EC motor with integrated variable frequency drive (fans) · BACnet points list

Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet points list

Updated 6 November 2026

Short answer

The Vari-Green (EC Titanium) motor has an integrated drive with an RS-485 port that speaks Modbus RTU or BACnet MS/TP (not both at once). BACnet is enabled with parameter 1103 = 9. The object list is short: run, direction and fault-reset commands, a speed setpoint in % of maximum speed, ramp and speed-limit settings, and readings for speed, frequency, current, power, temperature, energy, run hours, faults and I/O states.

This page lists 45 BACnet objects for the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greenheck’s own free documentation, linked below.

Manufacturer
Greenheck
Model
Vari-Green Motor (EC Titanium) BACnet MS/TP
Equipment
EC motor with integrated variable frequency drive (fans)
Equipment type
VFDs & pumps
BACnet objects
45 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Vari-Green, Vari-Green Motor, EC Titanium, MN448, Greenheck Vari-Green, Baldor EC Titanium
Source document
Vari-Green Motor (EC Titanium) single/three-phase User Manual · MN448 · rev. 01/2022
Download CSV 45 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greenheck’s current documentation and the live device before use. Not official Greenheck information. Terms of use.

BMS integration notes: Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP

Integration in brief

Set 1103 Primary Command Source Mode = 9 for BACnet MS/TP, set the address, baud rate and watchdog in 5302 and the device instance in 5840/5899. Command BV 10 run/stop and write the speed setpoint to AV 14 (% of maximum speed); reset faults with BV 14. Read BV 0, AV 1, AV 4, BV 2 and AV 16.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10RUN-STOP-CommandRun/stop command (1 = run)Command
AV 14Input-Reference-1Speed setpoint, % of maximum speedCommand
BV 14Fault-Reset-CommandFault reset (1 = reset)Write
BV 0Run / Stop-MonitorRunning statusRead
AV 1Output-FreqOutput frequency in HzRead
AV 4Output-CurrentMotor ampsRead
BV 2OK-Fault-MonitorDrive fault statusRead
AV 16Active-FaultActive fault codeRead

Enable & remote start

Set 1103 PRIMARY COMMAND SOURCE MODE = 9 (BACnet MS/TP; ramps from 2202/2203). Parameter 9902 then decides whether the speed reference and start/stop come from the network or the terminal strip. BV 4 shows Auto when the drive is under terminal or BACnet control.

Heartbeat & communication loss

Parameter 5302 includes a watchdog timeout of 0 (disabled), 30, 100, 1000 or 3000 ms. A 't' suffix trips the drive on loss of communication (fault F0010); an 'r' suffix coasts the motor to a stop without a trip.

