Booster pump system communication module · BACnet points list

Grundfos CIM 500 BACnet IP (booster systems) BACnet points list

Updated 28 October 2026

Short answer

The CIM 500 module gives Grundfos booster systems a BACnet IP interface. The booster object list differs from the single-pump profile: it adds per-subpump presence, communication, auto-mode, fault code, runtime, speed, current, power, motor temperature and start counts for up to six subpumps plus pilot and back-up pumps, tank-filling limits and system pressures, levels and flows. Availability depends on the booster type and fitted sensors.

This page lists 174 BACnet objects for the Grundfos CIM 500 BACnet IP (booster systems) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Grundfos’s own free documentation, linked below.

Manufacturer
Grundfos
Model
CIM 500 BACnet IP (booster systems)
Equipment
Booster pump system communication module
Equipment type
VFDs & pumps
BACnet objects
174 (27 writable)
Transport
BACnet IP
Firmware
CIM 500 V01.05 (PICS)
Also known as
CIM 500, CIU 500, CIM500, Hydro MPC, Hydro Multi-E, Hydro Multi-B, Control MPC, CU 35X, CU 323
Source document
BACnet PICS CIM 500 - Protocol Implementation Conformance Statement for Grundfos CIM 500 BACnet IP for Grundfos pumps and booster systems · rev. 2014-04-25
Download CSV 174 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Grundfos CIM 500 BACnet IP (booster systems)

Integration in brief

Take bus control with BO 0 = 1, then start or stop the booster with MO 1 and write the setpoint to AO 0 (and the control mode to MO 0 on Hydro MPC). Read control source, rotation status, actual setpoint and the system fault and warning codes; reset alarms with BO 4.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0Set control sourceTakes bus control (1) or gives it back (0)Write
MO 1Set operating modeStart/stop: 1 = Start, 2 = StopWrite
MO 0Set control modeControl mode (Hydro MPC only)Write
AO 0Set setpointSystem setpoint in %Write
BO 4Reset faultResets an alarm on a 0-to-1 edge (bus control only)Write
BI 0Control source statusConfirms bus control (1) or local (0)Read
BI 2Rotation statusOne or more pumps runningRead
AI 9Actual setpointSetpoint actually in useRead
AI 0Fault codeActive Grundfos alarm codeRead

Enable & remote start

Set control source BO 0 = 1 (bus control); 0 = local control (default). MO 0, MO 1 and AO 0 only act while bus control is enabled; BI 0 confirms the active source.

Network setup

Watch out for

Grundfos CIM 500 BACnet IP (booster systems) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

