- Home
- BACnet points lists
- LG
- ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
Air handling unit via BACnet IP gateway · BACnet points list
LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet points list
Updated 7 November 2026Unofficial source
The ACP BACnet gateway serves each LG AHU on its LG-NET as a fixed block of 53 BACnet IP objects on the gateway's AHU device (Device ID + 2). Besides on/off, mode, setpoint and alarm, the AHU block carries humidity control, supply, outdoor and mixed air readings, CO2, fan and heater status and per-mode damper positions. The same manual's indoor, ventilation and outdoor tables are in the separate ACP BACnet entry.
This page lists 53 BACnet objects for the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of LG’s documentation hosted by SupplyHouse.com, not by LG itself, so treat it as unofficial.
- Manufacturer
- LG
- Model
- ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
- Equipment
- Air handling unit via BACnet IP gateway
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 53 (18 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 9002
- Also known as
- PQNFB17C0, PQNFB17C1, ACP BACnet AHU, ACP-BAC AHU
- Source document
- BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (copyright date) (unofficial copy, hosted by SupplyHouse.com)
Reference only, provided as-is: verify against LG’s current documentation and the live device before use. Not official LG information. Terms of use.
BMS integration notes: LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
Give the ACP BACnet an IP address and Device ID, let it find the AHU on LG-NET, then read the AHU device (Device ID + 2) at 131072 + address x 256. Map on/off, mode and setpoint, then room, supply and outdoor readings and the alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 131073 | StartStopCommand_XXX | On/off (131073 + AHU address x 256) | Command |
| MO 131079 | ModeCommand_XXX | 1 Cool, 2 Dry, 3 Fan, 4 Heat | Command |
| AV 131085 | SetRoomTemp_XXX | Room temperature setpoint | Write |
| BI 131074 | StartStopStatus_XXX | Running status | Read |
| AI 131086 | RoomTemp_XXX | Room temperature | Read |
| AI 131100 | SupplyTempStatus_XXX | Supply air temperature | Read |
| BI 131087 | Alarm_XXX | Unit alarm | Read |
| AI 131088 | MalfunctionCode_XXX | LG error code | Read |
Network setup
- Default Device ID 9000; the AHU device is Device ID + 2.
- Device ID and network settings are set from the ACP's front-panel menu.
- Wire the AHU RS-485 line to CH5 on the ACP BACnet (indoor-unit lines use CH1-CH4).
Watch out for
- The on/off command is sent to the unit whatever its current state.
- Mode commands are ignored by a unit that does not hold the mode-select right.
LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 131073 | StartStopCommand_XXX | [AHU] On/off command | Command | Inactive=Stop, Active=Run | |
| BImin | 131074 | StartStopStatus_XXX | [AHU] On/off status | Read | Inactive=Stop, Active=Run | |
| BO | 131075 | LockCommand_XXX | [AHU] Remote controller lock command | Command | Inactive=Permit, Active=Prohibit | |
| BI | 131076 | LockStatus_XXX | [AHU] Remote controller lock status | Read | Inactive=Permit, Active=Prohibit | |
