Dedicated outdoor air system (DOAS) · BACnet points list

Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet BACnet points list

Updated 28 October 2026

Short answer

Greenheck's DOAS units use a factory controller that can be licensed for BACnet. The BMS mainly enables the unit, commands occupancy, resets alarms and adjusts temperature, dehumidification and airflow setpoints; it can also take over fan speeds, the outdoor air damper and sensor values. A BMS watchdog must be written regularly whenever the BMS does that, or the unit alarms and returns to local control. The points list is the same on every unit regardless of heating and cooling options.

This page lists 109 BACnet objects for the Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet — 45 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greenheck’s own free documentation, linked below.

Manufacturer
Greenheck
Model
Dedicated Outdoor Air Systems (DOAS) - BACnet
Equipment
Dedicated outdoor air system (DOAS)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
109 (45 writable)
Transport
BACnet IP
Firmware
DOAS_10.006
Also known as
Greenheck DOAS, DOAS, DOAS_10.006, 485940
Source document
BACnet Integration Guide for Dedicated Outdoor Air Systems · Document 485940 (DOAS_10.006 Rev 5) · rev. 2025-09
Download CSV 109 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet

Integration in brief

With BACnet licensed and set up on the controller, the minimum integration is to enable the unit (BV-2) and command occupancy (BV-3). Add alarm reset and global alarm monitoring, plus the temperature setpoint if needed. If the BMS will also drive fan speeds or the outdoor air damper, or send sensor values, it must keep writing the BMS watchdog, or the unit alarms and returns to local control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2System_EnableEnables or disables the unitCommand
BV 3BMS_Occupancy_CommandOccupancy; Active = Unoccupied, Inactive = OccupiedCommand
AV 1Temperature_SetpointOccupied temperature setpointCommand
BV 1BMS_WatchdogHeartbeat when BMS controls fans or sensorsCommand
BV 4Reset_All_AlarmsRemote alarm resetCommand
AV 40Unit_Status_ModeCurrent operating mode codeRead
AI 2Supply_Temp_Analog_InputSupply (discharge) air temperatureRead
BV 23Global_AlarmAny active alarmRead
IV 5LatestAlmMost recent alarm codeRead

Enable & remote start

BV-2 System_Enable enables or disables the unit from the BMS; in disabled mode some protective sequences may still run. By default occupancy is expected from BV-3 BMS_Occupancy_Command. The controller can instead be set to an internal schedule, always occupied/unoccupied, or a digital input. With warm-up/cool-down enabled, the unit recirculates after the occupied command until it reaches setpoint or the timer (default 30 min) ends.

Heartbeat & communication loss

BV-1 BMS_Watchdog must be written to True (1) regularly whenever the BMS commands fan speeds or damper positions or sends sensor values. If it stays False longer than the Timeout Delay (15 minutes, adjustable), an alarm is raised and the controller falls back to local control and local sensor values. BV-24 shows watchdog status. If the relinquish-default-on-comm-loss option is enabled, priority arrays are cleared 5 minutes after the watchdog goes inactive.

Sensors & values from the BMS

For each sensor, set its source-select binary to BMS (BV-7 to BV-16, e.g. BV-8 Outside_Temp_Source_BMS, BV-16 Space_Temp_Source_BMS). Then write the matching *_from_BMS analog (AV-26 to AV-35, e.g. AV-27 outside temp, AV-35 space temp, AV-33 space RH, AV-30/31 space CO2). The watchdog must be satisfied; if it isn't, the controller reverts to the local sensor (if installed and valid) or to local control. Fan speeds and the outdoor air damper are taken over the same way with BV-17/18/19 plus AV-36/37/38.

