Easy BACnet
  1. Home
  2. BACnet points lists
  3. Greenheck
  4. Greenheck Kitchen Controls (GKC) main board

Kitchen hood exhaust and supply fan controls · BACnet points list

Greenheck Kitchen Controls (GKC) main board BACnet points list

Updated 7 November 2026

Short answer

Greenheck Kitchen Controls (GKC) run kitchen hood exhaust and supply fans, hood lights, hood wash and temperature or optic-based demand control. The main board talks BACnet MS/TP directly on J23; BACnet IP panels get a Modbus RTU to BACnet IP gateway. The list covers room, hood and supply temperatures, optic opacity, fan VFD data, zone and fan commands, hood light and wash commands, tuning values and packed status/fault words.

This page lists 276 BACnet objects for the Greenheck Kitchen Controls (GKC) main board — 135 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greenheck’s own free documentation, linked below.

Manufacturer
Greenheck
Model
Greenheck Kitchen Controls (GKC) main board
Equipment
Kitchen hood exhaust and supply fan controls
Equipment type
Other equipment
BACnet objects
276 (135 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
77000
Also known as
GKC, Greenheck Kitchen Controls, 484600, GKC-CV, GKC-DCV, Kitchen hood controls
Source document
Kitchen Controls Installation, Operation and Maintenance Manual - BACnet Points List · 484600 Rev. 6 · rev. 2026-10
Download CSV 276 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greenheck’s current documentation and the live device before use. Not official Greenheck information. Terms of use.

BMS integration notes: Greenheck Kitchen Controls (GKC) main board

Integration in brief

Turn zone fans on and off with BV 0-7 (Fans - Zone n) and hood lights with BV 8-24. Read hood and room temperatures (AI 0-8 and the HCB AIs), fan VFD frequency, and the Faults word (instance 11) for alarms. Hood wash can be started per hood control board with BV 38-53.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Fans - Zone 1Zone 1 fans on/off (1 = on)Write
BV 8Hood Lights - Main BoardMain board hood lights on/offWrite
BV 25Max Fan EnableMax fan (full speed) on/offWrite
AI 0MB Room Sensor TempRoom temperature at the main boardRead
AI 1MB Hood Temp Sensor 1Hood temperature sensor 1Read
Other 0Zone 1 StatusZone 1 status bits: why the fans are onRead
Other 11FaultsFault bits; first bit = any faultRead

Enable & remote start

BV 0-7 turn zone fans on and off from the BMS. Each zone status word has a 'fan on via BMS' bit, so the BMS can see when its command is holding the fans on.

Network setup

Watch out for

Greenheck Kitchen Controls (GKC) main board BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