174 of 174 shown
Type
Access
Show
Grundfos CIM 500 BACnet IP (booster systems) BACnet Points List
DescriptionStates
BImin0Control source statusStatus of the actual control sourceRead0=Local control, 1=Bus control
BImin2Rotation statusRead0=No rotation, 1=Rotation (one or more pumps running)
BI3At minimum speedAvailable on MPC and Multi-ERead0=Not running at minimum speed, 1=Running at minimum speed
BI4At maximum speedAvailable on MPC and Multi-ERead0=Not running at maximum speed, 1=Running at maximum speed
BI5Standby pumps activeHydro MPC onlyRead0=Standby pumps not active, 1=Standby pumps active
BI6Pressure relief activeHydro MPC onlyRead0=Pressure relief not active, 1=Pressure relief active
BI7Soft pressure activeHydro MPC onlyRead0=Soft pressure not active, 1=Soft pressure active
BI8Low-flow boost activeHydro MPC onlyRead0=Low-flow boost not active, 1=Low-flow boost active
BI9Low-flow stop activeAvailable on Multi-B and MPCRead0=Low-flow stop not active, 1=Low-flow stop active
BI10Alternative setpoint activeHydro MPC onlyRead0=Alternative setpoint not active, 1=Alternative setpoint active
BI11Digital input 1 statusRead0=Not active, 1=Active
BI12Digital input 2 statusRead0=Not active, 1=Active
BI13Digital input 3 statusRead0=Not active, 1=Active
BI14Digital output 1 statusRead0=Not active, 1=Active
BI15Digital output 2 statusRead0=Not active, 1=Active
BI16Subpump 1 presenceRead0=Subpump not present, 1=Subpump present
BI17Subpump 1 communication statusRead0=Communication OK, 1=Communication fault
BI18Subpump 2 presenceRead0=Subpump not present, 1=Subpump present
BI19Subpump 2 communication statusRead0=Communication OK, 1=Communication fault
BI20Subpump 3 presenceRead0=Subpump not present, 1=Subpump present
BI21Subpump 3 communication statusRead0=Communication OK, 1=Communication fault
BI22Subpump 4 presenceRead0=Subpump not present, 1=Subpump present
BI23Subpump 4 communication statusRead0=Communication OK, 1=Communication fault
BI24Subpump 5 presenceAvailable on MPC and Multi-ERead0=Subpump not present, 1=Subpump present
BI25Subpump 5 communication statusAvailable on MPC and Multi-ERead0=Communication OK, 1=Communication fault
BI26Subpump 6 presenceAvailable on MPC and Multi-ERead0=Subpump not present, 1=Subpump present
BI27Subpump 6 communication statusAvailable on MPC and Multi-ERead0=Communication OK, 1=Communication fault
BI28Fault simulation statusAvailable on Multi-B and MPCRead0=Fault simulation disabled, 1=Fault simulation enabled
BI32Subpump 1 auto modeAvailable on Multi-B and MPCRead0=Manual control, 1=Auto-control
BI33Subpump 2 auto modeAvailable on Multi-B and MPCRead0=Manual control, 1=Auto-control
BI34Subpump 3 auto modeAvailable on Multi-B and MPCRead0=Manual control, 1=Auto-control
BI35Subpump 4 auto modeAvailable on Multi-B and MPCRead0=Manual control, 1=Auto-control
BI36Subpump 5 auto modeHydro MPC onlyRead0=Manual control, 1=Auto-control
BI37Subpump 6 auto modeHydro MPC onlyRead0=Manual control, 1=Auto-control
BI38Setpoint influence activeHydro MPC onlyRead0=No influence on setpoint, 1=Setpoint influence active
BI40Pilot pump auto modeHydro MPC onlyRead0=Manual control, 1=Auto-control
BI41Pilot pump presenceHydro MPC onlyRead0=Pilot pump not present, 1=Pilot pump present
BI42Pilot pump communication statusHydro MPC onlyRead0=Communication OK, 1=Communication fault
BI43Back-up pump auto modeHydro MPC onlyRead0=Manual control, 1=Auto-control
BI44Back-up pump presenceHydro MPC onlyRead0=Backup pump not present, 1=Backup pump present
BI45Back-up pump communication statusHydro MPC onlyRead0=Communication OK, 1=Communication fault
BOmin0Set control sourceSet to 1 for BACnet (bus) controlWrite0=Local control (default), 1=Bus control
BOmin4Reset faultResets alarm on rising edge (bus control only)Write0=No resetting (default), 1=Resetting
BO5Fault simulationEnables fault simulation (Multi-B and MPC)Write0=Disabled (default), 1=Enabled
MI0Actual control modeReads the current control modeRead1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=RESERVED, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage
MI1Actual operating modeReads the current operating modeRead1=Start (normal), 2=Stop, 3=Minimum, 4=Maximum
MI3CIM statusCIM module status, for fault findingRead1=OK, 2=EEPROM fault, 3=Memory fault
MI4Subpump 1 control sourceAvailable on Multi-B and MPCRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MI5Subpump 2 control sourceAvailable on Multi-B and MPCRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MI6Subpump 3 control sourceAvailable on Multi-B and MPCRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MI7Subpump 4 control sourceAvailable on Multi-B and MPCRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MI8Subpump 5 control sourceHydro MPC onlyRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MI9Subpump 6 control sourceHydro MPC onlyRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MI10Application typeAvailable on Multi-B and MPCRead1=Pressure boosting, 2=Heating pumps on hot side, 3=Heating pumps on cold side, 4=AirCon pumps on hot side, 5=AirCon pumps on cold side, 6=MPC S2000 heating pumps on hot side, 7=MPC S2000 heating pumps on cold side, 8=MPC S2000 AirCon pumps on hot side, 9=MPC S2000 AirCon pumps on cold side, 10=Tank filling, 11=Tank filling (float switches), 12=Undefined