Network setup

Watch out for

Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

45 of 45 shown
Type
Access
Show
Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet Points List
DescriptionStates
BI0R01 – MonitorStatus of relay output 1Read0=Off, 1=On
BI5D01 – MonitorStatus of digital output 1 (valid when 1501 = 0-7)Read0=Off, 1=On
BI6DI1 – MonitorStatus of digital input 1Read0=Off, 1=On
BI7DI2 – MonitorStatus of digital input 2Read0=Off, 1=On
BI8DI3 – MonitorStatus of digital input 3Read0=Off, 1=On
BO0R01 – CommandOutput state of relay 1Read0=Off, 1=On
BO5DO1 – CommandOutput state of digital output 1Read0=Off, 1=On
BVmin0Run / Stop-MonitorDrive's run statusRead0=Stop, 1=Run
BV1Direction-MonitorRotational direction of the motorRead0=Forward, 1=Reverse
BVmin2OK-Fault-MonitorActual fault status of the driveRead0=OK, 1=Fault
BV4Warning-MonitorOperator mode: Hand = keypad, Auto = terminal or BACnetRead0=Auto, 1=Hand
BV5Ready-MonitorOverload warning (output current above motor rated current)Read0=OK, 1=Warning
BV7At-Setpoint-MonitorActual ready statusRead0=Not-Ready, 1=Ready
BV8At-Setpoint-MonitorActual at-setpoint statusRead0=No, 1=Yes
BVmin10RUN-STOP-CommandCommand to start driveCommand0=Stop, 1=Run
BV11Direction-CommandRotational direction commandCommand0=Forward, 1=Reverse
BVmin14Fault-Reset-CommandFault reset commandWrite0=No, 1=Reset
BV17Lock-ParametersActual status of parameter lockRead0=Unlock, 1=Lock
BV41Fire ModeDrive is in fire modeRead0=Off, 1=On
AI0AI1 – MonitorInput level of analog input 1 (0-100 %)%Read
AI1AI2 - MonitorInput level of analog input 2 (0-100 %)%Read
AV0*Output-RPMMotor speed (needs rated speed in 9908)rpmRead
AVmin1Output-FreqOutput frequencyHzRead
AV2DC-VoltageDC bus voltageVRead
AV3Output-VoltageAC output voltageVRead
AVmin4Output-CurrentOutput current of driveARead
AV5Output-TorqueOutput torque, % of nominal torque%Read
AV6Output-PowerOutput powerkWRead
AV7Operating-Temp-RangeHeatsink temperature°CCommand
AV8Kilowatt-Hour-Meter-NRCumulative energy usage (not resettable)kWhRead
AV9Running-HoursResettable run timehRead
AVmin14Input-Reference-1Speed setpoint 1, % of maximum speed%Command
AVmin16Active-FaultMost recent fault currently activeRead
AV18Previous-Fault-1Most recent stored (non-active) faultRead
AV20Previous-Fault-2Second most recent stored faultRead
AV21AO1-MonitorOutput level of analog output 1%Read
AV23Accel-1-SecondsRamp 1 acceleration timesWrite
AV24Decel-1-SecondsRamp 1 deceleration timesWrite
AV29Min-SpeedMinimum allowed output frequencyHzWrite
AV30Max-SpeedMaximum allowed output frequencyHzWrite
AV31Output-SpeedMotor speed, % of rated frequency (9907)%Read
AV32Output-Current-RangeMotor current, % of rated current (9906)%Read
AV33Max-CurrentMax motor current (rated current in 9906)AWrite
AV40PID FeedbackPID controller feedback value%Read
AV41PID referencePID controller reference value%Read
Object ID lookup: Greenheck Vari-Green Motor BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vari-Green Motor (EC Titanium) BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP

How many BACnet points does the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP have?

This list has 45 BACnet objects: 2 analog inputs, 24 analog values, 5 binary inputs, 2 binary outputs, 12 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet points are writable?

10 of the 45 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet documentation?

The source is Vari-Green Motor (EC Titanium) single/three-phase User Manual (MN448), revision 01/2022, published free by Greenheck at https://webcontent.greenheck.com/atg-cms-v2-prod/docs/default-source/resource-library/installation-manuals/fans/single_threephase_varigreenmotor_usermanual_jan2022.pdf.

What are the minimum BACnet points to integrate the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP?

Start with BV 10 RUN-STOP-Command (Run/stop command (1 = run)); AV 14 Input-Reference-1 (Speed setpoint, % of maximum speed); BV 14 Fault-Reset-Command (Fault reset (1 = reset)); BV 0 Run / Stop-Monitor (Running status); AV 1 Output-Freq (Output frequency in Hz); AV 4 Output-Current (Motor amps); BV 2 OK-Fault-Monitor (Drive fault status); AV 16 Active-Fault (Active fault code).

How do I enable BMS control of the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP?

Set 1103 PRIMARY COMMAND SOURCE MODE = 9 (BACnet MS/TP; ramps from 2202/2203). Parameter 9902 then decides whether the speed reference and start/stop come from the network or the terminal strip. BV 4 shows Auto when the drive is under terminal or BACnet control.

Does the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP need a BACnet heartbeat or have a communication timeout?

Parameter 5302 includes a watchdog timeout of 0 (disabled), 30, 100, 1000 or 3000 ms. A 't' suffix trips the drive on loss of communication (fault F0010); an 'r' suffix coasts the motor to a stop without a trip.

How do I check these points on the real Vari-Green Motor (EC Titanium) BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greenheck BACnet points lists

Source: Vari-Green Motor (EC Titanium) single/three-phase User Manual · MN448 · rev. 01/2022. Object names, instances and units are reproduced as published; descriptions are our own.