Pump communication module · BACnet points list

Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet points list

Updated 28 October 2026

Short answer

The CIM 300 add-on module (or CIU 300 box) gives Grundfos electronic pumps a BACnet MS/TP interface; the CIM 500 does the same over BACnet IP. The pump functional profile is a fixed object list: status binary inputs, command binary outputs, multistate objects for control and operating mode, analog inputs for measured values and counters, analog outputs for setpoint and flow limit, and analog values for module configuration. Many points depend on pump family, MGE motor model (G, H or later) and fitted sensors.

This page lists 105 BACnet objects for the Grundfos CIM 300 / CIM 500 BACnet (pumps) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Grundfos’s own free documentation, linked below.

Manufacturer
Grundfos
Model
CIM 300 / CIM 500 BACnet (pumps)
Equipment
Pump communication module
Equipment type
VFDs & pumps
BACnet objects
105 (21 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
227000 + MAC address (CIM 300 default); custom value via AV 0 with SW3 on
Also known as
CIM 300, CIU 300, CIM 500, CIU 500, CIM300, MAGNA3, TPE, MGE, CUE, E-pumps
Source document
BACnet for Grundfos pumps, CIM/CIU 300 BACnet MS/TP, CIM/CIU 500 Ethernet for BACnet IP - Functional profile and user manual · 97572650 · rev. 09.2025
Download CSV 105 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Grundfos CIM 300 / CIM 500 BACnet (pumps)

Integration in brief

Set the control mode (MO 0), operating mode (MO 1) and setpoint (AO 0) first, then take control by writing BO 0 = 1 (bus control). Set AV 1 so the pump drops back to its local settings if BACnet goes quiet. Read status from the BI, MI and AI objects, and reset faults with BO 4.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0Set control sourceTakes bus control (1) or gives it back (0)Write
MO 1Set operating modeStart/stop: 1 = Start, 2 = StopWrite
MO 0Set control modeControl mode, e.g. constant or proportional pressureWrite
AO 0Set setpointSetpoint in % of range or nominal frequencyWrite
BO 4Reset faultResets an alarm on a 0-to-1 edge (bus control only)Write
BI 0Control source statusConfirms bus control; drops to local if the watchdog tripsRead
BI 2Rotation statusPump runningRead
AI 9Actual setpointSetpoint actually in useRead
AI 0Fault codeActive Grundfos alarm codeRead

Enable & remote start

Write the desired control mode (MO 0), operating mode (MO 1, 1 = Start, 2 = Stop) and setpoint (AO 0), then set BO 0 Set control source = 1 for bus control. BI 0 and MI 14 show the active control source. Relay, reset and simulation commands only act while bus control is on.

Heartbeat & communication loss

AV 1 BACnet watchdog: 0 = disabled (default), or 5-3600 s. If no BACnet traffic is seen for that time while in bus control, the pump switches to local control and uses its local settings. After comms return the BAS must set BO 0 back to 1. Make the local settings first (Grundfos GO or PC Tool).

Sensors & values from the BMS

AV 12 Remote sensor feedback lets the BAS send the sensor value (0-100 %) to MAGNA3 and MGE model H and later pumps.

