EC motor with integrated variable frequency drive (fans) · BACnet points list
Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet points list
Updated 6 November 2026
The Vari-Green (EC Titanium) motor has an integrated drive with an RS-485 port that speaks Modbus RTU or BACnet MS/TP (not both at once). BACnet is enabled with parameter 1103 = 9. The object list is short: run, direction and fault-reset commands, a speed setpoint in % of maximum speed, ramp and speed-limit settings, and readings for speed, frequency, current, power, temperature, energy, run hours, faults and I/O states.
This page lists 45 BACnet objects for the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greenheck’s own free documentation, linked below.
- Manufacturer
- Greenheck
- Model
- Vari-Green Motor (EC Titanium) BACnet MS/TP
- Equipment
- EC motor with integrated variable frequency drive (fans)
- Equipment type
- VFDs & pumps
- BACnet objects
- 45 (10 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Vari-Green, Vari-Green Motor, EC Titanium, MN448, Greenheck Vari-Green, Baldor EC Titanium
Reference only, provided as-is: verify against Greenheck’s current documentation and the live device before use. Not official Greenheck information. Terms of use.
BMS integration notes: Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP
Set 1103 Primary Command Source Mode = 9 for BACnet MS/TP, set the address, baud rate and watchdog in 5302 and the device instance in 5840/5899. Command BV 10 run/stop and write the speed setpoint to AV 14 (% of maximum speed); reset faults with BV 14. Read BV 0, AV 1, AV 4, BV 2 and AV 16.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10 | RUN-STOP-Command | Run/stop command (1 = run) | Command |
| AV 14 | Input-Reference-1 | Speed setpoint, % of maximum speed | Command |
| BV 14 | Fault-Reset-Command | Fault reset (1 = reset) | Write |
| BV 0 | Run / Stop-Monitor | Running status | Read |
| AV 1 | Output-Freq | Output frequency in Hz | Read |
| AV 4 | Output-Current | Motor amps | Read |
| BV 2 | OK-Fault-Monitor | Drive fault status | Read |
| AV 16 | Active-Fault | Active fault code | Read |
Enable & remote start
Set 1103 PRIMARY COMMAND SOURCE MODE = 9 (BACnet MS/TP; ramps from 2202/2203). Parameter 9902 then decides whether the speed reference and start/stop come from the network or the terminal strip. BV 4 shows Auto when the drive is under terminal or BACnet control.
Heartbeat & communication loss
Parameter 5302 includes a watchdog timeout of 0 (disabled), 30, 100, 1000 or 3000 ms. A 't' suffix trips the drive on loss of communication (fault F0010); an 'r' suffix coasts the motor to a stop without a trip.
Network setup
- 5302 serial settings: drive address 0-63 (default 1), baud 9.6-115.2 kbps (default 38.4 kbps), watchdog timeout.
- BACnet MS/TP format is 8N1; Modbus RTU and BACnet MS/TP cannot run at the same time.
- Device instance is set with 5840 (Device Object ID Low) and 5899 (Device Object ID High); the manual's formula reads 5840 x 65536 + 5899.
- 5841 BACnet maximum masters 0-127; takes effect after a reboot.
- Connect RS-485 on the RJ45 port (pins 7 -, 8 +) or terminals T10 (+) / T11 (-); a third 0 V wire to T9 is recommended.
Watch out for
- AV 14 is a percentage of maximum speed, not Hz or rpm.
- Min/max speed, ramps and max current (AV 23-33) change motor settings; don't write them cyclically.
- BV names are shifted against their descriptions in the manual; check BV 4-8 on a live unit.
- The RJ45 port is RS-485, not Ethernet.
Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 0 | R01 – Monitor | Status of relay output 1 | Read | 0=Off, 1=On | |
| BI | 5 | D01 – Monitor | Status of digital output 1 (valid when 1501 = 0-7) | Read | 0=Off, 1=On | |
| BI | 6 | DI1 – Monitor | Status of digital input 1 | Read | 0=Off, 1=On | |
| BI | 7 | DI2 – Monitor | Status of digital input 2 | Read | 0=Off, 1=On | |
| BI | 8 | DI3 – Monitor | Status of digital input 3 | Read | 0=Off, 1=On | |
| BO | 0 | R01 – Command | Output state of relay 1 | Read | 0=Off, 1=On | |
| BO | 5 | DO1 – Command | Output state of digital output 1 | Read | 0=Off, 1=On | |
| BVmin | 0 | Run / Stop-Monitor | Drive's run status | Read | 0=Stop, 1=Run | |
| BV | 1 | Direction-Monitor | Rotational direction of the motor | Read | 0=Forward, 1=Reverse | |
| BVmin | 2 | OK-Fault-Monitor | Actual fault status of the drive | Read | 0=OK, 1=Fault | |
| BV | 4 | Warning-Monitor | Operator mode: Hand = keypad, Auto = terminal or BACnet | Read | 0=Auto, 1=Hand | |
| BV | 5 | Ready-Monitor | Overload warning (output current above motor rated current) | Read | 0=OK, 1=Warning | |
| BV | 7 | At-Setpoint-Monitor | Actual ready status | Read | 0=Not-Ready, 1=Ready | |
| BV | 8 | At-Setpoint-Monitor | Actual at-setpoint status | Read | 0=No, 1=Yes | |
| BVmin | 10 | RUN-STOP-Command | Command to start drive | Command | 0=Stop, 1=Run | |
| BV | 11 | Direction-Command | Rotational direction command | Command | 0=Forward, 1=Reverse | |
| BVmin | 14 | Fault-Reset-Command | Fault reset command | Write | 0=No, 1=Reset | |
| BV | 17 | Lock-Parameters | Actual status of parameter lock | Read | 0=Unlock, 1=Lock | |
| BV | 41 | Fire Mode | Drive is in fire mode | Read | 0=Off, 1=On | |
| AI | 0 | AI1 – Monitor | Input level of analog input 1 (0-100 %) | % | Read | |
| AI | 1 | AI2 - Monitor | Input level of analog input 2 (0-100 %) | % | Read | |
| AV | 0 | *Output-RPM | Motor speed (needs rated speed in 9908) | rpm | Read | |
| AVmin | 1 | Output-Freq | Output frequency | Hz | Read | |
| AV | 2 | DC-Voltage | DC bus voltage | V | Read | |
| AV | 3 | Output-Voltage | AC output voltage | V | Read | |
| AVmin | 4 | Output-Current | Output current of drive | A | Read | |
| AV | 5 | Output-Torque | Output torque, % of nominal torque | % | Read | |
| AV | 6 | Output-Power | Output power | kW | Read | |
| AV | 7 | Operating-Temp-Range | Heatsink temperature | °C | Command | |
| AV | 8 | Kilowatt-Hour-Meter-NR | Cumulative energy usage (not resettable) | kWh | Read | |
| AV | 9 | Running-Hours | Resettable run time | h | Read | |
| AVmin | 14 | Input-Reference-1 | Speed setpoint 1, % of maximum speed | % | Command | |
| AVmin | 16 | Active-Fault | Most recent fault currently active | Read | ||
| AV | 18 | Previous-Fault-1 | Most recent stored (non-active) fault | Read | ||
| AV | 20 | Previous-Fault-2 | Second most recent stored fault | Read | ||
| AV | 21 | AO1-Monitor | Output level of analog output 1 | % | Read | |
| AV | 23 | Accel-1-Seconds | Ramp 1 acceleration time | s | Write | |
| AV | 24 | Decel-1-Seconds | Ramp 1 deceleration time | s | Write | |
| AV | 29 | Min-Speed | Minimum allowed output frequency | Hz | Write | |
| AV | 30 | Max-Speed | Maximum allowed output frequency | Hz | Write | |
| AV | 31 | Output-Speed | Motor speed, % of rated frequency (9907) | % | Read | |
| AV | 32 | Output-Current-Range | Motor current, % of rated current (9906) | % | Read | |
| AV | 33 | Max-Current | Max motor current (rated current in 9906) | A | Write | |
| AV | 40 | PID Feedback | PID controller feedback value | % | Read | |
| AV | 41 | PID reference | PID controller reference value | % | Read |
No points match these filters.
Object ID lookup: Greenheck Vari-Green Motor BACnet MS/TP point IDs by name
BI0R01 – MonitorBI5D01 – MonitorBI6DI1 – MonitorBI7DI2 – MonitorBI8DI3 – MonitorBO0R01 – CommandBO5DO1 – CommandBV0Run / Stop-MonitorBV1Direction-MonitorBV2OK-Fault-MonitorBV4Warning-MonitorBV5Ready-MonitorBV7At-Setpoint-MonitorBV8At-Setpoint-MonitorBV10RUN-STOP-CommandBV11Direction-CommandBV14Fault-Reset-CommandBV17Lock-ParametersBV41Fire ModeAI0AI1 – MonitorAI1AI2 - MonitorAV0*Output-RPMAV1Output-FreqAV2DC-VoltageAV3Output-VoltageAV4Output-CurrentAV5Output-TorqueAV6Output-PowerAV7Operating-Temp-RangeAV8Kilowatt-Hour-Meter-NRAV9Running-HoursAV14Input-Reference-1AV16Active-FaultAV18Previous-Fault-1AV20Previous-Fault-2AV21AO1-MonitorAV23Accel-1-SecondsAV24Decel-1-SecondsAV29Min-SpeedAV30Max-SpeedAV31Output-SpeedAV32Output-Current-RangeAV33Max-CurrentAV40PID FeedbackAV41PID reference
Integration notes
- Object dictionary from appendix B.6 of the manual (pages 103-104).
