Dedicated outdoor air system (DOAS) unit controller · BACnet points list

Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) BACnet points list

Updated 6 November 2026

Short answer

This is the points list of Greenheck's DOAS controller at program v6.2, which uses different object numbering from the later DOAS programs (for example DOAS v9.4 and DOAS_10.006). It offers BACnet MS/TP, BACnet IP, Modbus RTU and Modbus TCP. The BMS can enable the unit, command occupancy, reset alarms, write setpoints, send sensor values and take over fans and the outdoor air damper through source-select points, with a watchdog. A long list of read-only binary values reports individual alarms, outputs and status.

This page lists 295 BACnet objects for the Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) — 60 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greenheck’s own free documentation, linked below.

Manufacturer
Greenheck
Model
DOAS Microprocessor Controller v6.2 (legacy points list)
Equipment
Dedicated outdoor air system (DOAS) unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
295 (60 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
DOAS v6.2
Also known as
485175, Document 485175, DOAS v6.2, Greenheck DOAS controller, c.pCO
Source document
Microprocessor Controller for DOAS - Reference Guide (DOAS v6.2) · 485175 · rev. 2021-04 (Rev. 1; program version date 7/21)
Download CSV 295 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greenheck’s current documentation and the live device before use. Not official Greenheck information. Terms of use.

BMS integration notes: Greenheck DOAS Microprocessor Controller v6.2 (legacy points list)

Integration in brief

Enable the unit with BV 2 Master System Enable and command occupancy with BV 3, write the main temperature setpoint AV 1 and reset alarms with BV 4. Keep the BV 1 watchdog alive if the BMS sends sensor values or controls fans or the damper. Monitor unit status (AV 40), supply temperature, the general alarm BV 24 and the most recent alarm IV 7.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2Master System EnableEnables or disables the unitCommand
BV 3Occupancy CommandOccupancy; 1 = Unoccupied, 0 = OccupiedCommand
AV 1Main Temperature Setpoint - Supply, Space, or ReturnMain temperature setpointCommand
BV 1BMS Watchdog CommandHeartbeat when BMS controls fans or sensorsCommand
BV 4Alarm Reset CommandRemote alarm resetCommand
AV 40Unit StatusCurrent operating mode codeRead
AI 45Supply TemperatureSupply (discharge) air temperatureRead
BV 24General Alarm StatusAny (or shutdown) alarm activeRead
IV 7Most Recent AlarmMost recent alarm codeRead

Enable & remote start

BV 2 Master System Enable enables or disables the unit; BV 3 Occupancy Command sets occupancy (1 = Unoccupied).

Heartbeat & communication loss

The BMS watchdog must be toggled by the BMS within the timeout delay whenever the BMS replaces a hardwired sensor. If the timer expires the controller alarms and falls back to its hardwired sensors until the BMS returns.

Sensors & values from the BMS

Set the sensor's source-select BV to BMS (1), then write the matching 'from BMS' AV; fans and the outdoor air damper are taken over the same way (e.g. BV-59 with AV-136 for the damper).