Network setup

Watch out for

Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

105 of 105 shown
Type
Access
Show
Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet Points List
DescriptionStates
BImin0Control source statusWhether the pump is under local or bus controlRead0=Local control, 1=Bus control
BI1Actual directionImpeller rotation directionRead0=Clockwise, 1=Counterclockwise
BImin2Rotation statusPump runningRead0=No rotation, 1=Rotation (pump running)
BI3At minimum speedRunning at minimum speedRead0=Not at minimum speed, 1=At minimum speed
BI4At maximum speedRunning at maximum speedRead0=Not at maximum speed, 1=At maximum speed
BI9Low Flow stop activeLow flow stop function activeRead0=Not active, 1=Active
BI11Digital input 1 statusDigital input 1 stateRead0=Not active, 1=Active
BI12Digital input 2 statusDigital input 2 stateRead0=Not active, 1=Active
BI13Digital input 3 statusDigital input 3 stateRead0=Not active, 1=Active
BI14Digital output 1 statusDigital output 1 stateRead0=Not active, 1=Active
BI15Digital output 2 statusDigital output 2 stateRead0=Not active, 1=Active
BI28Fault simulation statusFault simulation runningRead0=Not active, 1=Active
BI31At power limitRunning at power limitRead0=Not at power limit, 1=At power limit
BI38Setpoint influenceSetpoint influence activeRead0=Not active, 1=Active
BI39Max. flow limitMaximum flow limit activeRead0=Not active, 1=Active
BI62Flow estimation below rangeEstimated flow below the estimation rangeRead0=Inside range, 1=Below range
BI63Flow estimation above rangeEstimated flow above the estimation rangeRead0=Not above range, 1=Above range
BI64Forced to localPump forced to local controlRead0=Not forced to local, 1=Forced to local
BI86Status direct control (Positive Kp)Direct control (positive Kp) statusRead0=Disabled, 1=Enabled (positive Kp)
BOmin0Set control sourceSelects local or BACnet (bus) controlWrite0=Local control (default), 1=Bus control
BO1Relay 1 controlRelay 1 command when bus control and bus relay mode are setWrite0=Closed (default), 1=Open
BO2Relay 2 controlRelay 2 command when bus control and bus relay mode are setWrite0=Closed (default), 1=Open
BOmin4Reset faultResets an alarm on a rising edge (bus control only)Write0=No reset (default), 1=Reset
BO5Fault simulationTurns on a simulated fault (bus control only)Write0=Disabled (default), 1=Enabled
BO6Copy settings to localCopies remote settings to local settings on remote-to-local changeWrite0=Disabled, 1=Enabled
BO9Enable max. flow limitEnables the maximum flow limitWrite0=Disabled, 1=Enabled
BO21Set direct controlSelects direct (positive Kp) or reverse controlWrite0=Disabled (negative Kp), 1=Enabled (positive Kp)
MI0Actual control modeControl mode currently in useRead1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=Automatic/AUTOADAPT, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage, 9=FLOWADAPT, 10=Closed-loop sensor control, 11=Constant diff. pressure, 12=Constant diff. temperature
MI1Actual operating modeOperating mode currently in useRead1=Start (normal), 2=Stop, 3=Minimum, 4=Maximum, 5=User curve
MI2Next bearing-service typeType of the next bearing serviceRead1=Service type unknown, 2=Lubricate bearings, 3=Change bearings
MI3CIM statusCIM module healthRead1=OK, 2=EEPROM fault, 3=Memory fault
MI11Feedback sensor unitEngineering unit of the feedback sensorRead1=Unknown, 2=bar, 3=mbar, 4=m, 5=kPa, 6=psi, 7=ft, 8=m3/h, 9=m3/s, 10=l/s, 11=gpm, 12=°C, 13=°F, 14=%, 15=K, 16=l/h
MI14Control SourceWhere the pump is currently controlled fromRead1=Display, 2=Bus, 3=Handheld, 4=Digital in, 5=ON/OFF button
MOmin0Set control modeSets the control mode (bus control only)Write1=Constant speed (default), 2=Constant pressure, 3=Proportional pressure, 4=Automatic/AUTOADAPT, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage, 9=FLOWADAPT, 10=Closed-loop sensor control, 11=Constant diff. pressure, 12=Constant diff. temperature
MOmin1Set operating modeSets the operating mode (bus control only)Write1=Start (normal), 2=Stop (default), 3=Minimum, 4=Maximum
MO2Product simulationSimulates a pump type for commissioning without a pumpWrite1=Disabled (default), 2=MAGNA, 3=E-pumps 0.25-7.5 kW, 4=E-pumps 11-22 kW / CUE, 8=MAGNA3, 9=E-pumps based on MGE model H
AImin0Fault codeGrundfos alarm (fault) codeRead
AI1Warning codeGrundfos warning codeRead
AI2Time to bearing serviceMonths until bearing service (24 means 24 or more)monthRead
AI3CapacityActual capacity value (process feedback)%Read
AI4HeadActual system head/pressurebarRead
AI5FlowActual system flow ratem3/hRead
AI6Relative performancePerformance relative to maximum performance%Read
AI7SpeedMotor speedrpmRead
AI8FrequencyActual control signal applied to motorHzRead
AImin9Actual setpointSetpoint in use (% of frequency or sensor range)%Read
AI10Motor currentActual motor currentARead
AI11DC link voltageFrequency converter DC Link voltageVRead
AI12Motor voltageMotor voltageVRead
AI13PowerTotal power consumption of the pumpWRead
AI14Remote flowMeasured flow at external sensorm3/hRead
AI15Inlet pressureSystem inlet pressurebarRead
AI16Remote pressureMeasured pressure at external sensorbarRead
AI17LevelTank levelmRead
AI18Power electronic temp.Temperature in frequency converter°CRead
AI19Motor temperatureMotor winding temperature°CRead
AI20Remote temperatureTemperature at external sensor°CRead
AI21Electronic temperaturePump electronics temperature°CRead
AI22Fluid temperaturePumped-liquid temperature°CRead
AI23Bearing temperature DEBearing temperature, drive end°CRead
AI24Bearing temp. NDEBearing temperature, non-drive end°CRead
AI25Auxiliary sensor inputAuxiliary sensor input%Read
AI26Specific energySpecific energy consumptionkWh/m3Read
AI27RuntimeTotal operating time of the pumphRead
AI28Total on timeTotal power-on time of the pumphRead
AI29TorqueMotor torqueNmRead
AI30Energy consumptionTotal energy consumption of the pumpkWhRead
AI31Number of startsNumber of times the pump has startedRead
AI32VolumeTotal pumped volumem3Read
AI37Outlet pressureSystem outlet pressurebarRead
AI57Remote temperature 2Temperature at external temperature sensor 2°CRead
AI58User setpointUser-selected setpoint (% of frequency or setpoint range)%Read
AI85Min. of feedback sensorMinimum value of feedback sensorRead
AI86Max. of feedback sensorMaximum value of feedback sensorRead
AI92Load percentMotor current in percent of rated motor current%Read
AI93Differential pressurePressure between pump flangesbarRead
AI95Actual flow limitActual maximum flow limitm3/hRead
AI114Remote diff. temperatureDifferential temperature at remote sensor°CRead
AI115Inlet diff. pressureDifferential pressure at the inlet pipebarRead
AI116Outlet diff. pressureDifferential pressure at the outlet pipebarRead
AI117Remote diff. pressureDifferential pressure at remote sensorbarRead
AI118Storage tank LevelWater level in the storage tankmRead
AI119Heat energy counterAccumulated heat energy in pump lifekWhRead
AI120Heat powerActual heat powerWRead
AI121Heat diff. temperatureDifferential temperature (heat)KRead
AI130Nominal frequencyNominal pump frequencyHzRead
AI131Minimum frequencyMinimum frequency in % of nominal frequency%Read
AI132Maximum frequencyMaximum frequency in % of nominal frequency%Read
AI133Setpoint range minimumSetpoint range minimum, % of sensor maximum%Read
AI134Setpoint range maximumSetpoint range maximum, % of sensor maximum%Read
AI135Heat energy counter 2Heat energy counter 2 (Cooling)kWhRead
AI136Volume counter 2Volume counter 2m3Read
AI145ConductivityConductivity, 1 S/m resolutionS/mRead
AI146PhMeasurepH, 0.1 pH resolutionpHRead
AI147TurbidityTurbidity, 0.1 NTU resolutionNTURead
AOmin0Set setpointPump setpoint (bus control only); 0 does not stop the pump%Write
AO5Set max. flow limitMaximum flow limit valuem3/hWrite
AV0Custom Device Object Instance NumberCustom device instance (used when DIP switch SW3 is on)Write
AV1BACnet watchdogWatchdog time before falling back to local control; 0 = offsWrite
AV2Simulation fault codeFault code to simulate; write 0 to clearWrite
AV3Simulation warning codeWarning code to simulate; write 0 to clearWrite
AV9Product time and datePump time and date in UNIX secondssWrite
AV12Remote sensor feedbackSensor value written by the BAS (remote feedback)%Write
AV19Set KpController proportional gain KpWrite
AV20Set TiController integral time TisWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CIM 300 / CIM 500 BACnet (pumps) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Grundfos CIM 300 / CIM 500 BACnet (pumps)

