 "manufacturer": "LG",
 "manufacturer_slug": "lg",
 "model": "MultiSITE MS8350 Room Controller (fan coil)",
 "model_slug": "multisite-ms8350",
 "aliases": [
  "MS8350",
  "VUCQMS8350",
  "LG MS8350",
  "MultiSITE MS8000"
 ],
 "equipment_type": "Fan coil unit controller (room thermostat)",
 "applies_to": "LG MultiSITE MS8350 (VUCQMS8350) room controllers for commercial and hotel fan coil units.",
 "summary": "The MS8350 is LG's MultiSITE touchscreen room controller for fan coil units. It is a BACnet MS/TP application specific controller (B-ASC) with about 280 objects: room and outdoor temperature, setpoints, system and fan mode, fan and universal outputs, alarms, display and configuration values, Wi-Fi status and paired ZigBee wireless sensor objects.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Access follows the guide's object-property tables: AV, AO, BV, BO and MSV present values are commandable, CSVs writable, and AI/MSI present values only writable while Out_Of_Service is TRUE.",
  "The guide gives no description column, only default, range and a units/state column; descriptions here show the printed default and range.",
  "Some object names print the subscript 2 of CO2 out of place (e.g. 'CO level 2'); they are written as CO2 here (AV 106 'CO2 level').",
  "Wireless Device objects only report data for paired ZigBee Pro sensors.",
  "The guide mentions 10 program (PG) objects for LUA4RC scripts but does not list them."
 ],
 "source": {
  "title": "MultiSITE MS8000 Series Room Controllers BACnet Integration Guide (MS8350 VUCQMS8350, MS8650 VUCQMS8650)",
  "doc_number": "UM_MultiSITE_MS8000_Series_BACnet_Integration_05_20",
  "revision_date": "2020-05",
  "url": "https://media.us.lg.com/m/11d3a44fc9cab7aa/original/UM_MultiSITE_MS8000_Series_BACnet_Integration-pdf.pdf"
 },
 "integration": {
  "summary": "Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy and MV 112 control status.",
  "minimum_points": [
   {
    "ref": "MV 10",
    "name": "Occupancy Command",
    "why": "BMS occupancy: local, occupied or unoccupied"
   },
   {
    "ref": "MV 16",
    "name": "System Mode",
    "why": "Off / auto / cool / heat"
   },
   {
    "ref": "MV 17",
    "name": "Fan Mode",
    "why": "Fan mode: on / auto / smart"
   },
   {
    "ref": "AV 39",
    "name": "Occ. Heat",
    "why": "Occupied heating setpoint"
   },
   {
    "ref": "AV 40",
    "name": "Occ. Cool",
    "why": "Occupied cooling setpoint"
   },
   {
    "ref": "MV 112",
    "name": "Control Status",
    "why": "Current state: off, cooling or heating"
   },
   {
    "ref": "MI 33",
    "name": "Effective Occupancy",
    "why": "Actual occupancy state"
   },
   {
    "ref": "AV 100",
    "name": "Room Temperature",
    "why": "Space temperature used for control"
   },
   {
    "ref": "BV 37",
    "name": "Service Alarm",
    "why": "Service alarm from an input set to Service"
   }
  ],
  "enable": "The BMS writes MV 10 Occupancy Command (1 = Loc. occ; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 chooses whether local occupancy follows motion or the schedule.",
  "heartbeat": null,
  "remote_sensors": "The guide does not describe feeding room temperature from the BMS. MV 145 selects the wired, internal or a paired ZigBee wireless sensor, and MI 312 Effective Temperature Sensor shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.",
  "setup": [
   "BACnet MS/TP baud rate is MV 8 (9600, 19200, 38400, 57600, 76800, 115200 or Auto; default Auto). Max_Master is writable, 0-127, default 127.",
   "AV 10 COM Address holds the MS/TP address. Device Object_Identifier and Object_Name are writable; no default device instance is printed.",
   "MI 317 BACnet IP Status shows whether BACnet IP is enabled; separate Wi-Fi objects report the Wi-Fi module state.",
   "The controller is a B-ASC with COV, time synchronization and an internal schedule (SCHED-I-B); it does not support segmented requests or responses."
