Greenheck Kitchen Controls (GKC) run kitchen hood exhaust and supply fans, hood lights, hood wash and temperature or optic-based demand control. The main board talks BACnet MS/TP directly on J23; BACnet IP panels get a Modbus RTU to BACnet IP gateway. The list covers room, hood and supply temperatures, optic opacity, fan VFD data, zone and fan commands, hood light and wash commands, tuning values and packed status/fault words.
This page lists 276 BACnet objects for the Greenheck Kitchen Controls (GKC) main board — 135 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greenheck’s own free documentation, linked below.
- Manufacturer
- Greenheck
- Model
- Greenheck Kitchen Controls (GKC) main board
- Equipment
- Kitchen hood exhaust and supply fan controls
- Equipment type
- Other equipment
- BACnet objects
- 276 (135 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 77000
- Also known as
- GKC, Greenheck Kitchen Controls, 484600, GKC-CV, GKC-DCV, Kitchen hood controls
Reference only, provided as-is: verify against Greenheck’s current documentation and the live device before use. Not official Greenheck information. Terms of use.
BMS integration notes: Greenheck Kitchen Controls (GKC) main board
Turn zone fans on and off with BV 0-7 (Fans - Zone n) and hood lights with BV 8-24. Read hood and room temperatures (AI 0-8 and the HCB AIs), fan VFD frequency, and the Faults word (instance 11) for alarms. Hood wash can be started per hood control board with BV 38-53.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Fans - Zone 1 | Zone 1 fans on/off (1 = on) | Write |
| BV 8 | Hood Lights - Main Board | Main board hood lights on/off | Write |
| BV 25 | Max Fan Enable | Max fan (full speed) on/off | Write |
| AI 0 | MB Room Sensor Temp | Room temperature at the main board | Read |
| AI 1 | MB Hood Temp Sensor 1 | Hood temperature sensor 1 | Read |
| Other 0 | Zone 1 Status | Zone 1 status bits: why the fans are on | Read |
| Other 11 | Faults | Fault bits; first bit = any fault | Read |
Enable & remote start
BV 0-7 turn zone fans on and off from the BMS. Each zone status word has a 'fan on via BMS' bit, so the BMS can see when its command is holding the fans on.
Network setup
- BACnet MS/TP: default Device Instance 77000, MAC 0, Max Master 127, Max Info Frames 20; baud 9600-115200 (default 9600). Set under BMS Settings.
- BACnet IP panels use a ProSoft Modbus RTU to BACnet IP QuickServer gateway; leave the main board at Modbus address 1 and 9600 baud. The gateway default IP is 192.168.2.101.
- Wire BACnet MS/TP to the main board J23 terminals with shielded twisted pair.
Watch out for
- Status and fault words must be unpacked bit by bit, and the bit order on MS/TP is the reverse of the IP gateway.
Greenheck Kitchen Controls (GKC) main board BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | MB Room Sensor Temp | MB Room Temp Sensor | °F | Read | |
| AImin | 1 | MB Hood Temp Sensor 1 | °F | Read | ||
| AI | 2 | MB Hood Temp Sensor 2 | °F | Read | ||
| AI | 3 | MB Hood Temp Sensor 3 | °F | Read | ||
| AI | 4 | MB Hood Temp Sensor 4 | °F | Read | ||
| AI | 5 | MB Hood Temp Sensor 5 | °F | Read | ||
| AI | 6 | MB Hood Temp Sensor 6 | °F | Read | ||
| AI | 7 | MB Hood Temp Sensor 7 | °F | Read | ||
| AI | 8 | MB Hood Temp Sensor 8 | °F | Read | ||
| AI | 9 | HCB1 Room Temp Sensor | °F | Read | ||
| AI | 10 | HCB1 Hood Temp Sensor | °F | Read | ||
| AI | 11 | HCB1 Supply Temp Sensor | °F | Read | ||
| AI | 12 | HCB1 Optics Opacity Level | % | Read | ||
| AI | 13 | HCB2 Room Temp Sensor | °F | Read | ||
| AI | 14 | HCB2 Hood Temp Sensor | °F | Read | ||
| AI | 15 | HCB2 Supply Temp Sensor | °F | Read | ||
| AI | 16 | HCB2 Optics Opacity Level | % | Read | ||
| AI | 17 | HCB3 Room Temp Sensor | °F | Read | ||
| AI | 18 | HCB3 Hood Temp Sensor | °F | Read | ||
| AI | 19 | HCB3 Supply Temp Sensor | °F | Read | ||
| AI | 20 | HCB3 Optics Opacity Level | % | Read | ||
| AI | 21 | HCB4 Room Temp Sensor | °F | Read | ||
| AI | 22 | HCB4 Hood Temp Sensor | °F | Read | ||
| AI | 23 | HCB4 Supply Temp Sensor | °F | Read | ||
| AI | 24 | HCB4 Optics Opacity Level | % | Read | ||
| AI | 25 | HCB5 Room Temp Sensor | °F | Read | ||
| AI | 26 | HCB5 Hood Temp Sensor | °F | Read | ||
| AI | 27 | HCB5 Supply Temp Sensor | °F | Read | ||
| AI | 28 | HCB5 Optics Opacity Level | % | Read | ||
| AI | 29 | HCB6 Room Temp Sensor | °F | Read | ||
| AI | 30 | HCB6 Hood Temp Sensor | °F | Read | ||
| AI | 31 | HCB6 Supply Temp Sensor | °F | Read | ||
| AI | 32 | HCB6 Optics Opacity Level | % | Read | ||
| AI | 33 | HCB7 Room Temp Sensor | °F | Read | ||
