- Home
- BACnet points lists
- Grundfos
- CIM 500 BACnet IP (booster systems)
Booster pump system communication module · BACnet points list
Grundfos CIM 500 BACnet IP (booster systems) BACnet points list
Updated 28 October 2026
The CIM 500 module gives Grundfos booster systems a BACnet IP interface. The booster object list differs from the single-pump profile: it adds per-subpump presence, communication, auto-mode, fault code, runtime, speed, current, power, motor temperature and start counts for up to six subpumps plus pilot and back-up pumps, tank-filling limits and system pressures, levels and flows. Availability depends on the booster type and fitted sensors.
This page lists 174 BACnet objects for the Grundfos CIM 500 BACnet IP (booster systems) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Grundfos’s own free documentation, linked below.
- Manufacturer
- Grundfos
- Model
- CIM 500 BACnet IP (booster systems)
- Equipment
- Booster pump system communication module
- Equipment type
- VFDs & pumps
- BACnet objects
- 174 (27 writable)
- Transport
- BACnet IP
- Firmware
- CIM 500 V01.05 (PICS)
- Also known as
- CIM 500, CIU 500, CIM500, Hydro MPC, Hydro Multi-E, Hydro Multi-B, Control MPC, CU 35X, CU 323
BMS integration notes: Grundfos CIM 500 BACnet IP (booster systems)
Take bus control with BO 0 = 1, then start or stop the booster with MO 1 and write the setpoint to AO 0 (and the control mode to MO 0 on Hydro MPC). Read control source, rotation status, actual setpoint and the system fault and warning codes; reset alarms with BO 4.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | Set control source | Takes bus control (1) or gives it back (0) | Write |
| MO 1 | Set operating mode | Start/stop: 1 = Start, 2 = Stop | Write |
| MO 0 | Set control mode | Control mode (Hydro MPC only) | Write |
| AO 0 | Set setpoint | System setpoint in % | Write |
| BO 4 | Reset fault | Resets an alarm on a 0-to-1 edge (bus control only) | Write |
| BI 0 | Control source status | Confirms bus control (1) or local (0) | Read |
| BI 2 | Rotation status | One or more pumps running | Read |
| AI 9 | Actual setpoint | Setpoint actually in use | Read |
| AI 0 | Fault code | Active Grundfos alarm code | Read |
Enable & remote start
Set control source BO 0 = 1 (bus control); 0 = local control (default). MO 0, MO 1 and AO 0 only act while bus control is enabled; BI 0 confirms the active source.
Network setup
- BACnet IP only (Annex J); no segmentation.
- AV 0 holds a custom device instance (range 0-0x3FFFFE, default 0xE7) that is used together with DIP switch SW3.
- MO 2 product simulation lets you commission the BMS side with no booster connected.
Watch out for
- A setpoint of 0 on AO 0 does not stop the booster; use MO 1 = 2 (Stop).
- MO 3-10 forced start is listed as not available; only automatic or forced stop work.
- Many points depend on the booster type and fitted sensors; check the availability note in each description.
