Easy BACnet
  1. Home
  2. BACnet points lists
  3. LG
  4. MultiSITE MS8350 Room Controller (fan coil)

Fan coil unit controller (room thermostat) · BACnet points list

LG MultiSITE MS8350 Room Controller (fan coil) BACnet points list

Updated 4 November 2026

Short answer

The MS8350 is LG's MultiSITE touchscreen room controller for fan coil units. It is a BACnet MS/TP application specific controller (B-ASC) with about 280 objects: room and outdoor temperature, setpoints, system and fan mode, fan and universal outputs, alarms, display and configuration values, Wi-Fi status and paired ZigBee wireless sensor objects.

This page lists 281 BACnet objects for the LG MultiSITE MS8350 Room Controller (fan coil) — 205 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from LG’s own free documentation, linked below.

Manufacturer
LG
Model
MultiSITE MS8350 Room Controller (fan coil)
Equipment
Fan coil unit controller (room thermostat)
Equipment type
VAV boxes & fan coils
BACnet objects
281 (205 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
MS8350, VUCQMS8350, LG MS8350, MultiSITE MS8000
Source document
MultiSITE MS8000 Series Room Controllers BACnet Integration Guide (MS8350 VUCQMS8350, MS8650 VUCQMS8650) · UM_MultiSITE_MS8000_Series_BACnet_Integration_05_20 · rev. 2020-05
Download CSV 281 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against LG’s current documentation and the live device before use. Not official LG information. Terms of use.

BMS integration notes: LG MultiSITE MS8350 Room Controller (fan coil)

Integration in brief

Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy and MV 112 control status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10Occupancy CommandBMS occupancy: local, occupied or unoccupiedCommand
MV 16System ModeOff / auto / cool / heatCommand
MV 17Fan ModeFan mode: on / auto / smartCommand
AV 39Occ. HeatOccupied heating setpointCommand
AV 40Occ. CoolOccupied cooling setpointCommand
MV 112Control StatusCurrent state: off, cooling or heatingCommand
MI 33Effective OccupancyActual occupancy stateRead
AV 100Room TemperatureSpace temperature used for controlCommand
BV 37Service AlarmService alarm from an input set to ServiceCommand

Enable & remote start

The BMS writes MV 10 Occupancy Command (1 = Loc. occ; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 chooses whether local occupancy follows motion or the schedule.

Sensors & values from the BMS

The guide does not describe feeding room temperature from the BMS. MV 145 selects the wired, internal or a paired ZigBee wireless sensor, and MI 312 Effective Temperature Sensor shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.

Network setup

Watch out for

LG MultiSITE MS8350 Room Controller (fan coil) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