  ],
  "gotchas": [
   "For the MS8350 the guide says writes at some priority levels go to EEPROM (locked at the controller and kept through a power cycle until released at the same priority or by Restore Factory Default) and others to RAM (lost on a power cycle), but it does not print which priority numbers fall in each group.",
   "On the MS8350 the relinquish default is the value set at the thermostat and it survives power cycles; on the MS8650 the relinquish default of AV 100 and above is read-only.",
   "Keep Read Property Multiple requests small; segmentation is not supported."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 2,
   "name": "Light Sensor Level",
   "description": "Default 0; range 0 to 30000",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "UI20 Raw Value",
   "description": "Default 0; range 0 to 4095",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "UI23 Raw Value",
   "description": "Default 0; range 0 to 4095",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "UI22 Raw Value",
   "description": "Default 0; range 0 to 4095",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "UI24 Raw Value",
   "description": "Default 0; range 0 to 4095",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "UI19 Raw Value",
   "description": "Default 0; range 0 to 4095",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "Wireless Device 1 - Address",
   "description": "ZigBee® Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 220,
   "name": "Wireless Device 2 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 230,
   "name": "Wireless Device 3 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 240,
   "name": "Wireless Device 4 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 250,
   "name": "Wireless Device 5 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 260,
   "name": "Wireless Device 6 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 270,
   "name": "Wireless Device 7 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 280,
   "name": "Wireless Device 8 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 290,
   "name": "Wireless Device 9 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 300,
   "name": "Wireless Device 10 - Address",
   "description": "ZigBee Pro; default 0; range -32768 to 32767",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 315,
   "name": "Wireless Device 1 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 316,
   "name": "Wireless Device 2 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 317,
   "name": "Wireless Device 3 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 318,
   "name": "Wireless Device 4 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 319,
   "name": "Wireless Device 5 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 320,
   "name": "Wireless Device 6 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 321,
   "name": "Wireless Device 7 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 322,
   "name": "Wireless Device 8 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 323,
   "name": "Wireless Device 9 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 324,
   "name": "Wireless Device 10 - Temperature",
   "description": "Default 0; range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 327,
   "name": "Remote Relative Humidity",
   "description": "Default 0; range 0 to 100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 329,
   "name": "Effective Setpoint",
   "description": "Default 0°F (-18°C); range 40°F (4°C) to 100°F (38°C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 330,
   "name": "Paired ZigBee Devices",
   "description": "Number of paired devices; default 0; range 0 to 11",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 342,
   "name": "Wi-Fi Network Signal Strength",
   "description": "Default 0; range 0 to 100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 21,
   "name": "PI Heat Demand",
   "description": "Default 0; range 0 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 22,
   "name": "PI Cool Demand",
   "description": "Default 0; range 0 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 123,
   "name": "UO11 Analog Output",
   "description": "Default 0; range 0 to 10",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 124,
   "name": "UO12 Analog Output",
   "description": "Default 0; range 0 to 10",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 125,
   "name": "UO9 Analog Output",
   "description": "Default 0; range 0 to 10",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 126,
   "name": "UO10 Analog Output",
   "description": "Default 0; range 0 to 10",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "User HMI",
   "description": "Show/Hide screen icons; default 0; range 0 to 12",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Low Backlight",
   "description": "Default 60; range 0 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Night Backlight",
   "description": "Default 5; range 0 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Purge Sample",
   "description": "Default 2; range 0 to 4",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Purge Open",
   "description": "Default 2; range 1 to 3",
   "units": "min",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Calibrate Temperature",
   "description": "Default 0; range -5°F (-20°C) to 5°F (10°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Calibrate Humidity",
   "description": "Default 0; range -15 to 15",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "COM Address",
