Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) BACnet points list

Updated 4 November 2026

Short answer

MIXIT combines a mixing valve, sensors and a controller that also runs the connected Grundfos pump. With the CONNECT upgrade it speaks BACnet MS/TP on its RS-485 terminals or BACnet IP on its RJ45 port. The object list covers bus control, start/stop, setpoint source and remote setpoint, pump control modes and duty points, limiters, weather curve, energy data and alarm/warning codes.

This page lists 121 BACnet objects for the Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Grundfos’s own free documentation, linked below.

Manufacturer
Grundfos
Model
MIXIT mixing loop unit (BACnet MS/TP and IP)
Equipment
Mixing loop unit (valve + pump controller)
Equipment type
VFDs & pumps
BACnet objects
121 (62 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
227005
Also known as
MIXIT, Grundfos MIXIT, MIXIT DYNAMIC, MIXIT CONNECT, BACnet for MIXIT
Source document
BACnet for MIXIT - Functional profile and user manual · 99258495 · rev. 11.2024
Download CSV 121 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Grundfos’s current documentation and the live device before use. Not official Grundfos information. Terms of use.

BMS integration notes: Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP)

Integration in brief

Configure MIXIT and its fieldbus settings in Grundfos GO Remote first, and set a safe fallback setpoint on AV 6. Then write BO 0 = 1 (bus control), MV 0 = 3 (remote setpoint), the setpoint on AO 0 and BO 1 = 1 to start. Keep polling a point such as BI 0 every 30 s or MIXIT returns to its local setpoint.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0Set Control SourceTakes bus control (1) or gives it back (0)Write
MV 0Config Temp Setpoint SourceSetpoint source; 3 = remote setpoint on AO 0Write
BO 1Set Start StopStart/stop (1 = start, 0 = stop and close valve)Write
AO 0Set Temperature Setpoint RemoteRemote temperature setpoint, °CWrite
BO 2Reset faultResets alarms and warnings on a 0-to-1 edgeWrite
BI 0Status Control SourceConfirms bus controlRead
MI 2Status System StateSystem state, e.g. 5 = temperature controlRead
AI 22Data Controlled TempActual controlled temperature, °CRead
BI 4Status FaultSystem stopped by an alarmRead
AI 37Status System Alarm CodeMIXIT alarm codeRead

Enable & remote start

BO 0 Set Control Source = 1 puts MIXIT under bus control (BI 0 confirms). MV 0 = 3 makes AO 0 the setpoint; MV 0 = 5 uses the internal weather curve with the outdoor temperature written to AO 1. BO 1 starts (1) or stops (0) the system; stop also closes the valve.

Heartbeat & communication loss

The manual asks the BMS to keep communicating, e.g. read BI 0 every 30 s. If communication is lost MIXIT falls back to its local setpoint (AV 6). After a power failure it starts in local control, so the BMS must send the full start-up sequence again.

Sensors & values from the BMS

Outdoor temperature can come from the bus on AO 1 (MV 0 = 5). In heating coil and cooling applications the air temperature feedback can come from the bus on AO 2 after BO 7 = 1.

