  3. Grundfos
  4. Level Control LC 2X2 (CIM 300 / CIM 500)

Submersible pump level controller · BACnet points list

Grundfos Level Control LC 2X2 (CIM 300 / CIM 500) BACnet points list

Updated 6 November 2026

Short answer

The LC 2X2 controls up to two submersible pumps from a level sensor or float switches. With a CIM 300 or CIM 500 module it exposes a fixed object list: pit level, energy, flow and water-quality readings, daily run-time counters, per-pump status inputs, an overall system status, writable level setpoints in centimetres and a multistate Auto/Forced start/Forced stop command per pump.

This page lists 77 BACnet objects for the Grundfos Level Control LC 2X2 (CIM 300 / CIM 500) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Grundfos’s own free documentation, linked below.

Manufacturer
Grundfos
Model
Level Control LC 2X2 (CIM 300 / CIM 500)
Equipment
Submersible pump level controller
Equipment type
VFDs & pumps
BACnet objects
77 (11 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
CIM 300 V04.20.00 / CIM 500 V06.16 (as stated in the PICS)
Also known as
LC 2X2, LC2X2, Grundfos LC 2X2, Level Control LC 2X2, CIM 300, CIM 500, CIU 300, CIU 500
Source document
BACnet PICS CIM 300 - Supplement (pumps, booster systems, Level Control LC 2X1 and LC 2X2) · 97750025 · rev. 05.2021
Download CSV 77 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Grundfos’s current documentation and the live device before use. Not official Grundfos information. Terms of use.

BMS integration notes: Grundfos Level Control LC 2X2 (CIM 300 / CIM 500)

Integration in brief

Read the operating state (MI 0), pit level (AI 6) and the per-pump running and alarm inputs, and use MO 0/MO 1 to put each pump in Auto, Forced start or Forced stop. Alarms are reset with BO 0. The start, stop, high and dry-running levels can be written in centimetres through AO 0-4.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 0Control Pump 1Pump 1: 1 = Auto, 2 = Forced start, 3 = Forced stopWrite
MO 1Control Pump 2Pump 2: 1 = Auto, 2 = Forced start, 3 = Forced stopWrite
BO 0Reset alarmsAlarm reset (1 = reset)Write
MI 0System Operating ModeOperating state: standby, pumping, alarm states...Read
AI 6Pit water levelPit level in cmRead
BI 8Pump1RunningPump 1 running statusRead
BI 9Pump2RunningPump 2 running statusRead
BI 12Pump1AlarmPump 1 alarmRead
BI 13Pump2AlarmPump 2 alarmRead
AI 0Fault codeActive Grundfos fault codeRead

Network setup

Watch out for

Grundfos Level Control LC 2X2 (CIM 300 / CIM 500) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