Grundfos CIM 500 BACnet IP (booster systems) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | Control source status | Status of the actual control source | Read | 0=Local control, 1=Bus control | |
| BImin | 2 | Rotation status | Read | 0=No rotation, 1=Rotation (one or more pumps running) | ||
| BI | 3 | At minimum speed | Available on MPC and Multi-E | Read | 0=Not running at minimum speed, 1=Running at minimum speed | |
| BI | 4 | At maximum speed | Available on MPC and Multi-E | Read | 0=Not running at maximum speed, 1=Running at maximum speed | |
| BI | 5 | Standby pumps active | Hydro MPC only | Read | 0=Standby pumps not active, 1=Standby pumps active | |
| BI | 6 | Pressure relief active | Hydro MPC only | Read | 0=Pressure relief not active, 1=Pressure relief active | |
| BI | 7 | Soft pressure active | Hydro MPC only | Read | 0=Soft pressure not active, 1=Soft pressure active | |
| BI | 8 | Low-flow boost active | Hydro MPC only | Read | 0=Low-flow boost not active, 1=Low-flow boost active | |
| BI | 9 | Low-flow stop active | Available on Multi-B and MPC | Read | 0=Low-flow stop not active, 1=Low-flow stop active | |
| BI | 10 | Alternative setpoint active | Hydro MPC only | Read | 0=Alternative setpoint not active, 1=Alternative setpoint active | |
| BI | 11 | Digital input 1 status | Read | 0=Not active, 1=Active | ||
| BI | 12 | Digital input 2 status | Read | 0=Not active, 1=Active | ||
| BI | 13 | Digital input 3 status | Read | 0=Not active, 1=Active | ||
| BI | 14 | Digital output 1 status | Read | 0=Not active, 1=Active | ||
| BI | 15 | Digital output 2 status | Read | 0=Not active, 1=Active | ||
| BI | 16 | Subpump 1 presence | Read | 0=Subpump not present, 1=Subpump present | ||
| BI | 17 | Subpump 1 communication status | Read | 0=Communication OK, 1=Communication fault | ||
| BI | 18 | Subpump 2 presence | Read | 0=Subpump not present, 1=Subpump present | ||
| BI | 19 | Subpump 2 communication status | Read | 0=Communication OK, 1=Communication fault | ||
| BI | 20 | Subpump 3 presence | Read | 0=Subpump not present, 1=Subpump present | ||
| BI | 21 | Subpump 3 communication status | Read | 0=Communication OK, 1=Communication fault | ||
| BI | 22 | Subpump 4 presence | Read | 0=Subpump not present, 1=Subpump present | ||
| BI | 23 | Subpump 4 communication status | Read | 0=Communication OK, 1=Communication fault | ||
| BI | 24 | Subpump 5 presence | Available on MPC and Multi-E | Read | 0=Subpump not present, 1=Subpump present | |
| BI | 25 | Subpump 5 communication status | Available on MPC and Multi-E | Read | 0=Communication OK, 1=Communication fault | |
| BI | 26 | Subpump 6 presence | Available on MPC and Multi-E | Read | 0=Subpump not present, 1=Subpump present | |
| BI | 27 | Subpump 6 communication status | Available on MPC and Multi-E | Read | 0=Communication OK, 1=Communication fault | |
| BI | 28 | Fault simulation status | Available on Multi-B and MPC | Read | 0=Fault simulation disabled, 1=Fault simulation enabled | |
| BI | 32 | Subpump 1 auto mode | Available on Multi-B and MPC | Read | 0=Manual control, 1=Auto-control | |
| BI | 33 | Subpump 2 auto mode | Available on Multi-B and MPC | Read | 0=Manual control, 1=Auto-control | |
| BI | 34 | Subpump 3 auto mode | Available on Multi-B and MPC | Read | 0=Manual control, 1=Auto-control | |
| BI | 35 | Subpump 4 auto mode | Available on Multi-B and MPC | Read | 0=Manual control, 1=Auto-control | |
| BI | 36 | Subpump 5 auto mode | Hydro MPC only | Read | 0=Manual control, 1=Auto-control | |
| BI | 37 | Subpump 6 auto mode | Hydro MPC only | Read | 0=Manual control, 1=Auto-control | |
| BI | 38 | Setpoint influence active | Hydro MPC only | Read | 0=No influence on setpoint, 1=Setpoint influence active | |