   "description": "COM address; default 254; range 0 to 254",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "BACnet Stack Poll Rate",
   "description": "Default 4; range 1 to 5",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Param. A (AV25)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Param. B (AV26)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Param. C (AV27)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Param. D (AV28)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Param. E (AV29)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Param. F (AV30)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "Occ. Heat",
   "description": "Default 72°F (22°C); range 40°F (4.5°C) to 90°F (32°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "Occ. Cool",
   "description": "Default 75°F (24°C); range 54°F (12°C) to 100°F (38°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "Standby Heat",
   "description": "Default 69°F (21°C); range 40°F (4.5°C) to 90°F (32°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Standby Cool",
   "description": "Default 78°F (21°C); range 54°F (26°C) to 100°F (38°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Unocc. Heat",
   "description": "Default 62°F (17°C); range 40°F (4.5°C) to 90°F (32°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Unocc. Cool",
   "description": "Default 80°F (27°C); range 54°F (26°C) to 100°F (38°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "Default Heat",
   "description": "Default 72°F (22°C); range 65°F (18°C) to 80°F (27°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Standby Differential",
   "description": "Default 4°F (1.5°C); range 1°F (0.5°C) to 5°F (2.5°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Number of Pipes",
   "description": "Number of pipes; default 2; range 2 to 4",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "Main Password",
   "description": "Installer password; default 0; range 0 to 9999",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "User Password",
   "description": "User password; default 0; range 0 to 999",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Heating Setpoint Limit",
   "description": "Default 90°F (32°C); range 40°F (4.5°C) to 90°F (32°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Cooling Setpoint Limit",
   "description": "Default 54°F (26°C); range 54°F (26°C) to 100°F (38°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Temp Occ. Time",
   "description": "Default 2; range 0 to 24",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Minimum Deadband",
   "description": "Default 3°F (1.5°C); range 2°F (1°C) to 5°F (2.5°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Proportional Band",
   "description": "Default 3; range 3 to 10",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Standby Time",
   "description": "Default 0.5; range 0.5 to 24",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "Unoccupied Time",
   "description": "Default 0.5; range 0.5 to 24",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Dehumidification Setpoint",
   "description": "Default 50; range 30 to 95",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Dehumidification Hysteresis",
   "description": "Default 50; range 30 to 95",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "Dehumidification Maximum Cool",
   "description": "Default 100; range 20 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "CPH",
   "description": "Default 4; range 3 to 8",
   "units": "cycles/h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "Heating Demand Limit",
   "description": "Default 0; range 0 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "Cooling Demand Limit",
   "description": "Default 0; range 0 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "Floating Time",
   "description": "Default 1.5; range .5 to 9",
   "units": "min",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "Heat Lockout",
   "description": "Default 120°F (49°C); range -15°F (-26°C) to 120°F (49°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "Keyboard Value",
   "description": "Default 0; range 0 to 35",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "Room Temperature",
   "description": "Default 0°F (0°C); range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "Outdoor Temperature",
   "description": "Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "Supply Temperature",
   "description": "Default 0°F (0°C); range -40°F (-40°C) to 122°F (50°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "Room Humidity",
   "description": "Default 0; range 0 to 100",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "UI19 Changeover Temperature",
   "description": "Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "UI20 Remote Temperature",
   "description": "Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "CO2 level",
   "description": "Default 0; range 0 to 5000",
   "units": "ppm",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "Terminal 24, 10 V",
   "description": "Default 0; range 0 to 10",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "UI24 Temperature",
   "description": "Default 0°F (0°C); range -40°F (-40°C) to 150°F (65.5°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "UI19 Lua",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "UI20 Lua",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 204,
   "name": "UI22 Lua",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 205,
   "name": "UI23 Lua",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 206,