276 of 276 shown
Type
BinaryOther
Access
Show
Greenheck Kitchen Controls (GKC) main board BACnet Points List
DescriptionStates
AImin0MB Room Sensor TempMB Room Temp Sensor°FRead
AImin1MB Hood Temp Sensor 1°FRead
AI2MB Hood Temp Sensor 2°FRead
AI3MB Hood Temp Sensor 3°FRead
AI4MB Hood Temp Sensor 4°FRead
AI5MB Hood Temp Sensor 5°FRead
AI6MB Hood Temp Sensor 6°FRead
AI7MB Hood Temp Sensor 7°FRead
AI8MB Hood Temp Sensor 8°FRead
AI9HCB1 Room Temp Sensor°FRead
AI10HCB1 Hood Temp Sensor°FRead
AI11HCB1 Supply Temp Sensor°FRead
AI12HCB1 Optics Opacity Level%Read
AI13HCB2 Room Temp Sensor°FRead
AI14HCB2 Hood Temp Sensor°FRead
AI15HCB2 Supply Temp Sensor°FRead
AI16HCB2 Optics Opacity Level%Read
AI17HCB3 Room Temp Sensor°FRead
AI18HCB3 Hood Temp Sensor°FRead
AI19HCB3 Supply Temp Sensor°FRead
AI20HCB3 Optics Opacity Level%Read
AI21HCB4 Room Temp Sensor°FRead
AI22HCB4 Hood Temp Sensor°FRead
AI23HCB4 Supply Temp Sensor°FRead
AI24HCB4 Optics Opacity Level%Read
AI25HCB5 Room Temp Sensor°FRead
AI26HCB5 Hood Temp Sensor°FRead
AI27HCB5 Supply Temp Sensor°FRead
AI28HCB5 Optics Opacity Level%Read
AI29HCB6 Room Temp Sensor°FRead
AI30HCB6 Hood Temp Sensor°FRead
AI31HCB6 Supply Temp Sensor°FRead
AI32HCB6 Optics Opacity Level%Read
AI33HCB7 Room Temp Sensor°FRead
AI34HCB7 Hood Temp Sensor°FRead
AI35HCB7 Supply Temp Sensor°FRead
AI36HCB7 Optics Opacity Level%Read
AI37HCB8 Room Temp Sensor°FRead
AI38HCB8 Hood Temp Sensor°FRead
AI39HCB8 Supply Temp Sensor°FRead
AI40HCB8 Optics Opacity Level%Read
AI41HCB9 Room Temp Sensor°FRead
AI42HCB9 Hood Temp Sensor°FRead
AI43HCB9 Supply Temp Sensor°FRead
AI44HCB9 Optics Opacity Level%Read
AI45HCB10 Room Temp Sensor°FRead
AI46HCB10 Hood Temp Sensor°FRead
AI47HCB10 Supply Temp Sensor°FRead
AI48HCB10 Optics Opacity Level%Read
AI49HCB11 Room Temp Sensor°FRead
AI50HCB11 Hood Temp Sensor°FRead
AI51HCB11 Supply Temp Sensor°FRead
AI52HCB11 Optics Opacity Level%Read
AI53HCB12 Room Temp Sensor°FRead
AI54HCB12 Hood Temp Sensor°FRead
AI55HCB12 Supply Temp Sensor°FRead
AI56HCB12 Optics Opacity Level%Read
AI57HCB13 Room Temp Sensor°FRead
AI58HCB13 Hood Temp Sensor°FRead
AI59HCB13 Supply Temp Sensor°FRead
AI60HCB13 Optics Opacity Level%Read
AI61HCB14 Room Temp Sensor°FRead
AI62HCB14 Hood Temp Sensor°FRead
AI63HCB14 Supply Temp Sensor°FRead
AI64HCB14 Optics Opacity Level%Read
AI65HCB15 Room Temp Sensor°FRead
AI66HCB15 Hood Temp Sensor°FRead
AI67HCB15 Supply Temp Sensor°FRead
AI68HCB15 Optics Opacity Level%Read
AI69HCB16 Room Temp Sensor°FRead
AI70HCB16 Hood Temp Sensor°FRead
AI71HCB16 Supply Temp Sensor°FRead
AI72HCB16 Optics Opacity Level%Read
AI73Operating % - Exhaust Fan 1Exhaust fan 1 Operating Percentage%Read
AI74Operating % - Exhaust Fan 2Exhaust fan 2 Operating Percentage%Read
AI75Operating % - Exhaust Fan 3Exhaust fan 3 Operating Percentage%Read
AI76Operating % - Exhaust Fan 4Exhaust fan 4 Operating Percentage%Read
AI77Operating % - Exhaust Fan 5Exhaust fan 5 Operating Percentage%Read
AI78Operating % - Exhaust Fan 6Exhaust fan 6 Operating Percentage%Read
AI79Operating % - Exhaust Fan 7Exhaust fan 7 Operating Percentage%Read
AI80Operating % - Exhaust Fan 8Exhaust fan 8 Operating Percentage%Read
AI81Operating % - Supply Fan 1Supply fan 1 Operating Percentage%Read
AI82Operating % - Supply Fan 2Supply fan 2 Operating Percentage%Read
AI83Operating % - Supply Fan 3Supply fan 3 Operating Percentage%Read
AI84Operating % - Supply Fan 4Supply fan 4 Operating Percentage%Read
AI85VFD Operating Frequency - Exhaust Fan 1Exhaust fan 1 VFD Operating FrequencyHzRead
AI86VFD Operating Frequency - Exhaust Fan 2Exhaust fan 2 VFD Operating FrequencyHzRead
AI87VFD Operating Frequency - Exhaust Fan 3Exhaust fan 3 VFD Operating FrequencyHzRead
AI88VFD Operating Frequency - Exhaust Fan 4Exhaust fan 4 VFD Operating FrequencyHzRead
