°C) | °F/°C | Command | |
| AV | 75 | Cooling Stages | Stages; default 2; range 1 to 1 | Command | ||
| AV | 76 | Power-up Delay | Default 10; range 10 to 120 | s | Command | |
| AV | 78 | Econo. Minimum Position | Default 0; range 0 to 100 | % | Command | |
| AV | 81 | Econo. Maximum Position | Default 0; range 0 to 100 | % | Command | |
| AV | 82 | High Balance Point | Default 90°F (32°C); range 34°F (1°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 83 | Low Balance Point | Default -12°F (-24°C); range -40°F (-40°C) to 30°F (-1°C) | °F/°C | Command | |
| AV | 84 | Heating CPH | Default 4; range 3 to 8 | cycles/h | Command | |
| AV | 85 | Cooling CPH | Default 4; range 3 to 4 | cycles/h | Command | |
| AV | 86 | Anti Short Cycle | Default 2; range 0 to 5 | min | Command | |
| AV | 87 | Heat Stages | Stages; default 2; range 0 to 2 | Command | ||
| AV | 88 | Heat Dehumidification Limit | Default 0; range 0 to 100 | % | Command | |
| AV | 89 | Cool Dehumidification Limit | Default 0; range 0 to 100 | % | Command | |
| AV | 91 | Heat Lockout | Default 120°F (49°C); range -15°F (-26°C) to 120°F (49°C) | °F/°C | Command | |
| AV | 92 | Keyboard Value | Default 0; range 0 to 35 | Command | ||
| AV | 93 | Cool Lockout | Default -40°F (-40°C); range -40°F (-40°C) to 95°F (35°C) | °F/°C | Command | |
| AV | 94 | Supply Air Setpoint | Default 55°F (13°C); range 50°F (10°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 95 | Changeover Setpoint | Default 55°F (13°C); range 14°F (10°C) to 70°F (21°C) | °F/°C | Command | |
| AV | 96 | Fresh Air Range | Default 0; range 0 to 20,000 | cfm | Command | |
| AV | 97 | Minimum Supply Heat | Default 64°F (18°C); range 50°F (10°C) to 72°F (22°C) | °F/°C | Command | |
| AV | 98 | Supply Heat Lockout | Default 32°F (0°C); range -15°F (-26°C) to 120°F (49°C) | °F/°C | Command | |
| AV | 99 | Discharge High Limit | Default 120°F (49°C); range 70°F (21°C) to 150°F (65.5°C) | °F/°C | Command | |
| AVmin | 100 | Room Temperature | Default 0°F (0°C); range -40°F (-40°C) to 122°F (50°C) | °F/°C | Command | |
| AV | 101 | Outdoor Temperature | Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C) | °F/°C | Command | |
| AV | 102 | Supply Temperature | Default 0°F (0°C); range -40°F (-40°C) to 122°F (50°C) | °F/°C | Command | |
| AV | 103 | Room Humidity | Default 0; range 0 to 100 | %RH | Command | |
| AV | 104 | UI19 Temperature | Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C) | °F/°C | Command | |
| AV | 105 | UI20 Temperature | Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C) | °F/°C | Command | |
| AV | 106 | CO2 level | Default 0; range 0 to 5000 | ppm | Command | |
| AV | 107 | Air Flow Level | Default 0; range 0 to 20,000 | cfm | Command | |
| AV | 108 | UI19 Analog | Default 0; range 0 to 100 | % | Command | |
| AV | 109 | UI24 Temperature | Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C) | °F/°C | Command | |
| AV | 202 | UI19 Lua | Default 0; range -32768 to 32767 | Command | ||
| AV | 203 | UI20 Lua | Default 0; range -32768 to 32767 | Command | ||
| AV | 204 | UI22 Lua | Default 0; range -32768 to 32767 | Command | ||
| AV | 205 | UI23 Lua | Default 0; range -32768 to 32767 | Command | ||
| AV | 206 | UI24 Lua | Default 0; range -32768 to 32767 | Command | ||
| AV | 207 | Offset Relay Closing | Default 0; range -20,000 to 20,000 | Command | ||
| AV | 208 | Offset Relay Opening | Default 0; range -20,000 to 20,000 | Command | ||
| AV | 209 | Threshold | Default 40°F; range 32°F to 45°F | °F | Command | |
| AV | 210 | Hysteresis | Default 4°F; range 0°F to 100°F | °F | Command | |
| AV | 211 | Shed Offset | Default 4°F (2°C); range 4°F (2°C) to 10°F (5.5°C) | °F/°C | Command | |
| BI | 29 | UI16 Binary Input | Default 0 | Read | 0 = Activated, 1 = Not Activated | |
| BI | 30 | UI17 Binary Input | Default 0 | Read | 0 = Activated, 1 = Not Activated | |
| BI | 91 | UI19 Binary Input | Default 0 | Read | 0 = Activated, 1 = Not Activated | |