Network setup

Watch out for

Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

109 of 109 shown
Type
Other
Access
Show
Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet BACnet Points List
DescriptionStates
BVmin2System_EnableMaster system enable/disable commandCommandActive=Enabled; Inactive=Disabled
BVmin3BMS_Occupancy_CommandBuilding Occupancy CommandCommandActive=Unoccupied; Inactive=Occupied
BVmin4Reset_All_AlarmsAlarm Reset CommandCommandActive=Reset; Inactive=Normal
BVmin23Global_AlarmGlobal AlarmReadActive=Alarm; Inactive=Normal
AVmin1Temperature_SetpointOccupied temperature setpoint (space, return or supply); default 72°F, 50-100°F°FCommand
BV29Supply_Fan_1_Alarm.ActiveSupply Fan Alarm ActiveReadActive=Alarm; Inactive=Normal
BV30Exhaust_Fan_1_Alarm.ActiveExhaust Fan Alarm ActiveReadActive=Alarm; Inactive=Normal
BV31Drain_Pan_Alarm.ActiveCondensate drain pan alarmReadActive=Alarm; Inactive=Normal
BV32Fire_Safety_Shutdown_Alarm.ActiveFire safety shutdown alarmReadActive=Alarm; Inactive=Normal
BV33Refrigerant_Leak_Compressor_Alarm.ActiveRefrigerant leak alarm, compressor sectionReadActive=Alarm; Inactive=Normal
BV34Refrigerant_Leak_Airstream_Alarm.ActiveRefrigerant leak alarm, airstreamReadActive=Alarm; Inactive=Normal
IVmin5LatestAlmMost recent active alarm codeReadCode list in source alarm table
AV93LatestAlmMost recent active alarm codeReadCode list in source alarm table
AVmin40Unit_Status_ModeUnit Operation Mode/StateReadMode code list in source status mode table
BI1Exhaust_Fan_1_Status_Digital_InputExhaust Fan 1 StatusReadActive=Active; Inactive=Inactive
BI2Supply_Fan_1_Status_Digital_InputSupply Fan 1 StatusReadActive=Active; Inactive=Inactive
AV73Exhaust_Fan_Speed_Analog_OutputExhaust Fan Speed Analog Output%Read
AV78Outside_Air_Damper_Analog_OutputOutside Air Damper Analog Output%Read
AV79Supply_Fan_Speed_Analog_OutputSupply Fan Speed Analog Output%Read
AV42Cooling_1_Ramp_CapacityCooling Ramp 1 Status Value%Read
AV51Heating_CapacityHeating Ramp%Read
AV72Energy_Recovery_Analog_OutputEnergy Recovery Analog Output%Read
AV50HP_Ramp_CapacityHeat Pump Heating Ramp%Read
AV53Hot_Gas_Reheat_RampHot Gas Reheat Ramp%Read
AV80Modulating_Compressor_Analog_Output_BMSModulating Compressor Analog Output%Read
AV68Chilled_Water_1_Valve_Analog_OutputChilled Water 1 Valve Analog Output%Read
AV74Hot_Water_Valve_1_Analog_OutputHot Water Valve 1 Analog Output%Read
AV76Mod_Gas_Furnace_1_Analog_OutputMod Gas Furnace 1 Analog Output%Read
AV70Electric_Heater_1_Analog_OutputElectric Heater 1 Analog Output%Read
AI1Space_Temp_Analog_InputSpace Air Temperature°FRead
AImin2Supply_Temp_Analog_InputSupply(discharge) Air Temperature°FRead
AI3Outside_Air_Temp_Analog_InputOutside Air Temperature°FRead
AI4Mixed_Temp_Analog_InputMixed Air Temperature°FRead
AI5Cold_Coil_1_Temp_Analog_InputCold Coil 1 Leaving Air Temperature°FRead
AI7Return_Temp_Analog_InputReturn Air Temperature°FRead
AI8Exhaust_Temp_Analog_InputExhaust Air Temperature°FRead
AI9Space_RH_Analog_InputSpace Air Relative Humidity%RHRead
AI10Outside_RH_Analog_InputOutside Air Relative Humidity%RHRead
AI11Return_RH_Analog_InputReturn Air Relative Humidity%RHRead
AI12Return_Duct_Static_Pressure_Analog_InputReturn Duct Static Pressurein. w.c.Read
AI13Space_Static_Pressure_Analog_InputSpace Static Pressurein. w.c.Read
AI14Supply_Duct_Static_Pressure_Analog_InputSupply Duct Static Pressurein. w.c.Read
AI15Space_CO2_1_Analog_InputSpace 1 CO2 ppmppmRead
AI17Return_CO2_Analog_InputReturn CO2 ppmppmRead
AV64Total_Exhaust_Fan_CFM_BMSTotal Exhaust Fan CFMCFMRead
AV65Total_Supply_Fan_CFM_BMSTotal Supply Fan CFMCFMRead
AV66OAD_CFM_BMSOutdoor Air Damper CFMCFMRead
AV41Supply_Temperature_Calculated_SetpointActive Supply Temperature Setpoint°FRead
AV90Coil_Temperature_Calculated_SetpointCalculated Coil Leaving Set point°FRead
IV6Device_Enable_DO_WordDevice Enable DO Word (bit-packed, 32-bit)Read
AV94Device_Enable_DO_WordDevice Enable DO Word bits 0-15 (16-bit copy)Read
AV95Device_Enable_DO_WordDevice Enable DO Word bits 16-31 (16-bit copy)Read
IV7Ref_Ckt_PressTemp_Alarm_WordRefrigeration Circuit Word (bit-packed, 32-bit)Read
AV96Ref_Ckt_PressTemp_Alarm_WordRefrigeration Circuit Word bits 0-15 (16-bit copy)Read
AV97Ref_Ckt_PressTemp_Alarm_WordRefrigeration Circuit Word bits 16-31 (16-bit copy)Read
IV8Device_Offline_WordDevice Offline Word (bit-packed, 32-bit)Read
