 "manufacturer": "Grundfos",
 "manufacturer_slug": "grundfos",
 "model": "MIXIT mixing loop unit (BACnet MS/TP and IP)",
 "model_slug": "mixit",
 "aliases": [
  "MIXIT",
  "Grundfos MIXIT",
  "MIXIT DYNAMIC",
  "MIXIT CONNECT",
  "BACnet for MIXIT"
 ],
 "equipment_type": "Mixing loop unit (valve + pump controller)",
 "applies_to": "Grundfos MIXIT mixing loop units (valve, controller and connected MAGNA3/UPM pump) with the CONNECT upgrade, for heating and cooling loops.",
 "summary": "MIXIT combines a mixing valve, sensors and a controller that also runs the connected Grundfos pump. With the CONNECT upgrade it speaks BACnet MS/TP on its RS-485 terminals or BACnet IP on its RJ45 port. The object list covers bus control, start/stop, setpoint source and remote setpoint, pump control modes and duty points, limiters, weather curve, energy data and alarm/warning codes.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": 227005,
 "access_inferred": false,
 "notes": [
  "BACnet needs the CONNECT upgrade, and the protocol is selected and set up in Grundfos GO Remote.",
  "Objects marked \"DYNAMIC variants only\" (energy, flow and limiter points) exist only on MIXIT DYNAMIC.",
  "The manual prints units in square brackets after many object names (e.g. \"[°C]\"); they are moved to the units field here.",
  "BO 6 is mentioned as the cooling energy reset but is not in the object tables, so it is not listed.",
  "Temperatures are written in whole °C on the bus.",
  "MI 4 has no access column in the manual; it is read-only as an input object."
 ],
 "integration": {
  "summary": "Configure MIXIT and its fieldbus settings in Grundfos GO Remote first, and set a safe fallback setpoint on AV 6. Then write BO 0 = 1 (bus control), MV 0 = 3 (remote setpoint), the setpoint on AO 0 and BO 1 = 1 to start. Keep polling a point such as BI 0 every 30 s or MIXIT returns to its local setpoint.",
  "minimum_points": [
   {
    "ref": "BO 0",
    "why": "Takes bus control (1) or gives it back (0)",
    "name": "Set Control Source"
   },
   {
    "ref": "MV 0",
    "why": "Setpoint source; 3 = remote setpoint on AO 0",
    "name": "Config Temp Setpoint Source"
   },
   {
    "ref": "BO 1",
    "why": "Start/stop (1 = start, 0 = stop and close valve)",
    "name": "Set Start Stop"
   },
   {
    "ref": "AO 0",
    "why": "Remote temperature setpoint, °C",
    "name": "Set Temperature Setpoint Remote"
   },
   {
    "ref": "BO 2",
    "why": "Resets alarms and warnings on a 0-to-1 edge",
    "name": "Reset fault"
   },
   {
    "ref": "BI 0",
    "why": "Confirms bus control",
    "name": "Status Control Source"
   },
   {
    "ref": "MI 2",
    "why": "System state, e.g. 5 = temperature control",
    "name": "Status System State"
   },
   {
    "ref": "AI 22",
    "why": "Actual controlled temperature, °C",
    "name": "Data Controlled Temp"
   },
   {
    "ref": "BI 4",
    "why": "System stopped by an alarm",
    "name": "Status Fault"
   },
   {
    "ref": "AI 37",
    "why": "MIXIT alarm code",
    "name": "Status System Alarm Code"
   }
  ],
  "enable": "BO 0 Set Control Source = 1 puts MIXIT under bus control (BI 0 confirms). MV 0 = 3 makes AO 0 the setpoint; MV 0 = 5 uses the internal weather curve with the outdoor temperature written to AO 1. BO 1 starts (1) or stops (0) the system; stop also closes the valve.",
  "heartbeat": "The manual asks the BMS to keep communicating, e.g. read BI 0 every 30 s. If communication is lost MIXIT falls back to its local setpoint (AV 6). After a power failure it starts in local control, so the BMS must send the full start-up sequence again.",
  "remote_sensors": "Outdoor temperature can come from the bus on AO 1 (MV 0 = 5). In heating coil and cooling applications the air temperature feedback can come from the bus on AO 2 after BO 7 = 1.",
  "setup": [
   "Default device instance 227005; a custom number can be enabled in Grundfos GO Remote and written to AV 0.",
   "MS/TP: MAC 0-127, default 5; Max Master 1-127 (default 127); baud set in Grundfos GO Remote. Built-in 120 ohm termination on a DIP switch; no bias resistors.",
   "IP: RJ45 port; static IP or DHCP (wait 1 minute for a DHCP address).",
   "No segmentation support."
