 "manufacturer": "Grundfos",
 "manufacturer_slug": "grundfos",
 "model": "CIM 500 BACnet IP (booster systems)",
 "model_slug": "cim-500-booster-systems",
 "aliases": [
  "CIM 500",
  "CIU 500",
  "CIM500",
  "Hydro MPC",
  "Hydro Multi-E",
  "Hydro Multi-B",
  "Control MPC",
  "CU 35X",
  "CU 323"
 ],
 "equipment_type": "Booster pump system communication module",
 "applies_to": "Grundfos Hydro MPC / Control MPC (CU 35X), Hydro Multi-E and Hydro Multi-B (CU 323) booster systems fitted with a CIM 500 (or CIU 500) BACnet IP module.",
 "summary": "The CIM 500 module gives Grundfos booster systems a BACnet IP interface. The booster object list differs from the single-pump profile: it adds per-subpump presence, communication, auto-mode, fault code, runtime, speed, current, power, motor temperature and start counts for up to six subpumps plus pilot and back-up pumps, tank-filling limits and system pressures, levels and flows. Availability depends on the booster type and fitted sensors.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "CIM 500 V01.05 (PICS)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "For single Grundfos pumps (MAGNA3, E-pumps, CUE) see the CIM 300 / CIM 500 pump profile instead.",
  "Descriptions show which booster types support each point (Hydro Multi-B, Hydro MPC, Hydro Multi-E) and when a sensor is needed.",
  "AI 61-84 are printed with the bare name 'Subpump N'; the description says which value (current, power, motor temperature, starts) each one is.",
  "MI 12 and MI 13 have no access column in the source; they are listed as read-only.",
  "This 2014 PICS (BACnet protocol revision 9) does not list the BACnet watchdog object found in the later CIM functional profile.",
  "Hydro Multi-E always runs in constant pressure mode; MO 0 only applies to Hydro MPC."
 ],
 "source": {
  "title": "BACnet PICS CIM 500 - Protocol Implementation Conformance Statement for Grundfos CIM 500 BACnet IP for Grundfos pumps and booster systems",
  "doc_number": null,
  "revision_date": "2014-04-25",
  "url": "https://www.bacnetinternational.net/catalog/manu/grundfos%20management%20as/BACnet_PICS_CIM500_Print_88363.pdf"
 },
 "integration": {
  "summary": "Take bus control with BO 0 = 1, then start or stop the booster with MO 1 and write the setpoint to AO 0 (and the control mode to MO 0 on Hydro MPC). Read control source, rotation status, actual setpoint and the system fault and warning codes; reset alarms with BO 4.",
  "minimum_points": [
   {
    "ref": "BO 0",
    "name": "Set control source",
    "why": "Takes bus control (1) or gives it back (0)"
   },
   {
    "ref": "MO 1",
    "name": "Set operating mode",
    "why": "Start/stop: 1 = Start, 2 = Stop"
   },
   {
    "ref": "MO 0",
    "name": "Set control mode",
    "why": "Control mode (Hydro MPC only)"
   },
   {
    "ref": "AO 0",
    "name": "Set setpoint",
    "why": "System setpoint in %"
   },
   {
    "ref": "BO 4",
    "name": "Reset fault",
    "why": "Resets an alarm on a 0-to-1 edge (bus control only)"
   },
   {
    "ref": "BI 0",
    "name": "Control source status",
    "why": "Confirms bus control (1) or local (0)"
   },
   {
    "ref": "BI 2",
    "name": "Rotation status",
    "why": "One or more pumps running"
   },
   {
    "ref": "AI 9",
    "name": "Actual setpoint",
    "why": "Setpoint actually in use"
   },
   {
    "ref": "AI 0",
    "name": "Fault code",
    "why": "Active Grundfos alarm code"
   }
  ],
  "enable": "Set control source BO 0 = 1 (bus control); 0 = local control (default). MO 0, MO 1 and AO 0 only act while bus control is enabled; BI 0 confirms the active source.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP only (Annex J); no segmentation.",
   "AV 0 holds a custom device instance (range 0-0x3FFFFE, default 0xE7) that is used together with DIP switch SW3.",
   "MO 2 product simulation lets you commission the BMS side with no booster connected."
  ],
  "gotchas": [
   "A setpoint of 0 on AO 0 does not stop the booster; use MO 1 = 2 (Stop).",
   "MO 3-10 forced start is listed as not available; only automatic or forced stop work.",
   "Many points depend on the booster type and fitted sensors; check the availability note in each description."