MI11Feedback sensor unitAvailable on Multi-B and MPCRead1=Unknown, 2=bar, 3=mbar, 4=m, 5=kPa, 6=psi, 7=ft, 8=m³/h, 9=m³/s, 10=l/s, 11=gpm, 12=°C, 13=°F, 14=%, 15=K, 16=W
MI12Pilot pump control sourceHydro MPC onlyRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MI13Back-up pump control sourceHydro MPC onlyRead1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control
MOmin0Set control modeSets control mode with bus control (Hydro MPC only)Write1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=RESERVED, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage. Note: Hydro Multi-E always runs in constant-pressure mode
MOmin1Set operating modeSets operating mode with bus controlWrite1=Start (normal), 2=Stop, 3=Minimum (Hydro MPC only), 4=Maximum (Hydro MPC and Hydro Multi-E only)
MO2Product simulationSimulated product for testing without a booster connectedWrite1=Disabled, 5=Hydro Multi-E, 6=Hydro MPC, 7=Hydro Multi-B
MO3Control subpump 1Manual control of subpump 1 (Multi-B and MPC)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
MO4Control subpump 2Manual control of subpump 2 (Multi-B and MPC)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
MO5Control subpump 3Manual control of subpump 3 (Multi-B and MPC)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
MO6Control subpump 4Manual control of subpump 4 (Multi-B and MPC)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
MO7Control subpump 5Manual control of subpump 5 (Hydro MPC only)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
MO8Control subpump 6Manual control of subpump 6 (Hydro MPC only)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
MO9Control pilot pumpManual control of pilot pump (Hydro MPC only)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
MO10Control back-up pumpManual control of back-up pump (Hydro MPC only)Write1=Automatic control (default), 2=Forced start (not available), 3=Forced stop
AImin0Fault codeGrundfos fault codeRead
AI1Warning codeGrundfos warning codeRead
AI3CapacityActual capacity value (process feedback)%Read
AI4HeadActual system head/pressure (MPC and Multi-E, needs sensor)barRead
AI5FlowActual system flow (MPC and Multi-E, needs sensor)m³/hRead
AI6Relative performancePerformance relative to maximum performance%Read
AImin9Actual setpoint%Read
AI10Motor currentActual motor current (Hydro Multi-E only)ARead
AI13PowerTotal power consumption of the systemWRead
AI15Inlet pressureSystem inlet pressure (Multi-B and MPC, needs sensor)barRead
AI16Remote pressureMeasured pressure at external sensor (Hydro MPC only, needs sensor)barRead
AI17LevelTank level (needs sensor)mRead
AI20Remote temperatureTemperature at external sensor (MPC and Multi-E, needs sensor)°CRead
AI25Auxiliary sensor inputAvailable on Multi-B and Multi-E, needs sensor%Read
AI26Specific EnergySpecific energy of the system (Hydro MPC only, needs sensor)kWh/m³Read
AI27RuntimeTotal operating time of the systemhRead
AI30Energy consumptionTotal energy consumption of the systemkWhRead
AI33Ambient temperatureHydro MPC only, needs sensor°CRead
AI34Forward temperatureFlow-pipe temperature (Hydro MPC only, needs sensor)°CRead
AI35Return temperatureReturn-pipe temperature (Hydro MPC only, needs sensor)°CRead
AI36Differential temperatureHydro MPC only, needs sensor°CRead
AI37Outlet pressureSystem outlet pressure (Multi-B and MPC, needs sensor)barRead
AI38Feed tank levelActual level in the feed tank (Hydro MPC only, needs sensor)mRead
AI39Subpump1 fault codeFault code, subpump 1Read
AI40Subpump 1 runtimeTotal operating time, subpump 1hRead
AI41Subpump 1 speedActual speed, subpump 1 (Multi-B and MPC)%Read
AI42Subpump 2 fault codeFault code, subpump 2Read
AI43Subpump 2 runtimeTotal operating time, subpump 2hRead
AI44Subpump 2 speedActual speed, subpump 2 (Multi-B and MPC)%Read
AI45Subpump 3 fault codeFault code, subpump 3Read
AI46Subpump 3 runtimeTotal operating time, subpump 3hRead
AI47Subpump 3 speedActual speed, subpump 3 (Multi-B and MPC)%Read
AI48Subpump 4 fault codeFault code, subpump 4Read
AI49Subpump 4 runtimeTotal operating time, subpump 4hRead
AI50Subpump 4 speedActual speed, subpump 4 (Multi-B and MPC)%Read
AI51Subpump 5 fault codeFault code, subpump 5 (MPC and Multi-E)Read
AI52Subpump 5 runtimeTotal operating time, subpump 5 (MPC and Multi-E)hRead
AI53Subpump 5 speedActual speed, subpump 5 (Hydro MPC only)%Read
AI54Subpump 6 fault codeFault code, subpump 6 (MPC and Multi-E)Read
AI55Subpump 6 runtimeTotal operating time, subpump 6 (MPC and Multi-E)hRead
AI56Subpump 6 speedActual speed, subpump 6 (Hydro MPC only)%Read
AI58User setpointUser-defined setpoint (Multi-B and MPC)%Read
AI59Analogue influenceAnalog setpoint influence (Multi-B and MPC)%Read
AI60Power-on counterNumber of power-on cycles (Multi-B and MPC)Read
AI61Subpump 1Line current, subpump 1 (Multi-B and MPC)ARead
AI62Subpump 1Power consumption, subpump 1 (Multi-B and MPC)WRead
AI63Subpump 1Motor temperature, subpump 1 (Multi-B and MPC)°CRead