| BI | 40 | Pilot pump auto mode | Hydro MPC only | Read | 0=Manual control, 1=Auto-control | |
| BI | 41 | Pilot pump presence | Hydro MPC only | Read | 0=Pilot pump not present, 1=Pilot pump present | |
| BI | 42 | Pilot pump communication status | Hydro MPC only | Read | 0=Communication OK, 1=Communication fault | |
| BI | 43 | Back-up pump auto mode | Hydro MPC only | Read | 0=Manual control, 1=Auto-control | |
| BI | 44 | Back-up pump presence | Hydro MPC only | Read | 0=Backup pump not present, 1=Backup pump present | |
| BI | 45 | Back-up pump communication status | Hydro MPC only | Read | 0=Communication OK, 1=Communication fault | |
| BOmin | 0 | Set control source | Set to 1 for BACnet (bus) control | Write | 0=Local control (default), 1=Bus control | |
| BOmin | 4 | Reset fault | Resets alarm on rising edge (bus control only) | Write | 0=No resetting (default), 1=Resetting | |
| BO | 5 | Fault simulation | Enables fault simulation (Multi-B and MPC) | Write | 0=Disabled (default), 1=Enabled | |
| MI | 0 | Actual control mode | Reads the current control mode | Read | 1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=RESERVED, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage | |
| MI | 1 | Actual operating mode | Reads the current operating mode | Read | 1=Start (normal), 2=Stop, 3=Minimum, 4=Maximum | |
| MI | 3 | CIM status | CIM module status, for fault finding | Read | 1=OK, 2=EEPROM fault, 3=Memory fault | |
| MI | 4 | Subpump 1 control source | Available on Multi-B and MPC | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MI | 5 | Subpump 2 control source | Available on Multi-B and MPC | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MI | 6 | Subpump 3 control source | Available on Multi-B and MPC | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MI | 7 | Subpump 4 control source | Available on Multi-B and MPC | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MI | 8 | Subpump 5 control source | Hydro MPC only | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MI | 9 | Subpump 6 control source | Hydro MPC only | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MI | 10 | Application type | Available on Multi-B and MPC | Read | 1=Pressure boosting, 2=Heating pumps on hot side, 3=Heating pumps on cold side, 4=AirCon pumps on hot side, 5=AirCon pumps on cold side, 6=MPC S2000 heating pumps on hot side, 7=MPC S2000 heating pumps on cold side, 8=MPC S2000 AirCon pumps on hot side, 9=MPC S2000 AirCon pumps on cold side, 10=Tank filling, 11=Tank filling (float switches), 12=Undefined | |
| MI | 11 | Feedback sensor unit | Available on Multi-B and MPC | Read | 1=Unknown, 2=bar, 3=mbar, 4=m, 5=kPa, 6=psi, 7=ft, 8=m³/h, 9=m³/s, 10=l/s, 11=gpm, 12=°C, 13=°F, 14=%, 15=K, 16=W | |
| MI | 12 | Pilot pump control source | Hydro MPC only | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MI | 13 | Back-up pump control source | Hydro MPC only | Read | 1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control | |
| MOmin | 0 | Set control mode | Sets control mode with bus control (Hydro MPC only) | Write | 1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=RESERVED, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage. Note: Hydro Multi-E always runs in constant-pressure mode | |
| MOmin | 1 | Set operating mode | Sets operating mode with bus control | Write | 1=Start (normal), 2=Stop, 3=Minimum (Hydro MPC only), 4=Maximum (Hydro MPC and Hydro Multi-E only) | |
| MO | 2 | Product simulation | Simulated product for testing without a booster connected | Write | 1=Disabled, 5=Hydro Multi-E, 6=Hydro MPC, 7=Hydro Multi-B | |
