Easy BACnet
  1. Home
  2. BACnet points lists
  3. LG
  4. ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)

Air handling unit via BACnet IP gateway · BACnet points list

LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ACP BACnet gateway serves each LG AHU on its LG-NET as a fixed block of 53 BACnet IP objects on the gateway's AHU device (Device ID + 2). Besides on/off, mode, setpoint and alarm, the AHU block carries humidity control, supply, outdoor and mixed air readings, CO2, fan and heater status and per-mode damper positions. The same manual's indoor, ventilation and outdoor tables are in the separate ACP BACnet entry.

This page lists 53 BACnet objects for the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of LG’s documentation hosted by SupplyHouse.com, not by LG itself, so treat it as unofficial.

Manufacturer
LG
Model
ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
Equipment
Air handling unit via BACnet IP gateway
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
53 (18 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
9002
Also known as
PQNFB17C0, PQNFB17C1, ACP BACnet AHU, ACP-BAC AHU
Source document
BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (copyright date) (unofficial copy, hosted by SupplyHouse.com)
Download CSV 53 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against LG’s current documentation and the live device before use. Not official LG information. Terms of use.

BMS integration notes: LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)

Integration in brief

Give the ACP BACnet an IP address and Device ID, let it find the AHU on LG-NET, then read the AHU device (Device ID + 2) at 131072 + address x 256. Map on/off, mode and setpoint, then room, supply and outdoor readings and the alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 131073StartStopCommand_XXXOn/off (131073 + AHU address x 256)Command
MO 131079ModeCommand_XXX1 Cool, 2 Dry, 3 Fan, 4 HeatCommand
AV 131085SetRoomTemp_XXXRoom temperature setpointWrite
BI 131074StartStopStatus_XXXRunning statusRead
AI 131086RoomTemp_XXXRoom temperatureRead
AI 131100SupplyTempStatus_XXXSupply air temperatureRead
BI 131087Alarm_XXXUnit alarmRead
AI 131088MalfunctionCode_XXXLG error codeRead