Network setup

Watch out for

Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

295 of 295 shown
Type
Other
Access
Show
Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) BACnet Points List
DescriptionStates
AI3Circuit A Suction TemperatureRead
AI4Circuit B Discharge TemperatureRead
AI6Circuit B Suction TemperatureRead
AI25Cold Coil 1 TemperatureRead
AI30Exhaust TemperatureRead
AI35Mixed TemperatureRead
AI37Outside Air TemperatureRead
AI41Return TemperatureRead
AI44Space TemperatureRead
AImin45Supply TemperatureRead
AI86Outside % Relative HumidityRead
AI88Return % Relative HumidityRead
AI89Space % Relative HumidityRead
AI93Return Duct Static PressureRead
AI94Space Static PressureRead
AI95Supply Duct Static PressureRead
AI116Space 1 CO2 ppmRead
AI118Return CO2 ppmRead
AI119Circuit A Discharge PressureRead
AI120Circuit A Suction PressureRead
AI121Circuit B Discharge PressureRead
AI122Circuit B Suction PressureRead
AI143Exhaust Fan Speed Remote CommandRead
AI155Supply Fan Speed Remote CommandRead
AI640Customer defined auxiliary inputRead
AI642Customer defined auxiliary inputRead
AI644Customer defined auxiliary inputRead
AI646Customer defined auxiliary inputRead
AI648Customer defined auxiliary inputRead
AI650Customer defined auxiliary inputRead
AVmin1Main Temperature Setpoint - Supply, Space, or ReturnCommand
AV2Heat/Cool Spt DeadbandSpace/return reset: Clg = Spt + DB/2, Htg = Spt - DB/2Command
AV3Cooling Coil Leaving Air Setpoint MinimumCommand
AV5Dehumidification Setpoint%RH, for space or return reset controlCommand
AV6Outside Dewpoint Dehumidification Trigger SetpointCommand
AV7Indoor Dewpoint Dehumidification Trigger SetpointCommand
AV9Unoccupied Indoor Dewpoint Dehumidification Trigger SetpointCommand
AV10Unoccupied Cooling SetpointCommand
AV11Unoccupied Dehumidification %RH SetpointCommand
AV12Unoccupied Heating SetpointCommand
AV16Economizer Ambient Temp Enable SetpointAllow Econ when OAT<SptCommand
AV17Economizer Enthalpy Enable SetpointAllow Econ when OA Enthalpy<SptCommand
AV21Outside RH from BMS(BV-5 set to 1 for BMS Control)Command
AV22Outside Temp from BMS(BV-6 set to 1 for BMS Control)Command
AV23Return RH from BMS(BV-7 set to 1 for BMS Control)Command
AV24Return Temp from BMS(BV-8 set to 1 for BMS Control)Command
AV25Space 1 CO2 from BMS(BV-9 set to 1 for BMS Control)Command
AV27Return CO2 from BMS(BV-11 set to 1 for BMS Control)Command
AV28Space RH from BMS(BV-12 set to 1 for BMS Control)Command
AV29Space Static from BMS(BV-13 set to 1 for BMS Control)Command
AV30Space Temp from BMS(BV-14 set to 1 for BMS Control)Command
AV31Cooling Ambient Lockout SetpointCommand
AV32Heating Ambient Lockout SetpointCommand
AV33Preheat Ambient Lockout SetpointCommand
AV36Return Duct Static Pressure SetpointCommand
AV37Space Static Pressure SetpointCommand
AV38Supply Duct Static Pressure SetpointCommand
AV39Space CO2 SetpointCommand
AV133Supply Fan Speed Control Signal from BMS(BV-56 set to 1 for BMS Control)Command
AV134Exhaust Fan Speed Control Signal from BMS(BV-57 set to 1 for BMS Control)Command
AV136OA Damper Position Control Signal from BMS(BV-59 set to 1 for BMS Control)Command
AV137Outside Air Damper Minimum SetpointCommand
AV138BMS Commanded auxiliary analog outputCommand
AV139BMS Commanded auxiliary analog outputCommand
