- ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
VRF BACnet IP gateway · BACnet points list
LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet points list
Updated 6 November 2026Unofficial source
LG's ACP BACnet controller serves every indoor unit, ventilation unit and outdoor unit on its LG-NET as a fixed block of BACnet IP objects. The instance number is built from the product type, the unit address and the point number, so one table covers every unit: on/off, mode, fan speed, setpoint, room temperature, alarm and error code for indoor units, plus ERV and outdoor unit data.
This page lists 75 BACnet objects for the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of LG’s documentation hosted by SupplyHouse.com, not by LG itself, so treat it as unofficial.
- Manufacturer
- LG
- Model
- ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
- Equipment
- VRF BACnet IP gateway
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 75 (27 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 9000
- Also known as
- PQNFB17C0, PQNFB17C1, ACP BACnet, ACP-BAC, LG BACnet gateway, LG VRF BACnet, AC Smart BACnet, PBACNA000, LG Multi V BACnet
- Source document
- BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (unofficial copy, hosted by SupplyHouse.com)
Instance calculator. This list prints one unit; the other units follow a formula. LG ACP BACnet / AC Smart BACnet instance calculator →
Reference only, provided as-is: verify against LG’s current documentation and the live device before use. Not official LG information. Terms of use.
BMS integration notes: LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
Set the ACP BACnet's IP and Device ID (default 9000) on its front panel, let it find the units on LG-NET, then map each indoor unit's block at address x 256: on/off, mode, fan speed, setpoint and room temperature first, plus alarm and error code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | StartStopCommand_XXX | On/off (address x 256 + 1) | Command |
| MO 7 | ModeCommand_XXX | 1 Cool, 2 Dry, 3 Fan, 4 Auto, 5 Heat | Command |
| MO 11 | FanSpeedCommand_XXX | 1 Low, 2 Middle, 3 High, 4 Auto | Command |
| AV 13 | SetRoomTemp_XXX | Setpoint | Write |
| AI 14 | RoomTemp_XXX | Room temperature | Read |
| BI 15 | Alarm_XXX | Unit alarm | Read |
| AI 16 | MalfunctionCode_XXX | LG error code | Read |
Network setup
- Default Device ID 9000; ERV, AHU, outdoor cycle and AWHP devices take Device ID +1 to +4.
- Device ID and network settings are set from the ACP's front-panel menu (Contents > Device ID).
LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 1 | StartStopCommand_XXX | [Indoor unit] On/off command | Command | Inactive=Stop, Active=Start | |
| BI | 2 | StartStopStatus_XXX | [Indoor unit] On/off status | Read | Inactive=Stop, Active=Run | |
| BO | 3 | LockCommand_XXX | [Indoor unit] Remote controller lock command | Command | Inactive=Permit, Active=Prohibit | |
| BI | 4 | LockStatus_XXX | [Indoor unit] Remote controller lock status | Read | Inactive=Permit, Active=Prohibit | |
| BI | 5 | Filter Sign_XXX | [Indoor unit] Filter sign | Read | Inactive=Off, Active=On | |
| BV | 6 | Filter Sign Reset_XXX | [Indoor unit] Filter sign reset | Write | Active=Reset | |
| MOmin | 7 | ModeCommand_XXX | [Indoor unit] Operation mode command | Command | 1=Cool, 2=Dry, 3=Fan, 4=Auto, 5=Heat | |
| MI | 8 | ModeStatus_XXX | [Indoor unit] Operation mode status | Read | 1=Cool, 2=Dry, 3=Fan, 4=Auto, 5=Heat | |