| BI | 94 | UI20 Binary Input | Default 0 | Read | 0 = Activated, 1 = Not Activated | |
| BI | 95 | UI22 Binary Input | Default 0 | Read | 0 = Activated, 1 = Not Activated | |
| BI | 96 | UI23 Binary Input | Default 0 | Read | 0 = Activated, 1 = Not Activated | |
| BI | 97 | UI24 Binary Input | Default 0 | Read | 0 = Activated, 1 = Not Activated | |
| BOmin | 25 | G Fan Status | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 26 | Y1 Status | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 27 | UY2 Status | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 28 | W1 Status | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 29 | W2/OB Status | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 94 | UO10 Binary Output | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 98 | BO1 Aux. Out | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 101 | UO11 Binary Output | Default 0 | Command | 0 = Off, 1 = On | |
| BO | 102 | UO12 Binary Output | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 1 | Door Status | Default 0 | Command | 0 = Closed, 1 = Open | |
| BV | 2 | Door Installed | Default 0 | Command | 0 = No, 1 = Yes | |
| BV | 3 | Window Status | Default 0 | Command | 0 = Closed, 1 = Open | |
| BV | 4 | Window Installed | Default 0 | Command | 0 = No, 1 = Yes | |
| BV | 5 | Low Battery | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 6 | Force High Backlight | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 7 | Long Message Display | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 8 | Clock Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 10 | Exception Status | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 32 | Local Motion | Default 0 | Command | 0 = No Motion, 1 = Motion | |
| BV | 35 | Window Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 36 | Filter Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 37 | Service Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 38 | Dehumidification Status | Default 0 | Command | 0 = Off, 1 = On | |
| BVmin | 39 | Fan Lock Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 40 | Recovery Status | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 41 | CO2 Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 42 | Low Air Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 43 | Frost Alarm | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 44 | Water Leak | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 45 | Water Installed | Default 0 | Command | 0 = No, 1 = Yes | |
| BV | 46 | Water Status | Default 0 | Command | 0 = Normal, 1 = Leak | |
| BV | 47 | Low Temperature | Default 0 | Command | 0 = Off, 1 = On | |
| BV | 48 | Shed Demand | Default 0 | Command | 0 = Closed, 1 = Open | |
| BV | 49 | Shed Status | Default 0 | Command | 0 = No, 1 = Yes | |
| BV | 50 | Shed Override | Default 0 | Command | 0 = Closed, 1 = Open | |
| BV | 200 | ZigBee PIR Status | Default 0 | Command | 0 = No, 1 = Yes | |
| BV | 201 | ZigBee Sensor Motion | Default 0 | Command | 0 = No Motion, 1 = Motion | |
| CSV | 1 | Short Screen Message | Text, length 0 to 64 | Write | ||
| CSV | 2 | Long Screen Message | Text, length 0 to 480 | Write | ||
| CSV | 3 | Ext. Mem. Revision | Text, length 0 to 9 | Write | ||
| CSV | 4 | Wi-Fi Device Name | Text, length 0 to 63 | Write | ||
| CSV | 5 | Wi-Fi Firmware Version | Text, length 0 to 63 | Write | ||
| CSV | 6 | MAC Address | Text, length 0 to 18 | Write | ||
| CSV | 7 | Wi-Fi Network SSID | Text, length 0 to 33 | Write | ||
| CSV | 8 | Wi-Fi Network IP Address | Text, length 0 to 46 | Write | ||
| CSV | 9 | ZigBee Firmware Revision | Text, length 0 to 32 | Write | ||
| CSV | 10 | ZigBee IEEE Address | Text, length 0 to 18 | Write | ||
| MI | 1 | BACnet Status | Default 1 | Read | 1 = Offline, 2 = Online | |
| MI | 2 | Network Status | Default 1 | Read | 1 = Not det., 2 = Pwr on, 3 = No NWK, 4 = Joined, 5 = Online | |
| MImin | 33 | Effective Occupancy | Default 1 | Read | 1 = Occupied, 2 = Unoccupied, 3 = Override, 4 = Standby | |