AI64Subpump 1Number of starts, subpump 1 (Multi-B and MPC)Read
AI65Subpump 2Line current, subpump 2 (Multi-B and MPC)ARead
AI66Subpump 2Power consumption, subpump 2 (Multi-B and MPC)WRead
AI67Subpump 2Motor temperature, subpump 2 (Multi-B and MPC)°CRead
AI68Subpump 2Number of starts, subpump 2 (Multi-B and MPC)Read
AI69Subpump 3Line current, subpump 3 (Multi-B and MPC)ARead
AI70Subpump 3Power consumption, subpump 3 (Multi-B and MPC)WRead
AI71Subpump 3Motor temperature, subpump 3 (Multi-B and MPC)°CRead
AI72Subpump 3Number of starts, subpump 3 (Multi-B and MPC)Read
AI73Subpump 4Line current, subpump 4 (Multi-B and MPC)ARead
AI74Subpump 4Power consumption, subpump 4 (Multi-B and MPC)WRead
AI75Subpump 4Motor temperature, subpump 4 (Multi-B and MPC)°CRead
AI76Subpump 4Number of starts, subpump 4 (Multi-B and MPC)Read
AI77Subpump 5Line current, subpump 5 (Hydro MPC only)ARead
AI78Subpump 5Power consumption, subpump 5 (Hydro MPC only)WRead
AI79Subpump 5Motor temperature, subpump 5 (Hydro MPC only)°CRead
AI80Subpump 5Number of starts, subpump 5 (Hydro MPC only)Read
AI81Subpump 6Line current, subpump 6 (Hydro MPC only)ARead
AI82Subpump 6Power consumption, subpump 6 (Hydro MPC only)WRead
AI83Subpump 6Motor temperature, subpump 6 (Hydro MPC only)°CRead
AI84Subpump 6Number of starts, subpump 6 (Hydro MPC only)Read
AI85Minimum of feedback sensorFeedback sensor minimum, unit per MI 11 (MPC and Multi-E)Read
AI86Maximum of feedback sensorFeedback sensor maximum, unit per MI 11 (MPC and Multi-E)Read
AI87Actual tank-filling tank heightTank height in tank-filling mode (Hydro Multi-B only)mRead
AI88Actual tank-filling start limitStart limit in percent of tank height (Hydro Multi-B only)%Read
AI89Actual tank-filling stop limitStop limit in percent of tank height (Hydro Multi-B only)%Read
AI90Actual tank-filling alarm high-limitAlarm high-limit in percent of tank height (Hydro Multi-B only)%Read
AI91Actual tank-filling warning low-limitWarning low-limit in percent of tank height (Hydro Multi-B only)%Read
AI96Specific energy averageAverage specific energy (Hydro MPC only, needs sensor)kWh/m³Read
AI97Flow measurement 1Hydro MPC only, needs sensorm³/hRead
AI98Flow measurement 2Hydro MPC only, needs sensorm³/hRead
AI99Flow measurement 3Hydro MPC only, needs sensorm³/hRead
AI100Pilot pump fault codeFault code, pilot pump (Hydro MPC only)Read
AI101Pilot pump runtimeTotal operating time, pilot pump (Hydro MPC only)hRead
AI102Pilot pump speedActual speed, pilot pump (Hydro MPC only)%Read
AI103Pilot pump line currentLine current, pilot pump (Hydro MPC only)ARead
AI104Pilot pump power consumptionPower consumption, pilot pump (Hydro MPC only)WRead
AI105Pilot pump motor temperatureMotor temperature, pilot pump (Hydro MPC only)°CRead
AI106Pilot pump number of startsNumber of starts, pilot pump (Hydro MPC only)Read
AI107Back-up pump fault codeFault code, backup pump (Hydro MPC only)Read
AI108Back-up pump runtimeTotal operating time, backup pump (Hydro MPC only)hRead
AI109Back-up pump speedActual speed, backup pump (Hydro MPC only)%Read
AI110Back-up pump line currentLine current, backup pump (Hydro MPC only)ARead
AI111Back-up pump power consumptionPower consumption, backup pump (Hydro MPC only)WRead
AI112Back-up pump motor temperatureMotor temperature, backup pump (Hydro MPC only)°CRead
AI113Back-up pump number of startsNumber of starts, backup pump (Hydro MPC only)Read
AOmin0Set setpointBooster setpoint when bus control is on; 0 does not stop%Write
AO1Tank-filling start limitStart limit, % of tank height (Hydro Multi-B only)%Write
AO2Tank-filling stop limitStop limit, % of tank height (Hydro Multi-B only)%Write
AO3Tank-filling alarm high-limitAlarm high-limit, % of tank height (Hydro Multi-B only)%Write
AO4Tank-filling warning low-limitWarning low-limit, % of tank height (Hydro Multi-B only)%Write
AV0Custom device object instance numberCustom device instance; used with DIP switch SW3Write
AV4Simulation event codeGrundfos event code to simulate (e.g. 210 = pressure high)Write
AV5Simulation device typeDevice type of simulated event (Multi-B and MPC)Write0=Controller, 2=Pump, 3=IO 351, 4=Primary sensor, 7=IO 351, 8=System, 9=Analog input, 10=Pilot booster system, 11=Limit-exceeded function
AV6Simulation device numberPump (1-6) or sensor (1-7) number of simulated eventWrite
AV7Simulation event action typeAction of the simulated event (Hydro MPC only)Write0=Go to operating mode "Stop", 1=Go to operating mode "Stop" (delay), 2=Go to operating mode "Minimum", 3=Go to operating mode "User- defined", 4=Go to operating mode "Maximum", 5=Set pumps in source mode to "Local control", 6=No action (warning only), 7=Go to operating mode "Emergency run"
AV8Simulation event reset typeResetting type for simulated event (Hydro MPC only)Write0=Manual resetting, 1=Automatic resetting
AV10Proportional-control reductionProportional-pressure reduction (Hydro MPC only)%Write
AV11Proportional-control flow max.Proportional-pressure max. flow (Hydro MPC only)m³/hWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CIM 500 BACnet IP (booster systems) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Grundfos CIM 500 BACnet IP (booster systems)