281 of 281 shown
Type
Other
Access
Show
LG MultiSITE MS8350 Room Controller (fan coil) BACnet Points List
DescriptionStates
AI2Light Sensor LevelDefault 0; range 0 to 30000Read
AI5UI20 Raw ValueDefault 0; range 0 to 4095Read
AI7UI23 Raw ValueDefault 0; range 0 to 4095Read
AI8UI22 Raw ValueDefault 0; range 0 to 4095Read
AI9UI24 Raw ValueDefault 0; range 0 to 4095Read
AI31UI19 Raw ValueDefault 0; range 0 to 4095Read
AI210Wireless Device 1 - AddressZigBee® Pro; default 0; range -32768 to 32767Read
AI220Wireless Device 2 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI230Wireless Device 3 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI240Wireless Device 4 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI250Wireless Device 5 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI260Wireless Device 6 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI270Wireless Device 7 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI280Wireless Device 8 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI290Wireless Device 9 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI300Wireless Device 10 - AddressZigBee Pro; default 0; range -32768 to 32767Read
AI315Wireless Device 1 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI316Wireless Device 2 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI317Wireless Device 3 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI318Wireless Device 4 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI319Wireless Device 5 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI320Wireless Device 6 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI321Wireless Device 7 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI322Wireless Device 8 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI323Wireless Device 9 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI324Wireless Device 10 - TemperatureDefault 0; range -40°F (-40°C) to 122°F (50°C)°F/°CRead
AI327Remote Relative HumidityDefault 0; range 0 to 100%Read
AI329Effective SetpointDefault 0°F (-18°C); range 40°F (4°C) to 100°F (38°C)°F/°CRead
AI330Paired ZigBee DevicesNumber of paired devices; default 0; range 0 to 11Read
AI342Wi-Fi Network Signal StrengthDefault 0; range 0 to 100%Read
AO21PI Heat DemandDefault 0; range 0 to 100%Command
AO22PI Cool DemandDefault 0; range 0 to 100%Command
AO123UO11 Analog OutputDefault 0; range 0 to 10VCommand
AO124UO12 Analog OutputDefault 0; range 0 to 10VCommand
AO125UO9 Analog OutputDefault 0; range 0 to 10VCommand
AO126UO10 Analog OutputDefault 0; range 0 to 10VCommand
AV2User HMIShow/Hide screen icons; default 0; range 0 to 12Command
AV3Low BacklightDefault 60; range 0 to 100%Command
AV4Night BacklightDefault 5; range 0 to 100%Command
AV5Purge SampleDefault 2; range 0 to 4hCommand
AV6Purge OpenDefault 2; range 1 to 3minCommand
AV7Calibrate TemperatureDefault 0; range -5°F (-20°C) to 5°F (10°C)°F/°CCommand
AV8Calibrate HumidityDefault 0; range -15 to 15%Command
AV10COM AddressCOM address; default 254; range 0 to 254Command
AV16BACnet Stack Poll RateDefault 4; range 1 to 5Command
AV25Param. A (AV25)Default 0; range -32768 to 32767Command
AV26Param. B (AV26)Default 0; range -32768 to 32767Command
AV27Param. C (AV27)Default 0; range -32768 to 32767Command
AV28Param. D (AV28)Default 0; range -32768 to 32767Command
AV29Param. E (AV29)Default 0; range -32768 to 32767Command
AV30Param. F (AV30)Default 0; range -32768 to 32767Command
AVmin39Occ. HeatDefault 72°F (22°C); range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AVmin40Occ. CoolDefault 75°F (24°C); range 54°F (12°C) to 100°F (38°C)°F/°CCommand
AV41Standby HeatDefault 69°F (21°C); range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AV42Standby CoolDefault 78°F (21°C); range 54°F (26°C) to 100°F (38°C)°F/°CCommand
AV43Unocc. HeatDefault 62°F (17°C); range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AV44Unocc. CoolDefault 80°F (27°C); range 54°F (26°C) to 100°F (38°C)°F/°CCommand
AV45Default HeatDefault 72°F (22°C); range 65°F (18°C) to 80°F (27°C)°F/°CCommand