| MI | 210 | Wireless Device 1 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 211 | Wireless Device 1 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 212 | Wireless Device 1 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 220 | Wireless Device 2 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 221 | Wireless Device 2 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 222 | Wireless Device 2 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 230 | Wireless Device 3 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 231 | Wireless Device 3 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 232 | Wireless Device 3 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 240 | Wireless Device 4 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 241 | Wireless Device 4 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 242 | Wireless Device 4 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 250 | Wireless Device 5 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 251 | Wireless Device 5 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 252 | Wireless Device 5 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 260 | Wireless Device 6 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 261 | Wireless Device 6 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 262 | Wireless Device 6 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 270 | Wireless Device 7 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 271 | Wireless Device 7 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 272 | Wireless Device 7 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 280 | Wireless Device 8 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 281 | Wireless Device 8 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 282 | Wireless Device 8 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 290 | Wireless Device 9 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 291 | Wireless Device 9 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 292 | Wireless Device 9 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 300 | Wireless Device 10 - Status | Default 1 | Read | 1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak | |
| MI | 301 | Wireless Device 10 - Battery | Default 1 | Read | 1 = None, 2 = Normal, 3 = Low | |
| MI | 302 | Wireless Device 10 - Communication Status | Default 1 | Read | 1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline | |
| MI | 312 | Effective Temperature Sensor | Default 1 | Read | 1 = Wired, 2 = Internal, 3 = WL IO, 4 = WL 1, 5 = WL 2, 6 = WL 3, 7 = WL 4, 8 = WL 5, 9 = WL 6, 10 = WL 7, 11 = WL 8, 12 = WL 9, 13 = WL 10, 4 = WL GP | |
| MI | 313 | Effective Relative Humidity Sensor | Default 1 | Read | 1 = None, 2 = Internal, 3 = WL 1, 4 = WL 2, 5 = WL 3, 6 = WL 4, 7 = WL 5, 8 = WL 6, 9 = WL 7, 10 = WL 8, 11 = WL 9, 12 = WL 10, 13 = WL GP | |
| MI | 314 | Effective System Mode | Default 1 | Read | 1 = Cool, 2 = Heat | |
| MI | 315 | Wi-Fi Module Status | Default 1 | Read | 1 = Offline, 2 = Initializing, 3 = Ready, 4 = Booting, 5 = Resetting, 6 = Fail, 7 = Testing | |
| MI | 316 | Wi-Fi Status | Default 1 | Read | 1 = Idle, 2 = Associate, 3 = Config., 4 = Ready, 5 = Online, 6 = Disconn., 7 = Failure | |
| MI | 317 | BACnet IP Status | Default 1 | Read | 1 = Disabled, 2 = Enabled | |
| MI | 318 | SMTP Server Status | Default 1 | Read | 1 = Unknown, 2 = Disabled, 3 = Offline, 4 = Online | |
| MV | 1 | Long Message Background Color | Default 1 | Command | 1 = White, 2 = Green, 3 = Blue, 4 = Grey, 5 = Dark Grey, 6 = Default, 7 = Red | |
| MV | 2 | HMI Color | Default 1 | Command | 1 = White, 2 = Green, 3 = Blue, 4 = Grey, 5 = Dark Grey | |
| MV | 3 | Main Display | Default 1 | Command | 1 = Temperature, 2 = Setpoint | |
| MV | 4 | Language | Default 1 | Command | 1 = English, 2 = French, 3 = Spanish, 4 = Chinese, 5 = Russian, 6 = Arabic, 7 = Bulgarian, 8 = Czech, 9 = Danish, 10 = Dutch, 11 = Finnish, 12 = German, 13 = Hungarian, 14 = Indonesian, 15 = Italian, 16 = Norwegian, 17 = Polish, 18 = Portuguese, 19 = Slovak, 20 = Swedish, 21 = Turkish, 22 = Japanese, 23 = Hebrew | |