AV98Device_Offline_WordDevice Offline Word bits 0-15 (16-bit copy)Read
AV99Device_Offline_WordDevice Offline Word bits 16-31 (16-bit copy)Read
IV9Device_Alarm_WordDevice Alarm Word (bit-packed, 32-bit)Read
AV100Device_Alarm_WordDevice Alarm Word bits 0-15 (16-bit copy)Read
AV101Device_Alarm_WordDevice Alarm Word bits 16-31 (16-bit copy)Read
IV10System_WordSystem Word (bit-packed, 32-bit)Read
AV102System_WordSystem Word bits 0-15 (16-bit copy)Read
AV103System_WordSystem Word bits 16-31 (16-bit copy)Read
IV11Unit_Status_WordUnit Status Word (bit-packed, 32-bit)Read
AV104Unit_Status_WordUnit Status Word bits 0-15 (16-bit copy)Read
AV105Unit_Status_WordUnit Status Word bits 16-31 (16-bit copy)Read
IV1Temperature_Reset_ModeOccupied temperature reset modeWrite1 = No Reset; 2 = Space Reset; 3 = Return Reset; 4 = Outside Reset
AV2Temperature_Heat_Cool_DeadbandOccupied heat/cool deadband for space/return reset; default 4°F°FCommand
IV2Temperature_Reset_Mode_UnoccupiedUnoccupied temperature reset modeWrite1 = No Reset; 2 = Space Reset; 3 = Return Reset; 4 = Outside Reset
AV3Temperature_Setpoint_UnoccupiedUnoccupied temperature setpoint; default 70°F°FCommand
AV4Temperature_Heat_Cool_Deadband_UnoccupiedUnoccupied heat/cool deadband for space/return reset°FCommand
AV5Cooling_Coil_Setpoint_MinPrimary Cooling Coil Leaving Air Setpoint; default 50°F, min 46°F, max 80°F°FCommand
AV6Cooling_Coil_Setpoint_MaxMax coil leaving air setpoint when coil reset is used; default 55°F°FCommand
AV7Dehumidification_SetpointOccupied dehumidification setpoint (space or return RH); default 55%RH%RHCommand
AV11Unoccupied_Dehumidification_SetpointUnoccupied Dehumidification %RH Setpoint; default 60% RH, min 0%, max 100%%RHCommand
AV21Return_Duct_Static_Pressure_SetpointReturn Duct Static Pressure Setpoint; default -2.0, min 0.0, max -5.0in. w.c.Command
AV22Space_Static_Pressure_SetpointSpace Static Pressure Setpoint; default 0.05, min -0.5, max 0.5in. w.c.Command
AV23Supply_Duct_Static_Pressure_SetpointSupply Duct Static Pressure Setpoint; default 1.0, min 0.0, max 5.0in. w.c.Command
AV24Space_CO2_SetpointSpace CO2 Setpoint; default 1,000 ppm, min 0 ppm, max 5,000 ppmppmCommand
AV25Outside_Air_Damper_Minimum_Setpoint_OccOccupied outside air damper minimum position; default 35%%Command
BVmin1BMS_WatchdogBMS Watchdog commandCommandActive=Active; Inactive=Inactive
BV24BMS_Watchdog_ActiveStatus of the BMS watchdog pingReadActive=Active; Inactive=Inactive
BV17SF_Control_Source_BMSAllows the BMS to control supply fan speedCommandActive=BMS; Inactive=Local
AV36SF_Control_Signal_BMSSupply Fan Command Speed%Command
BV18EF_Control_Source_BMSAllows the BMS to control exhaust fan speedCommandActive=BMS; Inactive=Local
AV37EF_Control_Signal_BMSExhaust Fan Command Speed%Command
BV19OAD_Control_Source_BMSAllows the BMS to control OAD positionCommandActive=BMS; Inactive=Local
AV38OAD_Control_Signal_BMSOutside air damper position command from the BMS%Command
BV7Outside_RH_Source_BMSOutside RH Source SelectionCommandActive=BMS; Inactive=Local
BV8Outside_Temp_Source_BMSOutside Temp Source SelectionCommandActive=BMS; Inactive=Local
BV9Return_RH_Source_BMSReturn RH Source SelectionCommandActive=BMS; Inactive=Local
BV10Return_Temp_Source_BMSReturn Temp Source SelectionCommandActive=BMS; Inactive=Local
BV11Space_1_CO2_Source_BMSSpace 1 CO2 Source SelectionCommandActive=BMS; Inactive=Local
BV12Space_2_CO2_Source_BMSSpace 2 CO2 Source SelectionCommandActive=BMS; Inactive=Local
BV13Return_CO2_Source_BMSReturn CO2 Source SelectionCommandActive=BMS; Inactive=Local
BV14Space_RH_Source_BMSSpace RH Source SelectionCommandActive=BMS; Inactive=Local
BV15Space_Static_Source_BMSSpace Static Source SelectionCommandActive=BMS; Inactive=Local
BV16Space_Temp_Source_BMSSpace Temp Source SelectionCommandActive=BMS; Inactive=Local
AV26Outside_RH_from_BMSOutside RH from BMS%RHCommand
AV27Outside_Temp_from_BMSOutside Temp from BMS°FCommand
AV28Return_RH_from_BMSReturn RH from BMS%RHCommand
AV29Return_Temp_from_BMSReturn Temp from BMS°FCommand
AV30Space_1_CO2_from_BMSSpace 1 CO2 from BMSppmCommand
AV31Space_2_CO2_from_BMSSpace 2 CO2 from BMSppmCommand
AV32Return_CO2_from_BMSReturn CO2 from BMSppmCommand
AV33Space_RH_from_BMSSpace RH from BMS%RHCommand
AV34Space_Static_from_BMSSpace Static from BMSin. w.c.Command
AV35Space_Temp_from_BMSSpace Temp from BMS°FCommand