| BO | 9 | SwingCommand_XXX | [Indoor unit] Swing command | Command | Inactive=Stop, Active=Run | |
| BI | 10 | SwingStatus_XXX | [Indoor unit] Swing status | Read | Inactive=Stop, Active=Run | |
| MOmin | 11 | FanSpeedCommand_XXX | [Indoor unit] Fan speed command | Command | 1=Low, 2=Middle, 3=High, 4=Auto | |
| MI | 12 | FanSpeedStatus_XXX | [Indoor unit] Fan speed status | Read | 1=Low, 2=Middle, 3=High, 4=Auto | |
| AVmin | 13 | SetRoomTemp_XXX | [Indoor unit] Setpoint (about 18-35 C) | °C | Write | |
| AImin | 14 | RoomTemp_XXX | [Indoor unit] Room temperature | °C | Read | |
| BImin | 15 | Alarm_XXX | [Indoor unit] Alarm | Read | Inactive=Normal, Active=Abnormal | |
| AImin | 16 | MalfunctionCode_XXX | [Indoor unit] LG error code (type left blank in the indoor table) | Read | ||
| AI | 19 | SetTempStatus_XXX | [Indoor unit] Setpoint status | °C | Read | |
| AI | 20 | AccumPowerStatus_XXX | [Indoor unit] Power distribution (units of 100 W) | Read | ||
| AV | 27 | SetUpperTempCommand_XXX | [Indoor unit] Upper setpoint limit command | °C | Write | |
| AI | 28 | SetLowerTempCommand_XXX | [Indoor unit] Lower setpoint limit command (printed as AI) | °C | Write | |
| AI | 29 | SetUpperTempStatus_XXX | [Indoor unit] Upper setpoint limit status | °C | Read | |
| AI | 30 | SetLowerTempStatus_XXX | [Indoor unit] Lower setpoint limit status | °C | Read | |
| BO | 31 | ModeLockCommand_XXX | [Indoor unit] Mode lock command | Command | Inactive=Permit, Active=Prohibit | |
| BI | 32 | ModeLockStatus_XXX | [Indoor unit] Mode lock status | Read | Inactive=Permit, Active=Prohibit | |
| BO | 33 | Fan LockCommand_XXX | [Indoor unit] Fan lock command | Command | Inactive=Permit, Active=Prohibit | |
| BI | 34 | FanLockStatus_XXX | [Indoor unit] Fan lock status | Read | Inactive=Permit, Active=Prohibit | |
| BO | 35 | OccupancyCommand_XXX | [Indoor unit] Occupancy command (2Set Auto Mode) | Command | Inactive=Unoccupied, Active=Occupied | |
| BI | 36 | OccupancyStatus_XXX | [Indoor unit] Occupancy status (2Set Auto Mode) | Read | Inactive=Unoccupied, Active=Occupied | |
| AV | 37 | 2SetCoolingTempCommand_XXX | [Indoor unit] Dual setpoint: cooling setpoint command | °C | Write | |
| AI | 38 | 2SetCoolingTempStatus_XXX | [Indoor unit] Dual setpoint: cooling setpoint status | °C | Read | |
| AV | 39 | 2SetHeatingTempCommand_XXX | [Indoor unit] Dual setpoint: heating setpoint command | °C | Write | |
| AI | 40 | 2SetHeatingTempStatus_XXX | [Indoor unit] Dual setpoint: heating setpoint status | °C | Read | |
| AV | 41 | 2SetCoolingUpperLimitCommand_XXX | [Indoor unit] Dual setpoint: cooling upper limit command | °C | Write | |
| AI | 42 | 2SetCoolingUpperLimitStatus_XXX | [Indoor unit] Dual setpoint: cooling upper limit status | °C | Read | |
| AV | 43 | 2SetHeatingUpperLimitCommand_XXX | [Indoor unit] Dual setpoint: heating upper limit command | °C | Write | |
| AI | 44 | 2SetHeatingUpperLimitStatus_XXX | [Indoor unit] Dual setpoint: heating upper limit status | °C | Read | |
| AV | 45 | 2SetCoolingLowerLimitCommand_XXX | [Indoor unit] Dual setpoint: cooling lower limit command | °C | Write | |
| AI | 46 | 2SetCoolingLowerLimitStatus_XXX | [Indoor unit] Dual setpoint: cooling lower limit status | °C | Read | |
| AV | 47 | 2SetHeatingLowerLimitCommand_XXX | [Indoor unit] Dual setpoint: heating lower limit command | °C | Write | |
| AI | 48 | 2SetHeatingLowerLimitStatus_XXX | [Indoor unit] Dual setpoint: heating lower limit status | °C | Read | |
| BI | 49 | ThermoStatus_XXX | [Indoor unit] Thermo on/off status (2Set Auto Mode) | Read | Inactive=Off, Active=On | |