| MV | 5 | Time Format | Default 1 | Command | 1 = AM-PM, 2 = 24 Hours | |
| MV | 6 | Network Units | Default 1 | Command | 1 = SI, 2 = Imperial | |
| MV | 7 | Network Language | Default 1 | Command | 1 = English, 2 = French, 3 = Spanish | |
| MV | 8 | BACnet Baud Rate | Default 7 | Command | 1 = 9600, 2 = 19200, 3 = 38400, 4 = 57600, 5 = 76800, 6 = 115200, 7 = Auto | |
| MVmin | 10 | Occupancy Command | Default 2 | Command | 1 = Loc. occ, 2 = Occupied, 3 = Unocc. | |
| MV | 11 | Standby Mode | Default 1 | Command | 1 = Absolute, 2 = Offset | |
| MV | 12 | Fan Delay | Default 2 | Command | 1 = Off, 2 = On | |
| MV | 13 | Dehumidification Lockout | Default 2 | Command | 1 = Disabled, 2 = Enabled | |
| MVmin | 16 | System Mode | Default 4 | Command | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat | |
| MVmin | 17 | Fan Mode | Default 2 | Command | 1 = On, 2 = Auto, 3 = Smart | |
| MV | 32 | Standby Screen | Default 1 | Command | 1 = No, 2 = Yes, 3 = Occ. only, 4 = Screen sav | |
| MV | 46 | UI16 Configuration | Default 1 | Command | 1 = None, 2 = Rem NSB, 3 = Motion NO, 4 = Motion NC, 5 = Window, 6 = Fan Lock | |
| MV | 47 | UI17 Configuration | Default 1 | Command | 1 = None, 2 = Door dry, 3 = Override, 4 =Filter, 5 = Service | |
| MV | 49 | UI19 Configuration | Default 1 | Command | 1 = None, 2 = CO2 | |
| MV | 51 | Temperature Units | Default 1 | Command | 1 = °C, 2 = °F | |
| MV | 55 | Frost Protection | Default 1 | Command | 1 = Off, 2 = On | |
| MV | 58 | Setpoint Function | Default 2 | Command | 1 = Dual SP, 2 = Attach SP | |
| MV | 70 | Relative Humidity Display | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 71 | Smart Recovery | Default 1 | Command | 1 = Off, 2 = On | |
| MV | 72 | Economizer Configuration | Default 1 | Command | 1 = Off, 2 = On | |
| MV | 73 | Schedule Menu | Default 2 | Command | 1 = Disabled, 2 = Enabled, 3 = Dis. no. clk., 4 =En. no. clk. | |
| MV | 79 | Mechanical Cooling | Default 1 | Command | 1 = Off, 2 = On | |
| MV | 92 | BO1 Auxiliary Configuration | Default 1 | Command | 1 = NO, 2 = NC | |
| MV | 95 | Fan Control Heat | Default 2 | Command | 1 = Off, 2 = On | |
| MV | 96 | UO9 Configuration | Default 4 | Command | 1 = Analog, 2 = Binary, 3 = Relay RC, 4 = Relay RH | |
| MV | 97 | UO10 Configuration | Default 1 | Command | 1 = Analog, 2 = Binary, 3 = Relay RC | |
| MV | 98 | UO11 Configuration | Default 1 | Command | 1 = Analog, 2 = Binary | |
| MV | 99 | UO12 Configuration | Default 2 | Command | 1 = Analog, 2 = Binary | |
| MV | 100 | English | Default 1 | Command | 1 = Enabled | |
| MV | 101 | French | Default 2 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 102 | Spanish | Default 2 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 103 | Chinese | Default 2 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 104 | Russian | Default 2 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 110 | Occupancy Screen | Default 1 | Command | 1 = Motion, 2 = Schedule | |
| MV | 111 | Mode Button | Default 1 | Command | 1 = Normal, 2 = Off-Auto | |
| MVmin | 112 | Control Status | Default 1 | Command | 1 = Off, 2 = Cool, 3 = Heat | |
| MV | 113 | Node Type | Default 1 | Command | 1 = Router, 2 = Coordinator | |
| MV | 114 | Custom Icon Buttons | Default 1 | Command | 1 = Default, 2 = None, 3 = System mode Heat/Cool, 4 = System mode On/Off, 5 = Fan mode, 6 = Override, 7 = Units, 8 = Help, 9 = Language, 10 = Schedule, 11 = Lighting, 12 = Blind, 13 = Lamp, 14 = Energy, 15 = Make up room, 16 = Setting, 17 = Timer | |
| MV | 115 | Custom Behavior | Default 1 | Command | 1 = Default, 2 = No function, 3 = System mode function, 4 = Fan function, 5 = Override, 6 = Schedule, 7 = Units, 8 = Help, 9= Language, 10 = Configuration, 11 = Custom, 12 = Standby | |
| MV | 116 | Comfort or Economy | Default 1 | Command | 1 = Comfort, 2 = Economy | |
