Make-up air unit controller · BACnet points list

Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) BACnet points list

Updated 6 November 2026

Short answer

Greenheck's make-up air controller (program v4.1) offers BACnet MS/TP, BACnet IP, Modbus RTU and Modbus TCP. The BMS can enable the unit, command occupancy, reset alarms, write occupied and unoccupied temperature setpoints, supply limits, lockouts, static pressure and damper setpoints, take over the supply fan and outdoor air damper and send sensor values while a watchdog is kept alive. Read-only objects cover temperatures, outputs, unit status mode, latest alarm and bit-packed status and alarm words.

This page lists 118 BACnet objects for the Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) — 46 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greenheck’s own free documentation, linked below.

Manufacturer
Greenheck
Model
Make-Up Air Microprocessor Controller (MUA v4.1)
Equipment
Make-up air unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
118 (46 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
MUA v4.1
Also known as
487036, Document 487036, MUA v4.1, Greenheck make-up air controller, c.pCO
Source document
Microprocessor Controller for Make-up Air - Reference Guide (MUA v4.1) · 487036 · rev. 2024-12
Download CSV 118 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greenheck’s current documentation and the live device before use. Not official Greenheck information. Terms of use.

BMS integration notes: Greenheck Make-Up Air Microprocessor Controller (MUA v4.1)

Integration in brief

With BACnet licensed and the protocol set in Network Settings, enable the unit with BV 2, command occupancy with BV 3, write the occupied temperature setpoint AV 1 and reset alarms with BV 4. Keep the BV 1 watchdog toggling if the BMS sends sensor values or controls the fan or damper. Monitor Unit_Status_Mode (AV 41), supply temperature, Global_Alarm (BV 19) and LatestAlm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2System_EnableEnables or disables the unitWrite
BV 3BMS_Occupancy_CommandOccupancy; Active = Unoccupied, Inactive = OccupiedWrite
AV 1Temperature_SetpointOccupied temperature setpointWrite
BV 1BMS_WatchdogHeartbeat when BMS controls fans or sensorsWrite
BV 4Reset_All_AlarmsRemote alarm resetWrite
AV 41Unit_Status_ModeCurrent operating mode codeRead
AI 2Supply_Temp_Analog_InputSupply (discharge) air temperatureRead
BV 19Global_AlarmAlarm output (any or shutdown alarms)Read
IV 9LatestAlmMost recent alarm codeRead

Enable & remote start

BV 2 System_Enable enables or disables the unit; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied).

Heartbeat & communication loss

BV 1 BMS_Watchdog must be toggled by the BMS within the timeout delay (15 minutes by default, adjustable) whenever the BMS replaces a hardwired sensor (or takes over fan speed or damper control). If the timer expires, the controller alarms (BMS Offline) and falls back to its hardwired sensors and local control until the BMS returns. The watchdog status is shown on a read-only BV.

Sensors & values from the BMS

Set the source-select BV to BMS (BV 6 outside temp, BV 9/10 CO2, BV 12 space static, BV 13 space temp), then write the matching *_from_BMS value (AV 30, 33, 34, 36, 37). BV 14 and BV 15 hand supply fan speed and damper position to the BMS. The watchdog must be kept alive.