| BO | 65537 | StartStopCommand_XXX | [Ventilation] On/off command | Command | Inactive=Stop, Active=Start | |
| BI | 65538 | StartStopStatus_XXX | [Ventilation] On/off status | Read | Inactive=Stop, Active=Run | |
| BO | 65539 | LockCommand_XXX | [Ventilation] Lock command | Command | Inactive=Permit, Active=Prohibit | |
| BI | 65540 | LockStatus_XXX | [Ventilation] Lock status | Read | Inactive=Permit, Active=Prohibit | |
| BI | 65541 | Filter Sign_XXX | [Ventilation] Filter sign | Read | Inactive=Off, Active=On | |
| BV | 65542 | Filter Sign Reset_XXX | [Ventilation] Filter sign reset | Write | Active=Reset | |
| MO | 65543 | ModeCommand_XXX | [Ventilation] Operation mode command | Command | 1=Heat Exchange, 2=Auto, 3=Normal | |
| MI | 65544 | ModeStatus_XXX | [Ventilation] Operation mode status | Read | 1=Heat Exchange, 2=Auto, 3=Normal | |
| MO | 65547 | FanSpeedCommand_XXX | [Ventilation] Fan speed command | Command | 1=Low, 2=High, 3=Super High, 4=Auto | |
| MI | 65548 | FanSpeedStatus_XXX | [Ventilation] Fan speed status | Read | 1=Low, 2=High, 3=Super High, 4=Auto | |
| BI | 65551 | Alarm_XXX | [Ventilation] Alarm | Read | Inactive=Off, Active=On | |
| AI | 65552 | MalfunctionCode_XXX | [Ventilation] LG error code | Read | ||
| MO | 65553 | UserModeCommand_XXX | [Ventilation] User mode command | Command | 1=Quick Fresh, 2=Energy Saving, 3=Heater | |
| MI | 65554 | UserModeStatus_XXX | [Ventilation] User mode status | Read | 1=Quick Fresh, 2=Energy Saving, 3=Heater | |
| MO | 65557 | HrvModeCommand_XXX | [Ventilation] AC operation mode command | Command | 1=Cool, 2=Auto, 3=Heat | |
| MI | 65558 | HrvModeStatus_XXX | [Ventilation] AC operation mode status | Read | 1=Cool, 2=Auto, 3=Heat | |
| BO | 65559 | HrvStartStopCommand_XXX | [Ventilation] AC on/off command | Command | Inactive=Stop, Active=Run | |
| BI | 65560 | HrvStartStopStatus_XXX | [Ventilation] AC on/off status | Read | Inactive=Stop, Active=Run | |
| BO | 65561 | HrvHumidifyCommand_XXX | [Ventilation] AC humidify command | Command | Inactive=Off, Active=On | |
| BI | 65562 | HrvHumidifyStatus_XXX | [Ventilation] AC humidify status | Read | Inactive=Off, Active=On | |
| BI | 196609 | CompOperStatus _XXX | [Outdoor unit] Compressor running | Read | Inactive=Stop, Active=Run | |
| MI | 196610 | RefrigentType_XXX | [Outdoor unit] Refrigerant type | Read | 1=R407C, 2=422 (as printed), 3=R410A | |
| AI | 196611 | InverterFanFreq_XXX | [Outdoor unit] Inverter fan 1 frequency | Read | ||
| AI | 196612 | HighPressure_XXX | [Outdoor unit] High pressure | Read | ||
| AI | 196613 | LowPressure_XXX | [Outdoor unit] Low pressure | Read | ||
| AI | 196614 | SunctionTemp_XXX | [Outdoor unit] Suction temperature | °C | Read | |
| AI | 196615 | LiquidPipeTemp_XXX | [Outdoor unit] Liquid pipe temperature | °C | Read | |
| AI | 196616 | HexTemp_XXX | [Outdoor unit] Heat exchanger temperature | °C | Read | |
| AI | 196617 | OutdoorEEV_XXX | [Outdoor unit] Outdoor EEV | Read | ||
| AI | 196618 | SubCoolEEV_XXX | [Outdoor unit] Subcool EEV | Read | ||
| BI | 196619 | HotgasValue_XXX | [Outdoor unit] Hot gas valve | Read | Inactive=Stop, Active=Run | |
| AI | 196620 | InverterDischargeTemp_XXX | [Outdoor unit] Inverter discharge temperature | °C | Read | |
| AI | 196621 | OutdoorTemp_XXX | [Outdoor unit] Outdoor temperature | °C | Read | |
| MI | 196622 | OperationMode_XXX | [Outdoor unit] Outdoor unit operation mode | Read | 1=Stop, 2=Cool, 3=Heat |
No points match these filters.
