- Home
- BACnet points lists
- FläktGroup
- vQ Stream unit with Carel uPC3 controller
Air handling unit controller (Carel uPC3) · BACnet points list
FläktGroup vQ Stream unit with Carel uPC3 controller BACnet points list
Updated 12 November 2026
The vQ Stream unit's Carel uPC3 controller publishes one variable list for Modbus, BACnet IP and OPC-UA. The BACnet side has Analog, Binary, Positive Integer and Integer Values: probe readings, outputs, setpoints, fan monitoring (up to 10 supply and 10 return fans), scheduler entries, unit configuration parameters, energy values and about 1,500 alarm flags (trigger and active bits per alarm).
This page lists 2422 BACnet objects for the FläktGroup vQ Stream unit with Carel uPC3 controller — 595 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FläktGroup’s own free documentation, linked below.
- Manufacturer
- FläktGroup
- Model
- vQ Stream unit with Carel uPC3 controller
- Equipment
- Air handling unit controller (Carel uPC3)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 2422 (595 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- vQ Stream, vQ Stream uPC3, Flakt vQ Stream BMS list, Carel uPC3 vQ Stream
- Source document
- vQ Stream - Communication list for BMS (uPC3 - BMS Variable)
Reference only, provided as-is: verify against FläktGroup’s current documentation and the live device before use. Not official FläktGroup information. Terms of use.
BMS integration notes: FläktGroup vQ Stream unit with Carel uPC3 controller
Select the BACnet port (BV 1680: Ethernet or pLAN) and network settings in the controller, then command the unit with PIV 397 SetTyp work mode and the per-mode setpoints, and read supply and return temperatures, fan running flags and the global alarm. BV 845 resets alarms from the BMS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| PIV 397 | SetTyp | Work mode: 0 Off, 1 Eco, 2 Optimal, 3 Comfort, 5 Auto | Write |
| AV 207 | UnitSetP.RoomTempSetP.Comfort | Comfort room temperature setpoint, °C | Write |
| BV 845 | AlarmMng.AlrmResByBms | Alarm reset from the BMS (1 = reset) | Write |
| AV 194 | RegTemp | Current temperature setpoint value, °C | Write |
| BV 24 | RunSupplyFan | Supply fan running | Read |
| AV 36 | SupplyTemp.Val | Supply air temperature, °C | Read |
| AV 32 | RetTemp.Val | Return / room air temperature, °C | Read |
| AV 6 | ExtTemp.Val | Outdoor (external) air temperature, °C | Read |
| AV 191 | SupplyFanVal | Supply fan output, % | Read |
| BV 18 | SrsAlrm.Val | Global alarm output (printed 0 = ON) | Read |
Enable & remote start
PIV 397 SetTyp (ReadWrite) is the work-mode selection; 5 = Auto follows the unit's scheduler. The setpoints used in each mode are the UnitSetP.* AVs (Economy, Optimal/PreComfort, Comfort, Standby).
Network setup
- BV 1680 BacNetSel chooses the BACnet port: 0 = Ethernet, 1 = pLAN.
- Units of measure (international or USA) are set with IV 686 Uom_Msk; temperature and flow units follow it.
Watch out for
- Many PAR/SYS objects are configuration parameters; do not write them cyclically.
- Alarm flags come in .Trigger and .Active pairs; map one set.