77 of 77 shown
Type
Access
Show
Grundfos Level Control LC 2X2 (CIM 300 / CIM 500) BACnet Points List
DescriptionStates
AV0Custom device object instance numberCustom device instance number (0-0x3FFFFE)Write
AV1Product time and dateController clock, UNIX timesWrite
AV2CIMSoftwareVersionCIM module software version (decimal)Read
BOmin0Reset alarmsResets alarms (1 = reset)Write0=No resetting, 1=Resetting alarms
BO1Reset EventLogResets the event log (1 = reset)Write0=No resetting, 1=Resetting alarms
MOmin0Control Pump 1Pump 1 command: auto, forced start or forced stopWrite1=Auto, 2=Forced Start, 3=Forced Stop
MOmin1Control Pump 2Pump 2 command: auto, forced start or forced stopWrite1=Auto, 2=Forced Start, 3=Forced Stop
AO0SetHighLevelSet high levelcmWrite
AO1SetDryRunningLevelSet dry running levelcmWrite
AO2SetStartLevelPump1Set start level for pump 1cmWrite
AO3SetStopLevelPump1Set stop level for pump 1cmWrite
AO4SetStartLevelPump2Set start level for pump 2cmWrite
MImin0System Operating ModePresent operating state of the level controllerRead0=Standby, 1=Start-up delay, 2=Pumping, 3=Stop delay, 4=Pumping max, 5=Stopped, 6=Foam draining, 7=Daily emptying, 8=Pump anti-seizing, 9=Manual control, 10=Interlock control, 11=Mains failure, 12=Level sensor error, 13=All pumps in alarm, 14=All pumps out of operation, 15=Service mode, alarms suppressed
MI1CIM statusCIM module statusRead1=OK, 2=EEPROM fault, 3=Memory fault, 4=Unknown
MI2System statusOverall system statusRead1=System OK, 2=Warnings present, 3=Alarms Present, 4=Unknown
MI3System control sensor typeSensor type controlling the systemRead1=Analog level sensor, 2=Float switch, 3=Unknown
AImin0Fault codeGrundfos fault codeRead
AI1Warning codeGrundfos warning codeRead
AI2HighLevelHigh levelcmRead
AI3StartLevelPump1Start level for pump 1cmRead
AI4StopLevelPump1Stop level for pump 1cmRead
AI5StartLevelPump2Start level for pump 2cmRead
AImin6Pit water levelPit water levelcmRead
AI7Pit power consumptionPit power consumptionWRead
AI8Pit energy consumptionPit energy consumptionkWhRead
AI9Pit running timePit running timeminRead
AI10Analog Input 1 (AI1)Analog Input 1%Read
AI11Analog Input 2 (AI2)Analog Input 2%Read
AI12Analog input 3 (AI3)Analog Input 3%Read
AI13Pump1 time to servicePump 1 time to serviceminRead
AI14Pump2 time to servicePump 2 time to serviceminRead
AI15Pump1 start counterPump 1 start counterRead
AI16Pump2 start counterPump 2 start counterRead
AI17Pump1 currentPump 1 currentARead
AI18Pump2 currentPump 2 currentARead
AI19Pump1 operating timePump 1 overall operating timeminRead
AI20Pump2 operating timePump 2 overall operating timeminRead
AI21UserAnalogInput1User-defined measurement, analog input 1%Read
AI22UserAnalogInput2User-defined measurement, analog input 2%Read
AI23UserAnalogInput3User-defined measurement, analog input 3%Read
AI24UserAnalogInput4User-defined measurement, analog input 4%Read
AI25UserAnalogInput5User-defined measurement, analog input 5%Read
AI26Latest operating time pump1Pump 1 latest running timeminRead
AI27Latest operating time pump2Pump 2 latest running timeminRead
AI28Energy consumption pump1Pump 1 energy consumptionkWhRead
AI29Energy consumption pump2Pump 2 energy consumptionkWhRead
AI30System Energy todaySystem energy used today, 0.1 kWh resolutionkWhRead
AI31PulseFlowMeterFlow from the pulse flow meterl/sRead
AI32TurbidityTurbidity, 0.1 NTU resolutionNTURead
AI33PhMeasurepH value, 0.1 pH resolutionpHRead
AI34ConductivityConductivity, 1 S/m resolutionS/mRead
AI35Pump1OprTimeTodayPump 1 run time todayminRead
AI36Pump2OprTimeTodayPump 2 run time todayminRead
AI37Pump1StartCounterTodayPump 1 starts today (unit printed as min)minRead
AI38Pump2StartCounterTodayPump 2 starts today (unit printed as min)minRead
AI39Alarms 1-5 and warnings 1-5Bit-coded: bits 0-4 warnings 1-5, bits 8-12 alarms 1-5Read
AI40Sensor present statusBit-coded sensor-present flags (bits 0-12)Read
BI0AcknowledgeAlarmAlarm acknowledgedRead0=Not acknowledged, 1=Acknowledged
BI1FloatSwitch1StatusFloat switch 1 stateRead0=Off (Float switch down), 1=On (Float switch up)
BI2FloatSwitch2StatusFloat switch 2 stateRead0=Off (Float switch down), 1=On (Float switch up)
BI3FloatSwitch3StatusFloat switch 3 stateRead0=Off (Float switch down), 1=On (Float switch up)
BI4FloatSwitch4StatusFloat switch 4 stateRead0=Off (Float switch down), 1=On (Float switch up)
BI5FloatSwitch5StatusFloat switch 5 stateRead0=Off (Float switch down), 1=On (Float switch up)
BI6Pump1PresentPump 1 fitted/detectedRead0=Not present, 1=Present
BI7Pump2PresentPump 2 fitted/detectedRead0=Not present, 1=Present
BImin8Pump1RunningPump 1 runningRead0=Not running, 1=Running
BImin9Pump2RunningPump 2 runningRead0=Not running, 1=Running
BI10Pump1CommFaultPump 1 communication faultRead0=No communication fault, 1=Pump or auxiliary device communication fault
BI11Pump2CommFaultPump 2 communication faultRead0=No communication fault, 1=Pump or auxiliary device communication fault
BImin12Pump1AlarmPump 1 alarmRead0=No alarm, 1=Alarm
BImin13Pump2AlarmPump 2 alarmRead0=No alarm, 1=Alarm
BI14Pump1WarningPump 1 warningRead0=No warning, 1=Warning
BI15Pump2WarningPump 2 warningRead0=No warning, 1=Warning
BI16Pump1DisabledPump 1 out of operationRead0=Enabled, 1=Disabled (Out of operation)
BI17Pump2DisabledPump 2 out of operationRead0=Enabled, 1=Disabled (Out of operation)
BI34Acknowledge ResetEventLogAlarmEvent log reset acknowledgedRead0=Not Acknowledged, 1=Acknowledged
BI35Control StatusAuto or manual controlRead0=Auto control, 1=Manual control
Object ID lookup: Grundfos Level Control LC 2X2 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Level Control LC 2X2 (CIM 300 / CIM 500) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Grundfos Level Control LC 2X2 (CIM 300 / CIM 500)