| AI | 34 | HCB7 Hood Temp Sensor | °F | Read | ||
| AI | 35 | HCB7 Supply Temp Sensor | °F | Read | ||
| AI | 36 | HCB7 Optics Opacity Level | % | Read | ||
| AI | 37 | HCB8 Room Temp Sensor | °F | Read | ||
| AI | 38 | HCB8 Hood Temp Sensor | °F | Read | ||
| AI | 39 | HCB8 Supply Temp Sensor | °F | Read | ||
| AI | 40 | HCB8 Optics Opacity Level | % | Read | ||
| AI | 41 | HCB9 Room Temp Sensor | °F | Read | ||
| AI | 42 | HCB9 Hood Temp Sensor | °F | Read | ||
| AI | 43 | HCB9 Supply Temp Sensor | °F | Read | ||
| AI | 44 | HCB9 Optics Opacity Level | % | Read | ||
| AI | 45 | HCB10 Room Temp Sensor | °F | Read | ||
| AI | 46 | HCB10 Hood Temp Sensor | °F | Read | ||
| AI | 47 | HCB10 Supply Temp Sensor | °F | Read | ||
| AI | 48 | HCB10 Optics Opacity Level | % | Read | ||
| AI | 49 | HCB11 Room Temp Sensor | °F | Read | ||
| AI | 50 | HCB11 Hood Temp Sensor | °F | Read | ||
| AI | 51 | HCB11 Supply Temp Sensor | °F | Read | ||
| AI | 52 | HCB11 Optics Opacity Level | % | Read | ||
| AI | 53 | HCB12 Room Temp Sensor | °F | Read | ||
| AI | 54 | HCB12 Hood Temp Sensor | °F | Read | ||
| AI | 55 | HCB12 Supply Temp Sensor | °F | Read | ||
| AI | 56 | HCB12 Optics Opacity Level | % | Read | ||
| AI | 57 | HCB13 Room Temp Sensor | °F | Read | ||
| AI | 58 | HCB13 Hood Temp Sensor | °F | Read | ||
| AI | 59 | HCB13 Supply Temp Sensor | °F | Read | ||
| AI | 60 | HCB13 Optics Opacity Level | % | Read | ||
| AI | 61 | HCB14 Room Temp Sensor | °F | Read | ||
| AI | 62 | HCB14 Hood Temp Sensor | °F | Read | ||
| AI | 63 | HCB14 Supply Temp Sensor | °F | Read | ||
| AI | 64 | HCB14 Optics Opacity Level | % | Read | ||
| AI | 65 | HCB15 Room Temp Sensor | °F | Read | ||
| AI | 66 | HCB15 Hood Temp Sensor | °F | Read | ||
| AI | 67 | HCB15 Supply Temp Sensor | °F | Read | ||
| AI | 68 | HCB15 Optics Opacity Level | % | Read | ||
| AI | 69 | HCB16 Room Temp Sensor | °F | Read | ||
| AI | 70 | HCB16 Hood Temp Sensor | °F | Read | ||
| AI | 71 | HCB16 Supply Temp Sensor | °F | Read | ||
| AI | 72 | HCB16 Optics Opacity Level | % | Read | ||
| AI | 73 | Operating % - Exhaust Fan 1 | Exhaust fan 1 Operating Percentage | % | Read | |
| AI | 74 | Operating % - Exhaust Fan 2 | Exhaust fan 2 Operating Percentage | % | Read | |
| AI | 75 | Operating % - Exhaust Fan 3 | Exhaust fan 3 Operating Percentage | % | Read | |
| AI | 76 | Operating % - Exhaust Fan 4 | Exhaust fan 4 Operating Percentage | % | Read | |
| AI | 77 | Operating % - Exhaust Fan 5 | Exhaust fan 5 Operating Percentage | % | Read | |
| AI | 78 | Operating % - Exhaust Fan 6 | Exhaust fan 6 Operating Percentage | % | Read | |
| AI | 79 | Operating % - Exhaust Fan 7 | Exhaust fan 7 Operating Percentage | % | Read | |
| AI | 80 | Operating % - Exhaust Fan 8 | Exhaust fan 8 Operating Percentage | % | Read | |
| AI | 81 | Operating % - Supply Fan 1 | Supply fan 1 Operating Percentage | % | Read | |
| AI | 82 | Operating % - Supply Fan 2 | Supply fan 2 Operating Percentage | % | Read | |
| AI | 83 | Operating % - Supply Fan 3 | Supply fan 3 Operating Percentage | % | Read | |
| AI | 84 | Operating % - Supply Fan 4 | Supply fan 4 Operating Percentage | % | Read | |
| AI | 85 | VFD Operating Frequency - Exhaust Fan 1 | Exhaust fan 1 VFD Operating Frequency | Hz | Read | |
| AI | 86 | VFD Operating Frequency - Exhaust Fan 2 | Exhaust fan 2 VFD Operating Frequency | Hz | Read | |
| AI | 87 | VFD Operating Frequency - Exhaust Fan 3 | Exhaust fan 3 VFD Operating Frequency | Hz | Read | |
| AI | 88 | VFD Operating Frequency - Exhaust Fan 4 | Exhaust fan 4 VFD Operating Frequency | Hz | Read | |
| AI | 89 | VFD Operating Frequency - Exhaust Fan 5 | Exhaust fan 5 VFD Operating Frequency | Hz | Read | |
| AI | 90 | VFD Operating Frequency - Exhaust Fan 6 | Exhaust fan 6 VFD Operating Frequency | Hz | Read | |
| AI | 91 | VFD Operating Frequency - Exhaust Fan 7 | Exhaust fan 7 VFD Operating Frequency | Hz | Read | |
| AI | 92 | VFD Operating Frequency - Exhaust Fan 8 | Exhaust fan 8 VFD Operating Frequency | Hz | Read | |
| AI | 93 | VFD Operating Frequency - Supply Fan 1 | Supply Fan 1 VFD Operating Frequency | Hz | Read | |
| AI | 94 | VFD Operating Frequency - Supply Fan 2 | Supply Fan 2 VFD Operating Frequency | Hz | Read | |
| AI | 95 | VFD Operating Frequency - Supply Fan 3 | Supply Fan 3 VFD Operating Frequency | Hz | Read | |
| AI | 96 | VFD Operating Frequency - Supply Fan 4 | Supply Fan 4 VFD Operating Frequency | Hz | Read | |
| AI | 97 | VFD Operating Amperage - Exhaust Fan 1 | Exhaust Fan 1 VFD Operating Amperage | A | Read | |