How many BACnet points does the Grundfos CIM 500 BACnet IP (booster systems) have?

This list has 174 BACnet objects: 93 analog inputs, 5 analog outputs, 8 analog values, 41 binary inputs, 3 binary outputs, 13 multi-state inputs, 11 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Grundfos CIM 500 BACnet IP (booster systems) BACnet points are writable?

27 of the 174 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Grundfos CIM 500 BACnet IP (booster systems) BACnet documentation?

The source is BACnet PICS CIM 500 - Protocol Implementation Conformance Statement for Grundfos CIM 500 BACnet IP for Grundfos pumps and booster systems, revision 2014-04-25, published free by Grundfos at https://www.bacnetinternational.net/catalog/manu/grundfos%20management%20as/BACnet_PICS_CIM500_Print_88363.pdf.

What are the minimum BACnet points to integrate the Grundfos CIM 500 BACnet IP (booster systems)?

Start with BO 0 Set control source (Takes bus control (1) or gives it back (0)); MO 1 Set operating mode (Start/stop: 1 = Start, 2 = Stop); MO 0 Set control mode (Control mode (Hydro MPC only)); AO 0 Set setpoint (System setpoint in %); BO 4 Reset fault (Resets an alarm on a 0-to-1 edge (bus control only)); BI 0 Control source status (Confirms bus control (1) or local (0)); BI 2 Rotation status (One or more pumps running); AI 9 Actual setpoint (Setpoint actually in use); AI 0 Fault code (Active Grundfos alarm code).

How do I enable BMS control of the Grundfos CIM 500 BACnet IP (booster systems)?

Set control source BO 0 = 1 (bus control); 0 = local control (default). MO 0, MO 1 and AO 0 only act while bus control is enabled; BI 0 confirms the active source.

How do I check these points on the real CIM 500 BACnet IP (booster systems)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Grundfos BACnet points lists