| MV | 117 | Reversing Valve | Default 1 | Command | 1 = O, 2 = B | |
| MV | 118 | Comp. Interlock | Default 1 | Command | 1 = Off, 2 = On | |
| MV | 119 | Application | Default 1 | Command | 1 = Rooftop, 2 = Heat Pump | |
| MV | 120 | Arabic | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 121 | Bulgarian | Default 1 | Command | 1 = Disabled | |
| MV | 122 | Czech | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 123 | Danish | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 124 | Dutch | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 125 | Finnish | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 126 | German | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 127 | Hungarian | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 128 | Indonesian | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 129 | Italian | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 130 | Norwegian | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 131 | Polish | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 132 | Portuguese | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 133 | Slovak | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 134 | Swedish | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 135 | Turkish | Default 1 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 136 | Schedule Type | Default 1 | Command | 1 = 7 days, 2 = 5 + 2 days, 3 = 5 + 1 + 1 days | |
| MV | 137 | Schedule Events | Default 3 | Command | 1 = 2/day, 2 = 4/day, 3 = 6/day | |
| MV | 140 | UI19 Input Type | Default 3 | Command | 1 = Thermistor, 2 = Binary, 3 = Voltage | |
| MV | 141 | UI20 Input Type | Default 1 | Command | 1 = Thermistor, 2 = Binary, 3 = Voltage | |
| MV | 142 | UI22 Input Type | Default 1 | Command | 1 = Thermistor, 2 = Binary, 3 = Voltage | |
| MV | 143 | UI23 Input Type | Default 1 | Command | 1 = Thermistor, 2 = Binary, 3 = Voltage | |
| MV | 144 | UI224 Input Type | Default 3 | Command | 1 = Thermistor, 2 = Binary, 3 = Voltage, 4 = Reserved | |
| MV | 145 | Temperature Sensor | Default 3 | Command | 1 = Wired, 2 = Internal, 3 = WL IO, 4 = WL 1, 5 = WL 2, 6 = WL 3, 7 = WL 4, 8 = WL 5, 9 = WL 6, 10 = WL 7, 11 = WL 8, 12 = WL 9, 13 = WL 10, 14 = WL GP | |
| MV | 146 | CO2 Sensor | Default 2 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 147 | CO2 Auto Calibration | Default 2 | Command | 1 = Disabled, 2 = Enabled | |
| MV | 148 | Lock Screen | Default 1 | Command | 1 = No, 2 = Yes | |
| MV | 149 | RH Sensor | Default 2 | Command | 1 = None, 2 = Internal, 3 = WL 1, 4 = WL 2, 5 = WL 3, 6 = WL 4, 7 = WL 5, 8 = WL 6, 9 = WL 7, 10 = WL 8, 11 = WL 9, 12 = WL 10, 13 = WL GP | |
| MV | 150 | Auto Mode Enable | Default 1 | Command | 1 = None, 2 = T-rH CO2, 3 = T-rH | |
| MV | 151 | ADR Permission | Default 1 | Command | 1 = Off, 2 = On | |
| MV | 152 | Wireless Device GP - Function | Default 1 | Command | 1 = Off, 2 = On | |
| MV | 153 | Function | Default 2 | Command | 1 = Remove, 2 = None, 3 = T | |
| MV | 155 | Japanese | Default 1 | Command | 1 = Disabled, 2=Enabled | |
| MV | 156 | Hebrew | Default 1 | Command | 1 = Disabled, 2=Enabled | |
| MV | 210 | Wireless Device 1 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 220 | Wireless Device 2 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 230 | Wireless Device 3 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 240 | Wireless Device 4 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 250 | Wireless Device 5 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 260 | Wireless Device 6 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 270 | Wireless Device 7 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 280 | Wireless Device 8 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 290 | Wireless Device 9 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water | |
| MV | 300 | Wireless Device 10 - Function | Default 6 | Command | 1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water |
No points match these filters.