AV46Standby DifferentialDefault 4°F (1.5°C); range 1°F (0.5°C) to 5°F (2.5°C)°F/°CCommand
AV52Number of PipesNumber of pipes; default 2; range 2 to 4Command
AV56Main PasswordInstaller password; default 0; range 0 to 9999Command
AV57User PasswordUser password; default 0; range 0 to 999Command
AV58Heating Setpoint LimitDefault 90°F (32°C); range 40°F (4.5°C) to 90°F (32°C)°F/°CCommand
AV59Cooling Setpoint LimitDefault 54°F (26°C); range 54°F (26°C) to 100°F (38°C)°F/°CCommand
AV62Temp Occ. TimeDefault 2; range 0 to 24hCommand
AV63Minimum DeadbandDefault 3°F (1.5°C); range 2°F (1°C) to 5°F (2.5°C)°F/°CCommand
AV65Proportional BandDefault 3; range 3 to 10Command
AV67Standby TimeDefault 0.5; range 0.5 to 24hCommand
AV68Unoccupied TimeDefault 0.5; range 0.5 to 24hCommand
AV71Dehumidification SetpointDefault 50; range 30 to 95%RHCommand
AV72Dehumidification HysteresisDefault 50; range 30 to 95%RHCommand
AV73Dehumidification Maximum CoolDefault 100; range 20 to 100%Command
AV84CPHDefault 4; range 3 to 8cycles/hCommand
AV88Heating Demand LimitDefault 0; range 0 to 100%Command
AV89Cooling Demand LimitDefault 0; range 0 to 100%Command
AV90Floating TimeDefault 1.5; range .5 to 9minCommand
AV91Heat LockoutDefault 120°F (49°C); range -15°F (-26°C) to 120°F (49°C)°F/°CCommand
AV92Keyboard ValueDefault 0; range 0 to 35Command
AVmin100Room TemperatureDefault 0°F (0°C); range -40°F (-40°C) to 122°F (50°C)°F/°CCommand
AV101Outdoor TemperatureDefault 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)°F/°CCommand
AV102Supply TemperatureDefault 0°F (0°C); range -40°F (-40°C) to 122°F (50°C)°F/°CCommand
AV103Room HumidityDefault 0; range 0 to 100%RHCommand
AV104UI19 Changeover TemperatureDefault 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)°F/°CCommand
AV105UI20 Remote TemperatureDefault 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)°F/°CCommand
AV106CO2 levelDefault 0; range 0 to 5000ppmCommand
AV107Terminal 24, 10 VDefault 0; range 0 to 10VCommand
AV109UI24 TemperatureDefault 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)°F/°CCommand
AV202UI19 LuaDefault 0; range -32768 to 32767Command
AV203UI20 LuaDefault 0; range -32768 to 32767Command
AV204UI22 LuaDefault 0; range -32768 to 32767Command
AV205UI23 LuaDefault 0; range -32768 to 32767Command
AV206UI24 LuaDefault 0; range -32768 to 32767Command
AV209Temperature Alarm ThresholdDefault 40°F; range 32°F to 45°F°FCommand
AV210Temperature Alarm HysteresisDefault 4°F; range 0°F to 100°F°FCommand
AV211Load Shedding OffsetDefault 4°F (2°C); range 4°F (2°C) to 10°F (5.5°C)°F/°CCommand
AV212ECM Fan Low VoltageUnit = Voltage Factor = 0.1; default 22; range 20 to 40Command
AV213ECM Fan Medium VoltageUnit = Voltage Factor = 0.1; default 60; range 41 to 70Command
AV214ECM Fan High VoltageUnit = Voltage Factor = 0.1; default 86; range 71 to 100Command
AV225Param. G (AV225)Default 0; range -32768 to 32767Command
AV226Param. H (AV226)Default 0; range -32768 to 32767Command
AV227Param. I (AV227)Default 0; range -32768 to 32767Command
AV228Param. J (AV228)Default 0; range -32768 to 32767Command
AV229Param. K (AV229)Default 0; range -32768 to 32767Command
AV230Param. L (AV230)Default 0; range -32768 to 32767Command
BI29UI16 Binary InputDefault 0Read0 = Activated, 1 = Not Activated
BI30UI17 Binary InputDefault 0Read0 = Activated, 1 = Not Activated
BI91UI19 Binary InputDefault 0Read0 = Activated, 1 = Not Activated
BI94UI20 Binary InputDefault 0Read0 = Activated, 1 = Not Activated
BI95UI22 Binary InputDefault 0Read0 = Activated, 1 = Not Activated
BI96UI23 Binary InputDefault 0Read0 = Activated, 1 = Not Activated
BI97UI24 Binary InputDefault 0Read0 = Activated, 1 = Not Activated
BO93UO9 Binary OutputDefault 0Command0 = Off, 1 = On
BO94UO10 Binary OutputDefault 0Command0 = Off, 1 = On
BO95BO4 High Speed Fan OutputDefault 0Command0 = Off, 1 = On
BO96BO3 Medium Speed Fan OutputDefault 0Command0 = Off, 1 = On
BO97BO2 Low Speed Fan OutputDefault 0Command0 = Off, 1 = On
BO98BO8 Auxiliary Binary OutputDefault 0Command0 = Off, 1 = On
BO101UO11 Binary OutputDefault 0Command0 = Off, 1 = On
BO102UO12 Binary OutputDefault 0Command0 = Off, 1 = On