How many BACnet points does the Grundfos Level Control LC 2X2 (CIM 300 / CIM 500) have?

This list has 77 BACnet objects: 41 analog inputs, 5 analog outputs, 3 analog values, 20 binary inputs, 2 binary outputs, 4 multi-state inputs, 2 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Grundfos Level Control LC 2X2 (CIM 300 / CIM 500) BACnet points are writable?

11 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Grundfos Level Control LC 2X2 (CIM 300 / CIM 500) BACnet documentation?

The source is BACnet PICS CIM 300 - Supplement (pumps, booster systems, Level Control LC 2X1 and LC 2X2) (97750025), revision 05.2021, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6013137.pdf.

What are the minimum BACnet points to integrate the Grundfos Level Control LC 2X2 (CIM 300 / CIM 500)?

Start with MO 0 Control Pump 1 (Pump 1: 1 = Auto, 2 = Forced start, 3 = Forced stop); MO 1 Control Pump 2 (Pump 2: 1 = Auto, 2 = Forced start, 3 = Forced stop); BO 0 Reset alarms (Alarm reset (1 = reset)); MI 0 System Operating Mode (Operating state: standby, pumping, alarm states); AI 6 Pit water level (Pit level in cm); BI 8 Pump1Running (Pump 1 running status); BI 9 Pump2Running (Pump 2 running status); BI 12 Pump1Alarm (Pump 1 alarm); BI 13 Pump2Alarm (Pump 2 alarm); AI 0 Fault code (Active Grundfos fault code).

How do I check these points on the real Level Control LC 2X2 (CIM 300 / CIM 500)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Grundfos BACnet points lists

Source: BACnet PICS CIM 300 - Supplement (pumps, booster systems, Level Control LC 2X1 and LC 2X2) · 97750025 · rev. 05.2021. Object names, instances and units are reproduced as published; descriptions are our own.