Boiler outdoor reset control · BACnet points list

Heat-Timer HWR Platinum (BACnet) BACnet points list

Updated 6 November 2026

Short answer

The HWR Platinum is an outdoor-reset control for one boiler burner or a motorized valve. With the BACnet board it exposes its settings and readings as Analog, Binary and Multi-state Values with instances in steps of 100. Most settings are writable from the BMS; the sensor readings, outputs and calculated target are read-only.

This page lists 32 BACnet objects for the Heat-Timer HWR Platinum (BACnet) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Heat-Timer’s own free documentation, linked below.

Manufacturer
Heat-Timer
Model
HWR Platinum (BACnet)
Equipment
Boiler outdoor reset control
Equipment type
Boilers & water heaters
BACnet objects
32 (25 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
HWR, HWR Platinum, Heat-Timer HWR, Platinum BACnet
Source document
Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - HWR Platinum BACnet Variable List (pp. 8-9) · HT# 059082-00C
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Heat-Timer’s current documentation and the live device before use. Not official Heat-Timer information. Terms of use.

BMS integration notes: Heat-Timer HWR Platinum (BACnet)

Integration in brief

The HWR runs its own outdoor reset. From the BMS, read the calculated target, system and outdoor temperatures and the burner/valve and pump outputs; adjust the reset with OFFSET, the reset ratio R or the minimum/maximum targets, and force a day/night shift if needed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2500SHIFTForce day/night: 1 ToDay, 2 ToNight, 3 ExtendDayWrite
AV 1500OFFSETShift of the reset curve, °F or °CWrite
AV 2800TARGCalculated water targetRead
AV 2600SYSSENSystem (supply) water temperatureRead
AV 1300ODTEMPOutdoor temperatureRead
BV 400BURNERBurner output (1 = on)Read
MV 2900VALVEValve: 1 inactive, 2 close, 3 openRead
BV 2000PUMPPump output (1 = on)Read

Network setup

Watch out for

Heat-Timer HWR Platinum (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

32 of 32 shown
Type
AnalogBinaryMulti-state
Access
Show
Heat-Timer HWR Platinum (BACnet) BACnet Points List
DescriptionStates
AV0BDIFFBurner Differential; range 0 - 8°C, 0 - 15°F°F or °C (per INMODE)Write
AV100BOOSTBoost Offset; range 0 - 33°C, 0 - 60°F°F or °C (per INMODE)Write
MV200BOOSTMODEBoost ModeWrite1=Off, 2=Vari Boost, 3=Vari Boost & ESD
AV300BPTIMEBypass Time; range 0 - 2,147,483,647minRead
BVmin400BURNERBurnerRead0=Off, 1=On
MV500BYPASSMODEBypass ModeWrite1=Auto, 2=Valve Close, 3=Valve Open / Bypass
AV600CUTOFFOutdoor Day Cutoff; range 0 - 25°C, 30 - 75°F°F or °C (per INMODE)Write
BV700DHWMODEDHW Call ModeWrite0=No Priority, 1=Priority
BV800DLSDay Light SavingWrite0=Enable, 1=Disable
BV900FAULTMODESensor Fault ModeWrite0=Output On, 1=Output Off
BV1000FCDFast Cool DownWrite0=Minimum Water Temp, 1=Off
BV1100INMODESensor TypeWrite0=°F, 1=°C
AV1200MINTGTMin Water Temperature; range 21 - 71°C, 70 - 170°F°F or °C (per INMODE)Write
AVmin1300ODTEMPOutdoor Sensor; range -40 - +122°C, -40 - +250°F°F or °C (per INMODE)Read
AV1400ODTRIMOutdoor Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
AVmin1500OFFSETOffset Temperature; range -22 - +22°C, -40 - +40°F°F or °C (per INMODE)Write
BV1600OPMODEOutput ModeWrite0=Burner, 1=Motorized Valve
AV1700PDATEPanel Date; range 0 - 2,147,483,647days since 1/1/1981Write
AV1800PRUNONPump Run-On; range 0 - 60minWrite
AV1900PTIMEPanel Time; range 0 - 1439min since 0:00Write
BVmin2000PUMPPumpRead0=Off, 1=On
MV2100RReset RatioWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J
AV2200SCHEDULES00Schedules; range 0 - 1439, 1440=empty schedule (first of 2200-2255)min since 0:00Write
AV2255SCHEDULES55Schedules; range 0 - 1439, 1440=empty schedule (last of 2200-2255)min since 0:00Write
BV2300SEASONSeasonWrite0=Winter, 1=Summer
AV2400SETBACKNight Setback Temperature; range -44 - 0°C, -80 - 0°F°F or °C (per INMODE)Write
MVmin2500SHIFTDay Night ShiftWrite1=ToDay, 2=ToNight, 3=ExtendDay, 4=Resync
AVmin2600SYSSENSystem Sensor; range -40 - +122°C, -40 - +250°F°F or °C (per INMODE)Read
AV2700SYTRIMSystem Sensor Trim; range -3 - +3°C, -5 - +5°F°F or °C (per INMODE)Write
AVmin2800TARGCalculated Target; range 0 - 116°C, 0 - 240°F°F or °C (per INMODE)Read
MVmin2900VALVEMotorized ValveRead1=Valve inactive, 2=Valve close, 3=Valve open
AV3000ZMAXTGTMax Target Temperature; range 32 - 116°C, 90 - 240°F°F or °C (per INMODE)Write
Object ID lookup: Heat-Timer HWR Platinum point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HWR Platinum (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Heat-Timer HWR Platinum (BACnet)

How many BACnet points does the Heat-Timer HWR Platinum (BACnet) have?

This list has 32 BACnet objects: 18 analog values, 9 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Heat-Timer HWR Platinum (BACnet) BACnet points are writable?

25 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Heat-Timer HWR Platinum (BACnet) BACnet documentation?

The source is Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - HWR Platinum BACnet Variable List (pp. 8-9) (HT# 059082-00C), published free by Heat-Timer at https://www.heat-timer.com/wp-content/uploads/2019/04/Platinum-BACnet-Configuration-Manual-059082C-Color.pdf.

What are the minimum BACnet points to integrate the Heat-Timer HWR Platinum (BACnet)?

Start with MV 2500 SHIFT (Force day/night: 1 ToDay, 2 ToNight, 3 ExtendDay); AV 1500 OFFSET (Shift of the reset curve, °F or °C); AV 2800 TARG (Calculated water target); AV 2600 SYSSEN (System (supply) water temperature); AV 1300 ODTEMP (Outdoor temperature); BV 400 BURNER (Burner output (1 = on)); MV 2900 VALVE (Valve: 1 inactive, 2 close, 3 open); BV 2000 PUMP (Pump output (1 = on)).

How do I check these points on the real HWR Platinum (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Heat-Timer BACnet points lists

Source: Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - HWR Platinum BACnet Variable List (pp. 8-9) · HT# 059082-00C. Object names, instances and units are reproduced as published; descriptions are our own.