| MO | 3 | Control subpump 1 | Manual control of subpump 1 (Multi-B and MPC) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| MO | 4 | Control subpump 2 | Manual control of subpump 2 (Multi-B and MPC) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| MO | 5 | Control subpump 3 | Manual control of subpump 3 (Multi-B and MPC) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| MO | 6 | Control subpump 4 | Manual control of subpump 4 (Multi-B and MPC) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| MO | 7 | Control subpump 5 | Manual control of subpump 5 (Hydro MPC only) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| MO | 8 | Control subpump 6 | Manual control of subpump 6 (Hydro MPC only) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| MO | 9 | Control pilot pump | Manual control of pilot pump (Hydro MPC only) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| MO | 10 | Control back-up pump | Manual control of back-up pump (Hydro MPC only) | Write | 1=Automatic control (default), 2=Forced start (not available), 3=Forced stop | |
| AImin | 0 | Fault code | Grundfos fault code | Read | ||
| AI | 1 | Warning code | Grundfos warning code | Read | ||
| AI | 3 | Capacity | Actual capacity value (process feedback) | % | Read | |
| AI | 4 | Head | Actual system head/pressure (MPC and Multi-E, needs sensor) | bar | Read | |
| AI | 5 | Flow | Actual system flow (MPC and Multi-E, needs sensor) | m³/h | Read | |
| AI | 6 | Relative performance | Performance relative to maximum performance | % | Read | |
| AImin | 9 | Actual setpoint | % | Read | ||
| AI | 10 | Motor current | Actual motor current (Hydro Multi-E only) | A | Read | |
| AI | 13 | Power | Total power consumption of the system | W | Read | |
| AI | 15 | Inlet pressure | System inlet pressure (Multi-B and MPC, needs sensor) | bar | Read | |
| AI | 16 | Remote pressure | Measured pressure at external sensor (Hydro MPC only, needs sensor) | bar | Read | |
| AI | 17 | Level | Tank level (needs sensor) | m | Read | |
| AI | 20 | Remote temperature | Temperature at external sensor (MPC and Multi-E, needs sensor) | °C | Read | |
| AI | 25 | Auxiliary sensor input | Available on Multi-B and Multi-E, needs sensor | % | Read | |
| AI | 26 | Specific Energy | Specific energy of the system (Hydro MPC only, needs sensor) | kWh/m³ | Read | |
| AI | 27 | Runtime | Total operating time of the system | h | Read | |
| AI | 30 | Energy consumption | Total energy consumption of the system | kWh | Read | |
| AI | 33 | Ambient temperature | Hydro MPC only, needs sensor | °C | Read | |
| AI | 34 | Forward temperature | Flow-pipe temperature (Hydro MPC only, needs sensor) | °C | Read | |
| AI | 35 | Return temperature | Return-pipe temperature (Hydro MPC only, needs sensor) | °C | Read | |
| AI | 36 | Differential temperature | Hydro MPC only, needs sensor | °C | Read | |
| AI | 37 | Outlet pressure | System outlet pressure (Multi-B and MPC, needs sensor) | bar | Read | |
| AI | 38 | Feed tank level | Actual level in the feed tank (Hydro MPC only, needs sensor) | m | Read | |
| AI | 39 | Subpump1 fault code | Fault code, subpump 1 | Read | ||
| AI | 40 | Subpump 1 runtime | Total operating time, subpump 1 | h | Read | |
| AI | 41 | Subpump 1 speed | Actual speed, subpump 1 (Multi-B and MPC) | % | Read | |
| AI | 42 | Subpump 2 fault code | Fault code, subpump 2 | Read | ||
| AI | 43 | Subpump 2 runtime | Total operating time, subpump 2 | h | Read | |
| AI | 44 | Subpump 2 speed | Actual speed, subpump 2 (Multi-B and MPC) | % | Read | |
| AI | 45 | Subpump 3 fault code | Fault code, subpump 3 | Read | ||
| AI | 46 | Subpump 3 runtime | Total operating time, subpump 3 | h | Read | |
| AI | 47 | Subpump 3 speed | Actual speed, subpump 3 (Multi-B and MPC) | % | Read | |
| AI | 48 | Subpump 4 fault code | Fault code, subpump 4 | Read | ||