  ]
 },
 "short_model": "CIM 500 BACnet IP (booster systems)",
 "points": [
  {
   "type": "BI",
   "instance": 0,
   "name": "Control source status",
   "description": "Status of the actual control source",
   "units": "",
   "access": "R",
   "states": "0=Local control, 1=Bus control"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Rotation status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=No rotation, 1=Rotation (one or more pumps running)"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "At minimum speed",
   "description": "Available on MPC and Multi-E",
   "units": "",
   "access": "R",
   "states": "0=Not running at minimum speed, 1=Running at minimum speed"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "At maximum speed",
   "description": "Available on MPC and Multi-E",
   "units": "",
   "access": "R",
   "states": "0=Not running at maximum speed, 1=Running at maximum speed"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Standby pumps active",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Standby pumps not active, 1=Standby pumps active"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Pressure relief active",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Pressure relief not active, 1=Pressure relief active"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Soft pressure active",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Soft pressure not active, 1=Soft pressure active"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Low-flow boost active",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Low-flow boost not active, 1=Low-flow boost active"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Low-flow stop active",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "0=Low-flow stop not active, 1=Low-flow stop active"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Alternative setpoint active",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Alternative setpoint not active, 1=Alternative setpoint active"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Digital input 1 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Not active, 1=Active"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Digital input 2 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Not active, 1=Active"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Digital input 3 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Not active, 1=Active"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Digital output 1 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Not active, 1=Active"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Digital output 2 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Not active, 1=Active"
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "Subpump 1 presence",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Subpump not present, 1=Subpump present"
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "Subpump 1 communication status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "Subpump 2 presence",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Subpump not present, 1=Subpump present"
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "Subpump 2 communication status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "Subpump 3 presence",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Subpump not present, 1=Subpump present"
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "Subpump 3 communication status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "Subpump 4 presence",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Subpump not present, 1=Subpump present"
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "Subpump 4 communication status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "Subpump 5 presence",
   "description": "Available on MPC and Multi-E",
   "units": "",
   "access": "R",
   "states": "0=Subpump not present, 1=Subpump present"
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "Subpump 5 communication status",
   "description": "Available on MPC and Multi-E",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "Subpump 6 presence",
   "description": "Available on MPC and Multi-E",
   "units": "",
   "access": "R",
   "states": "0=Subpump not present, 1=Subpump present"
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "Subpump 6 communication status",
   "description": "Available on MPC and Multi-E",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "Fault simulation status",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "0=Fault simulation disabled, 1=Fault simulation enabled"
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "Subpump 1 auto mode",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "Subpump 2 auto mode",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "Subpump 3 auto mode",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "Subpump 4 auto mode",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "Subpump 5 auto mode",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "Subpump 6 auto mode",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "Setpoint influence active",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=No influence on setpoint, 1=Setpoint influence active"
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "Pilot pump auto mode",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "Pilot pump presence",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Pilot pump not present, 1=Pilot pump present"
  },
  {
   "type": "BI",
   "instance": 42,
   "name": "Pilot pump communication status",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "Back-up pump auto mode",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Manual control, 1=Auto-control"
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "Back-up pump presence",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Backup pump not present, 1=Backup pump present"
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "Back-up pump communication status",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "0=Communication OK, 1=Communication fault"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "Set control source",
   "description": "Set to 1 for BACnet (bus) control",
   "units": "",
   "access": "W",
   "states": "0=Local control (default), 1=Bus control"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "Reset fault",
   "description": "Resets alarm on rising edge (bus control only)",
   "units": "",
   "access": "W",
   "states": "0=No resetting (default), 1=Resetting"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "Fault simulation",
   "description": "Enables fault simulation (Multi-B and MPC)",