| AI | 98 | VFD Operating Amperage - Exhaust Fan 2 | Exhaust Fan 2 VFD Operating Amperage | A | Read | |
| AI | 99 | VFD Operating Amperage - Exhaust Fan 3 | Exhaust fan 3 VFD Operating Amperage | A | Read | |
| AI | 100 | VFD Operating Amperage - Exhaust Fan 4 | Exhaust fan 4 VFD Operating Amperage | A | Read | |
| AI | 101 | VFD Operating Amperage - Exhaust Fan 5 | Exhaust fan 5 VFD Operating Amperage | A | Read | |
| AI | 102 | VFD Operating Amperage - Exhaust Fan 6 | Exhaust fan 6 VFD Operating Amperage | A | Read | |
| AI | 103 | VFD Operating Amperage - Exhaust Fan 7 | Exhaust fan 7 VFD Operating Amperage | A | Read | |
| AI | 104 | VFD Operating Amperage - Exhaust Fan 8 | Exhaust fan 8 VFD Operating Amperage | A | Read | |
| AI | 105 | VFD Operating Amperage - Supply Fan 1 | Supply Fan 1 VFD Operating Amperage | A | Read | |
| AI | 106 | VFD Operating Amperage - Supply Fan 2 | Supply Fan 2 VFD Operating Amperage | A | Read | |
| AI | 107 | VFD Operating Amperage - Supply Fan 3 | Supply Fan 3 VFD Operating Amperage | A | Read | |
| AI | 108 | VFD Operating Amperage - Supply Fan 4 | Supply Fan 4 VFD Operating Amperage | A | Read | |
| AI | 109 | VFD Power Output - Exhaust Fan 1 | Exhaust Fan 1 VFD Output Power | W | Read | |
| AI | 110 | VFD Power Output - Exhaust Fan 2 | Exhaust Fan 2 VFD Output Power | W | Read | |
| AI | 111 | VFD Power Output - Exhaust Fan 3 | Exhaust Fan 3 VFD Output Power | W | Read | |
| AI | 112 | VFD Power Output - Exhaust Fan 4 | Exhaust Fan 4 VFD Output Power | W | Read | |
| AI | 113 | VFD Power Output - Exhaust Fan 5 | Exhaust Fan 5 VFD Output Power | W | Read | |
| AI | 114 | VFD Power Output - Exhaust Fan 6 | Exhaust Fan 6 VFD Output Power | W | Read | |
| AI | 115 | VFD Power Output - Exhaust Fan 7 | Exhaust Fan 7 VFD Output Power | W | Read | |
| AI | 116 | VFD Power Output - Exhaust Fan 8 | Exhaust Fan 8 VFD Output Power | W | Read | |
| AI | 117 | VFD Power Output - Supply Fan 1 | Supply Fan 1 VFD Output Power | W | Read | |
| AI | 118 | VFD Power Output - Supply Fan 2 | Supply Fan 2 VFD Output Power | W | Read | |
| AI | 119 | VFD Power Output - Supply Fan 3 | Supply Fan 3 VFD Output Power | W | Read | |
| AI | 120 | VFD Power Output - Supply Fan 4 | Supply Fan 4 VFD Output Power | W | Read | |
| AI | 121 | Fan VDC 1 Status (J7 Analog Output) | V | Read | ||
| AI | 122 | Fan VDC 2 Status (J8 Analog Output) | V | Read | ||
| AI | 123 | Fan VDC 3 Status (J9 Analog Output) | V | Read | ||
| AI | 124 | Fan VDC 4 Status (J10 Analog Output) | V | Read | ||
| AI | 125 | Fan VDC 5 Status (J11 Analog Output) | V | Read | ||
| AI | 126 | Fan VDC 6 Status (J12 Analog Output) | V | Read | ||
| AI | 127 | Fan VDC 7 Status (J13 Analog Output) | V | Read | ||
| AI | 128 | Fan VDC 8 Status (J14 Analog Output) | V | Read | ||
| AV | 0 | Minimum VDC - Exhaust Fan 1 | V | Write | ||
| AV | 1 | Minimum VDC - Exhaust Fan 2 | V | Write | ||
| AV | 2 | Minimum VDC - Exhaust Fan 3 | V | Write | ||
| AV | 3 | Minimum VDC - Exhaust Fan 4 | V | Write | ||
| AV | 4 | Minimum VDC - Exhaust Fan 5 | V | Write | ||
| AV | 5 | Minimum VDC - Exhaust Fan 6 | V | Write | ||
| AV | 6 | Minimum VDC - Exhaust Fan 7 | V | Write | ||
| AV | 7 | Minimum VDC - Exhaust Fan 8 | V | Write | ||
| AV | 8 | Minimum VDC - Supply Fan 1 | V | Write | ||
| AV | 9 | Minimum VDC - Supply Fan 2 | V | Write | ||
| AV | 10 | Minimum VDC - Supply Fan 3 | V | Write | ||
| AV | 11 | Minimum VDC - Supply Fan 4 | V | Write | ||
| AV | 12 | Maximum VDC - Exhaust Fan 1 | V | Write | ||
| AV | 13 | Maximum VDC - Exhaust Fan 2 | V | Write | ||
| AV | 14 | Maximum VDC - Exhaust Fan 3 | V | Write | ||
| AV | 15 | Maximum VDC - Exhaust Fan 4 | V | Write | ||
| AV | 16 | Maximum VDC - Exhaust Fan 5 | V | Write | ||
| AV | 17 | Maximum VDC - Exhaust Fan 6 | V | Write | ||
| AV | 18 | Maximum VDC - Exhaust Fan 7 | V | Write | ||
| AV | 19 | Maximum VDC - Exhaust Fan 8 | V | Write | ||
| AV | 20 | Maximum VDC - Supply Fan 1 | V | Write | ||
| AV | 21 | Maximum VDC - Supply Fan 2 | V | Write | ||
| AV | 22 | Maximum VDC - Supply Fan 3 | V | Write | ||
| AV | 23 | Maximum VDC - Supply Fan 4 | V | Write | ||
| AV | 24 | VFD Minimum Frequency - Exhaust Fan 1 | Hz | Write | ||
| AV | 25 | VFD Minimum Frequency - Exhaust Fan 2 | Hz | Write | ||
| AV | 26 | VFD Minimum Frequency - Exhaust Fan 3 | Hz | Write | ||
| AV | 27 | VFD Minimum Frequency - Exhaust Fan 4 | Hz | Write | ||
| AV | 28 | VFD Minimum Frequency - Exhaust Fan 5 | Hz | Write | ||
| AV | 29 | VFD Minimum Frequency - Exhaust Fan 6 | Hz | Write | ||
| AV | 30 | VFD Minimum Frequency - Exhaust Fan 7 | Hz | Write | ||