- The manual prints BI 8 twice: DI3 - Monitor and DI4 - Monitor (status of digital input 4). Only the DI3 row is listed to avoid a duplicate object ID; check where DI4 sits on a live unit.
- Several BV names don't match their descriptions: BV 4 'Warning-Monitor' is described as Hand/Auto mode, BV 5 'Ready-Monitor' as the overload warning, and BV 7 and BV 8 are both named 'At-Setpoint-Monitor' (ready status and at-setpoint status). Names, descriptions and state texts are listed as printed.
- BO 0 and BO 5 are marked read-only in the table.
- AV 0 Output-RPM reads 0 unless the motor rated speed is entered in parameter 9908. AV 8 is printed with unit 'kW/h' and listed here as kWh.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vari-Green Motor (EC Titanium) BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP
How many BACnet points does the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP have?
This list has 45 BACnet objects: 2 analog inputs, 24 analog values, 5 binary inputs, 2 binary outputs, 12 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet points are writable?
10 of the 45 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP BACnet documentation?
The source is Vari-Green Motor (EC Titanium) single/three-phase User Manual (MN448), revision 01/2022, published free by Greenheck at https://webcontent.greenheck.com/atg-cms-v2-prod/docs/default-source/resource-library/installation-manuals/fans/single_threephase_varigreenmotor_usermanual_jan2022.pdf.
What are the minimum BACnet points to integrate the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP?
Start with BV 10 RUN-STOP-Command (Run/stop command (1 = run)); AV 14 Input-Reference-1 (Speed setpoint, % of maximum speed); BV 14 Fault-Reset-Command (Fault reset (1 = reset)); BV 0 Run / Stop-Monitor (Running status); AV 1 Output-Freq (Output frequency in Hz); AV 4 Output-Current (Motor amps); BV 2 OK-Fault-Monitor (Drive fault status); AV 16 Active-Fault (Active fault code).
How do I enable BMS control of the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP?
Set 1103 PRIMARY COMMAND SOURCE MODE = 9 (BACnet MS/TP; ramps from 2202/2203). Parameter 9902 then decides whether the speed reference and start/stop come from the network or the terminal strip. BV 4 shows Auto when the drive is under terminal or BACnet control.
Does the Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP need a BACnet heartbeat or have a communication timeout?
Parameter 5302 includes a watchdog timeout of 0 (disabled), 30, 100, 1000 or 3000 ms. A 't' suffix trips the drive on loss of communication (fault F0010); an 'r' suffix coasts the motor to a stop without a trip.
How do I check these points on the real Vari-Green Motor (EC Titanium) BACnet MS/TP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Greenheck BACnet points lists
- Dedicated outdoor air system (DOAS)
Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet
Greenheck dedicated outdoor air units whose factory controller runs the DOAS_10 program with BACnet licensed.
Also known as: Greenheck DOAS, DOAS, DOAS_10.006, 485940 - Dedicated outdoor air system (DOAS) unit controller
Greenheck DOAS Microprocessor Controller v6.2 (legacy points list)
Greenheck dedicated outdoor air units running the older DOAS v6.2 controller program (July 2021 guide).
Also known as: 485175, Document 485175, DOAS v6.2, Greenheck DOAS controller, c.pCO - Kitchen hood exhaust and supply fan controls
Greenheck Kitchen Controls (GKC) main board
Greenheck Kitchen Controls panels (standard and advanced) for kitchen hoods: up to 8 exhaust fans, 4 supply fans, 8 zones and 16 hood control boards.
Also known as: GKC, Greenheck Kitchen Controls, 484600, GKC-CV, GKC-DCV, Kitchen hood controls - Energy recovery ventilator
Greenheck IVE Indoor Energy Recovery Ventilator (BACnet)
Greenheck IVE indoor energy recovery ventilators with the factory c.pCO Mini controller.
Also known as: IVE, Greenheck IVE, IVE_01.002, 487690, c.pCO Mini - Make-up air unit controller
Greenheck Make-Up Air Microprocessor Controller (MUA v4.1)
Greenheck make-up air units with the factory microprocessor controller, MUA program v4.1.
Also known as: 487036, Document 487036, MUA v4.1, Greenheck make-up air controller, c.pCO - Rooftop unit (RTU) controller
Greenheck RTU Microprocessor Controller (RTU v1.4)
Greenheck (and Valent) packaged rooftop units with the factory microprocessor controller, RTU program v1.4.
Also known as: 487424, Document 487424, 487426, Valent RTU controller, RTU v1.4, Greenheck rooftop unit controller, c.pCO - Fan variable frequency drive (VFD)
Greenheck Vari-Green Drive VGD-100+
Greenheck Vari-Green Drive (VGD-100+) motor drives used on Greenheck fans.
Also known as: VGD, VGD-100, VGD-100+, Vari-Green Drive, 481200
Source: Vari-Green Motor (EC Titanium) single/three-phase User Manual · MN448 · rev. 01/2022. Object names, instances and units are reproduced as published; descriptions are our own.