Network setup

Watch out for

Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

118 of 118 shown
Type
Other
Access
Show
Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) BACnet Points List
DescriptionStates
AI1Space_Temp_Analog_InputSpace Temperature°FRead
AImin2Supply_Temp_Analog_InputSupply Temperature°FRead
AI3Outside_Air_Temp_Analog_InputOutside Air Temperature°FRead
AI6Space_RH_Analog_InputSpace % Relative HumidityRead%RH
AI9Space_Static_Pressure_Analog_InputSpace Static Pressurein. w.c.Read
AI10Supply_Duct_Static_Pressure_Analog_InputSupply Duct Static Pressurein. w.c.Read
AI11Space_CO2_1_Analog_InputSpace CO2 ppmppmRead
AI12Return_CO2_Analog_InputReturn CO2 ppmppmRead
AI22Aux_In_Customer_1Customer defined auxiliary input (units selectable)Read
AI23Aux_In_Customer_2Customer defined auxiliary input (units selectable)Read
AI24Aux_In_Customer_3Customer defined auxiliary input (units selectable)Read
AI25Aux_In_Customer_4Customer defined auxiliary input (units selectable)Read
AI26Aux_In_Customer_5Customer defined auxiliary input (units selectable)Read
AI27Aux_In_Customer_6Customer defined auxiliary input (units selectable)Read
AI28Aux_In_Customer_7Customer defined auxiliary input (units selectable)Read
AI29Aux_In_Customer_8Customer defined auxiliary input (units selectable)Read
AI30Aux_In_Customer_9Customer defined auxiliary input (units selectable)Read
AI31Aux_In_Customer_10Customer defined auxiliary input (units selectable)Read
AVmin1Temperature_SetpointOccupied Temperature Setpoint°FWrite
AV2Temperature_Heat_Cool_DeadbandOccupied Spt Deadband - Space/Return ResetΔ°FWrite
AV3Temperature_Setpoint_UnoccupiedUnoccupied Temperature Setpoint°FWrite
AV4Temperature_Heat_Cool_Deadband_UnoccupiedUnoccupied Spt Deadband - Space/Return ResetΔ°FWrite
AV5Supply_Temperature_Minimum_Cooling_SetpointMinimum supply air temperature - Cooling°FWrite
AV6Supply_Temperature_Maximum_Cooling_SetpointMaximum supply air temperature - Cooling°FWrite
AV7Supply_Temperature_Minimum_Heating_SetpointMinimum supply air temperature - Heating°FWrite
AV8Supply_Temperature_Maximum_Heating_SetpointMaximum supply air temperature - Heating°FWrite
AV9Economizer_Temp_Enable_SetpointEconomizer Ambient Temp Enable Setpoint°FWrite
AV13Cooling_Lockout_SetpointCooling Ambient Lockout Setpoint°FWrite
AV14Heating_Lockout_SetpointHeating Ambient Lockout Setpoint°FWrite
AV15Economizer_Lockout_SetpointEconomizer Lockout Setpoint°FWrite
AV16Space_Static_Pressure_SetpointSpace Static Pressure Setpointin. w.c.Write
AV17Supply_Duct_Static_Pressure_SetpointSupply Duct Static Pressure Setpointin. w.c.Write
AV18Space_CO2_SetpointSpace CO2 SetpointppmWrite
AV19Outside_Air_Damper_Minimum_Setpoint_OccOccupied Outside Air Damper Min Setpoint%Write
AV20Outside_Air_Damper_Minimum_Setpoint_UnoccUnoccupied Outside Air Damper Min Setpoint%Write
AV21Heat_Vent_Changeover_TempHeat Vent Changeover Setpoint°FWrite
AV22Heat_Vent_Changeover_HysteresisHeat Vent Changeover Hysteresis (Summer Only)°FWrite
AV23HV_Summer_Damper_Setpoint_OccOccupied OAD Setpoint when in Summer Mode%Write
AV24HV_Summer_Damper_Setpoint_UnoccUnoccupied OAD Setpoint when in Summer Mode%Write
AV25HV_Summer_LockoutSummer Mode Ambient Lockout Setpoint°FWrite
AV26HV_Winter_Damper_Setpoint_OccOccupied OAD Setpoint when in Winter Mode%Write
AV27HV_Winter_Damper_Setpoint_UnoccUnoccupied OAD Setpoint when in Winter Mode%Write
AV28Supply_Air_Low_Limit_SetpointLow Supply Temp resulting in unit shutdown°FWrite
AV30Outside_Temp_from_BMSOutside Temp from BMS. (Source set to BMS)°FWrite
AV33Space_1_CO2_from_BMSSpace CO2 from BMS - source is BMSppmWrite
AV34Return_CO2_from_BMSReturn CO2 from BMS - source is BMSppmWrite
AV36Space_Static_from_BMSSpace Static from BMS - source is BMSin. w.c.Write
AV37Space_Temp_from_BMSSpace Temp from BMS - source is BMS°FWrite
AV38SF_Control_Signal_BMSBMS to control signal for supply fan speed%Write
AV39OAD_Control_Signal_BMSAllows the BMS to control OAD position%Write
AV40Aux_BMS_Analog_Output_1BMS Commanded auxilary analog output (units selectable)Write
AVmin41Unit_Status_ModeUnit Status Mode - See TableRead
AV42Supply_Temperature_Calculated_SetpointActive Supply Temperature Setpoint°FRead
AV43Cooling_1_Ramp_CapacityCooling Ramp 1 Status Value%Read
AV44Economizer_RampEconomizer Ramp%Read
AV46Heating_CapacityHeating Ramp%Read
AV56OAD_CFM_BMSOAD CFMcfmRead
AV57Active_Temperature_SetpointActive Temperature Setpoint°FRead
AV58Chilled_Water_1_Valve_Analog_OutputChilled Water 1 Valve Analog Output%Read
AV59Electric_Heater_1_Analog_OutputElectric Heater 1 Analog Output%Read
AV60Hot_Water_Valve_1_Analog_OutputHot Water Valve 1 Analog Output%Read
AV61Mod_Gas_Furnace_1_Analog_OutputMod Gas Furnace 1 Analog Output%Read
AV62Outside_Airflow_MaskPercentage of Outside Airflow%Read
AV63Supply_Fan_Speed_Analog_OutputSupply Fan Speed Analog Output%Read
AV64Modulating_Compressor_Analog_Output_BMSModulating Compressor Analog Output%Read
AV69Active_Cooling_SetpointActive Cooling Setpoint - Unoccupied°FRead