AI89VFD Operating Frequency - Exhaust Fan 5Exhaust fan 5 VFD Operating FrequencyHzRead
AI90VFD Operating Frequency - Exhaust Fan 6Exhaust fan 6 VFD Operating FrequencyHzRead
AI91VFD Operating Frequency - Exhaust Fan 7Exhaust fan 7 VFD Operating FrequencyHzRead
AI92VFD Operating Frequency - Exhaust Fan 8Exhaust fan 8 VFD Operating FrequencyHzRead
AI93VFD Operating Frequency - Supply Fan 1Supply Fan 1 VFD Operating FrequencyHzRead
AI94VFD Operating Frequency - Supply Fan 2Supply Fan 2 VFD Operating FrequencyHzRead
AI95VFD Operating Frequency - Supply Fan 3Supply Fan 3 VFD Operating FrequencyHzRead
AI96VFD Operating Frequency - Supply Fan 4Supply Fan 4 VFD Operating FrequencyHzRead
AI97VFD Operating Amperage - Exhaust Fan 1Exhaust Fan 1 VFD Operating AmperageARead
AI98VFD Operating Amperage - Exhaust Fan 2Exhaust Fan 2 VFD Operating AmperageARead
AI99VFD Operating Amperage - Exhaust Fan 3Exhaust fan 3 VFD Operating AmperageARead
AI100VFD Operating Amperage - Exhaust Fan 4Exhaust fan 4 VFD Operating AmperageARead
AI101VFD Operating Amperage - Exhaust Fan 5Exhaust fan 5 VFD Operating AmperageARead
AI102VFD Operating Amperage - Exhaust Fan 6Exhaust fan 6 VFD Operating AmperageARead
AI103VFD Operating Amperage - Exhaust Fan 7Exhaust fan 7 VFD Operating AmperageARead
AI104VFD Operating Amperage - Exhaust Fan 8Exhaust fan 8 VFD Operating AmperageARead
AI105VFD Operating Amperage - Supply Fan 1Supply Fan 1 VFD Operating AmperageARead
AI106VFD Operating Amperage - Supply Fan 2Supply Fan 2 VFD Operating AmperageARead
AI107VFD Operating Amperage - Supply Fan 3Supply Fan 3 VFD Operating AmperageARead
AI108VFD Operating Amperage - Supply Fan 4Supply Fan 4 VFD Operating AmperageARead
AI109VFD Power Output - Exhaust Fan 1Exhaust Fan 1 VFD Output PowerWRead
AI110VFD Power Output - Exhaust Fan 2Exhaust Fan 2 VFD Output PowerWRead
AI111VFD Power Output - Exhaust Fan 3Exhaust Fan 3 VFD Output PowerWRead
AI112VFD Power Output - Exhaust Fan 4Exhaust Fan 4 VFD Output PowerWRead
AI113VFD Power Output - Exhaust Fan 5Exhaust Fan 5 VFD Output PowerWRead
AI114VFD Power Output - Exhaust Fan 6Exhaust Fan 6 VFD Output PowerWRead
AI115VFD Power Output - Exhaust Fan 7Exhaust Fan 7 VFD Output PowerWRead
AI116VFD Power Output - Exhaust Fan 8Exhaust Fan 8 VFD Output PowerWRead
AI117VFD Power Output - Supply Fan 1Supply Fan 1 VFD Output PowerWRead
AI118VFD Power Output - Supply Fan 2Supply Fan 2 VFD Output PowerWRead
AI119VFD Power Output - Supply Fan 3Supply Fan 3 VFD Output PowerWRead
AI120VFD Power Output - Supply Fan 4Supply Fan 4 VFD Output PowerWRead
AI121Fan VDC 1 Status (J7 Analog Output)VRead
AI122Fan VDC 2 Status (J8 Analog Output)VRead
AI123Fan VDC 3 Status (J9 Analog Output)VRead
AI124Fan VDC 4 Status (J10 Analog Output)VRead
AI125Fan VDC 5 Status (J11 Analog Output)VRead
AI126Fan VDC 6 Status (J12 Analog Output)VRead
AI127Fan VDC 7 Status (J13 Analog Output)VRead
AI128Fan VDC 8 Status (J14 Analog Output)VRead
AV0Minimum VDC - Exhaust Fan 1VWrite
AV1Minimum VDC - Exhaust Fan 2VWrite
AV2Minimum VDC - Exhaust Fan 3VWrite
AV3Minimum VDC - Exhaust Fan 4VWrite
AV4Minimum VDC - Exhaust Fan 5VWrite
AV5Minimum VDC - Exhaust Fan 6VWrite
AV6Minimum VDC - Exhaust Fan 7VWrite
AV7Minimum VDC - Exhaust Fan 8VWrite
AV8Minimum VDC - Supply Fan 1VWrite
AV9Minimum VDC - Supply Fan 2VWrite
AV10Minimum VDC - Supply Fan 3VWrite
AV11Minimum VDC - Supply Fan 4VWrite
AV12Maximum VDC - Exhaust Fan 1VWrite
AV13Maximum VDC - Exhaust Fan 2VWrite
AV14Maximum VDC - Exhaust Fan 3VWrite
AV15Maximum VDC - Exhaust Fan 4VWrite
AV16Maximum VDC - Exhaust Fan 5VWrite
AV17Maximum VDC - Exhaust Fan 6VWrite
AV18Maximum VDC - Exhaust Fan 7VWrite
AV19Maximum VDC - Exhaust Fan 8VWrite
AV20Maximum VDC - Supply Fan 1VWrite
AV21Maximum VDC - Supply Fan 2VWrite
AV22Maximum VDC - Supply Fan 3VWrite
AV23Maximum VDC - Supply Fan 4VWrite
