Boiler / steam heating plant control · BACnet points list

Heat-Timer MPC Platinum (BACnet) BACnet points list

Updated 6 November 2026

Short answer

The MPC Platinum runs a heating plant (burner, valve or district steam) on outdoor temperature with day and night heat adjustments. Its BACnet board exposes the settings, schedule slots, sensor readings and relay states as Analog, Binary and Multi-state Values with instances in steps of 100.

This page lists 32 BACnet objects for the Heat-Timer MPC Platinum (BACnet) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Heat-Timer’s own free documentation, linked below.

Manufacturer
Heat-Timer
Model
MPC Platinum (BACnet)
Equipment
Boiler / steam heating plant control
Equipment type
Boilers & water heaters
BACnet objects
32 (27 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
MPC, MPC Platinum, Heat-Timer MPC, Platinum BACnet
Source document
Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - MPC Platinum BACnet Variable List (pp. 12-13) · HT# 059082-00C
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Heat-Timer’s current documentation and the live device before use. Not official Heat-Timer information. Terms of use.

BMS integration notes: Heat-Timer MPC Platinum (BACnet)

Integration in brief

The MPC cycles a heating plant (burner/valve or district steam) on outdoor temperature. From the BMS, read the system and outdoor temperatures and the output and system relays; adjust the day/night heat adjustments, cutoffs or system setpoint, and force a day/night shift if needed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2200SHIFTForce day/night: 1 To-Day, 2 To-Night, 3 Extend-DayWrite
MV 600DADJUSTDay heat adjustment curve, A-PWrite
AV 2900XYZTEMPSystem setpoint (burner/valve mode)Write
AV 2400SYSSENSystem sensor temperatureRead
AV 1400ODTEMPOutdoor temperatureRead
BV 1700OUTPUTOutput relay (1 = on)Read
BV 2500SYSTEMSystem relay (1 = on)Read

Network setup

Watch out for

Heat-Timer MPC Platinum (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

32 of 32 shown
Type
AnalogBinaryMulti-state
Access
Show
Heat-Timer MPC Platinum (BACnet) BACnet Points List
DescriptionStates
AV0BOOSTADJVari-Boost Adjustment; range printed "0 1 - 6 4"Write
MV100BOOSTMODEBoost ModeWrite1=BoostOff, 2=ManualBoost, 3=VariDay, 4=VariDayNight
AV200BOOSTTIMEManual Boost Time; range 0 - 120minWrite
AV300BPTIMEBypass Time; range 0 - 2,147,483,647minRead
BV400BYPASSMODEBypass ModeWrite0=AUTO, 1=ON
AV500CLENGTHCycle Length; range 10 - 240minWrite
MVmin600DADJUSTDay Heat AdjustmentWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J, 11=K, 12=L, 13=M, 14=N, 15=O, 16=P
AV700DCUTOFFOutdoor Day Cutoff; range -6 - 38°C, 20 - 100°F°F or °C (per INMODE)Write
BV800DLSDay Light SavingWrite0=Enable, 1=Disable
BV900FAULTMODESensor Fault ModeWrite0=OutputOn, 1=OutputOff
AV1000HDIFFSystem Differential; range 2 - 42°C, 3 - 75°F°F or °C (per INMODE)Write
BV1100INMODESensor ModeWrite0=°F, 1=°C
MV1200NADJUSTNight Heat AdjustmentWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J, 11=K, 12=L, 13=M, 14=N, 15=O, 16=P
AV1300NCUTOFFOutdoor Night Cutoff; range -6 - 38°C, 20 - 100°F°F or °C (per INMODE)Write
AVmin1400ODTEMPOutdoor Sensor; range -40 - +122°C, -40 - +250°F°F or °C (per INMODE)Read
AV1500ODTRIMOutdoor Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
BV1600OPMODEOperation ModeWrite0=Burner/valve, 1=District Steam
BVmin1700OUTPUTOutput RelayRead0=Off, 1=On
AV1800PDATEPanel Date; range 0 - 2,147,483,647days since 1/1/1981Write
AV1900PTIMEPanel Time; range 0 - 1439min since 0:00Write
AV2000SCHEDULES00Schedules; range 0 - 1439, 1440=empty schedule (first of 2000-2055)min since 0:00Write
AV2055SCHEDULES55Schedules; range 0 - 1439, 1440=empty schedule (last of 2000-2055)min since 0:00Write
BV2100SEASONSeasonWrite0=Winter, 1=Summer
MVmin2200SHIFTDay/Night ShiftWrite1=To-Day, 2=To-Night, 3=Extend-Day, 4=To-Schedule
AV2300SRUNONSystem Run-on; range 0 - 60minWrite
AVmin2400SYSSENSystem Sensor; range -40 - +122°C, -40 - +250°F°F or °C (per INMODE)Read
BVmin2500SYSTEMSystem RelayRead0=Off, 1=On
AV2600SYTRIMSystem Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
BV2700TLOCKOUTThermal Lockout EnableWrite0=OFF, 1=ON
AV2800XYZMINDistrict Steam Delay; range 0 - 30minWrite
AVmin2900XYZTEMPSystem Setpoint; range 21 - 122°C, 70 - 250°F°F or °C (per INMODE)Write
AV3000ZMAXTGTMax Target Temperature; range 32 - 116°C, 90 - 240°F°F or °C (per INMODE)Write
Object ID lookup: Heat-Timer MPC Platinum point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MPC Platinum (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Heat-Timer MPC Platinum (BACnet)

How many BACnet points does the Heat-Timer MPC Platinum (BACnet) have?

This list has 32 BACnet objects: 19 analog values, 9 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Heat-Timer MPC Platinum (BACnet) BACnet points are writable?

27 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Heat-Timer MPC Platinum (BACnet) BACnet documentation?

The source is Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - MPC Platinum BACnet Variable List (pp. 12-13) (HT# 059082-00C), published free by Heat-Timer at https://www.heat-timer.com/wp-content/uploads/2019/04/Platinum-BACnet-Configuration-Manual-059082C-Color.pdf.

What are the minimum BACnet points to integrate the Heat-Timer MPC Platinum (BACnet)?

Start with MV 2200 SHIFT (Force day/night: 1 To-Day, 2 To-Night, 3 Extend-Day); MV 600 DADJUST (Day heat adjustment curve, A-P); AV 2900 XYZTEMP (System setpoint (burner/valve mode)); AV 2400 SYSSEN (System sensor temperature); AV 1400 ODTEMP (Outdoor temperature); BV 1700 OUTPUT (Output relay (1 = on)); BV 2500 SYSTEM (System relay (1 = on)).

How do I check these points on the real MPC Platinum (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Heat-Timer BACnet points lists

Source: Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - MPC Platinum BACnet Variable List (pp. 12-13) · HT# 059082-00C. Object names, instances and units are reproduced as published; descriptions are our own.