How many BACnet points does the Grundfos CIM 300 / CIM 500 BACnet (pumps) have?

This list has 105 BACnet objects: 59 analog inputs, 2 analog outputs, 8 analog values, 19 binary inputs, 8 binary outputs, 6 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet points are writable?

21 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet documentation?

The source is BACnet for Grundfos pumps, CIM/CIU 300 BACnet MS/TP, CIM/CIU 500 Ethernet for BACnet IP - Functional profile and user manual (97572650), revision 09.2025, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6012933.pdf.

What are the minimum BACnet points to integrate the Grundfos CIM 300 / CIM 500 BACnet (pumps)?

Start with BO 0 Set control source (Takes bus control (1) or gives it back (0)); MO 1 Set operating mode (Start/stop: 1 = Start, 2 = Stop); MO 0 Set control mode (Control mode, e.g. constant or proportional pressure); AO 0 Set setpoint (Setpoint in % of range or nominal frequency); BO 4 Reset fault (Resets an alarm on a 0-to-1 edge (bus control only)); BI 0 Control source status (Confirms bus control; drops to local if the watchdog trips); BI 2 Rotation status (Pump running); AI 9 Actual setpoint (Setpoint actually in use); AI 0 Fault code (Active Grundfos alarm code).

How do I enable BMS control of the Grundfos CIM 300 / CIM 500 BACnet (pumps)?

Write the desired control mode (MO 0), operating mode (MO 1, 1 = Start, 2 = Stop) and setpoint (AO 0), then set BO 0 Set control source = 1 for bus control. BI 0 and MI 14 show the active control source. Relay, reset and simulation commands only act while bus control is on.

Does the Grundfos CIM 300 / CIM 500 BACnet (pumps) need a BACnet heartbeat or have a communication timeout?

AV 1 BACnet watchdog: 0 = disabled (default), or 5-3600 s. If no BACnet traffic is seen for that time while in bus control, the pump switches to local control and uses its local settings. After comms return the BAS must set BO 0 back to 1. Make the local settings first (Grundfos GO or PC Tool).

Can the BMS supply sensor values to the Grundfos CIM 300 / CIM 500 BACnet (pumps)?

AV 12 Remote sensor feedback lets the BAS send the sensor value (0-100 %) to MAGNA3 and MGE model H and later pumps.

How do I check these points on the real CIM 300 / CIM 500 BACnet (pumps)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Grundfos BACnet points lists