AV24VFD Minimum Frequency - Exhaust Fan 1HzWrite
AV25VFD Minimum Frequency - Exhaust Fan 2HzWrite
AV26VFD Minimum Frequency - Exhaust Fan 3HzWrite
AV27VFD Minimum Frequency - Exhaust Fan 4HzWrite
AV28VFD Minimum Frequency - Exhaust Fan 5HzWrite
AV29VFD Minimum Frequency - Exhaust Fan 6HzWrite
AV30VFD Minimum Frequency - Exhaust Fan 7HzWrite
AV31VFD Minimum Frequency - Exhaust Fan 8HzWrite
AV32VFD Minimum Frequency - Supply Fan 1HzWrite
AV33VFD Minimum Frequency - Supply Fan 2HzWrite
AV34VFD Minimum Frequency - Supply Fan 3HzWrite
AV35VFD Minimum Frequency - Supply Fan 4HzWrite
AV36VFD Maximum Frequency - Exhaust Fan 1HzWrite
AV37VFD Maximum Frequency - Exhaust Fan 2HzWrite
AV38VFD Maximum Frequency - Exhaust Fan 3HzWrite
AV39VFD Maximum Frequency - Exhaust Fan 4HzWrite
AV40VFD Maximum Frequency - Exhaust Fan 5HzWrite
AV41VFD Maximum Frequency - Exhaust Fan 6HzWrite
AV42VFD Maximum Frequency - Exhaust Fan 7HzWrite
AV43VFD Maximum Frequency - Exhaust Fan 8HzWrite
AV44VFD Maximum Frequency - Supply Fan 1HzWrite
AV45VFD Maximum Frequency - Supply Fan 2HzWrite
AV46VFD Maximum Frequency - Supply Fan 3HzWrite
AV47VFD Maximum Frequency - Supply Fan 4HzWrite
AV48Temp Interlock Offset - Zone 1°FWrite
AV49Temp Interlock Offset - Zone 2°FWrite
AV50Temp Interlock Offset - Zone 3°FWrite
AV51Temp Interlock Offset - Zone 4°FWrite
AV52Temp Interlock Offset - Zone 5°FWrite
AV53Temp Interlock Offset - Zone 6°FWrite
AV54Temp Interlock Offset - Zone 7°FWrite
AV55Temp Interlock Offset - Zone 8°FWrite
AV56Temp Interlock Hysteresis - Zone 1°FWrite
AV57Temp Interlock Hysteresis - Zone 2°FWrite
AV58Temp Interlock Hysteresis - Zone 3°FWrite
AV59Temp Interlock Hysteresis - Zone 4°FWrite
AV60Temp Interlock Hysteresis - Zone 5°FWrite
AV61Temp Interlock Hysteresis - Zone 6°FWrite
AV62Temp Interlock Hysteresis - Zone 7°FWrite
AV63Temp Interlock Hysteresis - Zone 8°FWrite
AV64Temp Interlock Hysteresis Timer - Zone 1minWrite
AV65Temp Interlock Hysteresis Timer - Zone 2minWrite
AV66Temp Interlock Hysteresis Timer - Zone 3minWrite
AV67Temp Interlock Hysteresis Timer - Zone 4minWrite
AV68Temp Interlock Hysteresis Timer - Zone 5minWrite
AV69Temp Interlock Hysteresis Timer - Zone 6minWrite
AV70Temp Interlock Hysteresis Timer - Zone 7minWrite
AV71Temp Interlock Hysteresis Timer - Zone 8minWrite
AV72Modulation Temp Range - Exhaust Fan 1°FWrite
AV73Modulation Temp Range - Exhaust Fan 2°FWrite
AV74Modulation Temp Range - Exhaust Fan 3°FWrite
AV75Modulation Temp Range - Exhaust Fan 4°FWrite
AV76Modulation Temp Range - Exhaust Fan 5°FWrite
AV77Modulation Temp Range - Exhaust Fan 6°FWrite
AV78Modulation Temp Range - Exhaust Fan 7°FWrite
AV79Modulation Temp Range - Exhaust Fan 8°FWrite
BVmin0Fans - Zone 11/0 to turn on/off zone 1Write0=Off, 1=On
BV1Fans - Zone 21/0 to turn on/off zone 2Write0=Off, 1=On
BV2Fans - Zone 31/0 to turn on/off zone 3Write0=Off, 1=On
BV3Fans - Zone 41/0 to turn on/off zone 4Write0=Off, 1=On
BV4Fans - Zone 51/0 to turn on/off zone 5Write0=Off, 1=On
BV5Fans - Zone 61/0 to turn on/off zone 6Write0=Off, 1=On
BV6Fans - Zone 71/0 to turn on/off zone 7Write0=Off, 1=On
BV7Fans - Zone 81/0 to turn on/off zone 8Write0=Off, 1=On
BVmin8Hood Lights - Main Board1/0 to turn on/off MB Hood LightsWrite0=Off, 1=On
BV9Hood Lights - HCB11/0 to turn on/off HCB1 Hood LightsWrite0=Off, 1=On
BV10Hood Lights - HCB21/0 to turn on/off HCB2 Hood LightsWrite0=Off, 1=On
BV11Hood Lights - HCB31/0 to turn on/off HCB3 Hood LightsWrite0=Off, 1=On
BV12Hood Lights - HCB41/0 to turn on/off HCB4 Hood LightsWrite0=Off, 1=On
BV13Hood Lights - HCB51/0 to turn on/off HCB5 Hood LightsWrite0=Off, 1=On
BV14Hood Lights - HCB61/0 to turn on/off HCB6 Hood LightsWrite0=Off, 1=On
BV15Hood Lights - HCB71/0 to turn on/off HCB7 Hood LightsWrite0=Off, 1=On
BV16Hood Lights - HCB81/0 to turn on/off HCB8 Hood LightsWrite0=Off, 1=On