| AI | 49 | Subpump 4 runtime | Total operating time, subpump 4 | h | Read | |
| AI | 50 | Subpump 4 speed | Actual speed, subpump 4 (Multi-B and MPC) | % | Read | |
| AI | 51 | Subpump 5 fault code | Fault code, subpump 5 (MPC and Multi-E) | Read | ||
| AI | 52 | Subpump 5 runtime | Total operating time, subpump 5 (MPC and Multi-E) | h | Read | |
| AI | 53 | Subpump 5 speed | Actual speed, subpump 5 (Hydro MPC only) | % | Read | |
| AI | 54 | Subpump 6 fault code | Fault code, subpump 6 (MPC and Multi-E) | Read | ||
| AI | 55 | Subpump 6 runtime | Total operating time, subpump 6 (MPC and Multi-E) | h | Read | |
| AI | 56 | Subpump 6 speed | Actual speed, subpump 6 (Hydro MPC only) | % | Read | |
| AI | 58 | User setpoint | User-defined setpoint (Multi-B and MPC) | % | Read | |
| AI | 59 | Analogue influence | Analog setpoint influence (Multi-B and MPC) | % | Read | |
| AI | 60 | Power-on counter | Number of power-on cycles (Multi-B and MPC) | Read | ||
| AI | 61 | Subpump 1 | Line current, subpump 1 (Multi-B and MPC) | A | Read | |
| AI | 62 | Subpump 1 | Power consumption, subpump 1 (Multi-B and MPC) | W | Read | |
| AI | 63 | Subpump 1 | Motor temperature, subpump 1 (Multi-B and MPC) | °C | Read | |
| AI | 64 | Subpump 1 | Number of starts, subpump 1 (Multi-B and MPC) | Read | ||
| AI | 65 | Subpump 2 | Line current, subpump 2 (Multi-B and MPC) | A | Read | |
| AI | 66 | Subpump 2 | Power consumption, subpump 2 (Multi-B and MPC) | W | Read | |
| AI | 67 | Subpump 2 | Motor temperature, subpump 2 (Multi-B and MPC) | °C | Read | |
| AI | 68 | Subpump 2 | Number of starts, subpump 2 (Multi-B and MPC) | Read | ||
| AI | 69 | Subpump 3 | Line current, subpump 3 (Multi-B and MPC) | A | Read | |
| AI | 70 | Subpump 3 | Power consumption, subpump 3 (Multi-B and MPC) | W | Read | |
| AI | 71 | Subpump 3 | Motor temperature, subpump 3 (Multi-B and MPC) | °C | Read | |
| AI | 72 | Subpump 3 | Number of starts, subpump 3 (Multi-B and MPC) | Read | ||
| AI | 73 | Subpump 4 | Line current, subpump 4 (Multi-B and MPC) | A | Read | |
| AI | 74 | Subpump 4 | Power consumption, subpump 4 (Multi-B and MPC) | W | Read | |
| AI | 75 | Subpump 4 | Motor temperature, subpump 4 (Multi-B and MPC) | °C | Read | |
| AI | 76 | Subpump 4 | Number of starts, subpump 4 (Multi-B and MPC) | Read | ||
| AI | 77 | Subpump 5 | Line current, subpump 5 (Hydro MPC only) | A | Read | |
| AI | 78 | Subpump 5 | Power consumption, subpump 5 (Hydro MPC only) | W | Read | |
| AI | 79 | Subpump 5 | Motor temperature, subpump 5 (Hydro MPC only) | °C | Read | |
| AI | 80 | Subpump 5 | Number of starts, subpump 5 (Hydro MPC only) | Read | ||
| AI | 81 | Subpump 6 | Line current, subpump 6 (Hydro MPC only) | A | Read | |
| AI | 82 | Subpump 6 | Power consumption, subpump 6 (Hydro MPC only) | W | Read | |
| AI | 83 | Subpump 6 | Motor temperature, subpump 6 (Hydro MPC only) | °C | Read | |
| AI | 84 | Subpump 6 | Number of starts, subpump 6 (Hydro MPC only) | Read | ||
| AI | 85 | Minimum of feedback sensor | Feedback sensor minimum, unit per MI 11 (MPC and Multi-E) | Read | ||
| AI | 86 | Maximum of feedback sensor | Feedback sensor maximum, unit per MI 11 (MPC and Multi-E) | Read | ||
| AI | 87 | Actual tank-filling tank height | Tank height in tank-filling mode (Hydro Multi-B only) | m | Read | |
| AI | 88 | Actual tank-filling start limit | Start limit in percent of tank height (Hydro Multi-B only) | % | Read | |
| AI | 89 | Actual tank-filling stop limit | Stop limit in percent of tank height (Hydro Multi-B only) | % | Read | |
| AI | 90 | Actual tank-filling alarm high-limit | Alarm high-limit in percent of tank height (Hydro Multi-B only) | % | Read | |