BO103BO1Default 0Command0 = Off, 1 = On
BV1Door StatusDefault 0Command0 = Closed, 1 = Open
BV2Door InstalledDefault 0Command0 = No, 1 = Yes
BV3Window StatusDefault 0Command0 = Closed, 1 = Open
BV4Window InstalledDefault 0Command0 = No, 1 = Yes
BV5Low BatteryDefault 0Command0 = Off, 1 = On
BV6Force High BacklightDefault 0Command0 = Off, 1 = On
BV7Long Message DisplayDefault 0Command0 = Off, 1 = On
BV8Clock AlarmDefault 0Command0 = Off, 1 = On
BV10Exception StatusDefault 0Command0 = Off, 1 = On
BV32Local MotionDefault 0Command0 = No Motion, 1 = Motion
BV35Window AlarmDefault 0Command0 = Off, 1 = On
BV36Filter AlarmDefault 0Command0 = Off, 1 = On
BVmin37Service AlarmDefault 0Command0 = Off, 1 = On
BV38Dehumidification StatusDefault 0Command0 = Off, 1 = On
BV40Recovery StatusDefault 0Command0 = Off, 1 = On
BV44Water LeakDefault 0Command0 = Off, 1 = On
BV45Water InstalledDefault 0Command0 = No, 1 = Yes
BV46Water StatusDefault 0Command0 = Normal, 1 = Leak
BV47Low TemperatureDefault 0Command0 = Off, 1 = On
BV48Shed DemandDefault 0Command0 = Closed, 1 = Open
BV49Shed StatusDefault 0Command0 = No, 1 = Yes
BV50Shed OverrideDefault 0Command0 = Closed, 1 = Open
BV200ZigBee PIR StatusDefault 0Command0 = No, 1 = Yes
BV201ZigBee Sensor MotionDefault 0Command0 = No Motion, 1 = Motion
CSV1Short Screen MessageText, length 0 to 64Write
CSV2Long Screen MessageText, length 0 to 480Write
CSV3Ext. Mem. RevisionText, length 0 to 9Write
CSV4Wi-Fi Device NameText, length 0 to 63Write
CSV5Wi-Fi Firmware VersionText, length 0 to 63Write
CSV6MAC AddressText, length 0 to 18Write
CSV7Wi-Fi Network SSIDText, length 0 to 33Write
CSV8Wi-Fi Network IP AddressText, length 0 to 46Write
CSV9ZigBee Firmware RevisionText, length 0 to 32Write
CSV10ZigBee IEEE AddressText, length 0 to 18Write
MI2Network StatusDefault 1Read1 = Not det., 2 = Pwr on, 3 = No NWK, 4 = Joined, 5 = Online
MImin33Effective OccupancyDefault 1Read1 = Occupied, 2 = Unoccupied, 3 = Override, 4 = Standby
MI210Wireless Device 1 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI211Wireless Device 1 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI212Wireless Device 1 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI220Wireless Device 2 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI221Wireless Device 2 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI222Wireless Device 2 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI230Wireless Device 3 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI231Wireless Device 3 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI232Wireless Device 3 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI240Wireless Device 4 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI241Wireless Device 4 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI242Wireless Device 4 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI250Wireless Device 5 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI251Wireless Device 5 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI252Wireless Device 5 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI260Wireless Device 6 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI261Wireless Device 6 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI262Wireless Device 6 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI270Wireless Device 7 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI271Wireless Device 7 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI272Wireless Device 7 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI280Wireless Device 8 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI281Wireless Device 8 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI282Wireless Device 8 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI290Wireless Device 9 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI291Wireless Device 9 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI292Wireless Device 9 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI300Wireless Device 10 - StatusDefault 1Read1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak
