- ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)
Air-to-water heat pump via BACnet IP gateway · BACnet points list
LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1) BACnet points list
Updated 7 November 2026Unofficial source
The ACP BACnet gateway serves each LG air-to-water heat pump on its LG-NET as a fixed block of 23 BACnet IP objects on the gateway's AWHP device (Device ID + 4). The block has run/stop, mode, room, hot water and leaving water setpoints, hot water on/off, water and tank temperatures, alarm and error code.
This page lists 23 BACnet objects for the LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of LG’s documentation hosted by SupplyHouse.com, not by LG itself, so treat it as unofficial.
- Manufacturer
- LG
- Model
- ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)
- Equipment
- Air-to-water heat pump via BACnet IP gateway
- Equipment type
- Heat pumps
- BACnet objects
- 23 (7 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 9004
- Also known as
- PQNFB17C0, PQNFB17C1, ACP BACnet AWHP, ACP-BAC AWHP, LG air to water heat pump BACnet
- Source document
- BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (copyright date) (unofficial copy, hosted by SupplyHouse.com)
Reference only, provided as-is: verify against LG’s current documentation and the live device before use. Not official LG information. Terms of use.
BMS integration notes: LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)
Give the ACP BACnet an IP address and Device ID, let it find the heat pump on LG-NET, then read the AWHP device (Device ID + 4) at 262144 + address x 256. Map run/stop, mode and the setpoint the unit controls on (air or water, see AirWaterFlag), then hot water and alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 262145 | StartStopCommand_XXX | Run/stop (262145 + AWHP address x 256) | Command |
| BO 262162 | HotWaterCommand_XXX | Hot water on/off | Command |
| MO 262149 | ModeCommand_XXX | 1 Cool, 2 Heat, 3 Auto | Command |
| AO 262151 | SetRoomTempCommand_XXX | Room temperature setpoint | Command |
| AO 262155 | SetPipeOutWaterTempCommand_XXX | Leaving water setpoint | Command |
| AO 262153 | SetHotWaterTempCommand_XXX | Hot water setpoint | Command |
| BI 262146 | StartStopStatus_XXX | Running status | Read |
| AI 262165 | TankTempStatus_XXX | Water tank temperature | Read |
| BI 262160 | Alarm_XXX | Unit alarm | Read |
| AI 262161 | MalfunctionCode_XXX | LG error code | Read |
Network setup
- Default Device ID 9000; the AWHP device is Device ID + 4.
- Device ID and network settings are set from the ACP's front-panel menu.
Watch out for
- AirWaterFlag shows whether the unit controls on room air or water temperature; write the matching setpoint.
LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 262145 | StartStopCommand_XXX | [AWHP] Run/stop command | Command | Inactive=Stop, Active=Run | |
| BImin | 262146 | StartStopStatus_XXX | [AWHP] Run/stop status | Read | Inactive=Stop, Active=Run | |
| BO | 262147 | LockCommand_XXX | [AWHP] Lock command | Command | Inactive=Stop, Active=Run | |
| BI | 262148 | LockStatus_XXX | [AWHP] Lock status | Read | Inactive=Stop, Active=Run | |
| MOmin | 262149 | ModeCommand_XXX | [AWHP] Operation mode command | Command | 1=Cool, 2=Heat, 3=Auto | |
| MI | 262150 | ModeStatus_XXX | [AWHP] Operation mode status | Read | 1=Cool, 2=Heat, 3=Auto | |
| AOmin | 262151 | SetRoomTempCommand_XXX | [AWHP] Room temperature setpoint command | Command | ||
| AI | 262152 | SetRoomTempStatus_XXX | [AWHP] Room temperature setpoint status | Read | ||
| AOmin | 262153 | SetHotWaterTempCommand_XXX | [AWHP] Hot water setpoint command | Command | ||
| AI | 262154 | SetHotWaterTempStatus_XXX | [AWHP] Hot water setpoint status | Read | ||
| AOmin | 262155 | SetPipeOutWaterTempCommand_XXX | [AWHP] Leaving water setpoint command | Command | ||
| AI | 262156 | SetPipeOutWaterTempStatus_XXX | [AWHP] Leaving water setpoint status | Read | ||
| BI | 262157 | AirWaterFlag_XXX | [AWHP] Setpoint reference: air or water | Read | Inactive=Air, Active=Water | |
| BI | 262158 | HotWaterOnlyFlag_XXX | [AWHP] Hot-water-only mode | Read | Inactive=Normal, Active=Hot Water Only | |
| AI | 262159 | RoomTemp_XXX | [AWHP] Current room temperature | Read | ||
| BImin | 262160 | Alarm_XXX | [AWHP] Alarm | Read | Inactive=No error, Active=Error | |
| AImin | 262161 | MalfunctionCode_XXX | [AWHP] LG error code | Read | ||
| BOmin | 262162 | HotWaterCommand_XXX | [AWHP] Hot water on/off command | Command | ||
| BI | 262163 | HotWaterStatus_XXX | [AWHP] Hot water on/off status | Read | ||
| AI | 262164 | PipeInTempStatus_XXX | [AWHP] Water inlet temperature | Read | ||
| AImin | 262165 | TankTempStatus_XXX | [AWHP] Water tank temperature | Read | ||
| AI | 262166 | SolarTempStatus_XXX | [AWHP] Solar temperature | Read | ||
| AI | 262167 | PipeOutTempStatus_XXX | [AWHP] Water outlet temperature | Read |
No points match these filters.