FläktGroup vQ Stream unit with Carel uPC3 controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | AfterPreHeatCoilTemp.Val | IO - Probe - Temperature - After PreHeat | °C | Read | |
| BV | 1 | Cool_1.Val | IO - Digital Output - Cooler - Stage 1 | Read | 0=ON; 1=OFF | |
| BV | 2 | Cool_2.Val | IO - Digital Output - Cooler - Stage 2 | Read | 0=ON; 1=OFF | |
| BV | 3 | CoolAlrm.Val | IO - Digital Input - Cooler - Alarm | Read | ||
| BV | 4 | CoolHeat.Val | IO - Digital Output - Heating - Signal | Read | 0=ON; 1=OFF | |
| AV | 2 | CoolVlv.Val | IO - Analog Output - Cooling (0 - 100 %) | % | Read | |
| BV | 5 | DoubleDamp.Val | IO - Digital Output - Damper - Redundant | Read | 0=ON; 1=OFF | |
| BV | 6 | ExhAirDamp.Val | IO - Digital Output - Damper - Supply | Read | 0=ON; 1=OFF | |
| AV | 3 | ExhAirFlow | IO - Probe - Air Flow - Return (For airflow < 32767) | m3/h | Read | |
| AV | 4 | ExhAirP_Val | IO - Probe - Pressure - Return | Pa | Read | |
| AV | 5 | ExhTemp.Val | IO - Probe - Temperature - Recovery | °C | Read | |
| AVmin | 6 | ExtTemp.Val | IO - Probe - Temperature - External | °C | Read | |
| BV | 7 | FireAlrm.Val | IO - Digital Input - Fire - Alarm | Read | ||
| BV | 8 | Heat_1.Val | IO - Digital Output - Heater - Stage 1 | Read | 0=ON; 1=OFF | |
| BV | 9 | Heat_2.Val | IO - Digital Output - Heater - Stage 2 | Read | 0=ON; 1=OFF | |
| AV | 7 | HeatRecovery_Val | IO - Analog Output - Rotary - Value (0 - 100 %) | % | Read | |
| AV | 8 | HeatVlv.Val | IO - Analog Output - Heater (0 - 100 %) | % | Read | |
| BV | 10 | Hum.Val | IO - Digital Output - Humidifier | Read | 0=ON; 1=OFF | |
| AV | 9 | Hum_THTN_1 | IO - Probe - Humidity - TH Room (0 - 100 %) | % | Read | |
| BV | 11 | HumAlrm.Val | IO - Digital Input - Humidifier - Alarm | Read | ||
| BV | 12 | ID2_Alrm.Val | IO - Digital Input - Freeze - Alarm | Read | ||
| AV | 10 | MB_Devices.MB_MainBoard_1.AI_Temp_Fan_Return | IO - Module IO - Temperature Fan Return | °C | Read | |
| AV | 11 | MB_Devices.MB_MainBoard_1.AI_Temp_Fan_Supply | IO - Module IO - Temperature Fan Supply | °C | Read | |
| AV | 12 | MB_Devices.MB_MainBoard_1.AO_01_Read | IO - Module IO - Analog output 1 | % | Read | |
| AV | 13 | MB_Devices.MB_MainBoard_1.AO_02_Read | IO - Module IO - Analog output 2 | % | Read | |
| AV | 14 | MB_Devices.MB_MainBoard_1.AO_03_Read | IO - Module IO - Analog output 3 | % | Read | |
| AV | 15 | MB_Devices.MB_MainBoard_1.AO_04_Read | IO - Module IO - Analog output 4 | % | Read | |
| AV | 16 | MB_Devices.MB_MainBoard_1.Humid_Return | IO - Module IO - Humidity Return | % | Read | |
| AV | 17 | MB_Devices.MB_MainBoard_1.Pressure_Fan_Return | IO - Module IO - Pressure Fan Return | Pa | Read | |
| AV | 18 | MB_Devices.MB_MainBoard_1.Pressure_Fan_Supply | IO - Module IO - Pressure Fan Supply | Pa | Read | |
| AV | 19 | MB_Devices.MB_MainBoard_1.Pressure_Filter_Return | IO - Module IO - Pressure Filter Return | Pa | Read | |
| AV | 20 | MB_Devices.MB_MainBoard_1.Pressure_Filter_Supply | IO - Module IO - Pressure Filter Supply | Pa | Read | |
| AV | 21 | MB_Devices.MB_MainBoard_1.Supply_24V_Read | IO - Module IO - Supply 24V | V | Read | |
| AV | 22 | MB_Devices.MB_MainBoard_1.Supply_Control_Read | IO - Module IO - Supply Controller | V | Read | |
| AV | 23 | MB_Devices.MB_MainBoard_1.Temp_Return | IO - Module IO - Temperature Return | °C | Read | |
| AV | 24 | MixDampReq_Fresh | IO - Analog Output - Damper - External (0 - 100 %) | % | Read | |