   "units": "",
   "access": "W",
   "states": "0=Disabled (default), 1=Enabled"
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "Actual control mode",
   "description": "Reads the current control mode",
   "units": "",
   "access": "R",
   "states": "1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=RESERVED, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage"
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "Actual operating mode",
   "description": "Reads the current operating mode",
   "units": "",
   "access": "R",
   "states": "1=Start (normal), 2=Stop, 3=Minimum, 4=Maximum"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "CIM status",
   "description": "CIM module status, for fault finding",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=EEPROM fault, 3=Memory fault"
  },
  {
   "type": "MI",
   "instance": 4,
   "name": "Subpump 1 control source",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MI",
   "instance": 5,
   "name": "Subpump 2 control source",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MI",
   "instance": 6,
   "name": "Subpump 3 control source",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MI",
   "instance": 7,
   "name": "Subpump 4 control source",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MI",
   "instance": 8,
   "name": "Subpump 5 control source",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MI",
   "instance": 9,
   "name": "Subpump 6 control source",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MI",
   "instance": 10,
   "name": "Application type",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "1=Pressure boosting, 2=Heating pumps on hot side, 3=Heating pumps on cold side, 4=AirCon pumps on hot side, 5=AirCon pumps on cold side, 6=MPC S2000 heating pumps on hot side, 7=MPC S2000 heating pumps on cold side, 8=MPC S2000 AirCon pumps on hot side, 9=MPC S2000 AirCon pumps on cold side, 10=Tank filling, 11=Tank filling (float switches), 12=Undefined"
  },
  {
   "type": "MI",
   "instance": 11,
   "name": "Feedback sensor unit",
   "description": "Available on Multi-B and MPC",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=bar, 3=mbar, 4=m, 5=kPa, 6=psi, 7=ft, 8=m³/h, 9=m³/s, 10=l/s, 11=gpm, 12=°C, 13=°F, 14=%, 15=K, 16=W"
  },
  {
   "type": "MI",
   "instance": 12,
   "name": "Pilot pump control source",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MI",
   "instance": 13,
   "name": "Back-up pump control source",
   "description": "Hydro MPC only",
   "units": "",
   "access": "R",
   "states": "1=Buttons, 2=GENIbus, 3=GENIlink, 4=External control"
  },
  {
   "type": "MO",
   "instance": 0,
   "name": "Set control mode",
   "description": "Sets control mode with bus control (Hydro MPC only)",
   "units": "",
   "access": "W",
   "states": "1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=RESERVED, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage. Note: Hydro Multi-E always runs in constant-pressure mode"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Set operating mode",
   "description": "Sets operating mode with bus control",
   "units": "",
   "access": "W",
   "states": "1=Start (normal), 2=Stop, 3=Minimum (Hydro MPC only), 4=Maximum (Hydro MPC and Hydro Multi-E only)"
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "Product simulation",
   "description": "Simulated product for testing without a booster connected",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 5=Hydro Multi-E, 6=Hydro MPC, 7=Hydro Multi-B"
  },
  {
   "type": "MO",
   "instance": 3,
   "name": "Control subpump 1",
   "description": "Manual control of subpump 1 (Multi-B and MPC)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "MO",
   "instance": 4,
   "name": "Control subpump 2",
   "description": "Manual control of subpump 2 (Multi-B and MPC)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "MO",
   "instance": 5,
   "name": "Control subpump 3",
   "description": "Manual control of subpump 3 (Multi-B and MPC)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "MO",
   "instance": 6,
   "name": "Control subpump 4",
   "description": "Manual control of subpump 4 (Multi-B and MPC)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "MO",
   "instance": 7,
   "name": "Control subpump 5",
   "description": "Manual control of subpump 5 (Hydro MPC only)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "MO",
   "instance": 8,
   "name": "Control subpump 6",
   "description": "Manual control of subpump 6 (Hydro MPC only)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "MO",
   "instance": 9,
   "name": "Control pilot pump",
   "description": "Manual control of pilot pump (Hydro MPC only)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "MO",
   "instance": 10,
   "name": "Control back-up pump",
   "description": "Manual control of back-up pump (Hydro MPC only)",
   "units": "",
   "access": "W",
   "states": "1=Automatic control (default), 2=Forced start (not available), 3=Forced stop"
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "Fault code",
   "description": "Grundfos fault code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Warning code",
   "description": "Grundfos warning code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Capacity",
   "description": "Actual capacity value (process feedback)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Head",
   "description": "Actual system head/pressure (MPC and Multi-E, needs sensor)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Flow",
   "description": "Actual system flow (MPC and Multi-E, needs sensor)",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Relative performance",
   "description": "Performance relative to maximum performance",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Actual setpoint",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Motor current",
   "description": "Actual motor current (Hydro Multi-E only)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Power",
   "description": "Total power consumption of the system",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Inlet pressure",
   "description": "System inlet pressure (Multi-B and MPC, needs sensor)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Remote pressure",
   "description": "Measured pressure at external sensor (Hydro MPC only, needs sensor)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Level",
   "description": "Tank level (needs sensor)",
   "units": "m",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Remote temperature",
   "description": "Temperature at external sensor (MPC and Multi-E, needs sensor)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Auxiliary sensor input",