| AV | 31 | VFD Minimum Frequency - Exhaust Fan 8 | Hz | Write | ||
| AV | 32 | VFD Minimum Frequency - Supply Fan 1 | Hz | Write | ||
| AV | 33 | VFD Minimum Frequency - Supply Fan 2 | Hz | Write | ||
| AV | 34 | VFD Minimum Frequency - Supply Fan 3 | Hz | Write | ||
| AV | 35 | VFD Minimum Frequency - Supply Fan 4 | Hz | Write | ||
| AV | 36 | VFD Maximum Frequency - Exhaust Fan 1 | Hz | Write | ||
| AV | 37 | VFD Maximum Frequency - Exhaust Fan 2 | Hz | Write | ||
| AV | 38 | VFD Maximum Frequency - Exhaust Fan 3 | Hz | Write | ||
| AV | 39 | VFD Maximum Frequency - Exhaust Fan 4 | Hz | Write | ||
| AV | 40 | VFD Maximum Frequency - Exhaust Fan 5 | Hz | Write | ||
| AV | 41 | VFD Maximum Frequency - Exhaust Fan 6 | Hz | Write | ||
| AV | 42 | VFD Maximum Frequency - Exhaust Fan 7 | Hz | Write | ||
| AV | 43 | VFD Maximum Frequency - Exhaust Fan 8 | Hz | Write | ||
| AV | 44 | VFD Maximum Frequency - Supply Fan 1 | Hz | Write | ||
| AV | 45 | VFD Maximum Frequency - Supply Fan 2 | Hz | Write | ||
| AV | 46 | VFD Maximum Frequency - Supply Fan 3 | Hz | Write | ||
| AV | 47 | VFD Maximum Frequency - Supply Fan 4 | Hz | Write | ||
| AV | 48 | Temp Interlock Offset - Zone 1 | °F | Write | ||
| AV | 49 | Temp Interlock Offset - Zone 2 | °F | Write | ||
| AV | 50 | Temp Interlock Offset - Zone 3 | °F | Write | ||
| AV | 51 | Temp Interlock Offset - Zone 4 | °F | Write | ||
| AV | 52 | Temp Interlock Offset - Zone 5 | °F | Write | ||
| AV | 53 | Temp Interlock Offset - Zone 6 | °F | Write | ||
| AV | 54 | Temp Interlock Offset - Zone 7 | °F | Write | ||
| AV | 55 | Temp Interlock Offset - Zone 8 | °F | Write | ||
| AV | 56 | Temp Interlock Hysteresis - Zone 1 | °F | Write | ||
| AV | 57 | Temp Interlock Hysteresis - Zone 2 | °F | Write | ||
| AV | 58 | Temp Interlock Hysteresis - Zone 3 | °F | Write | ||
| AV | 59 | Temp Interlock Hysteresis - Zone 4 | °F | Write | ||
| AV | 60 | Temp Interlock Hysteresis - Zone 5 | °F | Write | ||
| AV | 61 | Temp Interlock Hysteresis - Zone 6 | °F | Write | ||
| AV | 62 | Temp Interlock Hysteresis - Zone 7 | °F | Write | ||
| AV | 63 | Temp Interlock Hysteresis - Zone 8 | °F | Write | ||
| AV | 64 | Temp Interlock Hysteresis Timer - Zone 1 | min | Write | ||
| AV | 65 | Temp Interlock Hysteresis Timer - Zone 2 | min | Write | ||
| AV | 66 | Temp Interlock Hysteresis Timer - Zone 3 | min | Write | ||
| AV | 67 | Temp Interlock Hysteresis Timer - Zone 4 | min | Write | ||
| AV | 68 | Temp Interlock Hysteresis Timer - Zone 5 | min | Write | ||
| AV | 69 | Temp Interlock Hysteresis Timer - Zone 6 | min | Write | ||
| AV | 70 | Temp Interlock Hysteresis Timer - Zone 7 | min | Write | ||
| AV | 71 | Temp Interlock Hysteresis Timer - Zone 8 | min | Write | ||
| AV | 72 | Modulation Temp Range - Exhaust Fan 1 | °F | Write | ||
| AV | 73 | Modulation Temp Range - Exhaust Fan 2 | °F | Write | ||
| AV | 74 | Modulation Temp Range - Exhaust Fan 3 | °F | Write | ||
| AV | 75 | Modulation Temp Range - Exhaust Fan 4 | °F | Write | ||
| AV | 76 | Modulation Temp Range - Exhaust Fan 5 | °F | Write | ||
| AV | 77 | Modulation Temp Range - Exhaust Fan 6 | °F | Write | ||
| AV | 78 | Modulation Temp Range - Exhaust Fan 7 | °F | Write | ||
| AV | 79 | Modulation Temp Range - Exhaust Fan 8 | °F | Write | ||
| BVmin | 0 | Fans - Zone 1 | 1/0 to turn on/off zone 1 | Write | 0=Off, 1=On | |
| BV | 1 | Fans - Zone 2 | 1/0 to turn on/off zone 2 | Write | 0=Off, 1=On | |
| BV | 2 | Fans - Zone 3 | 1/0 to turn on/off zone 3 | Write | 0=Off, 1=On | |
| BV | 3 | Fans - Zone 4 | 1/0 to turn on/off zone 4 | Write | 0=Off, 1=On | |
| BV | 4 | Fans - Zone 5 | 1/0 to turn on/off zone 5 | Write | 0=Off, 1=On | |
| BV | 5 | Fans - Zone 6 | 1/0 to turn on/off zone 6 | Write | 0=Off, 1=On | |
| BV | 6 | Fans - Zone 7 | 1/0 to turn on/off zone 7 | Write | 0=Off, 1=On | |
| BV | 7 | Fans - Zone 8 | 1/0 to turn on/off zone 8 | Write | 0=Off, 1=On | |
| BVmin | 8 | Hood Lights - Main Board | 1/0 to turn on/off MB Hood Lights | Write | 0=Off, 1=On | |
| BV | 9 | Hood Lights - HCB1 | 1/0 to turn on/off HCB1 Hood Lights | Write | 0=Off, 1=On | |
| BV | 10 | Hood Lights - HCB2 | 1/0 to turn on/off HCB2 Hood Lights | Write | 0=Off, 1=On | |
| BV | 11 | Hood Lights - HCB3 | 1/0 to turn on/off HCB3 Hood Lights | Write | 0=Off, 1=On | |
| BV | 12 | Hood Lights - HCB4 | 1/0 to turn on/off HCB4 Hood Lights | Write | 0=Off, 1=On | |
| BV | 13 | Hood Lights - HCB5 | 1/0 to turn on/off HCB5 Hood Lights | Write | 0=Off, 1=On | |
| BV | 14 | Hood Lights - HCB6 | 1/0 to turn on/off HCB6 Hood Lights | Write | 0=Off, 1=On | |
