LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet points list

Updated 6 November 2026Unofficial source

Short answer

LG's ACP BACnet controller serves every indoor unit, ventilation unit and outdoor unit on its LG-NET as a fixed block of BACnet IP objects. The instance number is built from the product type, the unit address and the point number, so one table covers every unit: on/off, mode, fan speed, setpoint, room temperature, alarm and error code for indoor units, plus ERV and outdoor unit data.

This page lists 75 BACnet objects for the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of LG’s documentation hosted by SupplyHouse.com, not by LG itself, so treat it as unofficial.

Manufacturer
LG
Model
ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
Equipment
VRF BACnet IP gateway
Equipment type
VRF & split air conditioners
BACnet objects
75 (27 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
9000
Also known as
PQNFB17C0, PQNFB17C1, ACP BACnet, ACP-BAC, LG BACnet gateway, LG VRF BACnet, AC Smart BACnet, PBACNA000, LG Multi V BACnet
Source document
BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (unofficial copy, hosted by SupplyHouse.com)

Instance calculator. This list prints one unit; the other units follow a formula. LG ACP BACnet / AC Smart BACnet instance calculator →

Download CSV 75 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against LG’s current documentation and the live device before use. Not official LG information. Terms of use.

BMS integration notes: LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)

Integration in brief

Set the ACP BACnet's IP and Device ID (default 9000) on its front panel, let it find the units on LG-NET, then map each indoor unit's block at address x 256: on/off, mode, fan speed, setpoint and room temperature first, plus alarm and error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1StartStopCommand_XXXOn/off (address x 256 + 1)Command
MO 7ModeCommand_XXX1 Cool, 2 Dry, 3 Fan, 4 Auto, 5 HeatCommand
MO 11FanSpeedCommand_XXX1 Low, 2 Middle, 3 High, 4 AutoCommand
AV 13SetRoomTemp_XXXSetpointWrite
AI 14RoomTemp_XXXRoom temperatureRead
BI 15Alarm_XXXUnit alarmRead
AI 16MalfunctionCode_XXXLG error codeRead