AV140BMS Commanded auxiliary analog outputCommand
AV141BMS Commanded auxiliary analog outputCommand
AV313Cooling Coil Leaving Air Setpoint MaximumCommand
AVmin40Unit StatusRead0=Off/Standby, 1=Unoccupied Start, 2=Occupied Start, 3=Opening Dampers, 4=End Switch, 5=Dampers Open, 6=Fan Start Delay, 7=Fans Starting, 8=Fans Starting, 9=Heat/Cool Delay, 10=System On, 11=Soft Shutdown, 12=System Disabled
AV41Active Supply Temperature SetpointRead
AV43Cooling Ramp 1 CapacityRead
AV47Defrost RampRead
AV48Economizer RampRead
AV49Exhaust Fan Space Static Pressure RampRead
AV50Exhaust Fan Supply Tracking RampRead
AV51Head Pressure Control Ramp 1Read
AV52Head Pressure Control Ramp 2Read
AV59Heat Pump Heating RampRead
AV60Heating RampRead
AV61Hot Gas Reheat RampRead
AV64OAD CFM RampRead
AV71Space CO2 Control RampRead
AV72Supply Duct Static Pressure RampRead
AV73Supply Fan CFM Control RampRead
AV74Supply Fan Space Static Pressure RampRead
AV75Winter Ramp OutputRead
AV82Outside DewpointRead
AV83Outside EnthalpyRead
AV86Return DewpointRead
AV87Return EnthalpyRead
AV88Space DewpointRead
AV89Space EnthalpyRead
AV93Circuit A SuperheatRead
AV95Circuit B SuperheatRead
AV107Total Exhaust Fan CFMRead
AV110Total Supply Fan CFMRead
AV129OAD CFMRead
AV131OAD Static Pressure Ramp %Read
AV132Active Temperature SetpointRead
AV201Chilled Water 1 Valve Position %Read
AV205Condenser Ramp 1 %Read
AV206Condenser Ramp 2 %Read
AV221Electric Heater Output %Read
AV229Energy Recovery Output %Read
AV231Exhaust Fan Speed %Read
AV235Hot Gas Reheat Valve Position %Read
AV236Hot Water Valve Position %Read
AV242Mod Gas Furnace Output %Read
AV250Outside Air Damper PositionRead
AV264Supply Fan Speed %Read
AV285Modulating Compressor Speed %Read
AV286Circuit A Saturated Discharge TemperatureRead
AV287Circuit B Saturated Discharge TemperatureRead
AV294Circuit A Saturated Suction TemperatureRead
AV295Circuit B Saturated Suction TemperatureRead
AV312Calculated Coil Leaving SetpointRead
BI3Circuit A High Pressure SwitchRead1=Active, 0=Inactive
BI4Circuit A Low Pressure SwitchRead1=Active, 0=Inactive
BI5Circuit B High Pressure SwitchRead1=Active, 0=Inactive
BI6Circuit B Low Pressure SwitchRead1=Active, 0=Inactive
BI21Drain Pan Alarm StatusRead1=Active, 0=Inactive
BI23Exhaust Fan 1 StatusRead1=Active, 0=Inactive
BI28Freeze Stat Alarm StatusRead1=Active, 0=Inactive
BI52OAD End Switch StatusRead1=Active, 0=Inactive
BI53Occupancy StatusRead1=Active, 0=Inactive
BI54Filter Alarm StatusRead1=Active, 0=Inactive
BI75Shutdown Alarm StatusRead1=Active, 0=Inactive
BI78Supply Fan 1 StatusRead1=Active, 0=Inactive
BI82Remote Unit Enable StatusRead1=Active, 0=Inactive
BI83Heat Wheel StatusRead1=Active, 0=Inactive
BVmin1BMS Watchdog CommandWrite a 1 to the watchdog within the timeout delay to establish communication from BMS...Command1=Active, 0=Inactive
BVmin2Master System EnableCommand1=Enable, 0=Disable
BVmin3Occupancy CommandCommand1=Unoccupied, 0=Occupied
BVmin4Alarm Reset CommandCommand1=Reset, 0=Normal
BV5Outside RH Source SelectionValue written to AV 21Command1=BMS, 0=Local
BV6Outside Temp Source SelectionValue written to AV 22Command1=BMS, 0=Local
BV7Return RH Source SelectionValue written to AV 23Command1=BMS, 0=Local
BV8Return Temp Source SelectionValue written to AV 24Command1=BMS, 0=Local