| BV | 15 | Hood Lights - HCB7 | 1/0 to turn on/off HCB7 Hood Lights | Write | 0=Off, 1=On | |
| BV | 16 | Hood Lights - HCB8 | 1/0 to turn on/off HCB8 Hood Lights | Write | 0=Off, 1=On | |
| BV | 17 | Hood Lights - HCB9 | 1/0 to turn on/off HCB9 Hood Lights | Write | 0=Off, 1=On | |
| BV | 18 | Hood Lights - HCB10 | 1/0 to turn on/off HCB10 Hood Lights | Write | 0=Off, 1=On | |
| BV | 19 | Hood Lights - HCB11 | 1/0 to turn on/off HCB11 Hood Lights | Write | 0=Off, 1=On | |
| BV | 20 | Hood Lights - HCB12 | 1/0 to turn on/off HCB12 Hood Lights | Write | 0=Off, 1=On | |
| BV | 21 | Hood Lights - HCB13 | 1/0 to turn on/off HCB13 Hood Lights | Write | 0=Off, 1=On | |
| BV | 22 | Hood Lights - HCB14 | 1/0 to turn on/off HCB14 Hood Lights | Write | 0=Off, 1=On | |
| BV | 23 | Hood Lights - HCB15 | 1/0 to turn on/off HCB15 Hood Lights | Write | 0=Off, 1=On | |
| BV | 24 | Hood Lights - HCB16 | 1/0 to turn on/off HCB16 Hood Lights | Write | 0=Off, 1=On | |
| BVmin | 25 | Max Fan Enable | 1/0 to turn Max Fan on/off | Write | 0=Off, 1=On | |
| BV | 26 | Exhaust Fan 1 Enable | 1/0 to turn on/off Exhaust Fan 1 | Write | 0=Off, 1=On | |
| BV | 27 | Exhaust Fan 2 Enable | 1/0 to turn on/off Exhaust Fan 2 | Write | 0=Off, 1=On | |
| BV | 28 | Exhaust Fan 3 Enable | 1/0 to turn on/off Exhaust Fan 3 | Write | 0=Off, 1=On | |
| BV | 29 | Exhaust Fan 4 Enable | 1/0 to turn on/off Exhaust Fan 4 | Write | 0=Off, 1=On | |
| BV | 30 | Exhaust Fan 5 Enable | 1/0 to turn on/off Exhaust Fan 5 | Write | 0=Off, 1=On | |
| BV | 31 | Exhaust Fan 6 Enable | 1/0 to turn on/off Exhaust Fan 6 | Write | 0=Off, 1=On | |
| BV | 32 | Exhaust Fan 7 Enable | 1/0 to turn on/off Exhaust Fan 7 | Write | 0=Off, 1=On | |
| BV | 33 | Exhaust Fan 8 Enable | 1/0 to turn on/off Exhaust Fan 8 | Write | 0=Off, 1=On | |
| BV | 34 | Supply Fan 1 Enable | 1/0 to turn on/off Supply Fan 1 | Write | 0=Off, 1=On | |
| BV | 35 | Supply Fan 2 Enable | 1/0 to turn on/off Supply Fan 2 | Write | 0=Off, 1=On | |
| BV | 36 | Supply Fan 3 Enable | 1/0 to turn on/off Supply Fan 3 | Write | 0=Off, 1=On | |
| BV | 37 | Supply Fan 4 Enable | 1/0 to turn on/off Supply Fan 4 | Write | 0=Off, 1=On | |
| BV | 38 | HCB1 Hood Wash | 1/0 to start/stop HCB1 Hood Wash | Write | 0=Off, 1=On | |
| BV | 39 | HCB2 Hood Wash | 1/0 to start/stop HCB2 Hood Wash | Write | 0=Off, 1=On | |
| BV | 40 | HCB3 Hood Wash | 1/0 to start/stop HCB3 Hood Wash | Write | 0=Off, 1=On | |
| BV | 41 | HCB4 Hood Wash | 1/0 to start/stop HCB4 Hood Wash | Write | 0=Off, 1=On | |
| BV | 42 | HCB5 Hood Wash | 1/0 to start/stop HCB5 Hood Wash | Write | 0=Off, 1=On | |
| BV | 43 | HCB6 Hood Wash | 1/0 to start/stop HCB6 Hood Wash | Write | 0=Off, 1=On | |
| BV | 44 | HCB7 Hood Wash | 1/0 to start/stop HCB7 Hood Wash | Write | 0=Off, 1=On | |
| BV | 45 | HCB8 Hood Wash | 1/0 to start/stop HCB8 Hood Wash | Write | 0=Off, 1=On | |
| BV | 46 | HCB9 Hood Wash | 1/0 to start/stop HCB9 Hood Wash | Write | 0=Off, 1=On | |
| BV | 47 | HCB10 Hood Wash | 1/0 to start/stop HCB10 Hood Wash | Write | 0=Off, 1=On | |
| BV | 48 | HCB11 Hood Wash | 1/0 to start/stop HCB11 Hood Wash | Write | 0=Off, 1=On | |
| BV | 49 | HCB12 Hood Wash | 1/0 to start/stop HCB12 Hood Wash | Write | 0=Off, 1=On | |
| BV | 50 | HCB13 Hood Wash | 1/0 to start/stop HCB13 Hood Wash | Write | 0=Off, 1=On | |
| BV | 51 | HCB14 Hood Wash | 1/0 to start/stop HCB14 Hood Wash | Write | 0=Off, 1=On | |
| BV | 52 | HCB15 Hood Wash | 1/0 to start/stop HCB15 Hood Wash | Write | 0=Off, 1=On | |
| BV | 53 | HCB16 Hood Wash | 1/0 to start/stop HCB16 Hood Wash | Write | 0=Off, 1=On | |
| BV | 54 | Duct Sump Wash | 1/0 to start/stop Duct Sump Wash | Write | 0=Off, 1=On | |
| Othermin | 0 | Zone 1 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 1 | Zone 2 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 2 | Zone 3 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 3 | Zone 4 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 4 | Zone 5 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 5 | Zone 6 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 6 | Zone 7 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 7 | Zone 8 Status | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 8 | Exhaust Fan VFD Faults | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 9 | Supply Fan VFD Faults | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Other | 10 | Relay Statuses | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read | ||
| Othermin | 11 | Faults | Packed bit word: BitString Value (type 39) on MS/TP, AV over IP | Read |
No points match these filters.