   "description": "Available on Multi-B and Multi-E, needs sensor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Specific Energy",
   "description": "Specific energy of the system (Hydro MPC only, needs sensor)",
   "units": "kWh/m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Runtime",
   "description": "Total operating time of the system",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Energy consumption",
   "description": "Total energy consumption of the system",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Ambient temperature",
   "description": "Hydro MPC only, needs sensor",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Forward temperature",
   "description": "Flow-pipe temperature (Hydro MPC only, needs sensor)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Return temperature",
   "description": "Return-pipe temperature (Hydro MPC only, needs sensor)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "Differential temperature",
   "description": "Hydro MPC only, needs sensor",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Outlet pressure",
   "description": "System outlet pressure (Multi-B and MPC, needs sensor)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Feed tank level",
   "description": "Actual level in the feed tank (Hydro MPC only, needs sensor)",
   "units": "m",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Subpump1 fault code",
   "description": "Fault code, subpump 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Subpump 1 runtime",
   "description": "Total operating time, subpump 1",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Subpump 1 speed",
   "description": "Actual speed, subpump 1 (Multi-B and MPC)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Subpump 2 fault code",
   "description": "Fault code, subpump 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Subpump 2 runtime",
   "description": "Total operating time, subpump 2",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Subpump 2 speed",
   "description": "Actual speed, subpump 2 (Multi-B and MPC)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Subpump 3 fault code",
   "description": "Fault code, subpump 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Subpump 3 runtime",
   "description": "Total operating time, subpump 3",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Subpump 3 speed",
   "description": "Actual speed, subpump 3 (Multi-B and MPC)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Subpump 4 fault code",
   "description": "Fault code, subpump 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "Subpump 4 runtime",
   "description": "Total operating time, subpump 4",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "Subpump 4 speed",
   "description": "Actual speed, subpump 4 (Multi-B and MPC)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "Subpump 5 fault code",
   "description": "Fault code, subpump 5 (MPC and Multi-E)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "Subpump 5 runtime",
   "description": "Total operating time, subpump 5 (MPC and Multi-E)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "Subpump 5 speed",
   "description": "Actual speed, subpump 5 (Hydro MPC only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "Subpump 6 fault code",
   "description": "Fault code, subpump 6 (MPC and Multi-E)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "Subpump 6 runtime",
   "description": "Total operating time, subpump 6 (MPC and Multi-E)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "Subpump 6 speed",
   "description": "Actual speed, subpump 6 (Hydro MPC only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "User setpoint",
   "description": "User-defined setpoint (Multi-B and MPC)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "Analogue influence",
   "description": "Analog setpoint influence (Multi-B and MPC)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "Power-on counter",
   "description": "Number of power-on cycles (Multi-B and MPC)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "Subpump 1",
   "description": "Line current, subpump 1 (Multi-B and MPC)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "Subpump 1",
   "description": "Power consumption, subpump 1 (Multi-B and MPC)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "Subpump 1",
   "description": "Motor temperature, subpump 1 (Multi-B and MPC)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "Subpump 1",
   "description": "Number of starts, subpump 1 (Multi-B and MPC)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "Subpump 2",
   "description": "Line current, subpump 2 (Multi-B and MPC)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "Subpump 2",
   "description": "Power consumption, subpump 2 (Multi-B and MPC)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "Subpump 2",
   "description": "Motor temperature, subpump 2 (Multi-B and MPC)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "Subpump 2",
   "description": "Number of starts, subpump 2 (Multi-B and MPC)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "Subpump 3",
   "description": "Line current, subpump 3 (Multi-B and MPC)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "Subpump 3",
   "description": "Power consumption, subpump 3 (Multi-B and MPC)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "Subpump 3",
   "description": "Motor temperature, subpump 3 (Multi-B and MPC)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "Subpump 3",
   "description": "Number of starts, subpump 3 (Multi-B and MPC)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "Subpump 4",
   "description": "Line current, subpump 4 (Multi-B and MPC)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "Subpump 4",
   "description": "Power consumption, subpump 4 (Multi-B and MPC)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "Subpump 4",
   "description": "Motor temperature, subpump 4 (Multi-B and MPC)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "Subpump 4",
   "description": "Number of starts, subpump 4 (Multi-B and MPC)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "Subpump 5",
   "description": "Line current, subpump 5 (Hydro MPC only)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "Subpump 5",
   "description": "Power consumption, subpump 5 (Hydro MPC only)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "Subpump 5",
   "description": "Motor temperature, subpump 5 (Hydro MPC only)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "Subpump 5",
   "description": "Number of starts, subpump 5 (Hydro MPC only)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "Subpump 6",