   "name": "UI24 Lua",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 209,
   "name": "Temperature Alarm Threshold",
   "description": "Default 40°F; range 32°F to 45°F",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 210,
   "name": "Temperature Alarm Hysteresis",
   "description": "Default 4°F; range 0°F to 100°F",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "Load Shedding Offset",
   "description": "Default 4°F (2°C); range 4°F (2°C) to 10°F (5.5°C)",
   "units": "°F/°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "ECM Fan Low Voltage",
   "description": "Unit = Voltage Factor = 0.1; default 22; range 20 to 40",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "ECM Fan Medium Voltage",
   "description": "Unit = Voltage Factor = 0.1; default 60; range 41 to 70",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 214,
   "name": "ECM Fan High Voltage",
   "description": "Unit = Voltage Factor = 0.1; default 86; range 71 to 100",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 225,
   "name": "Param. G (AV225)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 226,
   "name": "Param. H (AV226)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "Param. I (AV227)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 228,
   "name": "Param. J (AV228)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 229,
   "name": "Param. K (AV229)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "Param. L (AV230)",
   "description": "Default 0; range -32768 to 32767",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "UI16 Binary Input",
   "description": "Default 0",
   "units": "",
   "access": "R",
   "states": "0 = Activated, 1 = Not Activated"
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "UI17 Binary Input",
   "description": "Default 0",
   "units": "",
   "access": "R",
   "states": "0 = Activated, 1 = Not Activated"
  },
  {
   "type": "BI",
   "instance": 91,
   "name": "UI19 Binary Input",
   "description": "Default 0",
   "units": "",
   "access": "R",
   "states": "0 = Activated, 1 = Not Activated"
  },
  {
   "type": "BI",
   "instance": 94,
   "name": "UI20 Binary Input",
   "description": "Default 0",
   "units": "",
   "access": "R",
   "states": "0 = Activated, 1 = Not Activated"
  },
  {
   "type": "BI",
   "instance": 95,
   "name": "UI22 Binary Input",
   "description": "Default 0",
   "units": "",
   "access": "R",
   "states": "0 = Activated, 1 = Not Activated"
  },
  {
   "type": "BI",
   "instance": 96,
   "name": "UI23 Binary Input",
   "description": "Default 0",
   "units": "",
   "access": "R",
   "states": "0 = Activated, 1 = Not Activated"
  },
  {
   "type": "BI",
   "instance": 97,
   "name": "UI24 Binary Input",
   "description": "Default 0",
   "units": "",
   "access": "R",
   "states": "0 = Activated, 1 = Not Activated"
  },
  {
   "type": "BO",
   "instance": 93,
   "name": "UO9 Binary Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 94,
   "name": "UO10 Binary Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 95,
   "name": "BO4 High Speed Fan Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 96,
   "name": "BO3 Medium Speed Fan Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 97,
   "name": "BO2 Low Speed Fan Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 98,
   "name": "BO8 Auxiliary Binary Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 101,
   "name": "UO11 Binary Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 102,
   "name": "UO12 Binary Output",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BO",
   "instance": 103,
   "name": "BO1",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Door Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Closed, 1 = Open"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Door Installed",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = No, 1 = Yes"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Window Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Closed, 1 = Open"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Window Installed",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = No, 1 = Yes"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Low Battery",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "Force High Backlight",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Long Message Display",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "Clock Alarm",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "Exception Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "Local Motion",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = No Motion, 1 = Motion"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "Window Alarm",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "Filter Alarm",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "Service Alarm",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "Dehumidification Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "Recovery Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "Water Leak",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "Water Installed",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = No, 1 = Yes"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "Water Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Normal, 1 = Leak"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "Low Temperature",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "Shed Demand",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Closed, 1 = Open"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "Shed Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = No, 1 = Yes"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "Shed Override",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = Closed, 1 = Open"