Object ID lookup: Greenheck Kitchen Controls main board point IDs by name
AI0MB Room Sensor TempAI1MB Hood Temp Sensor 1AI2MB Hood Temp Sensor 2AI3MB Hood Temp Sensor 3AI4MB Hood Temp Sensor 4AI5MB Hood Temp Sensor 5AI6MB Hood Temp Sensor 6AI7MB Hood Temp Sensor 7AI8MB Hood Temp Sensor 8AI9HCB1 Room Temp SensorAI10HCB1 Hood Temp SensorAI11HCB1 Supply Temp SensorAI12HCB1 Optics Opacity LevelAI13HCB2 Room Temp SensorAI14HCB2 Hood Temp SensorAI15HCB2 Supply Temp SensorAI16HCB2 Optics Opacity LevelAI17HCB3 Room Temp SensorAI18HCB3 Hood Temp SensorAI19HCB3 Supply Temp SensorAI20HCB3 Optics Opacity LevelAI21HCB4 Room Temp SensorAI22HCB4 Hood Temp SensorAI23HCB4 Supply Temp SensorAI24HCB4 Optics Opacity LevelAI25HCB5 Room Temp SensorAI26HCB5 Hood Temp SensorAI27HCB5 Supply Temp SensorAI28HCB5 Optics Opacity LevelAI29HCB6 Room Temp SensorAI30HCB6 Hood Temp SensorAI31HCB6 Supply Temp SensorAI32HCB6 Optics Opacity LevelAI33HCB7 Room Temp SensorAI34HCB7 Hood Temp SensorAI35HCB7 Supply Temp SensorAI36HCB7 Optics Opacity LevelAI37HCB8 Room Temp SensorAI38HCB8 Hood Temp SensorAI39HCB8 Supply Temp SensorAI40HCB8 Optics Opacity LevelAI41HCB9 Room Temp SensorAI42HCB9 Hood Temp SensorAI43HCB9 Supply Temp SensorAI44HCB9 Optics Opacity LevelAI45HCB10 Room Temp SensorAI46HCB10 Hood Temp SensorAI47HCB10 Supply Temp SensorAI48HCB10 Optics Opacity LevelAI49HCB11 Room Temp SensorAI50HCB11 Hood Temp SensorAI51HCB11 Supply Temp SensorAI52HCB11 Optics Opacity LevelAI53HCB12 Room Temp SensorAI54HCB12 Hood Temp SensorAI55HCB12 Supply Temp SensorAI56HCB12 Optics Opacity LevelAI57HCB13 Room Temp SensorAI58HCB13 Hood Temp SensorAI59HCB13 Supply Temp SensorAI60HCB13 Optics Opacity LevelAI61HCB14 Room Temp SensorAI62HCB14 Hood Temp SensorAI63HCB14 Supply Temp SensorAI64HCB14 Optics Opacity LevelAI65HCB15 Room Temp SensorAI66HCB15 Hood Temp SensorAI67HCB15 Supply Temp SensorAI68HCB15 Optics Opacity LevelAI69HCB16 Room Temp SensorAI70HCB16 Hood Temp SensorAI71HCB16 Supply Temp SensorAI72HCB16 Optics Opacity LevelAI73Operating % - Exhaust Fan 1AI74Operating % - Exhaust Fan 2AI75Operating % - Exhaust Fan 3AI76Operating % - Exhaust Fan 4AI77Operating % - Exhaust Fan 5AI78Operating % - Exhaust Fan 6AI79Operating % - Exhaust Fan 7AI80Operating % - Exhaust Fan 8AI81Operating % - Supply Fan 1AI82Operating % - Supply Fan 2AI83Operating % - Supply Fan 3AI84Operating % - Supply Fan 4AI85VFD Operating Frequency - Exhaust Fan 1AI86VFD Operating Frequency - Exhaust Fan 2AI87VFD Operating Frequency - Exhaust Fan 3AI88VFD Operating Frequency - Exhaust Fan 4AI89VFD Operating Frequency - Exhaust Fan 5AI90VFD Operating Frequency - Exhaust Fan 6AI91VFD Operating Frequency - Exhaust Fan 7AI92VFD Operating Frequency - Exhaust Fan 8AI93VFD Operating Frequency - Supply Fan 1AI94VFD Operating Frequency - Supply Fan 2AI95VFD Operating Frequency - Supply Fan 3AI96VFD Operating Frequency - Supply Fan 4AI97VFD Operating Amperage - Exhaust Fan 1AI98VFD Operating Amperage - Exhaust Fan 2AI99VFD Operating Amperage - Exhaust Fan 3AI100VFD Operating Amperage - Exhaust Fan 4AI101VFD Operating Amperage - Exhaust Fan 5AI102VFD Operating Amperage - Exhaust Fan 6AI103VFD Operating Amperage - Exhaust Fan 7AI104VFD Operating Amperage - Exhaust Fan 8AI105VFD Operating Amperage - Supply Fan 1AI106VFD Operating Amperage - Supply Fan 2AI107VFD Operating Amperage - Supply Fan 3AI108VFD Operating Amperage - Supply Fan 4AI109VFD Power Output - Exhaust Fan 1AI110VFD Power Output - Exhaust Fan 2AI111VFD Power Output - Exhaust Fan 3AI112VFD Power Output - Exhaust Fan 4AI113VFD Power Output - Exhaust Fan 5AI114VFD Power Output - Exhaust Fan 6AI115VFD Power Output - Exhaust Fan 7AI116VFD Power Output - Exhaust Fan 8AI117VFD Power Output - Supply Fan 1AI118VFD Power Output - Supply Fan 2AI119VFD Power Output - Supply Fan 3AI120VFD Power Output - Supply Fan 4AI121Fan VDC 1 Status (J7 Analog Output)AI122Fan VDC 2 Status (J8 Analog Output)AI123Fan VDC 3 Status (J9 Analog Output)AI124Fan VDC 4 Status (J10 Analog Output)AI125Fan VDC 5 Status (J11 Analog Output)AI126Fan VDC 6 Status (J12 Analog Output)AI127Fan VDC 7 Status (J13 Analog Output)AI128Fan VDC 8 Status (J14 Analog Output)AV0Minimum VDC - Exhaust Fan 1AV1Minimum