BV9Space 1 CO2 Source SelectionValue written to AV 25Command1=BMS, 0=Local
BV11Return CO2 Source SelectionValue written to AV 27Command1=BMS, 0=Local
BV12Space RH Source SelectionValue written to AV 28Command1=BMS, 0=Local
BV13Space Static Source SelectionValue written to AV 29Command1=BMS, 0=Local
BV14Space Temp Source SelectionValue written to AV 30Command1=BMS, 0=Local
BV56SF Control Source SelectionValue written to AV 133Command1=BMS, 0=Local
BV57EF Control Source SelectionValue written to AV 134Command1=BMS, 0=Local
BV59OAD Control Source SelectionValue written to AV 136Command1=BMS, 0=Local
BV207BMS Commanded auxiliary digital outputCommand1=Active, 0=Inactive
BV208BMS Commanded auxiliary digital outputCommand1=Active, 0=Inactive
BV209BMS Commanded auxiliary digital outputCommand1=Active, 0=Inactive
BV210BMS Commanded auxiliary digital outputCommand1=Active, 0=Inactive
BV211BMS Commanded auxiliary digital outputCommand1=Active, 0=Inactive
BV212BMS Commanded auxiliary digital outputCommand1=Active, 0=Inactive
BV16Occupied StatusRead1=Occupied, 0=Unoccupied
BV18Unoccupied Cooling Call StatusRead1=Active, 0=Inactive
BV19Unoccupied Dehumidification Call StatusRead1=Active, 0=Inactive
BV20Unoccupied Heating Call StatusRead1=Active, 0=Inactive
BVmin24General Alarm StatusOptionally set to indicate any alarm is active, or a shutdown alarm is active.Read1=Alarm, 0=Normal
BV25Shutdown Alarm StatusWhen in alarm, the System Enable is set to false and the unit will remain off.Read1=Shutdown, 0=Normal
BV27Unit CoolingRead1=Active, 0=Inactive
BV28Unit EconomizingRead1=Active, 0=Inactive
BV29Unit HeatingRead1=Active, 0=Inactive
BV31Unit DehumidifyingRead1=Active, 0=Inactive
BV32Manual Overrides ActiveRead1=Override, 0=Normal
BV33Cooling AllowedRead1=Allowed, 0=Locked_Out
BV34Heating AllowedRead1=Allowed, 0=Locked_Out
BV36PreHeat AllowedRead1=Allowed, 0=Locked_Out
BV37Hot Gas Reheat Purge CycleRead1=Active, 0=Inactive
BV43Dampers Opening Startup SequenceRead1=Yes, 0=No
BV44Exhaust Fan Startup SequenceRead1=Yes, 0=No
BV48Supply Fan Startup SequenceRead1=Yes, 0=No
BV49BMS Watchdog Ping ActiveRead1=Active, 0=Inactive
BV50BMS Occupancy CommandRead1=Occupied, 0=Unoccupied
BV60Condenser Water Pump RequiredRead1=Yes, 0=No
BV100Damper Actuator PowerRead1=Active, 0=Inactive
BV111Compressor 1 EnableRead1=Active, 0=Inactive
BV112Compressor 2 EnableRead1=Active, 0=Inactive
BV113Compressor 3 EnableRead1=Active, 0=Inactive
BV114Compressor 4 EnableRead1=Active, 0=Inactive
BV119Condenser Ramp 1 Stage 1 StartRead1=Active, 0=Inactive
BV120Condenser Ramp 1 Stage 2 StartRead1=Active, 0=Inactive
BV121Condenser Ramp 1 Stage 3 StartRead1=Active, 0=Inactive
BV123Condenser Ramp 2 Stage 1 StartRead1=Active, 0=Inactive
BV124Condenser Ramp 2 Stage 2 StartRead1=Active, 0=Inactive
BV125Condenser Ramp 2 Stage 3 StartRead1=Active, 0=Inactive
BV127Exhaust Fan 1Read1=Active, 0=Inactive
BV131Furnace 1 Stage 1Read1=Active, 0=Inactive
BV133Furnace 2 Stage 1Read1=Active, 0=Inactive
BV163Heat Wheel EnableRead1=Active, 0=Inactive
BV166PreHeat EnableRead1=Active, 0=Inactive
BV175Reversing Valve PositionRead1=Heat, 0=Cool
BV186Supply Fan 1Read1=Active, 0=Inactive
BV313BMS Offline AlarmRead1=Alarm, 0=Normal
