Steam boiler sequencing control · BACnet points list

Heat-Timer MPCQ Platinum (BACnet) BACnet points list

Updated 6 November 2026

Short answer

The MPCQ Platinum stages up to 32 steam boiler stages on system pressure, in cycle or setpoint mode. Its BACnet board exposes the settings, per-boiler mode, status, lockout and communication-error objects and the sensor readings as Analog, Binary and Multi-state Values with instances in steps of 100.

This page lists 49 BACnet objects for the Heat-Timer MPCQ Platinum (BACnet) — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Heat-Timer’s own free documentation, linked below.

Manufacturer
Heat-Timer
Model
MPCQ Platinum (BACnet)
Equipment
Steam boiler sequencing control
Equipment type
Boilers & water heaters
BACnet objects
49 (40 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
MPCQ, MPCQ Platinum, Heat-Timer MPCQ, Platinum BACnet
Source document
Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - MPCQ Platinum BACnet Variable List (pp. 14-15) · HT# 059082-00C
Download CSV 49 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Heat-Timer’s current documentation and the live device before use. Not official Heat-Timer information. Terms of use.

BMS integration notes: Heat-Timer MPCQ Platinum (BACnet)

Integration in brief

The MPCQ sequences up to 32 steam boiler stages on system pressure. From the BMS, read system pressure, outdoor temperature, boiler status and lockouts and the system relay; adjust the pressure setpoint, put individual boilers in Auto/Standby/Off/On with MODE, and force a day/night shift if needed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1900MODE00Boiler 1 mode: 1 Auto, 2 Standby, 3 Off, 4 OnWrite
AV 3700SETPTSteam pressure setpoint, 0-30 psiWrite
MV 3800SHIFTForce day/night: 1 ToDay, 2 ToNight, 3 ExtendDayWrite
AV 4000SYSPRESSystem steam pressure, psiRead
AV 2300ODTEMPOutdoor temperatureRead
BV 4200SYSTEMSystem relay (1 = on)Read
MV 400BSTATUSBoiler stage status; codes depend on BTYPERead
BV 1500LOCK00Boiler 1 lockout input (1 = L/O)Read
BV 800COMERR00Boiler 1 communication errorRead