Object ID lookup: LG ACP BACnet gateway point IDs by name
BO1StartStopCommand_XXXBI2StartStopStatus_XXXBO3LockCommand_XXXBI4LockStatus_XXXBI5Filter Sign_XXXBV6Filter Sign Reset_XXXMO7ModeCommand_XXXMI8ModeStatus_XXXBO9SwingCommand_XXXBI10SwingStatus_XXXMO11FanSpeedCommand_XXXMI12FanSpeedStatus_XXXAV13SetRoomTemp_XXXAI14RoomTemp_XXXBI15Alarm_XXXAI16MalfunctionCode_XXXAI19SetTempStatus_XXXAI20AccumPowerStatus_XXXAV27SetUpperTempCommand_XXXAI28SetLowerTempCommand_XXXAI29SetUpperTempStatus_XXXAI30SetLowerTempStatus_XXXBO31ModeLockCommand_XXXBI32ModeLockStatus_XXXBO33Fan LockCommand_XXXBI34FanLockStatus_XXXBO35OccupancyCommand_XXXBI36OccupancyStatus_XXXAV372SetCoolingTempCommand_XXXAI382SetCoolingTempStatus_XXXAV392SetHeatingTempCommand_XXXAI402SetHeatingTempStatus_XXXAV412SetCoolingUpperLimitCommand_XXXAI422SetCoolingUpperLimitStatus_XXXAV432SetHeatingUpperLimitCommand_XXXAI442SetHeatingUpperLimitStatus_XXXAV452SetCoolingLowerLimitCommand_XXXAI462SetCoolingLowerLimitStatus_XXXAV472SetHeatingLowerLimitCommand_XXXAI482SetHeatingLowerLimitStatus_XXXBI49ThermoStatus_XXXBO65537StartStopCommand_XXXBI65538StartStopStatus_XXXBO65539LockCommand_XXXBI65540LockStatus_XXXBI65541Filter Sign_XXXBV65542Filter Sign Reset_XXXMO65543ModeCommand_XXXMI65544ModeStatus_XXXMO65547FanSpeedCommand_XXXMI65548FanSpeedStatus_XXXBI65551Alarm_XXXAI65552MalfunctionCode_XXXMO65553UserModeCommand_XXXMI65554UserModeStatus_XXXMO65557HrvModeCommand_XXXMI65558HrvModeStatus_XXXBO65559HrvStartStopCommand_XXXBI65560HrvStartStopStatus_XXXBO65561HrvHumidifyCommand_XXXBI65562HrvHumidifyStatus_XXXBI196609CompOperStatus _XXXMI196610RefrigentType_XXXAI196611InverterFanFreq_XXXAI196612HighPressure_XXXAI196613LowPressure_XXXAI196614SunctionTemp_XXXAI196615LiquidPipeTemp_XXXAI196616HexTemp_XXXAI196617OutdoorEEV_XXXAI196618SubCoolEEV_XXXBI196619HotgasValue_XXXAI196620InverterDischargeTemp_XXXAI196621OutdoorTemp_XXXMI196622OperationMode_XXX
Integration notes
- Instance = product type x 65536 + unit address x 256 + point number. Product type: indoor 0, ventilation 1, AHU 2, outdoor unit 3, AWHP 4, general 5. The unit address is LG's address read as hex (tag 1A = 26). Instances here are for unit address 00 (e.g. indoor point 13 = AV 13, address 1A = AV 6669).