VDC - Exhaust Fan 2AV2Minimum VDC - Exhaust Fan 3AV3Minimum VDC - Exhaust Fan 4AV4Minimum VDC - Exhaust Fan 5AV5Minimum VDC - Exhaust Fan 6AV6Minimum VDC - Exhaust Fan 7AV7Minimum VDC - Exhaust Fan 8AV8Minimum VDC - Supply Fan 1AV9Minimum VDC - Supply Fan 2AV10Minimum VDC - Supply Fan 3AV11Minimum VDC - Supply Fan 4AV12Maximum VDC - Exhaust Fan 1AV13Maximum VDC - Exhaust Fan 2AV14Maximum VDC - Exhaust Fan 3AV15Maximum VDC - Exhaust Fan 4AV16Maximum VDC - Exhaust Fan 5AV17Maximum VDC - Exhaust Fan 6AV18Maximum VDC - Exhaust Fan 7AV19Maximum VDC - Exhaust Fan 8AV20Maximum VDC - Supply Fan 1AV21Maximum VDC - Supply Fan 2AV22Maximum VDC - Supply Fan 3AV23Maximum VDC - Supply Fan 4AV24VFD Minimum Frequency - Exhaust Fan 1AV25VFD Minimum Frequency - Exhaust Fan 2AV26VFD Minimum Frequency - Exhaust Fan 3AV27VFD Minimum Frequency - Exhaust Fan 4AV28VFD Minimum Frequency - Exhaust Fan 5AV29VFD Minimum Frequency - Exhaust Fan 6AV30VFD Minimum Frequency - Exhaust Fan 7AV31VFD Minimum Frequency - Exhaust Fan 8AV32VFD Minimum Frequency - Supply Fan 1AV33VFD Minimum Frequency - Supply Fan 2AV34VFD Minimum Frequency - Supply Fan 3AV35VFD Minimum Frequency - Supply Fan 4AV36VFD Maximum Frequency - Exhaust Fan 1AV37VFD Maximum Frequency - Exhaust Fan 2AV38VFD Maximum Frequency - Exhaust Fan 3AV39VFD Maximum Frequency - Exhaust Fan 4AV40VFD Maximum Frequency - Exhaust Fan 5AV41VFD Maximum Frequency - Exhaust Fan 6AV42VFD Maximum Frequency - Exhaust Fan 7AV43VFD Maximum Frequency - Exhaust Fan 8AV44VFD Maximum Frequency - Supply Fan 1AV45VFD Maximum Frequency - Supply Fan 2AV46VFD Maximum Frequency - Supply Fan 3AV47VFD Maximum Frequency - Supply Fan 4AV48Temp Interlock Offset - Zone 1AV49Temp Interlock Offset - Zone 2AV50Temp Interlock Offset - Zone 3AV51Temp Interlock Offset - Zone 4AV52Temp Interlock Offset - Zone 5AV53Temp Interlock Offset - Zone 6AV54Temp Interlock Offset - Zone 7AV55Temp Interlock Offset - Zone 8AV56Temp Interlock Hysteresis - Zone 1AV57Temp Interlock Hysteresis - Zone 2AV58Temp Interlock Hysteresis - Zone 3AV59Temp Interlock Hysteresis - Zone 4AV60Temp Interlock Hysteresis - Zone 5AV61Temp Interlock Hysteresis - Zone 6AV62Temp Interlock Hysteresis - Zone 7AV63Temp Interlock Hysteresis - Zone 8AV64Temp Interlock Hysteresis Timer - Zone 1AV65Temp Interlock Hysteresis Timer - Zone 2AV66Temp Interlock Hysteresis Timer - Zone 3AV67Temp Interlock Hysteresis Timer - Zone 4AV68Temp Interlock Hysteresis Timer - Zone 5AV69Temp Interlock Hysteresis Timer - Zone 6AV70Temp Interlock Hysteresis Timer - Zone 7AV71Temp Interlock Hysteresis Timer - Zone 8AV72Modulation Temp Range - Exhaust Fan 1AV73Modulation Temp Range - Exhaust Fan 2AV74Modulation Temp Range - Exhaust Fan 3AV75Modulation Temp Range - Exhaust Fan 4AV76Modulation Temp Range - Exhaust Fan 5AV77Modulation Temp Range - Exhaust Fan 6AV78Modulation Temp Range - Exhaust Fan 7AV79Modulation Temp Range - Exhaust Fan 8BV0Fans - Zone 1BV1Fans - Zone 2BV2Fans - Zone 3BV3Fans - Zone 4BV4Fans - Zone 5BV5Fans - Zone 6BV6Fans - Zone 7BV7Fans - Zone 8BV8Hood Lights - Main BoardBV9Hood Lights - HCB1BV10Hood Lights - HCB2BV11Hood Lights - HCB3BV12Hood Lights - HCB4BV13Hood Lights - HCB5BV14Hood Lights - HCB6BV15Hood Lights - HCB7BV16Hood Lights - HCB8BV17Hood Lights - HCB9BV18Hood Lights - HCB10BV19Hood Lights - HCB11BV20Hood Lights - HCB12BV21Hood Lights - HCB13BV22Hood Lights - HCB14BV23Hood Lights - HCB15BV24Hood Lights - HCB16BV25Max Fan EnableBV26Exhaust Fan 1 EnableBV27Exhaust Fan 2 EnableBV28Exhaust Fan 3 EnableBV29Exhaust Fan 4 EnableBV30Exhaust Fan 5 EnableBV31Exhaust Fan 6 EnableBV32Exhaust Fan 7 EnableBV33Exhaust Fan 8 EnableBV34Supply Fan 1 EnableBV35Supply Fan 2 EnableBV36Supply Fan 3 EnableBV37Supply Fan 4 EnableBV38HCB1 Hood WashBV39HCB2 Hood WashBV40HCB3 Hood WashBV41HCB4 Hood WashBV42HCB5 Hood WashBV43HCB6 Hood WashBV44HCB7 Hood WashBV45HCB8 Hood WashBV46HCB9 Hood WashBV47HCB10 Hood WashBV48HCB11 Hood WashBV49HCB12 Hood WashBV50HCB13 Hood WashBV51HCB14 Hood WashBV52HCB15 Hood WashBV53HCB16 Hood WashBV54Duct Sump Wash
Integration notes
- The list has objects for the full capacity (8 zones, 8 exhaust fans, 4 supply fans, 16 hood control boards); map only what the panel has.