BV315Circuit A Discharge Pressure Transducer AlarmRead1=Alarm, 0=Normal
BV316Circuit A Discharge Temp Sensor AlarmRead1=Alarm, 0=Normal
BV319Circuit A Suction Pressure Transducer AlarmRead1=Alarm, 0=Normal
BV320Circuit A Suction Temp Sensor AlarmRead1=Alarm, 0=Normal
BV324Circuit B Discharge Pressure Transducer AlarmRead1=Alarm, 0=Normal
BV325Circuit B Discharge Temp Sensor AlarmRead1=Alarm, 0=Normal
BV328Circuit B Suction Pressure Transducer AlarmRead1=Alarm, 0=Normal
BV329Circuit B Suction Temp Sensor AlarmRead1=Alarm, 0=Normal
BV387Cold Coil 1 Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV395Comp Circ A High Pressure AlarmRead1=Alarm, 0=Normal
BV396Comp Circ A Low Pressure AlarmRead1=Alarm, 0=Normal
BV397Comp Circ B High Pressure AlarmRead1=Alarm, 0=Normal
BV398Comp Circ B Low Pressure AlarmRead1=Alarm, 0=Normal
BV420Damper End Switch AlarmRead1=Alarm, 0=Normal
BV422Drain Pan AlarmRead1=Alarm, 0=Normal
BV423Exhaust Fan 1 AlarmRead1=Alarm, 0=Normal
BV424Exhaust Fan 1 CFM Transducer AlarmRead1=Alarm, 0=Normal
BV433Exhaust Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV434Expansion Board 1 AlarmRead1=Alarm, 0=Normal
BV435Expansion Board 2 AlarmRead1=Alarm, 0=Normal
BV436Expansion Board 3 AlarmRead1=Alarm, 0=Normal
BV441Freeze Stat AlarmRead1=Alarm, 0=Normal
BV448HP Circuit A High Sat Discharge Temp AlarmRead1=Alarm, 0=Normal
BV454HP Circuit B High Sat Discharge Temp AlarmRead1=Alarm, 0=Normal
BV498Internal Board Temp Alarm - Full Platform OnlyRead1=Alarm, 0=Normal
BV502Mixed Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV506OAD CFM Transducer AlarmRead1=Alarm, 0=Normal
BV507Outside Air Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV508Filter AlarmRead1=Alarm, 0=Normal
BV509Outside RH Sensor AlarmRead1=Alarm, 0=Normal
BV520Return CO2 Sensor AlarmRead1=Alarm, 0=Normal
BV521Return Duct Static Pressure Transducer AlarmRead1=Alarm, 0=Normal
BV531Return Low Static AlarmRead1=Alarm, 0=Normal
BV532Return RH Sensor AlarmRead1=Alarm, 0=Normal
BV533Return Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV535Space CO2 1 Sensor AlarmRead1=Alarm, 0=Normal
BV537Space High Static AlarmRead1=Alarm, 0=Normal
BV538Space RH Sensor AlarmRead1=Alarm, 0=Normal
BV540Space Static Pressure Transducer AlarmRead1=Alarm, 0=Normal
BV541Space Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV551Supply Air Temp Low Limit AlarmRead1=Alarm, 0=Normal
BV552Supply Air Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV553Supply Duct Static Pressure Transducer AlarmRead1=Alarm, 0=Normal
BV554Supply Fan 1 AlarmRead1=Alarm, 0=Normal
BV558Supply Fan 1 CFM Transducer AlarmRead1=Alarm, 0=Normal
BV563Supply High Duct Static AlarmRead1=Alarm, 0=Normal
BV565Supply Temp High Limit AlarmRead1=Alarm, 0=Normal
BV567TMem Error AlarmRead1=Alarm, 0=Normal
BV576Wheel Rotation AlarmRead1=Alarm, 0=Normal
BV589EVD Battery AlarmRead1=Alarm, 0=Normal
BV590EVD Configuration AlarmRead1=Alarm, 0=Normal
BV591Compressor Envelope - High Discharge Pressure AlarmRead1=Alarm, 0=Normal
BV592Compressor Envelope - High Discharge Temperature AlarmRead1=Alarm, 0=Normal
BV593EVD Low Discharge Pressure AlarmRead1=Alarm, 0=Normal
BV594EVD EEPROM AlarmRead1=Alarm, 0=Normal
BV595ExV Motor Alarm - Valve 1Read1=Alarm, 0=Normal
BV597EVD Emergency Closing AlarmRead1=Alarm, 0=Normal