- Each product type is its own BACnet device: indoor units on the Device ID (default 9000), ERV +1, AHU +2, outdoor unit cycle data +3, AWHP +4. The product type bits stay in the object instance.
- LG's examples: address 1 point 1 = 257, address 47 (0x2F) point 1 = 12033, ventilation address 0 point 1 = 65537.
- Points 35-49 work only when 2Set Auto Mode is enabled in the environment settings; the manual adds that PQNFB17C0 does not support them.
- Indoor point 28 (SetLowerTempCommand) is printed as AI; LG's BNU-BAC and AC Smart 5 manuals list it as AV. Check which one the gateway exposes.
- The indoor table leaves the object type of point 16 (MalfunctionCode) blank; the ventilation table gives AI.
- Outdoor unit data is for the master unit only, and some values read 0 on some models. The AHU and AWHP tables in the manual are not included here.
- The manual has no read/write column: access is inferred from the object type and the Setting/Status labels.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
How many BACnet points does the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) have?
This list has 75 BACnet objects: 24 analog inputs, 8 analog values, 17 binary inputs, 10 binary outputs, 2 binary values, 8 multi-state inputs, 6 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet points are writable?
27 of the 75 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet documentation?
LG does not publish it on its own website. This list comes from BACnet Gateway (ACP BACnet) Installation/User Manual (MFL67709501), revision 2014, a copy hosted by SupplyHouse.com at https://s3.amazonaws.com/s3.supplyhouse.com/product_files/LG-PQNFB17C1-Install-Instructions.pdf. Ask LG or its representative for the current revision.
What are the minimum BACnet points to integrate the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)?
Start with BO 1 StartStopCommand_XXX (On/off (address x 256 + 1)); MO 7 ModeCommand_XXX (1 Cool, 2 Dry, 3 Fan, 4 Auto, 5 Heat); MO 11 FanSpeedCommand_XXX (1 Low, 2 Middle, 3 High, 4 Auto); AV 13 SetRoomTemp_XXX (Setpoint); AI 14 RoomTemp_XXX (Room temperature); BI 15 Alarm_XXX (Unit alarm); AI 16 MalfunctionCode_XXX (LG error code).
How do I check these points on the real ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More LG BACnet points lists
- Air handling unit via BACnet IP gateway
LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
LG air handling units wired to the ACP BACnet gateway (RS-485 on its CH5 port) and served on its AHU device.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet AHU, ACP-BAC AHU - Air-to-water heat pump via BACnet IP gateway
LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)
LG air-to-water heat pumps (AWHP) served by the ACP BACnet gateway.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet AWHP, ACP-BAC AWHP, LG air to water heat pump BACnet - VRF indoor unit zone controller (room controller)
LG MultiSITE CRC2+Z Remote Controller (PREMTBVC4)
LG MultiSITE CRC2+Z wall remote controller (PREMTBVC4) for LG VRF and single-zone indoor units, up to 16 indoor units per controller.
Also known as: PREMTBVC4, CRC2, CRC2+Z, MultiSITE CRC2, LG CRC2 remote controller, PREMTBVC3 - Fan coil unit controller (room thermostat)
LG MultiSITE MS8350 Room Controller (fan coil)
LG MultiSITE MS8350 (VUCQMS8350) room controllers for commercial and hotel fan coil units.
Also known as: MS8350, VUCQMS8350, LG MS8350, MultiSITE MS8000 - Rooftop unit controller (room thermostat, rooftop, heat-pump and IAQ)
LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)
LG MultiSITE MS8650 (VUCQMS8650) room controllers for rooftop units, heat pumps and indoor air quality control.
Also known as: MS8650, VUCQMS8650, LG MS8650, MultiSITE MS8000
Source: BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014. Object names, instances and units are reproduced as published; descriptions are our own.