  },
  {
   "type": "BV",
   "instance": 200,
   "name": "ZigBee PIR Status",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = No, 1 = Yes"
  },
  {
   "type": "BV",
   "instance": 201,
   "name": "ZigBee Sensor Motion",
   "description": "Default 0",
   "units": "",
   "access": "C",
   "states": "0 = No Motion, 1 = Motion"
  },
  {
   "type": "CSV",
   "instance": 1,
   "name": "Short Screen Message",
   "description": "Text, length 0 to 64",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 2,
   "name": "Long Screen Message",
   "description": "Text, length 0 to 480",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 3,
   "name": "Ext. Mem. Revision",
   "description": "Text, length 0 to 9",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 4,
   "name": "Wi-Fi Device Name",
   "description": "Text, length 0 to 63",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 5,
   "name": "Wi-Fi Firmware Version",
   "description": "Text, length 0 to 63",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 6,
   "name": "MAC Address",
   "description": "Text, length 0 to 18",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 7,
   "name": "Wi-Fi Network SSID",
   "description": "Text, length 0 to 33",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 8,
   "name": "Wi-Fi Network IP Address",
   "description": "Text, length 0 to 46",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 9,
   "name": "ZigBee Firmware Revision",
   "description": "Text, length 0 to 32",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 10,
   "name": "ZigBee IEEE Address",
   "description": "Text, length 0 to 18",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Network Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not det., 2 = Pwr on, 3 = No NWK, 4 = Joined, 5 = Online"
  },
  {
   "type": "MI",
   "instance": 33,
   "name": "Effective Occupancy",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Occupied, 2 = Unoccupied, 3 = Override, 4 = Standby"
  },
  {
   "type": "MI",
   "instance": 210,
   "name": "Wireless Device 1 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 211,
   "name": "Wireless Device 1 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 212,
   "name": "Wireless Device 1 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 220,
   "name": "Wireless Device 2 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 221,
   "name": "Wireless Device 2 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 222,
   "name": "Wireless Device 2 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 230,
   "name": "Wireless Device 3 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 231,
   "name": "Wireless Device 3 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 232,
   "name": "Wireless Device 3 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 240,
   "name": "Wireless Device 4 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 241,
   "name": "Wireless Device 4 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 242,
   "name": "Wireless Device 4 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 250,
   "name": "Wireless Device 5 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 251,
   "name": "Wireless Device 5 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 252,
   "name": "Wireless Device 5 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 260,
   "name": "Wireless Device 6 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 261,
   "name": "Wireless Device 6 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 262,
   "name": "Wireless Device 6 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 270,
   "name": "Wireless Device 7 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 271,
   "name": "Wireless Device 7 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 272,
   "name": "Wireless Device 7 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 280,
   "name": "Wireless Device 8 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 281,
   "name": "Wireless Device 8 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 282,
   "name": "Wireless Device 8 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 290,
   "name": "Wireless Device 9 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 291,
   "name": "Wireless Device 9 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 292,
   "name": "Wireless Device 9 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 300,
   "name": "Wireless Device 10 - Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Closed, 3 = Opened, 4 = No Motion, 5 = Motion, 6 = Normal, 7 = Leak"
  },
  {
   "type": "MI",
   "instance": 301,
   "name": "Wireless Device 10 - Battery",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Normal, 3 = Low"
  },
  {
   "type": "MI",
   "instance": 302,
   "name": "Wireless Device 10 - Communication Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Not Paired, 2 = Online, 3 = Invalid, 4 = Offline"
  },
  {
   "type": "MI",
   "instance": 312,
   "name": "Effective Temperature Sensor",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Wired, 2 = Internal, 3 = WL IO, 4 = WL 1, 5 = WL 2, 6 = WL 3, 7 = WL 4, 8 = WL 5, 9 = WL 6, 10 = WL 7, 11 = WL 8, 12 = WL 9, 13 = WL 10, 14 = WL GP"
  },
  {
   "type": "MI",
   "instance": 313,
