Steam heating control (boiler or district steam valve) · BACnet points list

Heat-Timer SRC Platinum (BACnet) BACnet points list

Updated 6 November 2026

Short answer

The SRC Platinum controls steam heating on outdoor temperature, either through a burner/valve or a modulating district steam valve with position feedback or timed control. Its BACnet board exposes the settings, valve trims and position, schedule slots and sensor readings as Analog, Binary and Multi-state Values with instances in steps of 100.

This page lists 41 BACnet objects for the Heat-Timer SRC Platinum (BACnet) — 35 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Heat-Timer’s own free documentation, linked below.

Manufacturer
Heat-Timer
Model
SRC Platinum (BACnet)
Equipment
Steam heating control (boiler or district steam valve)
Equipment type
Boilers & water heaters
BACnet objects
41 (35 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
SRC, SRC Platinum, Heat-Timer SRC, Platinum BACnet
Source document
Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - SRC Platinum BACnet Variable List (pp. 18-19) · HT# 059082-00C
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Heat-Timer’s current documentation and the live device before use. Not official Heat-Timer information. Terms of use.

BMS integration notes: Heat-Timer SRC Platinum (BACnet)

Integration in brief

The SRC runs steam heating (burner/valve or a district steam valve) on outdoor temperature. From the BMS, read the system and outdoor temperatures, the valve position and the burner status; adjust the system setpoint or heat adjustments, set a manual valve target, and force a day/night shift if needed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2900SHIFTForce day/night: 1 To-Day, 2 To-Night, 3 Extend-DayWrite
AV 3900XYZTEMPSystem setpoint (burner/valve mode)Write
AV 1500MVTARGETManual valve target, %Write
AV 3000SYSSENSystem sensor temperatureRead
AV 1800ODTEMPOutdoor temperatureRead
AV 3200VALVEValve position, %Read
BV 400BURNERBurner status (1 = on)Read

Network setup

Watch out for

Heat-Timer SRC Platinum (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

41 of 41 shown
Type
AnalogBinaryMulti-state
Access
Show
Heat-Timer SRC Platinum (BACnet) BACnet Points List
DescriptionStates
AV0BOOSTADJVari-Boost Adjustment; range printed "0 1 - 6 4"Write
MV100BOOSTMODEBoost ModeWrite1=BoostOff, 2=ManualBoost, 3=VariDay, 4=VariDayNight
AV200BOOSTTIMEManual Boost Time; range 0 - 120minWrite
AV300BPTIMEBypass Time; range 0 - 2,147,483,647minRead
BVmin400BURNERBurner StatusRead0=Off, 1=On
BV500BYPASSMODEBypass ModeWrite0=AUTO, 1=ON
AV600CLENGTHCycle Length; range 10 - 240minWrite
AV700CUTOFFPCT*Valve % at Cutoff; range 0 - 100%Write
MV800DAYADJUSTDay Heat AdjustmentWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J, 11=K, 12=L, 13=M, 14=N, 15=O, 16=P
AV900DAYCUTOFFOutdoor Day Cutoff; range -6 - 38°C, 20 - 100°F°F or °C (per INMODE)Write
BV1000DLSDay Light SavingWrite0=Enable, 1=Disable
BV1100FAULTMODESensor Fault ModeWrite0=OutputOn, 1=OutputOff
AV1200FREEZPCTValve % at Freezing; range 0 - 100%Write
BV1300INMODESensor ModeRead0=°F, 1=°C
AV1400MOTORTIMEMotor Time; range 120 - 600sWrite
AVmin1500MVTARGETManual Valve Target; range 0 - 100%Write
MV1600NADJUSTNight Heat AdjustmentWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J, 11=K, 12=L, 13=M, 14=N, 15=O, 16=P
AV1700NCUTOFFOutdoor Night Cutoff; range -6 - 38°C, 20 - 100°F°F or °C (per INMODE)Write
AVmin1800ODTEMPOutdoor Sensor; range -40 - 122°C, -40 - +250°F°F or °C (per INMODE)Read
AV1900ODTRIMOutdoor Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
AV2000OFFPCTValve Off %; range 0 - 100%Write
BV2100OPMODEOperation ModeWrite0=Burner/valve, 1=District Steam
AV2200PAUSETIMEPause Time; range 0 - 60sWrite
AV2300PDATEPanel Date; range 0 - 2,147,483,647days since 1/1/1981Write
AV2400PTIMEPanel Time; range 0 - 1439min since 0:00Write
BV2500PULSECLOSEPulse Close EnableWrite0=No, 1=Yes
BV2600PUMPVacuum Pump RelayWrite0=Off, 1=On
AV2700SCHEDULES00Schedules; range 0 - 1439, 1440=empty schedule (first of 2700-2755)min since 0:00Write
AV2755SCHEDULES55Schedules; range 0 - 1439, 1440=empty schedule (last of 2700-2755)min since 0:00Write
BV2800SEASONSeasonWrite0=Winter, 1=Summer
MVmin2900SHIFTDay/Night ShiftWrite1=To-Day, 2=To-Night, 3=Extend-Day, 4=To-Schedule
AVmin3000SYSSENSystem Sensor; range -40 - 122°C, -40 - +250°F°F or °C (per INMODE)Read
AV3100SYTRIMSystem Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
AVmin3200VALVEValve Position; range 0 - 100%Read
AV3300VCLSODValve Close Overdrive; range 0 - 90sWrite
AV3400VCLSTRMValve Close Trim; range 0 - 5%Write
BV3500VMODEValve ModeWrite0=Positioning Sensor, 1=Time Based
AV3600VOPNTRMValve Open Trim; range 0 - 5%Write
AV3700VTRIMValve Trim; range 0 - 20%Write
AV3800XYZMINDistrict Steam Delay; range 0 - 30minWrite
AVmin3900XYZTEMPSystem Setpoint; range 21 - 122°C, 70 - 250°F°F or °C (per INMODE)Write
Object ID lookup: Heat-Timer SRC Platinum point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SRC Platinum (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Heat-Timer SRC Platinum (BACnet)

How many BACnet points does the Heat-Timer SRC Platinum (BACnet) have?

This list has 41 BACnet objects: 27 analog values, 10 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Heat-Timer SRC Platinum (BACnet) BACnet points are writable?

35 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Heat-Timer SRC Platinum (BACnet) BACnet documentation?

The source is Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - SRC Platinum BACnet Variable List (pp. 18-19) (HT# 059082-00C), published free by Heat-Timer at https://www.heat-timer.com/wp-content/uploads/2019/04/Platinum-BACnet-Configuration-Manual-059082C-Color.pdf.

What are the minimum BACnet points to integrate the Heat-Timer SRC Platinum (BACnet)?

Start with MV 2900 SHIFT (Force day/night: 1 To-Day, 2 To-Night, 3 Extend-Day); AV 3900 XYZTEMP (System setpoint (burner/valve mode)); AV 1500 MVTARGET (Manual valve target, %); AV 3000 SYSSEN (System sensor temperature); AV 1800 ODTEMP (Outdoor temperature); AV 3200 VALVE (Valve position, %); BV 400 BURNER (Burner status (1 = on)).

How do I check these points on the real SRC Platinum (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Heat-Timer BACnet points lists

Source: Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - SRC Platinum BACnet Variable List (pp. 18-19) · HT# 059082-00C. Object names, instances and units are reproduced as published; descriptions are our own.