   "description": "Line current, subpump 6 (Hydro MPC only)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "Subpump 6",
   "description": "Power consumption, subpump 6 (Hydro MPC only)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "Subpump 6",
   "description": "Motor temperature, subpump 6 (Hydro MPC only)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "Subpump 6",
   "description": "Number of starts, subpump 6 (Hydro MPC only)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "Minimum of feedback sensor",
   "description": "Feedback sensor minimum, unit per MI 11 (MPC and Multi-E)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "Maximum of feedback sensor",
   "description": "Feedback sensor maximum, unit per MI 11 (MPC and Multi-E)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "Actual tank-filling tank height",
   "description": "Tank height in tank-filling mode (Hydro Multi-B only)",
   "units": "m",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "Actual tank-filling start limit",
   "description": "Start limit in percent of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "Actual tank-filling stop limit",
   "description": "Stop limit in percent of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "Actual tank-filling alarm high-limit",
   "description": "Alarm high-limit in percent of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "Actual tank-filling warning low-limit",
   "description": "Warning low-limit in percent of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "Specific energy average",
   "description": "Average specific energy (Hydro MPC only, needs sensor)",
   "units": "kWh/m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "Flow measurement 1",
   "description": "Hydro MPC only, needs sensor",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "Flow measurement 2",
   "description": "Hydro MPC only, needs sensor",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "Flow measurement 3",
   "description": "Hydro MPC only, needs sensor",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "Pilot pump fault code",
   "description": "Fault code, pilot pump (Hydro MPC only)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "Pilot pump runtime",
   "description": "Total operating time, pilot pump (Hydro MPC only)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "Pilot pump speed",
   "description": "Actual speed, pilot pump (Hydro MPC only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "Pilot pump line current",
   "description": "Line current, pilot pump (Hydro MPC only)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "Pilot pump power consumption",
   "description": "Power consumption, pilot pump (Hydro MPC only)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "Pilot pump motor temperature",
   "description": "Motor temperature, pilot pump (Hydro MPC only)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "Pilot pump number of starts",
   "description": "Number of starts, pilot pump (Hydro MPC only)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "Back-up pump fault code",
   "description": "Fault code, backup pump (Hydro MPC only)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "Back-up pump runtime",
   "description": "Total operating time, backup pump (Hydro MPC only)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "Back-up pump speed",
   "description": "Actual speed, backup pump (Hydro MPC only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "Back-up pump line current",
   "description": "Line current, backup pump (Hydro MPC only)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "Back-up pump power consumption",
   "description": "Power consumption, backup pump (Hydro MPC only)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "Back-up pump motor temperature",
   "description": "Motor temperature, backup pump (Hydro MPC only)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "Back-up pump number of starts",
   "description": "Number of starts, backup pump (Hydro MPC only)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "Set setpoint",
   "description": "Booster setpoint when bus control is on; 0 does not stop",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Tank-filling start limit",
   "description": "Start limit, % of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "Tank-filling stop limit",
   "description": "Stop limit, % of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "Tank-filling alarm high-limit",
   "description": "Alarm high-limit, % of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "Tank-filling warning low-limit",
   "description": "Warning low-limit, % of tank height (Hydro Multi-B only)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Custom device object instance number",
   "description": "Custom device instance; used with DIP switch SW3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Simulation event code",
   "description": "Grundfos event code to simulate (e.g. 210 = pressure high)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Simulation device type",
   "description": "Device type of simulated event (Multi-B and MPC)",
   "units": "",
   "access": "W",
   "states": "0=Controller, 2=Pump, 3=IO 351, 4=Primary sensor, 7=IO 351, 8=System, 9=Analog input, 10=Pilot booster system, 11=Limit-exceeded function"
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Simulation device number",
   "description": "Pump (1-6) or sensor (1-7) number of simulated event",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Simulation event action type",
   "description": "Action of the simulated event (Hydro MPC only)",
   "units": "",
   "access": "W",
   "states": "0=Go to operating mode \"Stop\", 1=Go to operating mode \"Stop\" (delay), 2=Go to operating mode \"Minimum\", 3=Go to operating mode \"User- defined\", 4=Go to operating mode \"Maximum\", 5=Set pumps in source mode to \"Local control\", 6=No action (warning only), 7=Go to operating mode \"Emergency run\""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Simulation event reset type",
   "description": "Resetting type for simulated event (Hydro MPC only)",
   "units": "",
   "access": "W",
   "states": "0=Manual resetting, 1=Automatic resetting"
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Proportional-control reduction",
   "description": "Proportional-pressure reduction (Hydro MPC only)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Proportional-control flow max.",
   "description": "Proportional-pressure max. flow (Hydro MPC only)",
   "units": "m³/h",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/grundfos/cim-500-booster-systems",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}