BV17Hood Lights - HCB91/0 to turn on/off HCB9 Hood LightsWrite0=Off, 1=On
BV18Hood Lights - HCB101/0 to turn on/off HCB10 Hood LightsWrite0=Off, 1=On
BV19Hood Lights - HCB111/0 to turn on/off HCB11 Hood LightsWrite0=Off, 1=On
BV20Hood Lights - HCB121/0 to turn on/off HCB12 Hood LightsWrite0=Off, 1=On
BV21Hood Lights - HCB131/0 to turn on/off HCB13 Hood LightsWrite0=Off, 1=On
BV22Hood Lights - HCB141/0 to turn on/off HCB14 Hood LightsWrite0=Off, 1=On
BV23Hood Lights - HCB151/0 to turn on/off HCB15 Hood LightsWrite0=Off, 1=On
BV24Hood Lights - HCB161/0 to turn on/off HCB16 Hood LightsWrite0=Off, 1=On
BVmin25Max Fan Enable1/0 to turn Max Fan on/offWrite0=Off, 1=On
BV26Exhaust Fan 1 Enable1/0 to turn on/off Exhaust Fan 1Write0=Off, 1=On
BV27Exhaust Fan 2 Enable1/0 to turn on/off Exhaust Fan 2Write0=Off, 1=On
BV28Exhaust Fan 3 Enable1/0 to turn on/off Exhaust Fan 3Write0=Off, 1=On
BV29Exhaust Fan 4 Enable1/0 to turn on/off Exhaust Fan 4Write0=Off, 1=On
BV30Exhaust Fan 5 Enable1/0 to turn on/off Exhaust Fan 5Write0=Off, 1=On
BV31Exhaust Fan 6 Enable1/0 to turn on/off Exhaust Fan 6Write0=Off, 1=On
BV32Exhaust Fan 7 Enable1/0 to turn on/off Exhaust Fan 7Write0=Off, 1=On
BV33Exhaust Fan 8 Enable1/0 to turn on/off Exhaust Fan 8Write0=Off, 1=On
BV34Supply Fan 1 Enable1/0 to turn on/off Supply Fan 1Write0=Off, 1=On
BV35Supply Fan 2 Enable1/0 to turn on/off Supply Fan 2Write0=Off, 1=On
BV36Supply Fan 3 Enable1/0 to turn on/off Supply Fan 3Write0=Off, 1=On
BV37Supply Fan 4 Enable1/0 to turn on/off Supply Fan 4Write0=Off, 1=On
BV38HCB1 Hood Wash1/0 to start/stop HCB1 Hood WashWrite0=Off, 1=On
BV39HCB2 Hood Wash1/0 to start/stop HCB2 Hood WashWrite0=Off, 1=On
BV40HCB3 Hood Wash1/0 to start/stop HCB3 Hood WashWrite0=Off, 1=On
BV41HCB4 Hood Wash1/0 to start/stop HCB4 Hood WashWrite0=Off, 1=On
BV42HCB5 Hood Wash1/0 to start/stop HCB5 Hood WashWrite0=Off, 1=On
BV43HCB6 Hood Wash1/0 to start/stop HCB6 Hood WashWrite0=Off, 1=On
BV44HCB7 Hood Wash1/0 to start/stop HCB7 Hood WashWrite0=Off, 1=On
BV45HCB8 Hood Wash1/0 to start/stop HCB8 Hood WashWrite0=Off, 1=On
BV46HCB9 Hood Wash1/0 to start/stop HCB9 Hood WashWrite0=Off, 1=On
BV47HCB10 Hood Wash1/0 to start/stop HCB10 Hood WashWrite0=Off, 1=On
BV48HCB11 Hood Wash1/0 to start/stop HCB11 Hood WashWrite0=Off, 1=On
BV49HCB12 Hood Wash1/0 to start/stop HCB12 Hood WashWrite0=Off, 1=On
BV50HCB13 Hood Wash1/0 to start/stop HCB13 Hood WashWrite0=Off, 1=On
BV51HCB14 Hood Wash1/0 to start/stop HCB14 Hood WashWrite0=Off, 1=On
BV52HCB15 Hood Wash1/0 to start/stop HCB15 Hood WashWrite0=Off, 1=On
BV53HCB16 Hood Wash1/0 to start/stop HCB16 Hood WashWrite0=Off, 1=On
BV54Duct Sump Wash1/0 to start/stop Duct Sump WashWrite0=Off, 1=On
Othermin0Zone 1 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other1Zone 2 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other2Zone 3 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other3Zone 4 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other4Zone 5 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other5Zone 6 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other6Zone 7 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other7Zone 8 StatusPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other8Exhaust Fan VFD FaultsPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other9Supply Fan VFD FaultsPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Other10Relay StatusesPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Othermin11FaultsPacked bit word: BitString Value (type 39) on MS/TP, AV over IPRead
Object ID lookup: Greenheck Kitchen Controls main board point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Greenheck Kitchen Controls (GKC) main board and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greenheck Kitchen Controls (GKC) main board