| AV | 25 | ModulHum.Val | IO - Analog Output - Humidifier (0 - 100 %) | % | Read | |
| AV | 26 | ModulMixDamp_Val | IO - Analog Output - Damper - Mixing (0 - 100 %) | % | Read | |
| AV | 27 | ModulPreHeat.Val | IO - Analog Output - PreHeater (0 - 100 %) | % | Read | |
| BV | 13 | PreHeaterPump.Val | IO - Digital Output - PreHeater | Read | 0=ON; 1=OFF | |
| BV | 14 | RecoveryPump.Val | IO - Digital Output - Recovery | Read | 0=ON; 1=OFF | |
| AV | 28 | RecSupplyTemp.Val | IO - Probe - Temperature - Supply after recovery | °C | Read | |
| BV | 15 | ReHeat.Val | IO - Digital Output - ReHeater | Read | 0=ON; 1=OFF | |
| AV | 29 | ReHeatVlv.Val | IO - Analog Output - ReHeater (0 - 100 %) | % | Read | |
| BV | 16 | RemoteOn.Val | IO - Digital Input - Remote - ON | Read | ||
| AV | 30 | RetAir_CO2_Val | IO - Probe - CO2 - Return | ppm | Read | |
| BV | 17 | RetFilter.Val | IO - Digital Input - Filter - Return | Read | ||
| AV | 31 | RetHum_Val | IO - Probe - Humidity - Return (0 - 100 %) | % | Read | |
| AVmin | 32 | RetTemp.Val | IO - Probe - Temperature - Return / Room | °C | Read | |
| BVmin | 18 | SrsAlrm.Val | IO - Digital Output - Alarm - Global | Read | 0=ON; 1=OFF | |
| AV | 33 | SupplyAirFlow | IO - Probe - Air Flow - Supply (For airflow < 32767) | m3/h | Read | |
| AV | 34 | SupplyAirP_Val | IO - Probe - Pressure - Supply | Pa | Read | |
| BV | 19 | SupplyFilter.Val | IO - Digital Input - Filter - Supply | Read | ||
| AV | 35 | SupplyHum_Val | IO - Probe - Humidity - Supply (0 - 100 %) | % | Read | |
| AVmin | 36 | SupplyTemp.Val | IO - Probe - Temperature - Supply | °C | Read | |
| AV | 37 | Temp_THTN_1 | IO - Probe - Temperature - TH Room | °C | Read | |
| AV | 38 | W_HeatCoilTemp.Val | IO - Probe - Temperature - Water Heat | °C | Read | |
| AV | 39 | W_PreHeatCoilTemp.Val | IO - Probe - Temperature - Water PreHeat | °C | Read | |
| BV | 20 | WinSum.Val | IO - Digital Input - Winter / Summer | Read | ||
| AV | 40 | Y1Out_HW | IO - Analog Output - Y1 (0 - 100 %) | % | Read | |
| AV | 41 | Y2Out_HW | IO - Analog Output - Y2 (0 - 100 %) | % | Read | |
| AV | 42 | Y3Out_HW | IO - Analog Output - Y3 (0 - 100 %) | % | Read | |
| BV | 21 | UnitCoolHeatMode | MO - Unit - Cooling / Heating | Write | 0=Cooling; 1=Heating | |
| AV | 43 | ExhFan_1.Current | MO - Fan - Return 1 - Current | A | Read | |
| AV | 44 | ExhFan_1.DriveTemp | MO - Fan - Return 1 - Drive temperature (USA) | °C | Read | |
| AV | 45 | ExhFan_1.Freq | MO - Fan - Return 1 - Frequence | Hz | Read | |
| AV | 46 | ExhFan_1.kWh | MO - Fan - Return 1 - Consumption (USA) | kWh | Read | |
| AV | 47 | ExhFan_1.Power | MO - Fan - Return 1 - Power | W | Read | |
| AV | 48 | ExhFan_1.Rpm | MO - Fan - Return 1 - Speed | RPM | Read | |
| AV | 49 | ExhFan_1.Voltage | MO - Fan - Return 1 - Voltage | V | Read | |
| AV | 50 | ExhFan_10.Current | MO - Fan - Return 10 - Current | A | Read | |
| AV | 51 | ExhFan_10.DriveTemp | MO - Fan - Return 10 - Drive temperature (USA) | °C | Read | |
| AV | 52 | ExhFan_10.Freq | MO - Fan - Return 10 - Frequence | Hz | Read | |
| AV | 53 | ExhFan_10.kWh | MO - Fan - Return 10 - Consumption (USA) | kWh | Read | |
| AV | 54 | ExhFan_10.Power | MO - Fan - Return 10 - Power | W | Read | |
| AV | 55 | ExhFan_10.Rpm | MO - Fan - Return 10 - Speed | RPM | Read | |
| AV | 56 | ExhFan_10.Voltage | MO - Fan - Return 10 - Voltage | V | Read | |