BV598EVD Offline Communication AlarmRead1=Alarm, 0=Normal
BV599EVD Firmware Compatibility AlarmRead1=Alarm, 0=Normal
BV600Compressor Envelope - High Current AlarmRead1=Alarm, 0=Normal
BV601Compressor Envelope - High Pressure Ratio AlarmRead1=Alarm, 0=Normal
BV602EVD High Condenser Temp AlarmRead1=Alarm, 0=Normal
BV603EVD Incomplete Closing AlarmRead1=Alarm, 0=Normal
BV604EVD Low Operating Pressure AlarmRead1=Alarm, 0=Normal
BV606EVD Low SuperHeat AlarmRead1=Alarm, 0=Normal
BV608Compressor Envelope - Low Pressure DeltaAlarmRead1=Alarm, 0=Normal
BV609Compressor Envelope - Low Pressure Ratio AlarmRead1=Alarm, 0=Normal
BV610Low Suction Refrigerant TemperatureRead1=Alarm, 0=Normal
BV612EVD Max Operating Pressure AlarmRead1=Alarm, 0=Normal
BV614EVD-S1 Suction Pressure Sensor AlarmRead1=Alarm, 0=Normal
BV615EVD-S2 Suction Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV617EVD-S4 Discharge Temperature Sensor AlarmRead1=Alarm, 0=Normal
BV618Compressor Envelope - High Suction PressureRead1=Alarm, 0=Normal
BV619Compressor Envelope - Low Suction PressureRead1=Alarm, 0=Normal
BV631Heat Pump Defrost AlarmRead1=Alarm, 0=Normal
BV633Heat Pump Heating Locked OutRead1=Alarm, 0=Normal
BV634Unexpected EEV Position - Preposition FailedRead1=Alarm, 0=Normal
BV731Energy Recovery Wheel High Differential PressureRead1=Alarm, 0=Normal
BV733High Low Pressure Switch Alarm Circuit A - LegacyRead1=Alarm, 0=Normal
BV734High Low Pressure Switch Alarm Circuit B - LegacyRead1=Alarm, 0=Normal
BV735High Low Pressure Switch Alarm Circuit C - LegacyRead1=Alarm, 0=Normal
BV736High Low Pressure Switch Alarm Circuit D - LegacyRead1=Alarm, 0=Normal
BV737EF Greentrol Alarm - LegacyRead1=Alarm, 0=Normal
BV738OAD Greentrol AlarmRead1=Alarm, 0=Normal
BV739Greentrol Device 3 Alarm - LegacyRead1=Alarm, 0=Normal
BV741OAD Feedback Error - Not Opening When EconomizingRead1=Alarm, 0=Normal
BV742OAD Feedback Error - OAD is OpenRead1=Alarm, 0=Normal
BV743OAD Feedback Error - OAD is Not ModulatingRead1=Alarm, 0=Normal
BV744OAD Feedback Error - OAD is Not ClosingRead1=Alarm, 0=Normal
BV745Space Thermostat 1 OfflineRead1=Alarm, 0=Normal
BV746Space Thermostat 2 OfflineRead1=Alarm, 0=Normal
BV747Space Thermostat 3 OfflineRead1=Alarm, 0=Normal
BV748Space Thermostat 4 OfflineRead1=Alarm, 0=Normal
BV749Inverter Scroll 1 AlarmRead1=Alarm, 0=Normal
BV753IG Furnace AlarmRead1=Alarm, 0=Normal
BV754SF VFD Alarm - Mini PlatformRead1=Alarm, 0=Normal
BV758Embedded EVD Alarm - Mini PlatformRead1=Alarm, 0=Normal
BV759Supply Fan VFD Offline - Mini PlatformRead1=Alarm, 0=Normal
IV1Fan and Damper Startup Sequence Delay TimerRead
IV2Supply Fan Startup Sequence Delay TimerRead
IV3Exhaust Fan startup sequencetime before starting the exhaust fan.Read
IVmin7Most Recent AlarmCall technical support for the current tableRead
IV9Active Temperature Reset Sequence1. No Reset, Supply Control 2. Space 3. Return 4. OutsideRead
IV8Selected Temperature Reset Sequence1. No Reset, Supply Control 2. Space 3. Return 4. OutsideCommand
Object ID lookup: Greenheck DOAS Microprocessor Controller v6.2 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DOAS Microprocessor Controller v6.2 (legacy points list) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greenheck DOAS Microprocessor Controller v6.2 (legacy points list)