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dedicated Outdoor Air Systems (DOAS) - BACnet and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet

How many BACnet points does the Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet have?

This list has 109 BACnet objects: 15 analog inputs, 58 analog values, 2 binary inputs, 25 binary values, 9 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet BACnet points are writable?

45 of the 109 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet BACnet documentation?

The source is BACnet Integration Guide for Dedicated Outdoor Air Systems (Document 485940 (DOAS_10.006 Rev 5)), revision 2025-09, published free by Greenheck at https://content.greenheck.com/public/DAMProd/Original/10017/485940_BACnetGuide.pdf.

What are the minimum BACnet points to integrate the Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet?

Start with BV 2 System_Enable (Enables or disables the unit); BV 3 BMS_Occupancy_Command (Occupancy; Active = Unoccupied, Inactive = Occupied); AV 1 Temperature_Setpoint (Occupied temperature setpoint); BV 1 BMS_Watchdog (Heartbeat when BMS controls fans or sensors); BV 4 Reset_All_Alarms (Remote alarm reset); AV 40 Unit_Status_Mode (Current operating mode code); AI 2 Supply_Temp_Analog_Input (Supply (discharge) air temperature); BV 23 Global_Alarm (Any active alarm); IV 5 LatestAlm (Most recent alarm code).

How do I enable BMS control of the Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet?

BV-2 System_Enable enables or disables the unit from the BMS; in disabled mode some protective sequences may still run. By default occupancy is expected from BV-3 BMS_Occupancy_Command. The controller can instead be set to an internal schedule, always occupied/unoccupied, or a digital input. With warm-up/cool-down enabled, the unit recirculates after the occupied command until it reaches setpoint or the timer (default 30 min) ends.

Does the Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet need a BACnet heartbeat or have a communication timeout?

BV-1 BMS_Watchdog must be written to True (1) regularly whenever the BMS commands fan speeds or damper positions or sends sensor values. If it stays False longer than the Timeout Delay (15 minutes, adjustable), an alarm is raised and the controller falls back to local control and local sensor values. BV-24 shows watchdog status. If the relinquish-default-on-comm-loss option is enabled, priority arrays are cleared 5 minutes after the watchdog goes inactive.

Can the BMS supply sensor values to the Greenheck Dedicated Outdoor Air Systems (DOAS) - BACnet?

For each sensor, set its source-select binary to BMS (BV-7 to BV-16, e.g. BV-8 Outside_Temp_Source_BMS, BV-16 Space_Temp_Source_BMS). Then write the matching *_from_BMS analog (AV-26 to AV-35, e.g. AV-27 outside temp, AV-35 space temp, AV-33 space RH, AV-30/31 space CO2). The watchdog must be satisfied; if it isn't, the controller reverts to the local sensor (if installed and valid) or to local control. Fan speeds and the outdoor air damper are taken over the same way with BV-17/18/19 plus AV-36/37/38.

How do I check these points on the real Dedicated Outdoor Air Systems (DOAS) - BACnet?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greenheck BACnet points lists

Source: BACnet Integration Guide for Dedicated Outdoor Air Systems · Document 485940 (DOAS_10.006 Rev 5) · rev. 2025-09. Object names, instances and units are reproduced as published; descriptions are our own.