Network setup

Watch out for

Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

121 of 121 shown
Type
Access
Show
Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) BACnet Points List
DescriptionStates
BImin0Status Control SourceBus control activeRead0=Local control, 1=Bus control
BI1Status Fan and DampersCoil preheated, fan/dampers may run (heating coil)Read0=Disabled, 1=Enabled
BI2Status Actual Run State PumpActual pump run stateRead0=Stopped, 1=Started
BI3Status ReadySystem ready for operationRead0=Not ready, 1=Ready
BImin4Status FaultSystem stopped by an alarmRead0=No fault, 1=Fault
BI5Status Alarm SimulationAlarm/warning simulation activeRead0=Inactive, 1=Active
BI6Notification Flow Temp HighUnderfloor overheat detectedRead0=Not detected, 1=Detected
BI7Notification Frost Risk DetectedFrost risk detectedRead0=Not detected, 1=Detected
BI8Notification Supply Flow HighSupply flow above AV 10 limit for 3600 s (DYNAMIC variants only)Read0=Not above, 1=Above
BI9Notification Thermal Power HighThermal power above AV 11 limit for 3600 s (DYNAMIC variants only)Read0=Not above, 1=Above
BI10Notification Return Temperature ThresholdReturn temperature past AV 12 limit for 3600 s (DYNAMIC variants only)Read0=Not exceeded, 1=Exceeded
BI11Notification Differential Temperature HighPrimary delta T past AV 13 limit for 3600 s (DYNAMIC variants only)Read0=Not exceeded, 1=Exceeded
BI12Bus Feedback EnabledAir temperature feedback comes from the busRead0=False, 1=True
BI13Heat Curve Slope Factor EnabledWeather curve is non-linearRead0=False, 1=True
BI14Heat Curve Offset Range ExceededWeather curve offset outside -15..15Read0=Exceeded, 1=Not exceeded
BI15Heat Curve Slope Factor Range ExceededWeather curve slope outside 0.4..2.0Read0=Exceeded, 1=Not exceeded
BOmin0Set Control SourceTake bus control (1) or return to local (0)Write0=Local control, 1=Bus control
BOmin1Set Start StopStart/stop the system (stop also closes the valve)Write0=Stop, 1=Start
BOmin2Reset faultReset alarms and warnings (rising edge)Write
BO3Enable Overheat ProtectionForce the underfloor overheat indicationWrite0=Disable, 1=Set
BO4Enable Frost Protection, heatingFrost protection for heating coil applicationWrite0=Disable, 1=Enable
BO5Set Fault SimulationStart (rising edge) or stop alarm simulationWrite
BO7Enable Bus FeedbackUse air temperature feedback from the bus (AO 2)Write0=Disable, 1=Enable
BO8Enable Frost Protection Cooling ModeFrost protection in cooling modeWrite0=Disable, 1=Enable
BV0Config Supply Flow Limiting, HeatingEnable supply flow limit (AV 10) (DYNAMIC variants only)Write0=Disabled, 1=Enabled
BV1Config Thermal Power Limiting, HeatingEnable thermal power limit (AV 11) (DYNAMIC variants only)Write0=Disabled, 1=Enabled
BV2Config Return Temp Limiting, HeatingEnable return temperature limit (AV 12) (DYNAMIC variants only)Write0=Disabled, 1=Enabled
BV3Config Primary DeltaT Limiting, HeatingEnable primary delta T limit (AV 13) (DYNAMIC variants only)Write0=Disabled, 1=Enabled
BV4Config Supply Flow Limiting CoolingEnable cooling supply flow limit (AV 17) (DYNAMIC variants only)Write0=Disabled, 1=Enabled
BV5Config Thermal Power Limiting CoolingEnable cooling thermal power limit (AV 18) (DYNAMIC variants only)Write0=Disabled, 1=Enabled
BV6Config Return Temp Limiting CoolingEnable cooling return temperature limit (DYNAMIC variants only)Write0=Disabled, 1=Enabled
BV7Config Primary Delta T Limiting CoolingEnable cooling primary delta T limit (AV 20) (DYNAMIC variants only)Write0=Disabled, 1=Enabled
MI0Status Pump Control Mode, Heating and CoolingCurrent pump control modeRead1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=AUTOADAPT, 5=Constant flow
MI1Data Application Type HeatingHeating application typeRead1=Radiator heating, 2=Underfloor heating, 3=Heating coil
MImin2Status System StateSystem stateRead1=Powering up, 2=Fault, 3=Ready, 4=Preheating heating coil, 5=Temperature control, 6=Frost protection, 7=Underfloor overheat protection, 8=Shut down (start signal removed), 10=Valve 100 % open (backup), 11=Return temperature control
MI3Status Thermal selectionHeating or cooling activeRead1=Heating, 2=Cooling
MI4Data Application type CoolingCooling application typeRead1=General cooling
MI5Data Valve ModeValve modeRead1=Injection 2 way, 2=Mixing 3 way, 3=Injection 3 way
MO0Config Pump Control Mode, HeatingPump control mode for heatingWrite1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=AUTOADAPT, 5=Constant flow
MO1Set Manual Valve FunctionManual valve opening for serviceWrite1=Off, 2=100 % open, 3=50 % open, 4=25 % open, 5=0 % (closed)
MO2Set Application Type HeatingHeating application typeWrite1=Radiator heating, 2=Underfloor heating, 3=Heating coil
MO3Config Pump Control Mode CoolingPump control mode for coolingWrite1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=AUTOADAPT, 5=Constant flow
MO4Config Thermal selectionHeating/cooling change-over (combined applications)Write1=Heating, 2=Cooling
MO5Set Application Type CoolingCooling application typeWrite1=General cooling
MO6Config Valve ModeValve modeWrite1=Injection 2 way, 2=Mixing 3 way, 3=Injection 3 way
MO7Config Heating Cooling SelectionThermal application modeWrite1=Heating, 2=Cooling, 3=Combined
MVmin0Config Temp Setpoint SourceSource of the temperature setpointWrite1=Default setpoint, 2=Analog input setpoint, 3=Remote setpoint (AO 0), 4=Weather curve with local outdoor sensor, 5=Weather curve with bus outdoor temp (AO 1)
AI0Data Temp Setpoint RemoteRemote temperature setpoint received°CRead