  ],
  "gotchas": [
   "Avoid writing configuration (persistent) objects in the cyclic poll; read instead of rewriting every 30 s.",
   "Set AV 6 fallback setpoint separately for heating and cooling (switch with MO 4) in combined applications.",
   "BO 2 reset and BO 5 simulation are edge triggered.",
   "Pump control mode and duty points are separate for heating (MO 0, AV 7-9) and cooling (MO 3, AV 14-16)."
  ]
 },
 "source": {
  "title": "BACnet for MIXIT - Functional profile and user manual",
  "doc_number": "99258495",
  "revision_date": "11.2024",
  "url": "https://api.grundfos.com/literature/Grundfosliterature-6012796.pdf"
 },
 "points": [
  {
   "type": "BI",
   "instance": 0,
   "name": "Status Control Source",
   "description": "Bus control active",
   "units": "",
   "access": "R",
   "states": "0=Local control, 1=Bus control"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Status Fan and Dampers",
   "description": "Coil preheated, fan/dampers may run (heating coil)",
   "units": "",
   "access": "R",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Status Actual Run State Pump",
   "description": "Actual pump run state",
   "units": "",
   "access": "R",
   "states": "0=Stopped, 1=Started"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Status Ready",
   "description": "System ready for operation",
   "units": "",
   "access": "R",
   "states": "0=Not ready, 1=Ready"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Status Fault",
   "description": "System stopped by an alarm",
   "units": "",
   "access": "R",
   "states": "0=No fault, 1=Fault"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Status Alarm Simulation",
   "description": "Alarm/warning simulation active",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Notification Flow Temp High",
   "description": "Underfloor overheat detected",
   "units": "",
   "access": "R",
   "states": "0=Not detected, 1=Detected"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Notification Frost Risk Detected",
   "description": "Frost risk detected",
   "units": "",
   "access": "R",
   "states": "0=Not detected, 1=Detected"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Notification Supply Flow High",
   "description": "Supply flow above AV 10 limit for 3600 s (DYNAMIC variants only)",
   "units": "",
   "access": "R",
   "states": "0=Not above, 1=Above"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Notification Thermal Power High",
   "description": "Thermal power above AV 11 limit for 3600 s (DYNAMIC variants only)",
   "units": "",
   "access": "R",
   "states": "0=Not above, 1=Above"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Notification Return Temperature Threshold",
   "description": "Return temperature past AV 12 limit for 3600 s (DYNAMIC variants only)",
   "units": "",
   "access": "R",
   "states": "0=Not exceeded, 1=Exceeded"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Notification Differential Temperature High",
   "description": "Primary delta T past AV 13 limit for 3600 s (DYNAMIC variants only)",
   "units": "",
   "access": "R",
   "states": "0=Not exceeded, 1=Exceeded"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Bus Feedback Enabled",
   "description": "Air temperature feedback comes from the bus",
   "units": "",
   "access": "R",
   "states": "0=False, 1=True"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Heat Curve Slope Factor Enabled",
   "description": "Weather curve is non-linear",
   "units": "",
   "access": "R",
   "states": "0=False, 1=True"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Heat Curve Offset Range Exceeded",
   "description": "Weather curve offset outside -15..15",
   "units": "",
   "access": "R",
   "states": "0=Exceeded, 1=Not exceeded"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Heat Curve Slope Factor Range Exceeded",
   "description": "Weather curve slope outside 0.4..2.0",
   "units": "",
   "access": "R",
   "states": "0=Exceeded, 1=Not exceeded"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "Set Control Source",
   "description": "Take bus control (1) or return to local (0)",
   "units": "",
   "access": "W",
   "states": "0=Local control, 1=Bus control"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Set Start Stop",
   "description": "Start/stop the system (stop also closes the valve)",
   "units": "",
   "access": "W",
   "states": "0=Stop, 1=Start"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Reset fault",
   "description": "Reset alarms and warnings (rising edge)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "Enable Overheat Protection",
   "description": "Force the underfloor overheat indication",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Set"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "Enable Frost Protection, heating",
   "description": "Frost protection for heating coil application",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "Set Fault Simulation",
   "description": "Start (rising edge) or stop alarm simulation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "Enable Bus Feedback",