| BI | 131077 | Filter Sign_XXX | [AHU] Filter sign | Read | Inactive=Off, Active=On | |
| BV | 131078 | Filter Sign Reset_XXX | [AHU] Filter sign reset | Write | Active=Reset | |
| MOmin | 131079 | ModeCommand_XXX | [AHU] Operation mode command | Command | 1=Cool, 2=Dry, 3=Fan, 4=Heat | |
| MI | 131080 | ModeStatus_XXX | [AHU] Operation mode status | Read | 1=Cool, 2=Dry, 3=Fan, 4=Heat | |
| AVmin | 131085 | SetRoomTemp_XXX | [AHU] Room temperature setpoint | °C | Write | |
| AImin | 131086 | RoomTemp_XXX | [AHU] Room temperature | °C | Read | |
| BImin | 131087 | Alarm_XXX | [AHU] Alarm | Read | Inactive=Normal, Active=Abnormal | |
| AImin | 131088 | MalfunctionCode_XXX | [AHU] LG error code | Read | ||
| AI | 131091 | SetTempStatus_XXX | [AHU] Setpoint status | °C | Read | |
| BO | 131092 | EmergencySensorCommand_XXX | [AHU] Emergency sensor command | Command | Inactive=Stop, Active=Run | |
| BI | 131093 | EmergencySensorStatus_XXX | [AHU] Emergency sensor status | Read | Inactive=Stop, Active=Run | |
| AV | 131094 | SetHumidifyCommand_XXX | [AHU] Humidity setpoint command, 40-60 | Write | ||
| AI | 131095 | SetHumidifyStatus_XXX | [AHU] Humidity setpoint status, 40-60 | Read | ||
| BO | 131096 | HumidifyCommand_XXX | [AHU] Humidify on/off command | Command | Inactive=Stop, Active=Run | |
| BI | 131097 | HumidifyStatus_XXX | [AHU] Humidify on/off status | Read | Inactive=Stop, Active=Run | |
| BO | 131098 | AutoVentilCommand_XXX | [AHU] Auto ventilation command | Command | Inactive=Stop, Active=Run | |
| BI | 131099 | AutoVentilStatus_XXX | [AHU] Auto ventilation status | Read | Inactive=Stop, Active=Run | |
| AImin | 131100 | SupplyTempStatus_XXX | [AHU] Supply air temperature, -127 to 127 | Read | ||
| AI | 131101 | OutdoorTempStatus_XXX | [AHU] Outdoor air temperature, -127 to 127 | Read | ||
| AI | 131102 | MixTempStatus_XXX | [AHU] Mixed air temperature, -127 to 127 | Read | ||
| AI | 131103 | SuppyHumidifyStatus_XXX | [AHU] Supply air humidity, 30-90 | Read | ||
| AI | 131104 | OutdoorHumidifyStatus_XXX | [AHU] Outdoor air humidity, 30-90 | Read | ||
| AI | 131105 | VentilHumidifyStatus_XXX | [AHU] Ventilation (return) humidity, 30-90 | Read | ||
| AI | 131106 | CO2ValueStatus_XXX | [AHU] CO2, 0-255; value x 10 = ppm | Read | ||
| BI | 131107 | HumidifyUnitStatus_XXX | [AHU] Humidifier running | Read | Inactive=Stop, Active=Run | |
| BI | 131108 | HeaterUnitStatus_XXX | [AHU] Heater running | Read | Inactive=Stop, Active=Run | |
| BI | 131109 | VentilFANStatus_XXX | [AHU] Ventilation (exhaust) fan running | Read | Inactive=Stop, Active=Run | |
| BI | 131110 | SupplyFANStatus_XXX | [AHU] Supply fan running | Read | Inactive=Stop, Active=Run | |
| AI | 131111 | CurOADamperStatus_XXX | [AHU] Current outdoor air damper, 0-90 | Read | ||
| AI | 131112 | CurEADamperStatus_XXX | [AHU] Current exhaust air damper, 0-90 | Read | ||
| AI | 131113 | CurMixDamperStatus_XXX | [AHU] Current mixing damper, 0-90 | Read | ||
| AV | 131114 | OADamperCoolCommand_XXX | [AHU] Outdoor air damper in cooling mode, 0-90 | Write | ||
| AI | 131115 | OADamperCoolStatus_XXX | [AHU] Outdoor air damper in cooling mode, status | Read | ||
| AV | 131116 | EADamperCoolCommand_XXX | [AHU] Exhaust air damper in cooling mode, 0-90 | Write | ||