| AI | 91 | Actual tank-filling warning low-limit | Warning low-limit in percent of tank height (Hydro Multi-B only) | % | Read | |
| AI | 96 | Specific energy average | Average specific energy (Hydro MPC only, needs sensor) | kWh/m³ | Read | |
| AI | 97 | Flow measurement 1 | Hydro MPC only, needs sensor | m³/h | Read | |
| AI | 98 | Flow measurement 2 | Hydro MPC only, needs sensor | m³/h | Read | |
| AI | 99 | Flow measurement 3 | Hydro MPC only, needs sensor | m³/h | Read | |
| AI | 100 | Pilot pump fault code | Fault code, pilot pump (Hydro MPC only) | Read | ||
| AI | 101 | Pilot pump runtime | Total operating time, pilot pump (Hydro MPC only) | h | Read | |
| AI | 102 | Pilot pump speed | Actual speed, pilot pump (Hydro MPC only) | % | Read | |
| AI | 103 | Pilot pump line current | Line current, pilot pump (Hydro MPC only) | A | Read | |
| AI | 104 | Pilot pump power consumption | Power consumption, pilot pump (Hydro MPC only) | W | Read | |
| AI | 105 | Pilot pump motor temperature | Motor temperature, pilot pump (Hydro MPC only) | °C | Read | |
| AI | 106 | Pilot pump number of starts | Number of starts, pilot pump (Hydro MPC only) | Read | ||
| AI | 107 | Back-up pump fault code | Fault code, backup pump (Hydro MPC only) | Read | ||
| AI | 108 | Back-up pump runtime | Total operating time, backup pump (Hydro MPC only) | h | Read | |
| AI | 109 | Back-up pump speed | Actual speed, backup pump (Hydro MPC only) | % | Read | |
| AI | 110 | Back-up pump line current | Line current, backup pump (Hydro MPC only) | A | Read | |
| AI | 111 | Back-up pump power consumption | Power consumption, backup pump (Hydro MPC only) | W | Read | |
| AI | 112 | Back-up pump motor temperature | Motor temperature, backup pump (Hydro MPC only) | °C | Read | |
| AI | 113 | Back-up pump number of starts | Number of starts, backup pump (Hydro MPC only) | Read | ||
| AOmin | 0 | Set setpoint | Booster setpoint when bus control is on; 0 does not stop | % | Write | |
| AO | 1 | Tank-filling start limit | Start limit, % of tank height (Hydro Multi-B only) | % | Write | |
| AO | 2 | Tank-filling stop limit | Stop limit, % of tank height (Hydro Multi-B only) | % | Write | |
| AO | 3 | Tank-filling alarm high-limit | Alarm high-limit, % of tank height (Hydro Multi-B only) | % | Write | |
| AO | 4 | Tank-filling warning low-limit | Warning low-limit, % of tank height (Hydro Multi-B only) | % | Write | |
| AV | 0 | Custom device object instance number | Custom device instance; used with DIP switch SW3 | Write | ||
| AV | 4 | Simulation event code | Grundfos event code to simulate (e.g. 210 = pressure high) | Write | ||
| AV | 5 | Simulation device type | Device type of simulated event (Multi-B and MPC) | Write | 0=Controller, 2=Pump, 3=IO 351, 4=Primary sensor, 7=IO 351, 8=System, 9=Analog input, 10=Pilot booster system, 11=Limit-exceeded function | |
| AV | 6 | Simulation device number | Pump (1-6) or sensor (1-7) number of simulated event | Write | ||
| AV | 7 | Simulation event action type | Action of the simulated event (Hydro MPC only) | Write | 0=Go to operating mode "Stop", 1=Go to operating mode "Stop" (delay), 2=Go to operating mode "Minimum", 3=Go to operating mode "User- defined", 4=Go to operating mode "Maximum", 5=Set pumps in source mode to "Local control", 6=No action (warning only), 7=Go to operating mode "Emergency run" | |
| AV | 8 | Simulation event reset type | Resetting type for simulated event (Hydro MPC only) | Write | 0=Manual resetting, 1=Automatic resetting | |
| AV | 10 | Proportional-control reduction | Proportional-pressure reduction (Hydro MPC only) | % | Write | |
| AV | 11 | Proportional-control flow max. | Proportional-pressure max. flow (Hydro MPC only) | m³/h | Write |
No points match these filters.