   "description": "Use air temperature feedback from the bus (AO 2)",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "Enable Frost Protection Cooling Mode",
   "description": "Frost protection in cooling mode",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "Config Supply Flow Limiting, Heating",
   "description": "Enable supply flow limit (AV 10) (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Config Thermal Power Limiting, Heating",
   "description": "Enable thermal power limit (AV 11) (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Config Return Temp Limiting, Heating",
   "description": "Enable return temperature limit (AV 12) (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Config Primary DeltaT Limiting, Heating",
   "description": "Enable primary delta T limit (AV 13) (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Config Supply Flow Limiting Cooling",
   "description": "Enable cooling supply flow limit (AV 17) (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Config Thermal Power Limiting Cooling",
   "description": "Enable cooling thermal power limit (AV 18) (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "Config Return Temp Limiting Cooling",
   "description": "Enable cooling return temperature limit (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Config Primary Delta T Limiting Cooling",
   "description": "Enable cooling primary delta T limit (AV 20) (DYNAMIC variants only)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "Status Pump Control Mode, Heating and Cooling",
   "description": "Current pump control mode",
   "units": "",
   "access": "R",
   "states": "1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=AUTOADAPT, 5=Constant flow"
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "Data Application Type Heating",
   "description": "Heating application type",
   "units": "",
   "access": "R",
   "states": "1=Radiator heating, 2=Underfloor heating, 3=Heating coil"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Status System State",
   "description": "System state",
   "units": "",
   "access": "R",
   "states": "1=Powering up, 2=Fault, 3=Ready, 4=Preheating heating coil, 5=Temperature control, 6=Frost protection, 7=Underfloor overheat protection, 8=Shut down (start signal removed), 10=Valve 100 % open (backup), 11=Return temperature control"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "Status Thermal selection",
   "description": "Heating or cooling active",
   "units": "",
   "access": "R",
   "states": "1=Heating, 2=Cooling"
  },
  {
   "type": "MI",
   "instance": 4,
   "name": "Data Application type Cooling",
   "description": "Cooling application type",
   "units": "",
   "access": "R",
   "states": "1=General cooling"
  },
  {
   "type": "MI",
   "instance": 5,
   "name": "Data Valve Mode",
   "description": "Valve mode",
   "units": "",
   "access": "R",
   "states": "1=Injection 2 way, 2=Mixing 3 way, 3=Injection 3 way"
  },
  {
   "type": "MO",
   "instance": 0,
   "name": "Config Pump Control Mode, Heating",
   "description": "Pump control mode for heating",
   "units": "",
   "access": "W",
   "states": "1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=AUTOADAPT, 5=Constant flow"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Set Manual Valve Function",
   "description": "Manual valve opening for service",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=100 % open, 3=50 % open, 4=25 % open, 5=0 % (closed)"
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "Set Application Type Heating",
   "description": "Heating application type",
   "units": "",
   "access": "W",
   "states": "1=Radiator heating, 2=Underfloor heating, 3=Heating coil"
  },
  {
   "type": "MO",
   "instance": 3,
   "name": "Config Pump Control Mode Cooling",
   "description": "Pump control mode for cooling",
   "units": "",
   "access": "W",
   "states": "1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=AUTOADAPT, 5=Constant flow"
  },
  {
   "type": "MO",
   "instance": 4,
   "name": "Config Thermal selection",
   "description": "Heating/cooling change-over (combined applications)",
   "units": "",
   "access": "W",
   "states": "1=Heating, 2=Cooling"
  },
  {
   "type": "MO",
   "instance": 5,
   "name": "Set Application Type Cooling",
   "description": "Cooling application type",
   "units": "",
   "access": "W",
   "states": "1=General cooling"
  },
  {
   "type": "MO",
   "instance": 6,
   "name": "Config Valve Mode",
   "description": "Valve mode",
   "units": "",
   "access": "W",
   "states": "1=Injection 2 way, 2=Mixing 3 way, 3=Injection 3 way"
  },
  {
   "type": "MO",
   "instance": 7,
   "name": "Config Heating Cooling Selection",
   "description": "Thermal application mode",
   "units": "",
   "access": "W",
   "states": "1=Heating, 2=Cooling, 3=Combined"
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "Config Temp Setpoint Source",
   "description": "Source of the temperature setpoint",
   "units": "",
   "access": "W",
   "states": "1=Default setpoint, 2=Analog input setpoint, 3=Remote setpoint (AO 0), 4=Weather curve with local outdoor sensor, 5=Weather curve with bus outdoor temp (AO 1)"
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "Data Temp Setpoint Remote",
