Multiple boiler sequencing control · BACnet points list

Heat-Timer HWRQ Platinum (BACnet) BACnet points list

Updated 6 November 2026

Short answer

The HWRQ Platinum stages up to 32 boiler stages on outdoor reset or a fixed setpoint. Its BACnet board exposes the settings, per-boiler mode, status, lockout and communication-error objects, and the sensor readings, all as Analog, Binary and Multi-state Values with instances in steps of 100.

This page lists 50 BACnet objects for the Heat-Timer HWRQ Platinum (BACnet) — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Heat-Timer’s own free documentation, linked below.

Manufacturer
Heat-Timer
Model
HWRQ Platinum (BACnet)
Equipment
Multiple boiler sequencing control
Equipment type
Boilers & water heaters
BACnet objects
50 (41 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
HWRQ, HWRQ Platinum, Heat-Timer HWRQ, Platinum BACnet
Source document
Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - HWRQ Platinum BACnet Variable List (pp. 10-11) · HT# 059082-00C
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Heat-Timer’s current documentation and the live device before use. Not official Heat-Timer information. Terms of use.

BMS integration notes: Heat-Timer HWRQ Platinum (BACnet)

Integration in brief

The HWRQ sequences up to 32 boiler stages from its own outdoor reset or setpoint. From the BMS, read the calculated target, system and outdoor temperatures, boiler status and lockouts; adjust the setpoint/offset, put individual boilers in Auto/Standby/Off/On with MODE, and force a day/night shift if needed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2000MODE00Boiler 1 mode: 1 Auto, 2 Standby, 3 Off, 4 OnWrite
BV 700CONTROL0 = outdoor reset, 1 = fixed setpointWrite
AV 3800SETPTFixed setpoint (CONTROL = Set Point)Write
AV 2400OFFSETShift of the reset curveWrite
AV 4300TARGCalculated water targetWrite
AV 4100SYSSENSystem (supply) water temperatureRead
AV 2200ODTEMPOutdoor temperatureRead
MV 300BSTATUSBoiler stage status; codes depend on BTYPERead
BV 1500LOCK00Boiler 1 lockout input (1 = L/O)Read
BV 600COMERR00Boiler 1 communication errorRead