- Instances 0-11 (zone status, VFD fault, relay status and fault words) are BitString Value objects (BACnet type 39) on BACnet MS/TP; through the BACnet IP gateway the guide says they are Analog Values. The site has no BitString type, so they are listed as Other. Bit order is reversed between the two (bit 0 left-most on MS/TP, right-most over IP).
- Access is from the R / R/W column of the BACnet points list.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Greenheck Kitchen Controls (GKC) main board and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Greenheck Kitchen Controls (GKC) main board
How many BACnet points does the Greenheck Kitchen Controls (GKC) main board have?
This list has 276 BACnet objects: 129 analog inputs, 80 analog values, 55 binary values, 12 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Greenheck Kitchen Controls (GKC) main board BACnet points are writable?
135 of the 276 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Greenheck Kitchen Controls (GKC) main board BACnet documentation?
The source is Kitchen Controls Installation, Operation and Maintenance Manual - BACnet Points List (484600 Rev. 6), revision 2026-10, published free by Greenheck at https://content.greenheck.com/public/DAMProd/Original/10012/484600KitchenControls_iom.pdf.
What are the minimum BACnet points to integrate the Greenheck Kitchen Controls (GKC) main board?
Start with BV 0 Fans - Zone 1 (Zone 1 fans on/off (1 = on)); BV 8 Hood Lights - Main Board (Main board hood lights on/off); BV 25 Max Fan Enable (Max fan (full speed) on/off); AI 0 MB Room Sensor Temp (Room temperature at the main board); AI 1 MB Hood Temp Sensor 1 (Hood temperature sensor 1); Other 0 Zone 1 Status (Zone 1 status bits: why the fans are on); Other 11 Faults (Fault bits; first bit = any fault).
How do I enable BMS control of the Greenheck Kitchen Controls (GKC) main board?
BV 0-7 turn zone fans on and off from the BMS. Each zone status word has a 'fan on via BMS' bit, so the BMS can see when its command is holding the fans on.
How do I check these points on the real Greenheck Kitchen Controls (GKC) main board?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Greenheck BACnet points lists
- Dedicated outdoor air system (DOAS)
Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet
Greenheck dedicated outdoor air units whose factory controller runs the DOAS_10 program with BACnet licensed.
Also known as: Greenheck DOAS, DOAS, DOAS_10.006, 485940 - Dedicated outdoor air system (DOAS) unit controller
Greenheck DOAS Microprocessor Controller v6.2 (legacy points list)
Greenheck dedicated outdoor air units running the older DOAS v6.2 controller program (July 2021 guide).
Also known as: 485175, Document 485175, DOAS v6.2, Greenheck DOAS controller, c.pCO - Energy recovery ventilator
Greenheck IVE Indoor Energy Recovery Ventilator (BACnet)
Greenheck IVE indoor energy recovery ventilators with the factory c.pCO Mini controller.
Also known as: IVE, Greenheck IVE, IVE_01.002, 487690, c.pCO Mini - Make-up air unit controller
Greenheck Make-Up Air Microprocessor Controller (MUA v4.1)
Greenheck make-up air units with the factory microprocessor controller, MUA program v4.1.
Also known as: 487036, Document 487036, MUA v4.1, Greenheck make-up air controller, c.pCO - Rooftop unit (RTU) controller
Greenheck RTU Microprocessor Controller (RTU v1.4)
Greenheck (and Valent) packaged rooftop units with the factory microprocessor controller, RTU program v1.4.
Also known as: 487424, Document 487424, 487426, Valent RTU controller, RTU v1.4, Greenheck rooftop unit controller, c.pCO - Fan variable frequency drive (VFD)
Greenheck Vari-Green Drive VGD-100+
Greenheck Vari-Green Drive (VGD-100+) motor drives used on Greenheck fans.
Also known as: VGD, VGD-100, VGD-100+, Vari-Green Drive, 481200 - EC motor with integrated variable frequency drive (fans)
Greenheck Vari-Green Motor (EC Titanium) BACnet MS/TP
Greenheck Vari-Green single-phase and three-phase EC motors (EC Titanium integrated motor drive) controlled over BACnet MS/TP.
Also known as: Vari-Green, Vari-Green Motor, EC Titanium, MN448, Greenheck Vari-Green, Baldor EC Titanium
Source: Kitchen Controls Installation, Operation and Maintenance Manual - BACnet Points List · 484600 Rev. 6 · rev. 2026-10. Object names, instances and units are reproduced as published; descriptions are our own.