   "name": "Effective Relative Humidity Sensor",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = None, 2 = Internal, 3 = WL 1, 4 = WL 2, 5 = WL 3, 6 = WL 4, 7 = WL 5, 8 = WL 6, 9 = WL 7, 10 = WL 8, 11 = WL 9, 12 = WL 10, 13 = WL GP"
  },
  {
   "type": "MI",
   "instance": 314,
   "name": "Effective System Mode",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1=Cool, 2=Heat"
  },
  {
   "type": "MI",
   "instance": 315,
   "name": "Wi-Fi Module Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Offline, 2 = Initializing, 3 = Ready, 4 = Booting, 5 = Resetting, 6 = Fail, 7 = Testing"
  },
  {
   "type": "MI",
   "instance": 316,
   "name": "Wi-Fi Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Idle, 2 = Associate, 3 = Config., 4 = Ready, 5 = Online, 6 = Disconn., 7 = Failure"
  },
  {
   "type": "MI",
   "instance": 317,
   "name": "BACnet IP Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MI",
   "instance": 318,
   "name": "SMTP Server Status",
   "description": "Default 1",
   "units": "",
   "access": "R",
   "states": "1 = Unknown, 2 = Disabled, 3 = Offline, 4 = Online"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Long Message Background Color",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = White, 2 = Green, 3 = Blue, 4 = Grey, 5 = Dark Grey, 6 = Default, 7 = Red"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "HMI Color",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = White, 2 = Green, 3 = Blue, 4 = Grey, 5 = Dark Grey"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Main Display",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Temperature, 2 = Setpoint"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Display Language",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = English, 2 = French, 3 = Spanish, 4 = Chinese, 5 = Russian, 6 = Arabic, 7 = Bulgarian, 8 = Czech, 9 = Danish, 10 = Dutch, 11 = Finnish, 12 = German, 13 = Hungarian, 14 = Indonesian, 15 = Italian, 16 = Norwegian, 17 = Polish, 18 = Portuguese, 19 = Slovak, 20 = Swedish, 21 = Turkish, 22 = Japanese, 23 = Hebrew"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Time Format",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = AM-PM, 2 = 24 Hours"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "Network Units",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = SI, 2 = Imperial"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "Network Language",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = English, 2 = French, 3 = Spanish"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "BACnet Baud Rate",
   "description": "Default 7",
   "units": "",
   "access": "C",
   "states": "1 = 9600, 2 = 19200, 3 = 38400, 4 = 57600, 5 = 76800, 6 = 115200, 7 = Auto"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "No Active Sleep Mode",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "Occupancy Command",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Loc. occ, 2 = Occupied, 3 = Unocc."
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "Standby Mode Configuration",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Absolute, 2 = Offset"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "Dehumidification Lockout",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "Sequence of Operation",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Cool only, 2 = Heat only, 3 = Cool-rht, 4 = Heat-rht, 5 = Cool/Heat, 6 = Cl/ht-rht"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "System Mode",
   "description": "Default 4",
   "units": "",
   "access": "C",
   "states": "1 = Off, 2 = Auto, 3 = Cool, 4 = Heat"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "Fan Mode",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = On, 2 = Auto, 3 = Smart"
  },
  {
   "type": "MV",
   "instance": 32,
   "name": "Use Standby Screen",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = No, 2 = Yes, 3 = Occ. only, 4 = Screen sav"
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "UI16 Configuration",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Rem NSB, 3 = Motion NO, 4 = Motion NC, 5 = Window"
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "UI17 Configuration",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Door dry, 3 = Override, 4 =Filter, 5 = Service"
  },
  {
   "type": "MV",
   "instance": 49,
   "name": "UI19 Configuration",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = COC/NH, 3 = COC/NC, 4 = COS"
  },
  {
   "type": "MV",
   "instance": 50,
   "name": "Auto Mode Enable",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 51,
   "name": "Temperature Scale",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = °C, 2 = °F"
  },
  {
   "type": "MV",
   "instance": 57,
   "name": "Fan Sequence",
   "description": "Default 5",
   "units": "",
   "access": "C",
   "states": "1 = L-M-H, 2 = L-H, 3 = L-M-H-A, 4 =L-H-A, 5 = On-Auto"
  },
  {
   "type": "MV",
   "instance": 58,
   "name": "Setpoint Function",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Dual SP, 2 = Attach SP"
  },
  {
   "type": "MV",
   "instance": 66,
   "name": "Auto Fan Function",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = AS, 2 = AS/SD"
  },
  {
   "type": "MV",
   "instance": 70,
   "name": "Room Humidity Display",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "Enable Smart Recovery",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Off, 2 = On"
  },
  {
   "type": "MV",
   "instance": 73,
   "name": "Schedule Menu",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled, 3 = Dis. no. clk., 4 =En. no. clk."