| AI | 131117 | EADamperCoolStatus_XXX | [AHU] Exhaust air damper in cooling mode, status | Read | ||
| AV | 131118 | MixDamperCoolCommand_XXX | [AHU] Mixing damper in cooling mode, 0-90 | Write | ||
| AI | 131119 | MixDamperCoolStatus_XXX | [AHU] Mixing damper in cooling mode, status | Read | ||
| AV | 131120 | OADamperHeatCommand_XXX | [AHU] Outdoor air damper in heating mode, 0-90 | Write | ||
| AI | 131121 | OADamperHeatStatus_XXX | [AHU] Outdoor air damper in heating mode, status | Read | ||
| AV | 131122 | EADamperHeatCommand_XXX | [AHU] Exhaust air damper in heating mode, 0-90 | Write | ||
| AI | 131123 | EADamperHeatStatus_XXX | [AHU] Exhaust air damper in heating mode, status | Read | ||
| AV | 131124 | MixDamperHeatCommand_XXX | [AHU] Mixing damper in heating mode, 0-90 | Write | ||
| AI | 131125 | MixDamperHeatStatus_XXX | [AHU] Mixing damper in heating mode, status | Read | ||
| AV | 131126 | OADamperFANCommand_XXX | [AHU] Outdoor air damper in fan mode, 0-90 | Write | ||
| AI | 131127 | OADamperFANStatus_XXX | [AHU] Outdoor air damper in fan mode, status | Read | ||
| AV | 131128 | EADamperFANCommand_XXX | [AHU] Exhaust air damper in fan mode, 0-90 | Write | ||
| AI | 131129 | EADamperFANStatus_XXX | [AHU] Exhaust air damper in fan mode, status | Read | ||
| AV | 131130 | MixDamperFANCommand_XXX | [AHU] Mixing damper in fan mode, 0-90 | Write | ||
| AI | 131131 | MixDamperFANStatus_XXX | [AHU] Mixing damper in fan mode, status | Read |
No points match these filters.
Object ID lookup: LG ACP point IDs by name
BO131073StartStopCommand_XXXBI131074StartStopStatus_XXXBO131075LockCommand_XXXBI131076LockStatus_XXXBI131077Filter Sign_XXXBV131078Filter Sign Reset_XXXMO131079ModeCommand_XXXMI131080ModeStatus_XXXAV131085SetRoomTemp_XXXAI131086RoomTemp_XXXBI131087Alarm_XXXAI131088MalfunctionCode_XXXAI131091SetTempStatus_XXXBO131092EmergencySensorCommand_XXXBI131093EmergencySensorStatus_XXXAV131094SetHumidifyCommand_XXXAI131095SetHumidifyStatus_XXXBO131096HumidifyCommand_XXXBI131097HumidifyStatus_XXXBO131098AutoVentilCommand_XXXBI131099AutoVentilStatus_XXXAI131100SupplyTempStatus_XXXAI131101OutdoorTempStatus_XXXAI131102MixTempStatus_XXXAI131103SuppyHumidifyStatus_XXXAI131104OutdoorHumidifyStatus_XXXAI131105VentilHumidifyStatus_XXXAI131106CO2ValueStatus_XXXBI131107HumidifyUnitStatus_XXXBI131108HeaterUnitStatus_XXXBI131109VentilFANStatus_XXXBI131110SupplyFANStatus_XXXAI131111CurOADamperStatus_XXXAI131112CurEADamperStatus_XXXAI131113CurMixDamperStatus_XXXAV131114OADamperCoolCommand_XXXAI131115OADamperCoolStatus_XXXAV131116EADamperCoolCommand_XXXAI131117EADamperCoolStatus_XXXAV131118MixDamperCoolCommand_XXXAI131119MixDamperCoolStatus_XXXAV131120OADamperHeatCommand_XXXAI131121OADamperHeatStatus_XXXAV131122EADamperHeatCommand_XXXAI131123EADamperHeatStatus_XXXAV131124MixDamperHeatCommand_XXXAI131125MixDamperHeatStatus_XXXAV131126OADamperFANCommand_XXXAI131127OADamperFANStatus_XXXAV131128EADamperFANCommand_XXXAI131129EADamperFANStatus_XXXAV131130MixDamperFANCommand_XXXAI131131MixDamperFANStatus_XXX
Integration notes
- Instance = 2 x 65536 + unit address x 256 + point number (product type 2 = AHU). Instances here are for address 00, so point 1 = BO 131073; AHU address 01 point 1 = 131329.