Object ID lookup: LG MultiSITE MS8650 Room Controller point IDs by name
AI1ThermistorAI2Light Sensor LevelAI3Thermistor Self HeatAI4Relative Humidity ValueAI5UI20 Raw ValueAI7UI23 Raw ValueAI8UI22 Raw ValueAI9UI24 Raw ValueAI31UI19 Raw ValueAI210Wireless Device 1 - AddressAI220Wireless Device 2 - AddressAI230Wireless Device 3 - AddressAI240Wireless Device 4 - AddressAI250Wireless Device 5 - AddressAI260Wireless Device 6 - AddressAI270Wireless Device 7 - AddressAI280Wireless Device 8 - AddressAI290Wireless Device 9 - AddressAI300Wireless Device 10 - AddressAI315Wireless Device 1 - TemperatureAI316Wireless Device 2 - TemperatureAI317Wireless Device 3 - TemperatureAI318Wireless Device 4 - TemperatureAI319Wireless Device 5 - TemperatureAI320Wireless Device 6 - TemperatureAI321Wireless Device 7 - TemperatureAI322Wireless Device 8 - TemperatureAI323Wireless Device 9 - TemperatureAI324Wireless Device 10 - TemperatureAI327Remote Relative HumidityAI328Permit TimeoutAI329Effective SetpointAI330Paired ZigBee DevicesAI342Wi-Fi Network Signal StrengthAO21PI Heat DemandAO22PI Cool DemandAO23Economizer DemandAO24AO Heat DemandAO123UO11 Analog OutputAO124UO12 Analog OutputAO125UO9 Analog OutputAO126UO10 Analog OutputAV2User HMI IconsAV3Low BacklightAV4Night BacklightAV7Calibrate TemperatureAV8Calibrate HumidityAV10COM AddressAV11PAN IDAV12ChannelAV13Short AddressAV14IEEE AddressAV15Get from COMAV16BACnet Stack Poll RateAV20Discharge Low LimitAV21Minimum Fresh AirAV22Maximum Fresh AirAV23Minimum CO2AV24Maximum CO2AV25Param. A (AV25)AV26Param. B (AV26)AV27Param. C (AV27)AV28Param. D (AV28)AV29Param. E (AV29)AV30Param. F (AV30)AV39Occ. HeatAV40Occ. CoolAV41Standby HeatAV42Standby CoolAV43Unocc. HeatAV44Unocc. CoolAV45Default HeatAV46Standby DifferentialAV56Main PasswordAV57User PasswordAV58Maximum HeatingAV59Maximum CoolingAV62Temp Occ. TimeAV63Minimum DeadbandAV65Proportional BandAV67Standby TimeAV68Unoccupied TimeAV71Dehumidification SetpointAV72Dehumidification HysteresisAV74Calibrate Outside TemperatureAV75Cooling StagesAV76Power-up DelayAV78Econo. Minimum PositionAV81Econo. Maximum PositionAV82High Balance PointAV83Low Balance PointAV84Heating CPHAV85Cooling CPHAV86Anti Short CycleAV87Heat StagesAV88Heat Dehumidification LimitAV89Cool Dehumidification LimitAV91Heat LockoutAV92Keyboard ValueAV93Cool LockoutAV94Supply Air SetpointAV95Changeover SetpointAV96Fresh Air RangeAV97Minimum Supply HeatAV98Supply Heat LockoutAV99Discharge High LimitAV100Room TemperatureAV101Outdoor TemperatureAV102Supply TemperatureAV103Room HumidityAV104UI19 TemperatureAV105UI20 TemperatureAV106CO2 levelAV107Air Flow LevelAV108UI19 AnalogAV109UI24 TemperatureAV202UI19 LuaAV203UI20 LuaAV204UI22 LuaAV205UI23 LuaAV206UI24 LuaAV207Offset Relay ClosingAV208Offset Relay OpeningAV209ThresholdAV210HysteresisAV211Shed OffsetBI29UI16 Binary InputBI30UI17 Binary InputBI91UI19 Binary InputBI94UI20 Binary InputBI95UI22 Binary InputBI96UI23 Binary InputBI97UI24 Binary InputBO25G Fan StatusBO26Y1 StatusBO27UY2 StatusBO28W1 StatusBO29W2/OB StatusBO94UO10 Binary OutputBO98BO1 Aux. OutBO101UO11 Binary OutputBO102UO12 Binary OutputBV1Door StatusBV2Door InstalledBV3Window StatusBV4Window InstalledBV5Low BatteryBV6Force High BacklightBV7Long Message DisplayBV8Clock AlarmBV10Exception StatusBV32Local MotionBV35Window AlarmBV36Filter AlarmBV37Service AlarmBV38Dehumidification StatusBV39Fan Lock AlarmBV40Recovery StatusBV41CO2 AlarmBV42Low Air AlarmBV43Frost AlarmBV44Water LeakBV45Water InstalledBV46Water StatusBV47Low TemperatureBV48Shed DemandBV49Shed StatusBV50Shed