  },
  {
   "type": "MV",
   "instance": 81,
   "name": "Control Type",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = On/Off, 2 = Floating, 3 = Analog"
  },
  {
   "type": "MV",
   "instance": 91,
   "name": "BO8 Aux Out Time Base",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = 15 minutes, 2 = 10 seconds"
  },
  {
   "type": "MV",
   "instance": 92,
   "name": "BO8 Aux Output Configuration",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Reheat, 2 = Aux NO, 3 = Aux NC, 4 = F & NO, 5 = F & NC"
  },
  {
   "type": "MV",
   "instance": 94,
   "name": "Action",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = DA, 2 = RA"
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "UO9 Configuration",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Analog, 2 = Binary, 3 = Relay RC, 4 = Relay RH"
  },
  {
   "type": "MV",
   "instance": 97,
   "name": "UO10 Configuration",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Analog, 2 = Binary, 3 = Relay RC"
  },
  {
   "type": "MV",
   "instance": 98,
   "name": "UO11 Configuration",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Analog, 2 = Binary"
  },
  {
   "type": "MV",
   "instance": 99,
   "name": "UO12 Configuration",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Analog, 2 = Binary"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "French",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "Spanish",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 103,
   "name": "Chinese",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 104,
   "name": "Russian",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 110,
   "name": "Occupancy Source",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Motion, 2 = Schedule"
  },
  {
   "type": "MV",
   "instance": 111,
   "name": "Mode Button",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Normal, 2 = Off-Auto"
  },
  {
   "type": "MV",
   "instance": 112,
   "name": "Control Status",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Off, 2 = Cool, 3 = Heat"
  },
  {
   "type": "MV",
   "instance": 114,
   "name": "Custom Icon Buttons",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Default, 2 = None, 3 = System mode Heat/Cool, 4 = System mode On/Off, 5 = Fan mode, 6 = Override, 7 = Units, 8 = Help, 9 = Language, 10 = Schedule, 11 = Lighting, 12 = Blind, 13 = Lamp, 14 = Energy, 15 = Make up room, 16 = Setting, 17 = Timer"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "Custom Behavior Button",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Default, 2 = No function, 3 = System mode function, 4 = Fan function, 5 = Override, 6 = Schedule, 7 = Units, 8 = Help, 9= Language, 10 = Configuration, 11 = Custom, 12 = Standby"
  },
  {
   "type": "MV",
   "instance": 120,
   "name": "Arabic",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 121,
   "name": "Bulgarian",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled"
  },
  {
   "type": "MV",
   "instance": 122,
   "name": "Czech",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 123,
   "name": "Danish",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 124,
   "name": "Dutch",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 125,
   "name": "Finnish",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 126,
   "name": "German",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 127,
   "name": "Hungarian",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 128,
   "name": "Indonesian",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 129,
   "name": "Italian",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 130,
   "name": "Norwegian",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 131,
   "name": "Polish",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 132,
   "name": "Portuguese",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 133,
   "name": "Slovak",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 134,
   "name": "Swedish",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 135,
   "name": "Turkish",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 136,
   "name": "Schedule Type",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = 7 days, 2 = 5 + 2 days, 3 = 5 + 1 + 1 days"