AI1Data Outdoor Temp RemoteRemote outdoor temperature received°CRead
AI2Data Act Temp SetpointTemperature setpoint in use°CRead
AI5Status Pump Warning CodePump warning codeRead
AI6Status Pump Alarm CodePump alarm codeRead
AI7Data Heating EnergyLifetime heating energy (DYNAMIC variants only)kWhRead
AI8Data Heating PowerThermal power in heating mode (DYNAMIC variants only)kWRead
AI9Data Cooling EnergyLifetime cooling energy (DYNAMIC variants only)kWhRead
AI10Data Cooling PowerThermal power in cooling mode (DYNAMIC variants only)kWRead
AI11Data Heat Temp DifferenceForward/return temperature difference (DYNAMIC variants only)°CRead
AI12Data Pump PowerPump electrical powerWRead
AI13Data percentage SpeedPump speed, % of maximum%Read
AI14Data Pump Operating HoursPump operating hourshRead
AI15Data Pump EnergyPump energykWhRead
AI16Data Flow TempSecondary flow temperature (from pump)°CRead
AI17Data Supply TempSupply temperature at the valve°CRead
AI19Data Logical Valve OpeningValve opening request%Read
AI20Data Valve Supply FlowPrimary flow at the A-port (DYNAMIC variants only)m³/hRead
AI21Data Return TemperatureReturn temperature at the valve°CRead
AImin22Data Controlled TempActual controlled temperature°CRead
AI23Data Supply Source SetpointSupply source temperature reference°CRead
AI24Data Pump FlowPump flowm³/hRead
AI25Data Pump HeadPump headmRead
AI26Data Outdoor TempOutdoor temperature at the analog input°CRead
AI27Data Zone Air TempAir temperature at the analog input°CRead
AI28Data Bus Temperature FeedbackAir temperature feedback from the bus°CRead
AI35Status System Warning CodeMIXIT warning codeRead
AI36Status System Sub Warning CodeWarning sub-codeRead
AImin37Status System Alarm CodeMIXIT alarm codeRead
AI38Status System Sub Alarm CodeAlarm sub-codeRead
AI39Data HeatingVolumeTotal heating volume pumped (DYNAMIC variants only)m³Read
AI40Data CoolingVolumeTotal cooling volume pumped (DYNAMIC variants only)m³Read
AI41Data VolWeightAvgT1HeatVolume-weighted average T1, heating (DYNAMIC variants only)°C·m³Read
AI42Data VolWeightAvgT2HeatVolume-weighted average T2, heating (DYNAMIC variants only)°C·m³Read
AI43Data VolWeightAvgT1CoolVolume-weighted average T1, cooling (DYNAMIC variants only)°C·m³Read
AI44Data VolWeightAvgT2CoolVolume-weighted average T2, cooling (DYNAMIC variants only)°C·m³Read
AI45Data MIXIT Operating HoursMIXIT operating timesRead
AOmin0Set Temperature Setpoint RemoteTemperature setpoint from the bus (needs MV 0 = 3)°CWrite
AO1Set Outdoor Temperature RemoteOutdoor temperature from the bus (needs MV 0 = 5)°CWrite
AO2Set Bus Temperature FeedbackAir temperature feedback from the bus (needs BO 7 = 1)°CWrite
AV0Config Custom Device Object Instance NumberCustom device instance (enable in Grundfos GO)Write
AV1Config Product time and dateClock, UNIX secondsWrite
AV2Set Simulation Event CodeAlarm/warning code to simulateWrite
AV3Set Simulation Event Sub CodeSub-code to simulateWrite
AV4Config Heat curve offset (+/-)Weather curve offset, +/-15°CWrite
AV5Config Heat curve slope (+/-)Weather curve slope, 0.4-2Write
AV6Config Default Temp SetpointFallback setpoint if bus or sensor signal is lost°CWrite
AV7Config Pump Head Duty Point, HeatingPump head duty point, heatingmWrite
AV8Config Pump Flow Duty Point, HeatingPump flow duty point, heatingm³/hWrite
AV9Config Pump Speed DutyPoint, HeatingPump speed in constant speed mode, heating%Write
AV10Config Supply Flow Limit HeatingPrimary flow limit, heating (DYNAMIC variants only)m³/hWrite
AV11Config Thermal Power Limit HeatingThermal power limit, heating (DYNAMIC variants only)kWWrite
AV12Config Return Temp Limit HeatingReturn temperature limit, heating (DYNAMIC variants only)°CWrite
AV13Config Primary DeltaT Limit HeatingPrimary delta T limit, heating (DYNAMIC variants only)°CWrite
AV14Config Pump Head Duty Point CoolingPump head duty point, cooling (DYNAMIC variants only)mWrite
AV15Config Pump Flow Duty Point CoolingPump flow duty point, cooling (DYNAMIC variants only)m³/hWrite
AV16Config Pump Speed Duty Point CoolingPump speed in constant speed mode, cooling (DYNAMIC variants only)%Write
AV17Config Supply Flow Limit CoolingPrimary flow limit, cooling (DYNAMIC variants only)m³/hWrite
AV18Config Thermal Power Limit CoolingThermal power limit, cooling (DYNAMIC variants only)kWWrite
AV19Config Return Temp Limit CoolingReturn temperature limit, cooling (DYNAMIC variants only)°CWrite
AV20Config Primary Delta T Limit CoolingPrimary delta T limit, cooling (DYNAMIC variants only)°CWrite
AV21Config KpTemperature controller gain, 0.1-20Write
AV22Config TiTemperature controller integral time, 0-3600Write
AV23Config KvsValve capacity limitWrite
AV24Config Outdoor Temperature X1Weather curve outdoor point 1Write
AV25Config Setpoint Y1Weather curve setpoint 1Write
AV26Config Outdoor Temperature X2Weather curve outdoor point 2Write
AV27Config Setpoint Y2Weather curve setpoint 2Write
AV28Config Outdoor Temperature X3Weather curve outdoor point 3Write
AV29Config Setpoint Y3Weather curve setpoint 3Write
AV30Config Outdoor Temperature X4Weather curve outdoor point 4Write
AV31Config Setpoint Y4Weather curve setpoint 4Write
AV32Config Outdoor Temperature X5Weather curve outdoor point 5Write
AV33Config Setpoint Y5Weather curve setpoint 5Write
Object ID lookup: Grundfos MIXIT mixing loop unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MIXIT mixing loop unit (BACnet MS/TP and IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP)