MI301Wireless Device 10 - BatteryDefault 1Read1 = None, 2 = Normal, 3 = Low
MI302Wireless Device 10 - Communication StatusDefault 1Read1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline
MI312Effective Temperature SensorDefault 1Read1 = Wired, 2 = Internal, 3 = WL IO, 4 = WL 1, 5 = WL 2, 6 = WL 3, 7 = WL 4, 8 = WL 5, 9 = WL 6, 10 = WL 7, 11 = WL 8, 12 = WL 9, 13 = WL 10, 14 = WL GP
MI313Effective Relative Humidity SensorDefault 1Read1 = None, 2 = Internal, 3 = WL 1, 4 = WL 2, 5 = WL 3, 6 = WL 4, 7 = WL 5, 8 = WL 6, 9 = WL 7, 10 = WL 8, 11 = WL 9, 12 = WL 10, 13 = WL GP
MI314Effective System ModeDefault 1Read1=Cool, 2=Heat
MI315Wi-Fi Module StatusDefault 1Read1 = Offline, 2 = Initializing, 3 = Ready, 4 = Booting, 5 = Resetting, 6 = Fail, 7 = Testing
MI316Wi-Fi StatusDefault 1Read1 = Idle, 2 = Associate, 3 = Config., 4 = Ready, 5 = Online, 6 = Disconn., 7 = Failure
MI317BACnet IP StatusDefault 1Read1 = Disabled, 2 = Enabled
MI318SMTP Server StatusDefault 1Read1 = Unknown, 2 = Disabled, 3 = Offline, 4 = Online
MV1Long Message Background ColorDefault 1Command1 = White, 2 = Green, 3 = Blue, 4 = Grey, 5 = Dark Grey, 6 = Default, 7 = Red
MV2HMI ColorDefault 1Command1 = White, 2 = Green, 3 = Blue, 4 = Grey, 5 = Dark Grey
MV3Main DisplayDefault 1Command1 = Temperature, 2 = Setpoint
MV4Display LanguageDefault 1Command1 = English, 2 = French, 3 = Spanish, 4 = Chinese, 5 = Russian, 6 = Arabic, 7 = Bulgarian, 8 = Czech, 9 = Danish, 10 = Dutch, 11 = Finnish, 12 = German, 13 = Hungarian, 14 = Indonesian, 15 = Italian, 16 = Norwegian, 17 = Polish, 18 = Portuguese, 19 = Slovak, 20 = Swedish, 21 = Turkish, 22 = Japanese, 23 = Hebrew
MV5Time FormatDefault 1Command1 = AM-PM, 2 = 24 Hours
MV6Network UnitsDefault 1Command1 = SI, 2 = Imperial
MV7Network LanguageDefault 1Command1 = English, 2 = French, 3 = Spanish
MV8BACnet Baud RateDefault 7Command1 = 9600, 2 = 19200, 3 = 38400, 4 = 57600, 5 = 76800, 6 = 115200, 7 = Auto
MV9No Active Sleep ModeDefault 1Command1 = Disabled, 2 = Enabled
MVmin10Occupancy CommandDefault 2Command1 = Loc. occ, 2 = Occupied, 3 = Unocc.
MV11Standby Mode ConfigurationDefault 1Command1 = Absolute, 2 = Offset
MV13Dehumidification LockoutDefault 2Command1 = Disabled, 2 = Enabled
MV15Sequence of OperationDefault 2Command1 = Cool only, 2 = Heat only, 3 = Cool-rht, 4 = Heat-rht, 5 = Cool/Heat, 6 = Cl/ht-rht
MVmin16System ModeDefault 4Command1 = Off, 2 = Auto, 3 = Cool, 4 = Heat
MVmin17Fan ModeDefault 2Command1 = On, 2 = Auto, 3 = Smart
MV32Use Standby ScreenDefault 1Command1 = No, 2 = Yes, 3 = Occ. only, 4 = Screen sav
MV46UI16 ConfigurationDefault 1Command1 = None, 2 = Rem NSB, 3 = Motion NO, 4 = Motion NC, 5 = Window
MV47UI17 ConfigurationDefault 1Command1 = None, 2 = Door dry, 3 = Override, 4 =Filter, 5 = Service
MV49UI19 ConfigurationDefault 1Command1 = None, 2 = COC/NH, 3 = COC/NC, 4 = COS
MV50Auto Mode EnableDefault 1Command1 = Disabled, 2 = Enabled
MV51Temperature ScaleDefault 1Command1 = °C, 2 = °F
MV57Fan SequenceDefault 5Command1 = L-M-H, 2 = L-H, 3 = L-M-H-A, 4 =L-H-A, 5 = On-Auto
MV58Setpoint FunctionDefault 2Command1 = Dual SP, 2 = Attach SP
MV66Auto Fan FunctionDefault 1Command1 = AS, 2 = AS/SD
MV70Room Humidity DisplayDefault 1Command1 = Disabled, 2 = Enabled
MV71Enable Smart RecoveryDefault 1Command1 = Off, 2 = On
MV73Schedule MenuDefault 2Command1 = Disabled, 2 = Enabled, 3 = Dis. no. clk., 4 =En. no. clk.
MV81Control TypeDefault 2Command1 = On/Off, 2 = Floating, 3 = Analog
MV91BO8 Aux Out Time BaseDefault 1Command1 = 15 minutes, 2 = 10 seconds
MV92BO8 Aux Output ConfigurationDefault 1Command1 = Reheat, 2 = Aux NO, 3 = Aux NC, 4 = F & NO, 5 = F & NC
MV94ActionDefault 1Command1 = DA, 2 = RA
MV96UO9 ConfigurationDefault 2Command1 = Analog, 2 = Binary, 3 = Relay RC, 4 = Relay RH
MV97UO10 ConfigurationDefault 2Command1 = Analog, 2 = Binary, 3 = Relay RC
MV98UO11 ConfigurationDefault 2Command1 = Analog, 2 = Binary
MV99UO12 ConfigurationDefault 2Command1 = Analog, 2 = Binary
MV101FrenchDefault 2Command1 = Disabled, 2 = Enabled
MV102SpanishDefault 2Command1 = Disabled, 2 = Enabled