Network setup

Watch out for

Heat-Timer HWRQ Platinum (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

50 of 50 shown
Type
AnalogBinaryMulti-state
Access
Show
Heat-Timer HWRQ Platinum (BACnet) BACnet Points List
DescriptionStates
AV0BOOSTBoost Offset; range 0 - 33°C, 0 - 60°F°F or °C (per INMODE)Write
MV100BOOSTMODEBoost ModeWrite1=Off, 2=Vari Boost, 3=Vari Boost & ESD
AV200BPTIMEBypass Time; range 0 - 2,147,483,647minRead
MVmin300BSTATUSBoiler Status (printed for 300-331)ReadBTYPE On/Off: 1=Off, 2=On; 2-Stage: 1=Off, 2=Low, 3=High; 3-Stage: 1=Off, 2=Low, 3=Med, 4=High; 4-Stage: 1=Off, 2=Low, 3=MLow, 4=MHigh
MV400BTYPEBoiler TypeWrite1=On/Off, 2=2-Stage, 3=3-Stage, 4=4-Stage
BV500BYPASSMODEBypass ModeWrite0=Auto, 1=Bypass
BVmin600COMERR00Communication Error (first of 600-631)Read0=(blank), 1=C/E
BV631COMERR31Communication Error (last of 600-631)Read0=(blank), 1=C/E
BVmin700CONTROLControl ModeWrite0=Reset, 1=Set Point
AV800CUTOFFOutdoor Cut-off; range 0 - 25°C, 30 - 75°F°F or °C (per INMODE)Write
BV900DHWMODEDHW Call ModeWrite0=No Priority, 1=Priority
BV1000DLSDay Light SavingWrite0=Enable, 1=Disable
BV1100FAULTMODESensor Fault ModeWrite0=Stages On, 1=Stages Off
BV1200FCDFast Cool DownWrite0=Minimum Target Temp, 1=Off
BV1300INMODESensor TypeWrite0=°F Sensor, 1=°C Sensor
MV1400LEADLead boiler; coding depends on Boiler Type (table in manual)Write
BVmin1500LOCK00Lockout Input (first of 1500-1531)Read0=(inactive), 1=L/O
BV1531LOCK31Lockout Input (last of 1500-1531)Read0=(inactive), 1=L/O
BV1600LOGICLogic ModeWrite0=PID, 1=OSS
AV1700LSTHOLDLast Stage Hold; range 0 -17°C, 0 - 30°F°F or °C (per INMODE)Write
AV1800MINRUNMin Runtime; range 1-60minWrite
AV1900MINTGTMin Water Temp; range 21 - 77°C, 70 - 170°F°F or °C (per INMODE)Write
MVmin2000MODE00Boiler Mode (first of 2000-2031)Write1=Auto, 2=Standby, 3=Off, 4=On
MV2031MODE31Boiler Mode (last of 2000-2031)Write1=Auto, 2=Standby, 3=Off, 4=On
AV2100NBOILERTotal Boilers; range 1 - 32/(BTYPE+1)Write
AVmin2200ODTEMPOutdoor Sensor; range -40 - 121°C, -40 - +250°F°F or °C (per INMODE)Read
AV2300ODTRIMOutdoor Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
AVmin2400OFFSETOffset Temp; range -22 - +22°C, -40 - +40°F°F or °C (per INMODE)Write
AV2500PDATEPanel Date; range 0 - 2,147,483,647days since 1/1/1981Write
AV2600PRUNONPump Run-On; range 0 - 60minWrite
AV2700PTIMEPanel Time; range 0 - 1439min since 0:00Write
BV2800PUMPPumpRead0=Off, 1=On
AV2900PURGEPurge Delay; range 0-10minWrite
MV3000RReset RatioWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J
AV3100REACTReaction Time; range 1 - 10minWrite
MV3200RTMODELead Stage Rotation ModeWrite1=Time, 2=Manual, 3=FOFO (no FOFO when LOGIC=OSS)
AV3300RTTIMEPeriodic Rotation Interval; range 1 - 999hWrite
AV3400SCHEDULES00Schedules; range 0 - 1439, 1440=empty schedule (first of 3400-3455)min since 0:00Write
AV3455SCHEDULES55Schedules; range 0 - 1439, 1440=empty schedule (last of 3400-3455)min since 0:00Write
BV3500SEASONSeasonWrite0=Winter, 1=Summer
BV3600SEQUENCESequenceWrite0=Lo/Hi/Lo/Hi, 1=Lo/Lo/Hi/Hi
AV3700SETBACKNight Setback Temp; range -44 - 0°C, -80 - 0°F°F or °C (per INMODE)Write
AVmin3800SETPTSet point; range 21 - 116°C, 70 - 240°F°F or °C (per INMODE)Write
MV3900SHIFTDay Night ShiftWrite1=Day, 2=Night, 3=Day Extended 90 Minutes, 4=Resync to Schedule
AV4000STBYDLYStandby Delay; range 1 - 60minWrite
AVmin4100SYSSENSystem Sensor; range -40 - 121°C, -40 - +250°F°F or °C (per INMODE)Read
AV4200SYTRIMSystem Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
AVmin4300TARGCalculated Target; range 0 - 116°C, 0 - 240°F°F or °C (per INMODE)Write
AV4400THROTTLEThrottle Range; range 1 - 11°C , 2 - 20°F°F or °C (per INMODE)Write
AV4500ZMAXTGTMax Target Temp; range 32 - 116°C, 90 - 240°F°F or °C (per INMODE)Write
Object ID lookup: Heat-Timer HWRQ Platinum point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HWRQ Platinum (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Heat-Timer HWRQ Platinum (BACnet)

How many BACnet points does the Heat-Timer HWRQ Platinum (BACnet) have?

This list has 50 BACnet objects: 26 analog values, 15 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Heat-Timer HWRQ Platinum (BACnet) BACnet points are writable?

41 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Heat-Timer HWRQ Platinum (BACnet) BACnet documentation?

The source is Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - HWRQ Platinum BACnet Variable List (pp. 10-11) (HT# 059082-00C), published free by Heat-Timer at https://www.heat-timer.com/wp-content/uploads/2019/04/Platinum-BACnet-Configuration-Manual-059082C-Color.pdf.

What are the minimum BACnet points to integrate the Heat-Timer HWRQ Platinum (BACnet)?

Start with MV 2000 MODE00 (Boiler 1 mode: 1 Auto, 2 Standby, 3 Off, 4 On); BV 700 CONTROL (0 = outdoor reset, 1 = fixed setpoint); AV 3800 SETPT (Fixed setpoint (CONTROL = Set Point)); AV 2400 OFFSET (Shift of the reset curve); AV 4300 TARG (Calculated water target); AV 4100 SYSSEN (System (supply) water temperature); AV 2200 ODTEMP (Outdoor temperature); MV 300 BSTATUS (Boiler stage status; codes depend on BTYPE); BV 1500 LOCK00 (Boiler 1 lockout input (1 = L/O)); BV 600 COMERR00 (Boiler 1 communication error).

How do I check these points on the real HWRQ Platinum (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Heat-Timer BACnet points lists

Source: Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - HWRQ Platinum BACnet Variable List (pp. 10-11) · HT# 059082-00C. Object names, instances and units are reproduced as published; descriptions are our own.