Network setup

LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

75 of 75 shown
Type
Access
Show
LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet Points List
DescriptionStates
BOmin1StartStopCommand_XXX[Indoor unit] On/off commandCommandInactive=Stop, Active=Start
BI2StartStopStatus_XXX[Indoor unit] On/off statusReadInactive=Stop, Active=Run
BO3LockCommand_XXX[Indoor unit] Remote controller lock commandCommandInactive=Permit, Active=Prohibit
BI4LockStatus_XXX[Indoor unit] Remote controller lock statusReadInactive=Permit, Active=Prohibit
BI5Filter Sign_XXX[Indoor unit] Filter signReadInactive=Off, Active=On
BV6Filter Sign Reset_XXX[Indoor unit] Filter sign resetWriteActive=Reset
MOmin7ModeCommand_XXX[Indoor unit] Operation mode commandCommand1=Cool, 2=Dry, 3=Fan, 4=Auto, 5=Heat
MI8ModeStatus_XXX[Indoor unit] Operation mode statusRead1=Cool, 2=Dry, 3=Fan, 4=Auto, 5=Heat
BO9SwingCommand_XXX[Indoor unit] Swing commandCommandInactive=Stop, Active=Run
BI10SwingStatus_XXX[Indoor unit] Swing statusReadInactive=Stop, Active=Run
MOmin11FanSpeedCommand_XXX[Indoor unit] Fan speed commandCommand1=Low, 2=Middle, 3=High, 4=Auto
MI12FanSpeedStatus_XXX[Indoor unit] Fan speed statusRead1=Low, 2=Middle, 3=High, 4=Auto
AVmin13SetRoomTemp_XXX[Indoor unit] Setpoint (about 18-35 C)°CWrite
AImin14RoomTemp_XXX[Indoor unit] Room temperature°CRead
BImin15Alarm_XXX[Indoor unit] AlarmReadInactive=Normal, Active=Abnormal
AImin16MalfunctionCode_XXX[Indoor unit] LG error code (type left blank in the indoor table)Read
AI19SetTempStatus_XXX[Indoor unit] Setpoint status°CRead
AI20AccumPowerStatus_XXX[Indoor unit] Power distribution (units of 100 W)Read
AV27SetUpperTempCommand_XXX[Indoor unit] Upper setpoint limit command°CWrite
AI28SetLowerTempCommand_XXX[Indoor unit] Lower setpoint limit command (printed as AI)°CWrite
AI29SetUpperTempStatus_XXX[Indoor unit] Upper setpoint limit status°CRead
AI30SetLowerTempStatus_XXX[Indoor unit] Lower setpoint limit status°CRead
BO31ModeLockCommand_XXX[Indoor unit] Mode lock commandCommandInactive=Permit, Active=Prohibit
BI32ModeLockStatus_XXX[Indoor unit] Mode lock statusReadInactive=Permit, Active=Prohibit
BO33Fan LockCommand_XXX[Indoor unit] Fan lock commandCommandInactive=Permit, Active=Prohibit
BI34FanLockStatus_XXX[Indoor unit] Fan lock statusReadInactive=Permit, Active=Prohibit
BO35OccupancyCommand_XXX[Indoor unit] Occupancy command (2Set Auto Mode)CommandInactive=Unoccupied, Active=Occupied
BI36OccupancyStatus_XXX[Indoor unit] Occupancy status (2Set Auto Mode)ReadInactive=Unoccupied, Active=Occupied
AV372SetCoolingTempCommand_XXX[Indoor unit] Dual setpoint: cooling setpoint command°CWrite
AI382SetCoolingTempStatus_XXX[Indoor unit] Dual setpoint: cooling setpoint status°CRead
AV392SetHeatingTempCommand_XXX[Indoor unit] Dual setpoint: heating setpoint command°CWrite
AI402SetHeatingTempStatus_XXX[Indoor unit] Dual setpoint: heating setpoint status°CRead
AV412SetCoolingUpperLimitCommand_XXX[Indoor unit] Dual setpoint: cooling upper limit command°CWrite
AI422SetCoolingUpperLimitStatus_XXX[Indoor unit] Dual setpoint: cooling upper limit status°CRead
AV432SetHeatingUpperLimitCommand_XXX[Indoor unit] Dual setpoint: heating upper limit command°CWrite
AI442SetHeatingUpperLimitStatus_XXX[Indoor unit] Dual setpoint: heating upper limit status°CRead
AV452SetCoolingLowerLimitCommand_XXX[Indoor unit] Dual setpoint: cooling lower limit command°CWrite
AI462SetCoolingLowerLimitStatus_XXX[Indoor unit] Dual setpoint: cooling lower limit status°CRead
AV472SetHeatingLowerLimitCommand_XXX[Indoor unit] Dual setpoint: heating lower limit command°CWrite
AI482SetHeatingLowerLimitStatus_XXX[Indoor unit] Dual setpoint: heating lower limit status°CRead
BI49ThermoStatus_XXX[Indoor unit] Thermo on/off status (2Set Auto Mode)ReadInactive=Off, Active=On
BO65537StartStopCommand_XXX[Ventilation] On/off commandCommandInactive=Stop, Active=Start
BI65538StartStopStatus_XXX[Ventilation] On/off statusReadInactive=Stop, Active=Run