MV103ChineseDefault 2Command1 = Disabled, 2 = Enabled
MV104RussianDefault 2Command1 = Disabled, 2 = Enabled
MV110Occupancy SourceDefault 1Command1 = Motion, 2 = Schedule
MV111Mode ButtonDefault 1Command1 = Normal, 2 = Off-Auto
MVmin112Control StatusDefault 1Command1 = Off, 2 = Cool, 3 = Heat
MV114Custom Icon ButtonsDefault 1Command1 = Default, 2 = None, 3 = System mode Heat/Cool, 4 = System mode On/Off, 5 = Fan mode, 6 = Override, 7 = Units, 8 = Help, 9 = Language, 10 = Schedule, 11 = Lighting, 12 = Blind, 13 = Lamp, 14 = Energy, 15 = Make up room, 16 = Setting, 17 = Timer
MV115Custom Behavior ButtonDefault 1Command1 = Default, 2 = No function, 3 = System mode function, 4 = Fan function, 5 = Override, 6 = Schedule, 7 = Units, 8 = Help, 9= Language, 10 = Configuration, 11 = Custom, 12 = Standby
MV120ArabicDefault 1Command1 = Disabled, 2 = Enabled
MV121BulgarianDefault 1Command1 = Disabled
MV122CzechDefault 1Command1 = Disabled, 2 = Enabled
MV123DanishDefault 1Command1 = Disabled, 2 = Enabled
MV124DutchDefault 1Command1 = Disabled, 2 = Enabled
MV125FinnishDefault 1Command1 = Disabled, 2 = Enabled
MV126GermanDefault 1Command1 = Disabled, 2 = Enabled
MV127HungarianDefault 1Command1 = Disabled, 2 = Enabled
MV128IndonesianDefault 1Command1 = Disabled, 2 = Enabled
MV129ItalianDefault 1Command1 = Disabled, 2 = Enabled
MV130NorwegianDefault 1Command1 = Disabled, 2 = Enabled
MV131PolishDefault 1Command1 = Disabled, 2 = Enabled
MV132PortugueseDefault 1Command1 = Disabled, 2 = Enabled
MV133SlovakDefault 1Command1 = Disabled, 2 = Enabled
MV134SwedishDefault 1Command1 = Disabled, 2 = Enabled
MV135TurkishDefault 1Command1 = Disabled, 2 = Enabled
MV136Schedule TypeDefault 1Command1 = 7 days, 2 = 5 + 2 days, 3 = 5 + 1 + 1 days
MV137Schedule EventsDefault 3Command1 = 2/day, 2 = 4/day, 3 = 6/day
MV140UI19 Input TypeDefault 3Command1 = Thermistor, 2 = Binary, 3 = Voltage
MV141UI20 Input TypeDefault 1Command1 = Thermistor, 2 = Binary, 3 = Voltage
MV142UI22 Input TypeDefault 1Command1 = Thermistor, 2 = Binary, 3 = Voltage
MV143UI23 Input TypeDefault 1Command1 = Thermistor, 2 = Binary, 3 = Voltage
MV144UI24 Input TypeDefault 3Command1 = Thermistor, 2 = Binary, 3 = Voltage, 4 = Reserved
MV145Room Temperature SensorDefault 3Command1 = Wired, 2 = Internal, 3 = WL IO, 4 = WL 1, 5 = WL 2, 6 = WL 3, 7 = WL 4, 8 = WL 5, 9 = WL 6, 10 = WL 7, 11 = WL 8, 12 = WL 9, 13 = WL 10, 14 = WL GP
MV146CO2 DisplayDefault 2Command1 = Disabled, 2 = Enabled
MV147CO2 Auto CalibrationDefault 2Command1 = Disabled, 2 = Enabled
MV148Lock ScreenDefault 1Command1 = No, 2 = Yes
MV149Relative Humidity SensorDefault 2Command1 = None, 2 = Internal, 3 = WL 1, 4 = WL 2, 5 = WL 3, 6 = WL 4, 7 = WL 5, 8 = WL 6, 9 = WL 7, 10 = WL 8, 11 = WL 9, 12 = WL 10, 13 = WL GP
MV151Temperature Alarm EnableDefault 1Command1 = Off, 2 = On
MV152ADR PermissionDefault 1Command1 = Off, 2 = On
MV153Wireless Device GP - FunctionDefault 2Command1 = Remove, 2 = None, 3 = T
MV154Fan TypeDefault 1Command1=3 speed, 2=ECM
MV155JapaneseDefault 1Command1 = Disabled, 2=Enabled
MV156HebrewDefault 1Command1 = Disabled, 2=Enabled
MV210Wireless Device 1 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV220Wireless Device 2 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV230Wireless Device 3 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV240Wireless Device 4 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV250Wireless Device 5 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV260Wireless Device 6 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV270Wireless Device 7 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV280Wireless Device 8 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV290Wireless Device 9 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
MV300Wireless Device 10 - FunctionDefault 6Command1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water
Object ID lookup: LG MultiSITE MS8350 Room Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MultiSITE MS8350 Room Controller (fan coil) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the LG MultiSITE MS8350 Room Controller (fan coil)