Object ID lookup: LG ACP point IDs by name
BO262145StartStopCommand_XXXBI262146StartStopStatus_XXXBO262147LockCommand_XXXBI262148LockStatus_XXXMO262149ModeCommand_XXXMI262150ModeStatus_XXXAO262151SetRoomTempCommand_XXXAI262152SetRoomTempStatus_XXXAO262153SetHotWaterTempCommand_XXXAI262154SetHotWaterTempStatus_XXXAO262155SetPipeOutWaterTempCommand_XXXAI262156SetPipeOutWaterTempStatus_XXXBI262157AirWaterFlag_XXXBI262158HotWaterOnlyFlag_XXXAI262159RoomTemp_XXXBI262160Alarm_XXXAI262161MalfunctionCode_XXXBO262162HotWaterCommand_XXXBI262163HotWaterStatus_XXXAI262164PipeInTempStatus_XXXAI262165TankTempStatus_XXXAI262166SolarTempStatus_XXXAI262167PipeOutTempStatus_XXX
Integration notes
- Instance = 4 x 65536 + unit address x 256 + point number (product type 4 = AWHP). Instances here are for address 00, so point 1 = BO 262145.
- AWHP objects sit on their own BACnet device: the gateway Device ID (default 9000) + 4.
- The AWHP table prints no units, and no state texts for the hot water on/off points (18, 19).
- The manual has no read/write column: access is inferred from the object type and the setting/status labels.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)
How many BACnet points does the LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1) have?
This list has 23 BACnet objects: 9 analog inputs, 3 analog outputs, 6 binary inputs, 3 binary outputs, 1 multi-state input, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1) BACnet points are writable?
7 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1) BACnet documentation?
LG does not publish it on its own website. This list comes from BACnet Gateway (ACP BACnet) Installation/User Manual (MFL67709501), revision 2014 (copyright date), a copy hosted by SupplyHouse.com at https://s3.amazonaws.com/s3.supplyhouse.com/product_files/LG-PQNFB17C1-Install-Instructions.pdf. Ask LG or its representative for the current revision.
What are the minimum BACnet points to integrate the LG ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)?
Start with BO 262145 StartStopCommand_XXX (Run/stop (262145 + AWHP address x 256)); BO 262162 HotWaterCommand_XXX (Hot water on/off); MO 262149 ModeCommand_XXX (1 Cool, 2 Heat, 3 Auto); AO 262151 SetRoomTempCommand_XXX (Room temperature setpoint); AO 262155 SetPipeOutWaterTempCommand_XXX (Leaving water setpoint); AO 262153 SetHotWaterTempCommand_XXX (Hot water setpoint); BI 262146 StartStopStatus_XXX (Running status); AI 262165 TankTempStatus_XXX (Water tank temperature); BI 262160 Alarm_XXX (Unit alarm); AI 262161 MalfunctionCode_XXX (LG error code).
How do I check these points on the real ACP BACnet gateway - AWHP (air-to-water heat pump) objects (PQNFB17C0 / PQNFB17C1)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More LG BACnet points lists
- VRF BACnet IP gateway
LG ACP BACnet gateway (PQNFB17C0 / PQNFB17C1)
LG Multi V VRF and single-split indoor units, ventilation (ERV) units and outdoor units on the ACP BACnet's LG-NET. LG's AC Smart BACnet (PBACNA000) manual prints the same tables.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet, ACP-BAC, LG BACnet gateway, LG VRF BACnet, AC Smart BACnet, PBACNA000, LG Multi V BACnet - Air handling unit via BACnet IP gateway
LG ACP BACnet gateway - AHU kit objects (PQNFB17C0 / PQNFB17C1)
LG air handling units wired to the ACP BACnet gateway (RS-485 on its CH5 port) and served on its AHU device.
Also known as: PQNFB17C0, PQNFB17C1, ACP BACnet AHU, ACP-BAC AHU - VRF indoor unit zone controller (room controller)
LG MultiSITE CRC2+Z Remote Controller (PREMTBVC4)
LG MultiSITE CRC2+Z wall remote controller (PREMTBVC4) for LG VRF and single-zone indoor units, up to 16 indoor units per controller.
Also known as: PREMTBVC4, CRC2, CRC2+Z, MultiSITE CRC2, LG CRC2 remote controller, PREMTBVC3 - Fan coil unit controller (room thermostat)
LG MultiSITE MS8350 Room Controller (fan coil)
LG MultiSITE MS8350 (VUCQMS8350) room controllers for commercial and hotel fan coil units.
Also known as: MS8350, VUCQMS8350, LG MS8350, MultiSITE MS8000 - Rooftop unit controller (room thermostat, rooftop, heat-pump and IAQ)
LG MultiSITE MS8650 Room Controller (rooftop / heat pump / IAQ)
LG MultiSITE MS8650 (VUCQMS8650) room controllers for rooftop units, heat pumps and indoor air quality control.
Also known as: MS8650, VUCQMS8650, LG MS8650, MultiSITE MS8000
Source: BACnet Gateway (ACP BACnet) Installation/User Manual · MFL67709501 · rev. 2014 (copyright date). Object names, instances and units are reproduced as published; descriptions are our own.