OverrideBV200ZigBee PIR StatusBV201ZigBee Sensor MotionCSV1Short Screen MessageCSV2Long Screen MessageCSV3Ext. Mem. RevisionCSV4Wi-Fi Device NameCSV5Wi-Fi Firmware VersionCSV6MAC AddressCSV7Wi-Fi Network SSIDCSV8Wi-Fi Network IP AddressCSV9ZigBee Firmware RevisionCSV10ZigBee IEEE AddressMI1BACnet StatusMI2Network StatusMI33Effective OccupancyMI210Wireless Device 1 - StatusMI211Wireless Device 1 - BatteryMI212Wireless Device 1 - Communication StatusMI220Wireless Device 2 - StatusMI221Wireless Device 2 - BatteryMI222Wireless Device 2 - Communication StatusMI230Wireless Device 3 - StatusMI231Wireless Device 3 - BatteryMI232Wireless Device 3 - Communication StatusMI240Wireless Device 4 - StatusMI241Wireless Device 4 - BatteryMI242Wireless Device 4 - Communication StatusMI250Wireless Device 5 - StatusMI251Wireless Device 5 - BatteryMI252Wireless Device 5 - Communication StatusMI260Wireless Device 6 - StatusMI261Wireless Device 6 - BatteryMI262Wireless Device 6 - Communication StatusMI270Wireless Device 7 - StatusMI271Wireless Device 7 - BatteryMI272Wireless Device 7 - Communication StatusMI280Wireless Device 8 - StatusMI281Wireless Device 8 - BatteryMI282Wireless Device 8 - Communication StatusMI290Wireless Device 9 - StatusMI291Wireless Device 9 - BatteryMI292Wireless Device 9 - Communication StatusMI300Wireless Device 10 - StatusMI301Wireless Device 10 - BatteryMI302Wireless Device 10 - Communication StatusMI312Effective Temperature SensorMI313Effective Relative Humidity SensorMI314Effective System ModeMI315Wi-Fi Module StatusMI316Wi-Fi StatusMI317BACnet IP StatusMI318SMTP Server StatusMV1Long Message Background ColorMV2HMI ColorMV3Main DisplayMV4LanguageMV5Time FormatMV6Network UnitsMV7Network LanguageMV8BACnet Baud RateMV10Occupancy CommandMV11Standby ModeMV12Fan DelayMV13Dehumidification LockoutMV16System ModeMV17Fan ModeMV32Standby ScreenMV46UI16 ConfigurationMV47UI17 ConfigurationMV49UI19 ConfigurationMV51Temperature UnitsMV55Frost ProtectionMV58Setpoint FunctionMV70Relative Humidity DisplayMV71Smart RecoveryMV72Economizer ConfigurationMV73Schedule MenuMV79Mechanical CoolingMV92BO1 Auxiliary ConfigurationMV95Fan Control HeatMV96UO9 ConfigurationMV97UO10 ConfigurationMV98UO11 ConfigurationMV99UO12 ConfigurationMV100EnglishMV101FrenchMV102SpanishMV103ChineseMV104RussianMV110Occupancy ScreenMV111Mode ButtonMV112Control StatusMV113Node TypeMV114Custom Icon ButtonsMV115Custom BehaviorMV116Comfort or EconomyMV117Reversing ValveMV118Comp. InterlockMV119ApplicationMV120ArabicMV121BulgarianMV122CzechMV123DanishMV124DutchMV125FinnishMV126GermanMV127HungarianMV128IndonesianMV129ItalianMV130NorwegianMV131PolishMV132PortugueseMV133SlovakMV134SwedishMV135TurkishMV136Schedule TypeMV137Schedule EventsMV140UI19 Input TypeMV141UI20 Input TypeMV142UI22 Input TypeMV143UI23 Input TypeMV144UI224 Input TypeMV145Temperature SensorMV146CO2 SensorMV147CO2 Auto CalibrationMV148Lock ScreenMV149RH SensorMV150Auto Mode EnableMV151ADR PermissionMV152Wireless Device GP - FunctionMV153FunctionMV155JapaneseMV156HebrewMV210Wireless Device 1 - FunctionMV220Wireless Device 2 - FunctionMV230Wireless Device 3 - FunctionMV240Wireless Device 4 - FunctionMV250Wireless Device 5 - FunctionMV260Wireless Device 6 - FunctionMV270Wireless Device 7 - FunctionMV280Wireless Device 8 - FunctionMV290Wireless Device 9 - FunctionMV300Wireless Device 10 - Function
Integration notes
- Access follows the guide's object-property tables: AV, AO, BV, BO and MSV present values are commandable, CSVs writable, and AI/MSI present values only writable while Out_Of_Service is TRUE.