   "description": "Remote temperature setpoint received",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Data Outdoor Temp Remote",
   "description": "Remote outdoor temperature received",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Data Act Temp Setpoint",
   "description": "Temperature setpoint in use",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Status Pump Warning Code",
   "description": "Pump warning code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Status Pump Alarm Code",
   "description": "Pump alarm code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Data Heating Energy",
   "description": "Lifetime heating energy (DYNAMIC variants only)",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Data Heating Power",
   "description": "Thermal power in heating mode (DYNAMIC variants only)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Data Cooling Energy",
   "description": "Lifetime cooling energy (DYNAMIC variants only)",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Data Cooling Power",
   "description": "Thermal power in cooling mode (DYNAMIC variants only)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Data Heat Temp Difference",
   "description": "Forward/return temperature difference (DYNAMIC variants only)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Data Pump Power",
   "description": "Pump electrical power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Data percentage Speed",
   "description": "Pump speed, % of maximum",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Data Pump Operating Hours",
   "description": "Pump operating hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Data Pump Energy",
   "description": "Pump energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Data Flow Temp",
   "description": "Secondary flow temperature (from pump)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Data Supply Temp",
   "description": "Supply temperature at the valve",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Data Logical Valve Opening",
   "description": "Valve opening request",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Data Valve Supply Flow",
   "description": "Primary flow at the A-port (DYNAMIC variants only)",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Data Return Temperature",
   "description": "Return temperature at the valve",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Data Controlled Temp",
   "description": "Actual controlled temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Data Supply Source Setpoint",
   "description": "Supply source temperature reference",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Data Pump Flow",
   "description": "Pump flow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Data Pump Head",
   "description": "Pump head",
   "units": "m",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Data Outdoor Temp",
   "description": "Outdoor temperature at the analog input",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Data Zone Air Temp",
   "description": "Air temperature at the analog input",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Data Bus Temperature Feedback",
   "description": "Air temperature feedback from the bus",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Status System Warning Code",
   "description": "MIXIT warning code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "Status System Sub Warning Code",
   "description": "Warning sub-code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Status System Alarm Code",
   "description": "MIXIT alarm code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Status System Sub Alarm Code",
   "description": "Alarm sub-code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Data HeatingVolume",
   "description": "Total heating volume pumped (DYNAMIC variants only)",
   "units": "m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Data CoolingVolume",
   "description": "Total cooling volume pumped (DYNAMIC variants only)",
   "units": "m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Data VolWeightAvgT1Heat",
   "description": "Volume-weighted average T1, heating (DYNAMIC variants only)",
   "units": "°C·m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Data VolWeightAvgT2Heat",
   "description": "Volume-weighted average T2, heating (DYNAMIC variants only)",
   "units": "°C·m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Data VolWeightAvgT1Cool",
   "description": "Volume-weighted average T1, cooling (DYNAMIC variants only)",
   "units": "°C·m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Data VolWeightAvgT2Cool",
   "description": "Volume-weighted average T2, cooling (DYNAMIC variants only)",
   "units": "°C·m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Data MIXIT Operating Hours",
   "description": "MIXIT operating time",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "Set Temperature Setpoint Remote",
   "description": "Temperature setpoint from the bus (needs MV 0 = 3)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Set Outdoor Temperature Remote",
