Modulating boiler sequencing control · BACnet points list

Heat-Timer Multi-MOD Platinum (BACnet) BACnet points list

Updated 6 November 2026

Short answer

The Multi-MOD Platinum sequences up to 20 modulating boilers on temperature, steam pressure or outdoor reset. Its BACnet board exposes per-stage run time, ignition level, mode, manual level, trims, relay and modulation readbacks, plus the system setpoint, sensor and target, as Analog, Binary and Multi-state Values.

This page lists 43 BACnet objects for the Heat-Timer Multi-MOD Platinum (BACnet) — 29 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Heat-Timer’s own free documentation, linked below.

Manufacturer
Heat-Timer
Model
Multi-MOD Platinum (BACnet)
Equipment
Modulating boiler sequencing control
Equipment type
Boilers & water heaters
BACnet objects
43 (29 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Multi-MOD, MultiMOD, Multi-MOD Platinum, Heat-Timer Multi-MOD, Platinum BACnet
Source document
Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - Multi-MOD Platinum BACnet Variable List (pp. 16-17) · HT# 059082-00C
Download CSV 43 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Heat-Timer’s current documentation and the live device before use. Not official Heat-Timer information. Terms of use.

BMS integration notes: Heat-Timer Multi-MOD Platinum (BACnet)

Integration in brief

The Multi-MOD sequences up to 20 modulating boilers (stages) on temperature, pressure or outdoor reset. From the BMS, read the system sensor, calculated target, stage relays and modulation levels and the lockout inputs; adjust the setpoint, put each stage in Auto/Standby/Manual/Off/On with MODE, and set a manual modulation level with MAN.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1400MODE00Stage 1 mode: 1 Auto ... 4 Off, 5 OnWrite
AV 2600SETPTSystem setpoint (units per INMODE)Write
AV 1100MAN00Stage 1 manual modulation level, %Write
AV 3200SYSSENSystem sensor readingRead
AV 3300TARGCalculated target (reset modes)Read
BV 3100SYSONOFFSystem relay (1 = on)Read
BV 2900STONOFF00Stage 1 relay (1 = on)Read
AV 3000STPCT00Stage 1 modulation level, %Read
MV 900LOCK00Stage 1 lockout: 2 = lockout, 3 = comm errorRead

Network setup

Watch out for

Heat-Timer Multi-MOD Platinum (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