How many BACnet points does the Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) have?

This list has 295 BACnet objects: 30 analog inputs, 85 analog values, 14 binary inputs, 160 binary values, 6 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) BACnet points are writable?

60 of the 295 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) BACnet documentation?

The source is Microprocessor Controller for DOAS - Reference Guide (DOAS v6.2) (485175), revision 2021-04 (Rev. 1; program version date 7/21), published free by Greenheck at https://webcontent.greenheck.com/atg-cms-v2-prod/docs/default-source/resource-library/installation-manuals/dedicated-outdoor-air-systems/485175_-doascontroller_iom.pdf.

What are the minimum BACnet points to integrate the Greenheck DOAS Microprocessor Controller v6.2 (legacy points list)?

Start with BV 2 Master System Enable (Enables or disables the unit); BV 3 Occupancy Command (Occupancy; 1 = Unoccupied, 0 = Occupied); AV 1 Main Temperature Setpoint - Supply, Space, or Return (Main temperature setpoint); BV 1 BMS Watchdog Command (Heartbeat when BMS controls fans or sensors); BV 4 Alarm Reset Command (Remote alarm reset); AV 40 Unit Status (Current operating mode code); AI 45 Supply Temperature (Supply (discharge) air temperature); BV 24 General Alarm Status (Any (or shutdown) alarm active); IV 7 Most Recent Alarm (Most recent alarm code).

How do I enable BMS control of the Greenheck DOAS Microprocessor Controller v6.2 (legacy points list)?

BV 2 Master System Enable enables or disables the unit; BV 3 Occupancy Command sets occupancy (1 = Unoccupied).

Does the Greenheck DOAS Microprocessor Controller v6.2 (legacy points list) need a BACnet heartbeat or have a communication timeout?

The BMS watchdog must be toggled by the BMS within the timeout delay whenever the BMS replaces a hardwired sensor. If the timer expires the controller alarms and falls back to its hardwired sensors until the BMS returns.

Can the BMS supply sensor values to the Greenheck DOAS Microprocessor Controller v6.2 (legacy points list)?

Set the sensor's source-select BV to BMS (1), then write the matching 'from BMS' AV; fans and the outdoor air damper are taken over the same way (e.g. BV-59 with AV-136 for the damper).

How do I check these points on the real DOAS Microprocessor Controller v6.2 (legacy points list)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greenheck BACnet points lists

Source: Microprocessor Controller for DOAS - Reference Guide (DOAS v6.2) · 485175 · rev. 2021-04 (Rev. 1; program version date 7/21). Object names, instances and units are reproduced as published; descriptions are our own.