- AHU objects sit on their own BACnet device: the gateway Device ID (default 9000) + 2.
- Point numbers 9-12, 17 and 18 are unused in the AHU table.
- Temperature and humidity readings are printed with ranges only (-127 to 127, 30-90) and no units. CO2 reads in tens of ppm (20 = 200 ppm).
- Damper points carry a 0-90 range with no unit stated.
- The manual has no read/write column: access is inferred from the object type and the Setting/Status labels.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
How many BACnet points does the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) have?
This list has 53 BACnet objects: 23 analog inputs, 11 analog values, 11 binary inputs, 5 binary outputs, 1 binary value, 1 multi-state input, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet points are writable?
18 of the 53 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet documentation?
LG does not publish it on its own website. This list comes from BACnet Gateway (ACP BACnet) Installation/User Manual (MFL67709501), revision 2014 (copyright date), a copy hosted by SupplyHouse.com at https://s3.amazonaws.com/s3.supplyhouse.com/product_files/LG-PQNFB17C1-Install-Instructions.pdf. Ask LG or its representative for the current revision.
What are the minimum BACnet points to integrate the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)?
Start with BO 131073 StartStopCommand_XXX (On/off (131073 + AHU address x 256)); MO 131079 ModeCommand_XXX (1 Cool, 2 Dry, 3 Fan, 4 Heat); AV 131085 SetRoomTemp_XXX (Room temperature setpoint); BI 131074 StartStopStatus_XXX (Running status); AI 131086 RoomTemp_XXX (Room temperature); AI 131100 SupplyTempStatus_XXX (Supply air temperature); BI 131087 Alarm_XXX (Unit alarm); AI 131088 MalfunctionCode_XXX (LG error code).
How do I check these points on the real ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More LG BACnet points lists
- VRF BACnet IP gateway
LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
LG Multi V VRF and single-split indoor units, ventilation (ERV) units and outdoor units on the ACP BACnet's LG-NET. LG's AC Smart BACnet (PBACNA000) manual prints the same tables.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet, ACP-BAC, LG BACnet gateway, LG VRF BACnet, AC Smart BACnet, PBACNA000, LG Multi V BACnet - Air-to-water heat pump via BACnet IP gateway
LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)
LG air-to-water heat pumps (AWHP) served by the ACP BACnet gateway.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet AWHP, ACP-BAC AWHP, LG air to water heat pump BACnet - VRF indoor unit zone controller (room controller)
LG MultiSITE CRC2+Z Remote Controller (PREMTBVC4)
LG MultiSITE CRC2+Z wall remote controller (PREMTBVC4) for LG VRF and single-zone indoor units, up to 16 indoor units per controller.
Also known as: PREMTBVC4, CRC2, CRC2+Z, MultiSITE CRC2, LG CRC2 remote controller, PREMTBVC3 - Fan coil unit controller (room thermostat)
LG MultiSITE MS8350 Room Controller (fan coil)
LG MultiSITE MS8350 (VUCQMS8350) room controllers for commercial and hotel fan coil units.
Also known as: MS8350, VUCQMS8350, LG MS8350, MultiSITE MS8000 - Rooftop unit controller (room thermostat, rooftop, heat-pump and IAQ)
LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)
LG MultiSITE MS8650 (VUCQMS8650) room controllers for rooftop units, heat pumps and indoor air quality control.
Also known as: MS8650, VUCQMS8650, LG MS8650, MultiSITE MS8000
Source: BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (copyright date). Object names, instances and units are reproduced as published; descriptions are our own.