  },
  {
   "type": "MV",
   "instance": 137,
   "name": "Schedule Events",
   "description": "Default 3",
   "units": "",
   "access": "C",
   "states": "1 = 2/day, 2 = 4/day, 3 = 6/day"
  },
  {
   "type": "MV",
   "instance": 140,
   "name": "UI19 Input Type",
   "description": "Default 3",
   "units": "",
   "access": "C",
   "states": "1 = Thermistor, 2 = Binary, 3 = Voltage"
  },
  {
   "type": "MV",
   "instance": 141,
   "name": "UI20 Input Type",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Thermistor, 2 = Binary, 3 = Voltage"
  },
  {
   "type": "MV",
   "instance": 142,
   "name": "UI22 Input Type",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Thermistor, 2 = Binary, 3 = Voltage"
  },
  {
   "type": "MV",
   "instance": 143,
   "name": "UI23 Input Type",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Thermistor, 2 = Binary, 3 = Voltage"
  },
  {
   "type": "MV",
   "instance": 144,
   "name": "UI24 Input Type",
   "description": "Default 3",
   "units": "",
   "access": "C",
   "states": "1 = Thermistor, 2 = Binary, 3 = Voltage, 4 = Reserved"
  },
  {
   "type": "MV",
   "instance": 145,
   "name": "Room Temperature Sensor",
   "description": "Default 3",
   "units": "",
   "access": "C",
   "states": "1 = Wired, 2 = Internal, 3 = WL IO, 4 = WL 1, 5 = WL 2, 6 = WL 3, 7 = WL 4, 8 = WL 5, 9 = WL 6, 10 = WL 7, 11 = WL 8, 12 = WL 9, 13 = WL 10, 14 = WL GP"
  },
  {
   "type": "MV",
   "instance": 146,
   "name": "CO2 Display",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 147,
   "name": "CO2 Auto Calibration",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2 = Enabled"
  },
  {
   "type": "MV",
   "instance": 148,
   "name": "Lock Screen",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = No, 2 = Yes"
  },
  {
   "type": "MV",
   "instance": 149,
   "name": "Relative Humidity Sensor",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Internal, 3 = WL 1, 4 = WL 2, 5 = WL 3, 6 = WL 4, 7 = WL 5, 8 = WL 6, 9 = WL 7, 10 = WL 8, 11 = WL 9, 12 = WL 10, 13 = WL GP"
  },
  {
   "type": "MV",
   "instance": 151,
   "name": "Temperature Alarm Enable",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Off, 2 = On"
  },
  {
   "type": "MV",
   "instance": 152,
   "name": "ADR Permission",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Off, 2 = On"
  },
  {
   "type": "MV",
   "instance": 153,
   "name": "Wireless Device GP - Function",
   "description": "Default 2",
   "units": "",
   "access": "C",
   "states": "1 = Remove, 2 = None, 3 = T"
  },
  {
   "type": "MV",
   "instance": 154,
   "name": "Fan Type",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1=3 speed, 2=ECM"
  },
  {
   "type": "MV",
   "instance": 155,
   "name": "Japanese",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2=Enabled"
  },
  {
   "type": "MV",
   "instance": 156,
   "name": "Hebrew",
   "description": "Default 1",
   "units": "",
   "access": "C",
   "states": "1 = Disabled, 2=Enabled"
  },
  {
   "type": "MV",
   "instance": 210,
   "name": "Wireless Device 1 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 220,
   "name": "Wireless Device 2 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 230,
   "name": "Wireless Device 3 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 240,
   "name": "Wireless Device 4 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 250,
   "name": "Wireless Device 5 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 260,
   "name": "Wireless Device 6 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 270,
   "name": "Wireless Device 7 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 280,
   "name": "Wireless Device 8 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 290,
   "name": "Wireless Device 9 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  },
  {
   "type": "MV",
   "instance": 300,
   "name": "Wireless Device 10 - Function",
   "description": "Default 6",
   "units": "",
   "access": "C",
   "states": "1 = None, 2 = Window, 3 = Door, 4 = Motion, 5 = Status, 6 = Remove, 7 = Water"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/lg/multisite-ms8350",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}