How many BACnet points does the LG MultiSITE MS8350 Room Controller (fan coil) have?

This list has 281 BACnet objects: 30 analog inputs, 6 analog outputs, 68 analog values, 7 binary inputs, 9 binary outputs, 24 binary values, 39 multi-state inputs, 88 multi-state values, 10 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which LG MultiSITE MS8350 Room Controller (fan coil) BACnet points are writable?

205 of the 281 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official LG MultiSITE MS8350 Room Controller (fan coil) BACnet documentation?

The source is MultiSITE MS8000 Series Room Controllers BACnet Integration Guide (MS8350 VUCQMS8350, MS8650 VUCQMS8650) (UM_MultiSITE_MS8000_Series_BACnet_Integration_05_20), revision 2020-05, published free by LG at https://media.us.lg.com/m/11d3a44fc9cab7aa/original/UM_MultiSITE_MS8000_Series_BACnet_Integration-pdf.pdf.

What are the minimum BACnet points to integrate the LG MultiSITE MS8350 Room Controller (fan coil)?

Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode: on / auto / smart); AV 39 Occ. Heat (Occupied heating setpoint); AV 40 Occ. Cool (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 37 Service Alarm (Service alarm from an input set to Service).

How do I enable BMS control of the LG MultiSITE MS8350 Room Controller (fan coil)?

The BMS writes MV 10 Occupancy Command (1 = Loc. occ; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 chooses whether local occupancy follows motion or the schedule.

Can the BMS supply sensor values to the LG MultiSITE MS8350 Room Controller (fan coil)?

The guide does not describe feeding room temperature from the BMS. MV 145 selects the wired, internal or a paired ZigBee wireless sensor, and MI 312 Effective Temperature Sensor shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.

How do I check these points on the real MultiSITE MS8350 Room Controller (fan coil)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More LG BACnet points lists

Source: MultiSITE MS8000 Series Room Controllers BACnet Integration Guide (MS8350 VUCQMS8350, MS8650 VUCQMS8650) · UM_MultiSITE_MS8000_Series_BACnet_Integration_05_20 · rev. 2020-05. Object names, instances and units are reproduced as published; descriptions are our own.