Integration notes
- For single Grundfos pumps (MAGNA3, E-pumps, CUE) see the CIM 300 / CIM 500 pump profile instead.
- Descriptions show which booster types support each point (Hydro Multi-B, Hydro MPC, Hydro Multi-E) and when a sensor is needed.
- AI 61-84 are printed with the bare name 'Subpump N'; the description says which value (current, power, motor temperature, starts) each one is.
- MI 12 and MI 13 have no access column in the source; they are listed as read-only.
- This 2014 PICS (BACnet protocol revision 9) does not list the BACnet watchdog object found in the later CIM functional profile.
- Hydro Multi-E always runs in constant pressure mode; MO 0 only applies to Hydro MPC.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CIM 500 BACnet IP (booster systems) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Grundfos CIM 500 BACnet IP (booster systems)
How many BACnet points does the Grundfos CIM 500 BACnet IP (booster systems) have?
This list has 174 BACnet objects: 93 analog inputs, 5 analog outputs, 8 analog values, 41 binary inputs, 3 binary outputs, 13 multi-state inputs, 11 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Grundfos CIM 500 BACnet IP (booster systems) BACnet points are writable?
27 of the 174 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Grundfos CIM 500 BACnet IP (booster systems) BACnet documentation?
The source is BACnet PICS CIM 500 - Protocol Implementation Conformance Statement for Grundfos CIM 500 BACnet IP for Grundfos pumps and booster systems, revision 2014-04-25, published free by Grundfos at https://www.bacnetinternational.net/catalog/manu/grundfos%20management%20as/BACnet_PICS_CIM500_Print_88363.pdf.
What are the minimum BACnet points to integrate the Grundfos CIM 500 BACnet IP (booster systems)?
Start with BO 0 Set control source (Takes bus control (1) or gives it back (0)); MO 1 Set operating mode (Start/stop: 1 = Start, 2 = Stop); MO 0 Set control mode (Control mode (Hydro MPC only)); AO 0 Set setpoint (System setpoint in %); BO 4 Reset fault (Resets an alarm on a 0-to-1 edge (bus control only)); BI 0 Control source status (Confirms bus control (1) or local (0)); BI 2 Rotation status (One or more pumps running); AI 9 Actual setpoint (Setpoint actually in use); AI 0 Fault code (Active Grundfos alarm code).
How do I enable BMS control of the Grundfos CIM 500 BACnet IP (booster systems)?
Set control source BO 0 = 1 (bus control); 0 = local control (default). MO 0, MO 1 and AO 0 only act while bus control is enabled; BI 0 confirms the active source.
How do I check these points on the real CIM 500 BACnet IP (booster systems)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Grundfos BACnet points lists
Source: BACnet PICS CIM 500 - Protocol Implementation Conformance Statement for Grundfos CIM 500 BACnet IP for Grundfos pumps and booster systems · rev. 2014-04-25. Object names, instances and units are reproduced as published; descriptions are our own.