AV70Active_Heating_SetpointActive Heating Setpoint - Unoccupied°FRead
AV71LatestAlm_RealMost recent alarm - See Alarm TableRead
AV72Digital_Output_Word_Real_1Digital Output Word - See TableReadBit-packed word (bit table in the manual)
AV73Digital_Output_Word_Real_2Digital Output Word - See TableReadBit-packed word (bit table in the manual)
AV74Cooling_Alarm_Word_Real_1Cooling Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV75Cooling_Alarm_Word_Real_2Cooling Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV76Device_Offline_Word_Real_1Device Offline Word - See TableReadBit-packed word (bit table in the manual)
AV77Device_Offline_Word_Real_2Device Offline Word - See TableReadBit-packed word (bit table in the manual)
AV78Device_Alarm_Word_Real_1Device Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV79Device_Alarm_Word_Real_2Device Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV80Heating_Alarm_Word_Real_1Heating Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV81Heating_Alarm_Word_Real_2Heating Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV82Unit_Status_Word_Real_1Unit Status Word - See TableReadBit-packed word (bit table in the manual)
AV83Unit_Status_Word_Real_2Unit Status Word - See TableReadBit-packed word (bit table in the manual)
BI1Exhaust_Fan_1_Status_Digital_InputExhaust Fan StatusReadActive=Active, Inactive=Inactive
BI2Supply_Fan_1_Status_Digital_InputSupply Fan StatusReadActive=Active, Inactive=Inactive
BVmin1BMS_WatchdogBMS Watchdog command Used to determine BMS comm statusWriteActive=Active, Inactive=Inactive
BVmin2System_EnableMaster system enable/disable pointWriteActive=Active, Inactive=Inactive
BVmin3BMS_Occupancy_CommandOccupancy CommandWriteActive=Unoccupied, Inactive=Occupied
BVmin4Reset_All_AlarmsAlarm Reset CommandWriteActive=Reset, Inactive=Normal
BV6Outside_Temp_Source_BMSOutside Temp Source SelectionWriteActive=BMS, Inactive=Local
BV9Space_1_CO2_Source_BMSSpace CO2 Source SelectionWriteActive=BMS, Inactive=Local
BV10Return_CO2_Source_BMSReturn CO2 Source SelectionWriteActive=BMS, Inactive=Local
BV12Space_Static_Source_BMSSpace Static Source SelectionWriteActive=BMS, Inactive=Local
BV13Space_Temp_Source_BMSSpace Temp Source SelectionWriteActive=BMS, Inactive=Local
BV14SF_Control_Source_BMSAllows the BMS to control supply fan speedWriteActive=BMS, Inactive=Local
BV15OAD_Control_Source_BMSAllows the BMS to control OAD positionWriteActive=BMS, Inactive=Local
BV16Aux_BMS_Digital_Output_1BMS Commanded auxilary digital outputWriteActive=Active, Inactive=Inactive
BV17Aux_BMS_Digital_Output_2BMS Commanded auxilary digital outputWriteActive=Active, Inactive=Inactive
BV18OccupiedOccupancyReadActive=Occupied, Inactive=Unoccupied
BVmin19Global_AlarmAlarm Output - Any or Shutdown SelectableReadActive=Alarm, Inactive=Normal
BV20BMS_Watchdog_ActiveStatus of the BMS Watchdog PingReadActive=Active, Inactive=Inactive
BV21Heat_Vent_Mode_ActiveCurrent Heat Vent ModeReadActive=Summer, Inactive=Winter
BV22Supply_Fan_1_Alarm.ActiveSupply Fan Alarm ActiveReadActive=Alarm, Inactive=Normal
BV23Exhaust_Fan_1_Alarm.ActiveExhaust Fan Alarm ActiveReadActive=Alarm, Inactive=Normal
BV25Fire_Safety_Shutdown_Alarm.ActiveFire Safety Alarm ActiveReadActive=Alarm, Inactive=Normal
BV26Refrigerant_Leak_Alarm.ActiveRefrigerant Leak Alarm ActiveReadActive=Alarm, Inactive=Normal
IV1Temperature_Reset_ModeOccupied Reset ModeRead1-Discharge; 2-Space; 3-Return; 4-Outside
IV2Temperature_Reset_Mode_UnoccupiedUnoccupied Reset ModeRead1-Discharge; 2-Space; 3-Return
IV3HV_Summer_Operation_OccHeat Vent Summer Operation OccupiedRead1-Off; 2-Continuous
IV4HV_Summer_Operation_UnoccHeat Vent Summer Operation UnoccupiedRead
IV5HV_Winter_Operation_OccHeat Vent Winter Operation OccupiedRead1-Off; 2-Continuous; 3-Cycle
IV6HV_Winter_Operation_UnoccHeat Vent Winter Operation UnoccupiedRead
IV7Active_Temperature_Reset_ModeActive Occupied Reset Type SetpointRead1-Discharge; 2-Space; 3-Return; 4-Outside
IV8Active_Temperature_Reset_Mode_UnoccActive Unoccupied Reset Type SetpointRead1-Discharge; 2-Space; 3-Return
IVmin9LatestAlmMost recent alarm - See Alarm TableRead
IV10Digital_Output_WordDigital Output Word - See TableReadBit-packed word (bit table in the manual)
IV11Cooling_Alarm_WordCooling Alarm Word - See TableReadBit-packed word (bit table in the manual)
IV12Device_Offline_WordDevice Offline Word - See TableReadBit-packed word (bit table in the manual)
IV13Device_Alarm_WordDevice Alarm Word - See TableReadBit-packed word (bit table in the manual)
IV14Heating_Alarm_WordHeating Alarm Word - See TableReadBit-packed word (bit table in the manual)
IV15Unit_Status_WordUnit Status Word - See TableReadBit-packed word (bit table in the manual)
Object ID lookup: Greenheck Make-Up Air Microprocessor Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Make-Up Air Microprocessor Controller (MUA v4.1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greenheck Make-Up Air Microprocessor Controller (MUA v4.1)