43 of 43 shown
Type
AnalogBinaryMulti-state
Access
Show
Heat-Timer Multi-MOD Platinum (BACnet) BACnet Points List
DescriptionStates
AV0BTIME00Stage Run-Time; range 0 - 2,147,483,647 (first of 0-19)minRead
AV19BTIME19Stage Run-Time; range 0 - 2,147,483,647 (last of 0-19)minRead
AV100COOutdoor Cutoff Temp; range -6 - 38°C, 20 - 100°F°F or °C (per INMODE)Write
AV200FIRE00Ignition Level; range 1 - 50 (first of 200-219)%Write
AV219FIRE19Ignition Level; range 1 - 50 (last of 200-219)%Write
AV300GAINModulation Gain; range depends on INMODE (see manual)Write
BV400HCHeat/CoolWrite0=heat, 1=cool
AV500HFHOLDHigh Fire Hold; range 0 - 60minWrite
MV600INMODESensor ModeRead1=°F, 2=°C, 3=15psi, 4=30psi, 5=100psi, 6=200psi, 7=300psi, 8=HWR, 9=Reset °F, 10=Reset °C
MV700LEADLead StageWrite0-19=A-T
AV800LFHOLDPre-purge Delay; range 0 - 10minWrite
MVmin900LOCK00Lockout Input (first of 900-919)Read1=(inactive), 2=Lockout, 3=Comm Error
MV919LOCK19Lockout Input (last of 900-919)Read1=(inactive), 2=Lockout, 3=Comm Error
AV1000LSTHOLDLast Stage Hold; range 0 - 3.0psi, 0 - 30psi °C °Fpsi, °C or °F (per INMODE)Write
AVmin1100MAN00Manual Modulation Level; range 0 - 100 (first of 1100-1119)%Write
AV1119MAN19Manual Modulation Level; range 0 - 100 (last of 1100-1119)%Write
AV1200MAXSTGMaximum Stages; range 4 - 20Read
AV1300MINMinimum Target; range 21 - 68°C, 70 - 180°F°F or °C (per INMODE)Write
MVmin1400MODE00Stage Mode (first of 1400-1419)Write1=Auto, 2=Standby, 3=Manual, 4=Off, 5=On
MV1419MODE19Stage Mode (last of 1400-1419)Write1=Auto, 2=Standby, 3=Manual, 4=Off, 5=On
AV1500MODST00Modulation Start Point; range 0 - 99 (first of 1500-1519)%Write
AV1519MODST19Modulation Start Point; range 0 - 99 (last of 1500-1519)%Write
AV1600MTRIM00Modulation Output Trim; range printed "-1 0 - +1 0" (first of 1600-1619)Write
AV1619MTRIM19Modulation Output Trim; range printed "-1 0 - +1 0" (last of 1600-1619)Write
AV1700ODTEMPOutdoor Sensor; range -40 - +122°C, -40 - +250°F°F or °C (per INMODE)Read
AV1800ODTRIMOutdoor Sensor Trim; range -5 - +5°F or °C (per INMODE)Write
AV1900OFFOffset Temp; range -28 - +28°C, -50 - +50°F°F or °C (per INMODE)Write
AV2000PDATEPanel Date; range 0 - 2,147,483,647days since 1/1/1981Write
AV2100PTIMEPanel Time; range 0 - 1439min since 0:00Write
MV2200RReset RatioWrite1=1:4, 2=1:3, 3=1:2, 4=1:1.5, 5=1:1.25, 6=1:1, 7=1.25:1, 8=1.5:1, 9=2:1, 10=3:1, 11=4:1
MV2300RTMODELead Stage Rotation ModeWrite1=Manual, 2=Time, 3=Last-On
AV2400RTTIMEPeriodic Rotation Interval; range 1 - 999hWrite
AV2500SBSetback; range 0 - 7.5psi, 0 - 75psi °C °Fpsi, °C or °F (per INMODE)Write
AVmin2600SETPTSet point; range 0.0-15.0psi, 0.0-30.0psi, 0-100psi, -40 - +122°C, -40 - +250°Fpsi, °C or °F (per INMODE)Write
AV2700SRUNONSystem Run-on; range 0 - 60minWrite
AV2800STBYDLYStandby Delay; range 1 - 60minWrite
BVmin2900STONOFF00Stage Relay (first of 2900-2919)Read0=Off, 1=On
BV2919STONOFF19Stage Relay (last of 2900-2919)Read0=Off, 1=On
AVmin3000STPCT00Modulation Level; range 0 - 100 (first of 3000-3019)%Read
AV3019STPCT19Modulation Level; range 0 - 100 (last of 3000-3019)%Read
BVmin3100SYSONOFFSystem RelayRead0=Off, 1=On
AVmin3200SYSSENSystem Sensor; range depends on INMODE (see manual)psi, °C or °F (per INMODE)Read
AVmin3300TARGCalculated Target; range 21 - 122°C, 70 - 250°F°F or °C (per INMODE)Read
Object ID lookup: Heat-Timer Multi-MOD Platinum point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Multi-MOD Platinum (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Heat-Timer Multi-MOD Platinum (BACnet)

How many BACnet points does the Heat-Timer Multi-MOD Platinum (BACnet) have?

This list has 43 BACnet objects: 31 analog values, 4 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Heat-Timer Multi-MOD Platinum (BACnet) BACnet points are writable?

29 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Heat-Timer Multi-MOD Platinum (BACnet) BACnet documentation?

The source is Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - Multi-MOD Platinum BACnet Variable List (pp. 16-17) (HT# 059082-00C), published free by Heat-Timer at https://www.heat-timer.com/wp-content/uploads/2019/04/Platinum-BACnet-Configuration-Manual-059082C-Color.pdf.

What are the minimum BACnet points to integrate the Heat-Timer Multi-MOD Platinum (BACnet)?

Start with MV 1400 MODE00 (Stage 1 mode: 1 Auto ... 4 Off, 5 On); AV 2600 SETPT (System setpoint (units per INMODE)); AV 1100 MAN00 (Stage 1 manual modulation level, %); AV 3200 SYSSEN (System sensor reading); AV 3300 TARG (Calculated target (reset modes)); BV 3100 SYSONOFF (System relay (1 = on)); BV 2900 STONOFF00 (Stage 1 relay (1 = on)); AV 3000 STPCT00 (Stage 1 modulation level, %); MV 900 LOCK00 (Stage 1 lockout: 2 = lockout, 3 = comm error).

How do I check these points on the real Multi-MOD Platinum (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Heat-Timer BACnet points lists

Source: Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - Multi-MOD Platinum BACnet Variable List (pp. 16-17) · HT# 059082-00C. Object names, instances and units are reproduced as published; descriptions are our own.