Network setup

Watch out for

Heat-Timer MPCQ Platinum (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

49 of 49 shown
Type
AnalogBinaryMulti-state
Access
Show
Heat-Timer MPCQ Platinum (BACnet) BACnet Points List
DescriptionStates
AV0BOOSTADJVari-Boost Adjustment; range printed "0 1 - 6 4"Write
MV100BOOSTMODEBoost ModeWrite1=Disabled, 2=Manual, 3=Vari, 4=Vari+ESD
AV200BOOSTTIMEManual Boost Time; range 0 - 120minWrite
AV300BPTIMEBypass Time; range 0 - 2,147,483,647minRead
MVmin400BSTATUSBoiler Status (printed for 400-431)ReadBTYPE On/Off: 1=Off, 2=On; 2-Stage: 1=Off, 2=Low, 3=High; 3-Stage: 1=Off, 2=Low, 3=Med, 4=High; 4-Stage: 1=Off, 2=Low, 3=MLow, 4=MHigh
MV500BTYPEBoiler TypeWrite1=On/Off, 2=2-Stage, 3=3-Stage, 4=4-Stage
BV600BYPASSMODEBypass ModeWrite0=AUTO, 1=ON
AV700CLENGTHCycle Length; range 10 - 240minWrite
BVmin800COMERR00Communication Error (first of 800-831)Read0=(blank), 1=C/E
BV831COMERR31Communication Error (last of 800-831)Read0=(blank), 1=C/E
MV900DADJUSTDay Heat AdjustmentWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J, 11=K, 12=L, 13=M, 14=N, 15=O, 16=P
AV1000DCUTOFFOutdoor Day Cutoff; range -6 - 38, 20 - 100°F or °C (per INMODE)Write
BV1100DLSDay Light SavingWrite0=Enable, 1=Disable
BV1200FAULTMODESensor Fault ModeWrite0=OutputOn, 1=OutputOff
BV1300INMODESensor ModeWrite0=°F, 1=°C
MV1400LEADLead boiler; coding depends on Boiler Type (table in manual)Write
BVmin1500LOCK00Lockout Input (first of 1500-1531)Read0=(inactive), 1=L/O
BV1531LOCK31Lockout Input (last of 1500-1531)Read0=(inactive), 1=L/O
BV1600LOGICLogic ModeWrite0=PID
AV1700LSTHOLDLast Stage Hold; range 0 - 5 psipsiWrite
AV1800MINRUNMin Runtime; range 1-60minWrite
MVmin1900MODE00Boiler Mode (first of 1900-1931)Write1=Auto, 2=Standby, 3=Off, 4=On
MV1931MODE31Boiler Mode (last of 1900-1931)Write1=Auto, 2=Standby, 3=Off, 4=On
AV2000NBOILERTotal Boilers; range 1 - 32/(BTYPE+1)Write
MV2100NADJUSTNight Heat AdjustmentWrite1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I, 10=J, 11=K, 12=L, 13=M, 14=N, 15=O, 16=P
AV2200NCUTOFFOutdoor Night Cutoff; range -6 - 38, 20 - 100°F or °C (per INMODE)Write
AVmin2300ODTEMPOutdoor Sensor; range -40 - +250°F or °C (per INMODE)Read
AV2400ODTRIMOutdoor Sensor Trim; range -3 - +3, -5 - +5°F or °C (per INMODE)Write
BV2500OPMODEOperation ModeWrite0=Cycle, 1=Set Point
AV2600PDATEPanel Date; range 0 - 2,147,483,647days since 1/1/1981Write
AV2700PRETRIMPressure Sensor Trim; range -3 - 3psiWrite
AV2800PTIMEPanel Time; range 0 - 1439min since 0:00Write
AV2900PURGEPurge Delay; range 0-10minWrite
AV3000REACTReaction Time; range 1 - 10minWrite
MV3100RTMODELead Stage Rotation ModeWrite1=Time
AV3200RTTIMEPeriodic Rotation Interval; range 1 - 999hWrite
AV3300SCHEDULES00Schedules; range 0 - 1439, 1440=empty schedule (first of 3300-3355)min since 0:00Write
AV3355SCHEDULES55Schedules; range 0 - 1439, 1440=empty schedule (last of 3300-3355)min since 0:00Write
BV3400SEASONSeasonWrite0=Winter, 1=Summer
BV3500SEQUENCESequenceWrite0=Lo/Hi/Lo/Hi, 1=Lo/Lo/Hi/Hi
AV3600SETBACKNight Setback Temp; range -10 - 0psipsiWrite
AVmin3700SETPTSet point; range 0 - 30psipsiWrite
MVmin3800SHIFTDay/Night ShiftWrite1=ToDay, 2=ToNight, 3=ExtendDay, 4=Resync
AV3900STBYDLYStandby Delay; range 1 - 60minWrite
AVmin4000SYSPRESSystem Pressure Sensor; range -5 - +35psiRead
AV4100SRUNONSystem Run-on; range 0 - 60minWrite
BVmin4200SYSTEMSystem RelayRead0=Off, 1=On
AV4300THROTTLEThrottle Range; range 0.5 - 5psiWrite
AV4400XYZPRESSUREHeat Establish Pressure; range 0.5 - 5psiWrite
Object ID lookup: Heat-Timer MPCQ Platinum point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MPCQ Platinum (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Heat-Timer MPCQ Platinum (BACnet)

How many BACnet points does the Heat-Timer MPCQ Platinum (BACnet) have?

This list has 49 BACnet objects: 26 analog values, 13 binary values, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Heat-Timer MPCQ Platinum (BACnet) BACnet points are writable?

40 of the 49 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Heat-Timer MPCQ Platinum (BACnet) BACnet documentation?

The source is Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - MPCQ Platinum BACnet Variable List (pp. 14-15) (HT# 059082-00C), published free by Heat-Timer at https://www.heat-timer.com/wp-content/uploads/2019/04/Platinum-BACnet-Configuration-Manual-059082C-Color.pdf.

What are the minimum BACnet points to integrate the Heat-Timer MPCQ Platinum (BACnet)?

Start with MV 1900 MODE00 (Boiler 1 mode: 1 Auto, 2 Standby, 3 Off, 4 On); AV 3700 SETPT (Steam pressure setpoint, 0-30 psi); MV 3800 SHIFT (Force day/night: 1 ToDay, 2 ToNight, 3 ExtendDay); AV 4000 SYSPRES (System steam pressure, psi); AV 2300 ODTEMP (Outdoor temperature); BV 4200 SYSTEM (System relay (1 = on)); MV 400 BSTATUS (Boiler stage status; codes depend on BTYPE); BV 1500 LOCK00 (Boiler 1 lockout input (1 = L/O)); BV 800 COMERR00 (Boiler 1 communication error).

How do I check these points on the real MPCQ Platinum (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Heat-Timer BACnet points lists

Source: Platinum BACnet Installation and Configuration Manual (IP and MS/TP) - MPCQ Platinum BACnet Variable List (pp. 14-15) · HT# 059082-00C. Object names, instances and units are reproduced as published; descriptions are our own.