How many BACnet points does the Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) have?

This list has 118 BACnet objects: 18 analog inputs, 62 analog values, 2 binary inputs, 21 binary values, 15 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) BACnet points are writable?

46 of the 118 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) BACnet documentation?

The source is Microprocessor Controller for Make-up Air - Reference Guide (MUA v4.1) (487036), revision 2024-12, published free by Greenheck at https://webcontent.greenheck.com/atg-cms-v2-prod/docs/default-source/resource-library/installation-manuals/make-up-air/487036_controller_iom.pdf.

What are the minimum BACnet points to integrate the Greenheck Make-Up Air Microprocessor Controller (MUA v4.1)?

Start with BV 2 System_Enable (Enables or disables the unit); BV 3 BMS_Occupancy_Command (Occupancy; Active = Unoccupied, Inactive = Occupied); AV 1 Temperature_Setpoint (Occupied temperature setpoint); BV 1 BMS_Watchdog (Heartbeat when BMS controls fans or sensors); BV 4 Reset_All_Alarms (Remote alarm reset); AV 41 Unit_Status_Mode (Current operating mode code); AI 2 Supply_Temp_Analog_Input (Supply (discharge) air temperature); BV 19 Global_Alarm (Alarm output (any or shutdown alarms)); IV 9 LatestAlm (Most recent alarm code).

How do I enable BMS control of the Greenheck Make-Up Air Microprocessor Controller (MUA v4.1)?

BV 2 System_Enable enables or disables the unit; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied).

Does the Greenheck Make-Up Air Microprocessor Controller (MUA v4.1) need a BACnet heartbeat or have a communication timeout?

BV 1 BMS_Watchdog must be toggled by the BMS within the timeout delay (15 minutes by default, adjustable) whenever the BMS replaces a hardwired sensor (or takes over fan speed or damper control). If the timer expires, the controller alarms (BMS Offline) and falls back to its hardwired sensors and local control until the BMS returns. The watchdog status is shown on a read-only BV.

Can the BMS supply sensor values to the Greenheck Make-Up Air Microprocessor Controller (MUA v4.1)?

Set the source-select BV to BMS (BV 6 outside temp, BV 9/10 CO2, BV 12 space static, BV 13 space temp), then write the matching *_from_BMS value (AV 30, 33, 34, 36, 37). BV 14 and BV 15 hand supply fan speed and damper position to the BMS. The watchdog must be kept alive.

How do I check these points on the real Make-Up Air Microprocessor Controller (MUA v4.1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greenheck BACnet points lists