How many BACnet points does the Greenheck Kitchen Controls (GKC) main board have?

This list has 276 BACnet objects: 129 analog inputs, 80 analog values, 55 binary values, 12 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greenheck Kitchen Controls (GKC) main board BACnet points are writable?

135 of the 276 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greenheck Kitchen Controls (GKC) main board BACnet documentation?

The source is Kitchen Controls Installation, Operation and Maintenance Manual - BACnet Points List (484600 Rev. 6), revision 2026-10, published free by Greenheck at https://content.greenheck.com/public/DAMProd/Original/10012/484600KitchenControls_iom.pdf.

What are the minimum BACnet points to integrate the Greenheck Kitchen Controls (GKC) main board?

Start with BV 0 Fans - Zone 1 (Zone 1 fans on/off (1 = on)); BV 8 Hood Lights - Main Board (Main board hood lights on/off); BV 25 Max Fan Enable (Max fan (full speed) on/off); AI 0 MB Room Sensor Temp (Room temperature at the main board); AI 1 MB Hood Temp Sensor 1 (Hood temperature sensor 1); Other 0 Zone 1 Status (Zone 1 status bits: why the fans are on); Other 11 Faults (Fault bits; first bit = any fault).

How do I enable BMS control of the Greenheck Kitchen Controls (GKC) main board?

BV 0-7 turn zone fans on and off from the BMS. Each zone status word has a 'fan on via BMS' bit, so the BMS can see when its command is holding the fans on.

How do I check these points on the real Greenheck Kitchen Controls (GKC) main board?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greenheck BACnet points lists

Source: Kitchen Controls Installation, Operation and Maintenance Manual - BACnet Points List · 484600 Rev. 6 · rev. 2026-10. Object names, instances and units are reproduced as published; descriptions are our own.