Network setup

Watch out for

LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

53 of 53 shown
Type
Access
Show
LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet Points List
DescriptionStates
BOmin131073StartStopCommand_XXX[AHU] On/off commandCommandInactive=Stop, Active=Run
BImin131074StartStopStatus_XXX[AHU] On/off statusReadInactive=Stop, Active=Run
BO131075LockCommand_XXX[AHU] Remote controller lock commandCommandInactive=Permit, Active=Prohibit
BI131076LockStatus_XXX[AHU] Remote controller lock statusReadInactive=Permit, Active=Prohibit
BI131077Filter Sign_XXX[AHU] Filter signReadInactive=Off, Active=On
BV131078Filter Sign Reset_XXX[AHU] Filter sign resetWriteActive=Reset
MOmin131079ModeCommand_XXX[AHU] Operation mode commandCommand1=Cool, 2=Dry, 3=Fan, 4=Heat
MI131080ModeStatus_XXX[AHU] Operation mode statusRead1=Cool, 2=Dry, 3=Fan, 4=Heat
AVmin131085SetRoomTemp_XXX[AHU] Room temperature setpoint°CWrite
AImin131086RoomTemp_XXX[AHU] Room temperature°CRead
BImin131087Alarm_XXX[AHU] AlarmReadInactive=Normal, Active=Abnormal
AImin131088MalfunctionCode_XXX[AHU] LG error codeRead
AI131091SetTempStatus_XXX[AHU] Setpoint status°CRead
BO131092EmergencySensorCommand_XXX[AHU] Emergency sensor commandCommandInactive=Stop, Active=Run
BI131093EmergencySensorStatus_XXX[AHU] Emergency sensor statusReadInactive=Stop, Active=Run
AV131094SetHumidifyCommand_XXX[AHU] Humidity setpoint command, 40-60Write
AI131095SetHumidifyStatus_XXX[AHU] Humidity setpoint status, 40-60Read
BO131096HumidifyCommand_XXX[AHU] Humidify on/off commandCommandInactive=Stop, Active=Run
BI131097HumidifyStatus_XXX[AHU] Humidify on/off statusReadInactive=Stop, Active=Run
BO131098AutoVentilCommand_XXX[AHU] Auto ventilation commandCommandInactive=Stop, Active=Run
BI131099AutoVentilStatus_XXX[AHU] Auto ventilation statusReadInactive=Stop, Active=Run
AImin131100SupplyTempStatus_XXX[AHU] Supply air temperature, -127 to 127Read
AI131101OutdoorTempStatus_XXX[AHU] Outdoor air temperature, -127 to 127Read
AI131102MixTempStatus_XXX[AHU] Mixed air temperature, -127 to 127Read
AI131103SuppyHumidifyStatus_XXX[AHU] Supply air humidity, 30-90Read
AI131104OutdoorHumidifyStatus_XXX[AHU] Outdoor air humidity, 30-90Read
AI131105VentilHumidifyStatus_XXX[AHU] Ventilation (return) humidity, 30-90Read
AI131106CO2ValueStatus_XXX[AHU] CO2, 0-255; value x 10 = ppmRead
BI131107HumidifyUnitStatus_XXX[AHU] Humidifier runningReadInactive=Stop, Active=Run
BI131108HeaterUnitStatus_XXX[AHU] Heater runningReadInactive=Stop, Active=Run
BI131109VentilFANStatus_XXX[AHU] Ventilation (exhaust) fan runningReadInactive=Stop, Active=Run
BI131110SupplyFANStatus_XXX[AHU] Supply fan runningReadInactive=Stop, Active=Run
AI131111CurOADamperStatus_XXX[AHU] Current outdoor air damper, 0-90Read
AI131112CurEADamperStatus_XXX[AHU] Current exhaust air damper, 0-90Read
AI131113CurMixDamperStatus_XXX[AHU] Current mixing damper, 0-90Read
AV131114OADamperCoolCommand_XXX[AHU] Outdoor air damper in cooling mode, 0-90Write
AI131115OADamperCoolStatus_XXX[AHU] Outdoor air damper in cooling mode, statusRead
AV131116EADamperCoolCommand_XXX[AHU] Exhaust air damper in cooling mode, 0-90Write
AI131117EADamperCoolStatus_XXX[AHU] Exhaust air damper in cooling mode, statusRead
AV131118MixDamperCoolCommand_XXX[AHU] Mixing damper in cooling mode, 0-90Write
AI131119MixDamperCoolStatus_XXX[AHU] Mixing damper in cooling mode, statusRead
AV131120OADamperHeatCommand_XXX[AHU] Outdoor air damper in heating mode, 0-90Write
AI131121OADamperHeatStatus_XXX[AHU] Outdoor air damper in heating mode, statusRead
AV131122EADamperHeatCommand_XXX[AHU] Exhaust air damper in heating mode, 0-90Write
AI131123EADamperHeatStatus_XXX[AHU] Exhaust air damper in heating mode, statusRead
AV131124MixDamperHeatCommand_XXX[AHU] Mixing damper in heating mode, 0-90Write
AI131125MixDamperHeatStatus_XXX[AHU] Mixing damper in heating mode, statusRead
AV131126OADamperFANCommand_XXX[AHU] Outdoor air damper in fan mode, 0-90Write
AI131127OADamperFANStatus_XXX[AHU] Outdoor air damper in fan mode, statusRead
AV131128EADamperFANCommand_XXX[AHU] Exhaust air damper in fan mode, 0-90Write
AI131129EADamperFANStatus_XXX[AHU] Exhaust air damper in fan mode, statusRead
AV131130MixDamperFANCommand_XXX[AHU] Mixing damper in fan mode, 0-90Write
AI131131MixDamperFANStatus_XXX[AHU] Mixing damper in fan mode, statusRead
Object ID lookup: LG ACP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)

How many BACnet points does the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) have?

This list has 53 BACnet objects: 23 analog inputs, 11 analog values, 11 binary inputs, 5 binary outputs, 1 binary value, 1 multi-state input, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet points are writable?

18 of the 53 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1) BACnet documentation?

LG does not publish it on its own website. This list comes from BACnet Gateway (ACP BACnet) Installation/User Manual (MFL67709501), revision 2014 (copyright date), a copy hosted by SupplyHouse.com at https://s3.amazonaws.com/s3.supplyhouse.com/product_files/LG-PQNFB17C1-Install-Instructions.pdf. Ask LG or its representative for the current revision.

What are the minimum BACnet points to integrate the LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)?

Start with BO 131073 StartStopCommand_XXX (On/off (131073 + AHU address x 256)); MO 131079 ModeCommand_XXX (1 Cool, 2 Dry, 3 Fan, 4 Heat); AV 131085 SetRoomTemp_XXX (Room temperature setpoint); BI 131074 StartStopStatus_XXX (Running status); AI 131086 RoomTemp_XXX (Room temperature); AI 131100 SupplyTempStatus_XXX (Supply air temperature); BI 131087 Alarm_XXX (Unit alarm); AI 131088 MalfunctionCode_XXX (LG error code).

How do I check these points on the real ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More LG BACnet points lists

Source: BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (copyright date). Object names, instances and units are reproduced as published; descriptions are our own.