   "description": "Outdoor temperature from the bus (needs MV 0 = 5)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "Set Bus Temperature Feedback",
   "description": "Air temperature feedback from the bus (needs BO 7 = 1)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Config Custom Device Object Instance Number",
   "description": "Custom device instance (enable in Grundfos GO)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Config Product time and date",
   "description": "Clock, UNIX seconds",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Set Simulation Event Code",
   "description": "Alarm/warning code to simulate",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Set Simulation Event Sub Code",
   "description": "Sub-code to simulate",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Config Heat curve offset (+/-)",
   "description": "Weather curve offset, +/-15",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Config Heat curve slope (+/-)",
   "description": "Weather curve slope, 0.4-2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Config Default Temp Setpoint",
   "description": "Fallback setpoint if bus or sensor signal is lost",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Config Pump Head Duty Point, Heating",
   "description": "Pump head duty point, heating",
   "units": "m",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Config Pump Flow Duty Point, Heating",
   "description": "Pump flow duty point, heating",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Config Pump Speed DutyPoint, Heating",
   "description": "Pump speed in constant speed mode, heating",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Config Supply Flow Limit Heating",
   "description": "Primary flow limit, heating (DYNAMIC variants only)",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Config Thermal Power Limit Heating",
   "description": "Thermal power limit, heating (DYNAMIC variants only)",
   "units": "kW",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Config Return Temp Limit Heating",
   "description": "Return temperature limit, heating (DYNAMIC variants only)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Config Primary DeltaT Limit Heating",
   "description": "Primary delta T limit, heating (DYNAMIC variants only)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Config Pump Head Duty Point Cooling",
   "description": "Pump head duty point, cooling (DYNAMIC variants only)",
   "units": "m",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Config Pump Flow Duty Point Cooling",
   "description": "Pump flow duty point, cooling (DYNAMIC variants only)",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Config Pump Speed Duty Point Cooling",
   "description": "Pump speed in constant speed mode, cooling (DYNAMIC variants only)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Config Supply Flow Limit Cooling",
   "description": "Primary flow limit, cooling (DYNAMIC variants only)",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Config Thermal Power Limit Cooling",
   "description": "Thermal power limit, cooling (DYNAMIC variants only)",
   "units": "kW",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Config Return Temp Limit Cooling",
   "description": "Return temperature limit, cooling (DYNAMIC variants only)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Config Primary Delta T Limit Cooling",
   "description": "Primary delta T limit, cooling (DYNAMIC variants only)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Config Kp",
   "description": "Temperature controller gain, 0.1-20",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Config Ti",
   "description": "Temperature controller integral time, 0-3600",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Config Kvs",
   "description": "Valve capacity limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Config Outdoor Temperature X1",
   "description": "Weather curve outdoor point 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Config Setpoint Y1",
   "description": "Weather curve setpoint 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Config Outdoor Temperature X2",
   "description": "Weather curve outdoor point 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Config Setpoint Y2",
   "description": "Weather curve setpoint 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Config Outdoor Temperature X3",
   "description": "Weather curve outdoor point 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Config Setpoint Y3",
   "description": "Weather curve setpoint 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Config Outdoor Temperature X4",
   "description": "Weather curve outdoor point 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Config Setpoint Y4",
   "description": "Weather curve setpoint 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Config Outdoor Temperature X5",
   "description": "Weather curve outdoor point 5",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Config Setpoint Y5",
   "description": "Weather curve setpoint 5",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/grundfos/mixit",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}