BO65539LockCommand_XXX[Ventilation] Lock commandCommandInactive=Permit, Active=Prohibit
BI65540LockStatus_XXX[Ventilation] Lock statusReadInactive=Permit, Active=Prohibit
BI65541Filter Sign_XXX[Ventilation] Filter signReadInactive=Off, Active=On
BV65542Filter Sign Reset_XXX[Ventilation] Filter sign resetWriteActive=Reset
MO65543ModeCommand_XXX[Ventilation] Operation mode commandCommand1=Heat Exchange, 2=Auto, 3=Normal
MI65544ModeStatus_XXX[Ventilation] Operation mode statusRead1=Heat Exchange, 2=Auto, 3=Normal
MO65547FanSpeedCommand_XXX[Ventilation] Fan speed commandCommand1=Low, 2=High, 3=Super High, 4=Auto
MI65548FanSpeedStatus_XXX[Ventilation] Fan speed statusRead1=Low, 2=High, 3=Super High, 4=Auto
BI65551Alarm_XXX[Ventilation] AlarmReadInactive=Off, Active=On
AI65552MalfunctionCode_XXX[Ventilation] LG error codeRead
MO65553UserModeCommand_XXX[Ventilation] User mode commandCommand1=Quick Fresh, 2=Energy Saving, 3=Heater
MI65554UserModeStatus_XXX[Ventilation] User mode statusRead1=Quick Fresh, 2=Energy Saving, 3=Heater
MO65557HrvModeCommand_XXX[Ventilation] AC operation mode commandCommand1=Cool, 2=Auto, 3=Heat
MI65558HrvModeStatus_XXX[Ventilation] AC operation mode statusRead1=Cool, 2=Auto, 3=Heat
BO65559HrvStartStopCommand_XXX[Ventilation] AC on/off commandCommandInactive=Stop, Active=Run
BI65560HrvStartStopStatus_XXX[Ventilation] AC on/off statusReadInactive=Stop, Active=Run
BO65561HrvHumidifyCommand_XXX[Ventilation] AC humidify commandCommandInactive=Off, Active=On
BI65562HrvHumidifyStatus_XXX[Ventilation] AC humidify statusReadInactive=Off, Active=On
BI196609CompOperStatus _XXX[Outdoor unit] Compressor runningReadInactive=Stop, Active=Run
MI196610RefrigentType_XXX[Outdoor unit] Refrigerant typeRead1=R407C, 2=422 (as printed), 3=R410A
AI196611InverterFanFreq_XXX[Outdoor unit] Inverter fan 1 frequencyRead
AI196612HighPressure_XXX[Outdoor unit] High pressureRead
AI196613LowPressure_XXX[Outdoor unit] Low pressureRead
AI196614SunctionTemp_XXX[Outdoor unit] Suction temperature°CRead
AI196615LiquidPipeTemp_XXX[Outdoor unit] Liquid pipe temperature°CRead
AI196616HexTemp_XXX[Outdoor unit] Heat exchanger temperature°CRead
AI196617OutdoorEEV_XXX[Outdoor unit] Outdoor EEVRead
AI196618SubCoolEEV_XXX[Outdoor unit] Subcool EEVRead
BI196619HotgasValue_XXX[Outdoor unit] Hot gas valveReadInactive=Stop, Active=Run
AI196620InverterDischargeTemp_XXX[Outdoor unit] Inverter discharge temperature°CRead
AI196621OutdoorTemp_XXX[Outdoor unit] Outdoor temperature°CRead
MI196622OperationMode_XXX[Outdoor unit] Outdoor unit operation modeRead1=Stop, 2=Cool, 3=Heat
Object ID lookup: LG ACP BACnet gateway point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)

How many BACnet points does the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) have?

This list has 75 BACnet objects: 24 analog inputs, 8 analog values, 17 binary inputs, 10 binary outputs, 2 binary values, 8 multi-state inputs, 6 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet points are writable?

27 of the 75 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1) BACnet documentation?

LG does not publish it on its own website. This list comes from BACnet Gateway (ACP BACnet) Installation/User Manual (MFL67709501), revision 2014, a copy hosted by SupplyHouse.com at https://s3.amazonaws.com/s3.supplyhouse.com/product_files/LG-PQNFB17C1-Install-Instructions.pdf. Ask LG or its representative for the current revision.

What are the minimum BACnet points to integrate the LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)?

Start with BO 1 StartStopCommand_XXX (On/off (address x 256 + 1)); MO 7 ModeCommand_XXX (1 Cool, 2 Dry, 3 Fan, 4 Auto, 5 Heat); MO 11 FanSpeedCommand_XXX (1 Low, 2 Middle, 3 High, 4 Auto); AV 13 SetRoomTemp_XXX (Setpoint); AI 14 RoomTemp_XXX (Room temperature); BI 15 Alarm_XXX (Unit alarm); AI 16 MalfunctionCode_XXX (LG error code).

How do I check these points on the real ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.