- The guide gives no description column, only default, range and a units/state column; descriptions here show the printed default and range.
- Some object names print the subscript 2 of CO2 out of place (e.g. 'CO level 2'); they are written as CO2 here (AV 106 'CO2 level').
- Wireless Device objects only report data for paired ZigBee Pro sensors.
- The guide mentions 10 program (PG) objects for LUA4RC scripts but does not list them.
- MI 312 prints its last state as '4 = WL GP' (the MS8350 table has 14); MV 110 is named 'Occupancy Screen' in the MS8650 table. Both are kept as printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)
How many BACnet points does the LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ) have?
This list has 311 BACnet objects: 34 analog inputs, 8 analog outputs, 84 analog values, 7 binary inputs, 9 binary outputs, 28 binary values, 40 multi-state inputs, 91 multi-state values, 10 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ) BACnet points are writable?
230 of the 311 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ) BACnet documentation?
The source is MultiSITE MS8000 Series Room Controllers BACnet Integration Guide (MS8350 VUCQMS8350, MS8650 VUCQMS8650) (UM_MultiSITE_MS8000_Series_BACnet_Integration_05_20), revision 2020-05, published free by LG at https://media.us.lg.com/m/11d3a44fc9cab7aa/original/UM_MultiSITE_MS8000_Series_BACnet_Integration-pdf.pdf.
What are the minimum BACnet points to integrate the LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)?
Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode: on / auto / smart); AV 39 Occ. Heat (Occupied heating setpoint); AV 40 Occ. Cool (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); BO 25 G Fan Status (Fan (G) output state); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 39 Fan Lock Alarm (Fan lock alarm (1 = on)).
How do I enable BMS control of the LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)?
The BMS writes MV 10 Occupancy Command (1 = Loc. occ; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 chooses whether local occupancy follows motion or the schedule.
Can the BMS supply sensor values to the LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)?
The guide does not describe feeding room temperature from the BMS. MV 145 selects the wired, internal or a paired ZigBee wireless sensor, and MI 312 Effective Temperature Sensor shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.
How do I check these points on the real MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More LG BACnet points lists
- VRF BACnet IP gateway
LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
LG Multi V VRF and single-split indoor units, ventilation (ERV) units and outdoor units on the ACP BACnet's LG-NET. LG's AC Smart BACnet (PBACNA000) manual prints the same tables.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet, ACP-BAC, LG BACnet gateway, LG VRF BACnet, AC Smart BACnet, PBACNA000, LG Multi V BACnet - Air handling unit via BACnet IP gateway
LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
LG air handling units wired to the ACP BACnet gateway (RS-485 on its CH5 port) and served on its AHU device.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet AHU, ACP-BAC AHU - Air-to-water heat pump via BACnet IP gateway
LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)
LG air-to-water heat pumps (AWHP) served by the ACP BACnet gateway.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet AWHP, ACP-BAC AWHP, LG air to water heat pump BACnet - VRF indoor unit zone controller (room controller)
LG MultiSITE CRC2+Z Remote Controller (PREMTBVC4)
LG MultiSITE CRC2+Z wall remote controller (PREMTBVC4) for LG VRF and single-zone indoor units, up to 16 indoor units per controller.
Also known as: PREMTBVC4, CRC2, CRC2+Z, MultiSITE CRC2, LG CRC2 remote controller, PREMTBVC3 - Fan coil unit controller (room thermostat)
LG MultiSITE MS8350 Room Controller (fan coil)
LG MultiSITE MS8350 (VUCQMS8350) room controllers for commercial and hotel fan coil units.
Also known as: MS8350, VUCQMS8350, LG MS8350, MultiSITE MS8000
Source: MultiSITE MS8000 Series Room Controllers BACnet Integration Guide (MS8350 VUCQMS8350, MS8650 VUCQMS8650) · UM_MultiSITE_MS8000_Series_BACnet_Integration_05_20 · rev. 2020-05. Object names, instances and units are reproduced as published; descriptions are our own.