How many BACnet points does the Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) have?

This list has 121 BACnet objects: 37 analog inputs, 3 analog outputs, 34 analog values, 16 binary inputs, 8 binary outputs, 8 binary values, 6 multi-state inputs, 8 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) BACnet points are writable?

62 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) BACnet documentation?

The source is BACnet for MIXIT - Functional profile and user manual (99258495), revision 11.2024, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6012796.pdf.

What are the minimum BACnet points to integrate the Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP)?

Start with BO 0 Set Control Source (Takes bus control (1) or gives it back (0)); MV 0 Config Temp Setpoint Source (Setpoint source; 3 = remote setpoint on AO 0); BO 1 Set Start Stop (Start/stop (1 = start, 0 = stop and close valve)); AO 0 Set Temperature Setpoint Remote (Remote temperature setpoint, °C); BO 2 Reset fault (Resets alarms and warnings on a 0-to-1 edge); BI 0 Status Control Source (Confirms bus control); MI 2 Status System State (System state, e.g. 5 = temperature control); AI 22 Data Controlled Temp (Actual controlled temperature, °C); BI 4 Status Fault (System stopped by an alarm); AI 37 Status System Alarm Code (MIXIT alarm code).

How do I enable BMS control of the Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP)?

BO 0 Set Control Source = 1 puts MIXIT under bus control (BI 0 confirms). MV 0 = 3 makes AO 0 the setpoint; MV 0 = 5 uses the internal weather curve with the outdoor temperature written to AO 1. BO 1 starts (1) or stops (0) the system; stop also closes the valve.

Does the Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP) need a BACnet heartbeat or have a communication timeout?

The manual asks the BMS to keep communicating, e.g. read BI 0 every 30 s. If communication is lost MIXIT falls back to its local setpoint (AV 6). After a power failure it starts in local control, so the BMS must send the full start-up sequence again.

Can the BMS supply sensor values to the Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP)?

Outdoor temperature can come from the bus on AO 1 (MV 0 = 5). In heating coil and cooling applications the air temperature feedback can come from the bus on AO 2 after BO 7 = 1.

How do I check these points on the real MIXIT mixing loop unit (BACnet MS/TP and IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Grundfos BACnet points lists

Source: BACnet for MIXIT - Functional profile and user manual · 99258495 · rev. 11.2024. Object names, instances and units are reproduced as published; descriptions are our own.