| AV | 57 | ExhFan_2.Current | MO - Fan - Return 2 - Current | A | Read | |
| AV | 58 | ExhFan_2.DriveTemp | MO - Fan - Return 2 - Drive temperature (USA) | °C | Read | |
| AV | 59 | ExhFan_2.Freq | MO - Fan - Return 2 - Frequence | Hz | Read | |
| AV | 60 | ExhFan_2.kWh | MO - Fan - Return 2 - Consumption (USA) | kWh | Read | |
| AV | 61 | ExhFan_2.Power | MO - Fan - Return 2 - Power | W | Read | |
| AV | 62 | ExhFan_2.Rpm | MO - Fan - Return 2 - Speed | RPM | Read | |
| AV | 63 | ExhFan_2.Voltage | MO - Fan - Return 2 - Voltage | V | Read | |
| AV | 64 | ExhFan_3.Current | MO - Fan - Return 3 - Current | A | Read | |
| AV | 65 | ExhFan_3.DriveTemp | MO - Fan - Return 3 - Drive temperature (USA) | °C | Read | |
| AV | 66 | ExhFan_3.Freq | MO - Fan - Return 3 - Frequence | Hz | Read | |
| AV | 67 | ExhFan_3.kWh | MO - Fan - Return 3 - Consumption (USA) | kWh | Read | |
| AV | 68 | ExhFan_3.Power | MO - Fan - Return 3 - Power | W | Read | |
| AV | 69 | ExhFan_3.Rpm | MO - Fan - Return 3 - Speed | RPM | Read | |
| AV | 70 | ExhFan_3.Voltage | MO - Fan - Return 3 - Voltage | V | Read | |
| AV | 71 | ExhFan_4.Current | MO - Fan - Return 4 - Current | A | Read | |
| AV | 72 | ExhFan_4.DriveTemp | MO - Fan - Return 4 - Drive temperature (USA) | °C | Read | |
| AV | 73 | ExhFan_4.Freq | MO - Fan - Return 4 - Frequence | Hz | Read | |
| AV | 74 | ExhFan_4.kWh | MO - Fan - Return 4 - Consumption (USA) | kWh | Read | |
| AV | 75 | ExhFan_4.Power | MO - Fan - Return 4 - Power | W | Read | |
| AV | 76 | ExhFan_4.Rpm | MO - Fan - Return 4 - Speed | RPM | Read | |
| AV | 77 | ExhFan_4.Voltage | MO - Fan - Return 4 - Voltage | V | Read | |
| AV | 78 | ExhFan_5.Current | MO - Fan - Return 5 - Current | A | Read | |
| AV | 79 | ExhFan_5.DriveTemp | MO - Fan - Return 5 - Drive temperature (USA) | °C | Read | |
| AV | 80 | ExhFan_5.Freq | MO - Fan - Return 5 - Frequence | Hz | Read | |
| AV | 81 | ExhFan_5.kWh | MO - Fan - Return 5 - Consumption (USA) | kWh | Read | |
| AV | 82 | ExhFan_5.Power | MO - Fan - Return 5 - Power | W | Read | |
| AV | 83 | ExhFan_5.Rpm | MO - Fan - Return 5 - Speed | RPM | Read | |
| AV | 84 | ExhFan_5.Voltage | MO - Fan - Return 5 - Voltage | V | Read | |
| AV | 85 | ExhFan_6.Current | MO - Fan - Return 6 - Current | A | Read | |
| AV | 86 | ExhFan_6.DriveTemp | MO - Fan - Return 6 - Drive temperature (USA) | °C | Read | |
| AV | 87 | ExhFan_6.Freq | MO - Fan - Return 6 - Frequence | Hz | Read | |
| AV | 88 | ExhFan_6.kWh | MO - Fan - Return 6 - Consumption (USA) | kWh | Read | |
| AV | 89 | ExhFan_6.Power | MO - Fan - Return 6 - Power | W | Read | |
| AV | 90 | ExhFan_6.Rpm | MO - Fan - Return 6 - Speed | RPM | Read | |
| AV | 91 | ExhFan_6.Voltage | MO - Fan - Return 6 - Voltage | V | Read | |
| AV | 92 | ExhFan_7.Current | MO - Fan - Return 7 - Current | A | Read | |
| AV | 93 | ExhFan_7.DriveTemp | MO - Fan - Return 7 - Drive temperature (USA) | °C | Read | |
| AV | 94 | ExhFan_7.Freq | MO - Fan - Return 7 - Frequence | Hz | Read | |
| AV | 95 | ExhFan_7.kWh | MO - Fan - Return 7 - Consumption (USA) | kWh | Read | |
| AV | 96 | ExhFan_7.Power | MO - Fan - Return 7 - Power | W | Read | |
| AV | 97 | ExhFan_7.Rpm | MO - Fan - Return 7 - Speed | RPM | Read | |
| AV | 98 | ExhFan_7.Voltage | MO - Fan - Return 7 - Voltage | V | Read | |
| AV | 99 | ExhFan_8.Current | MO - Fan - Return 8 - Current | A | Read | |
| AV | 100 | ExhFan_8.DriveTemp | MO - Fan - Return 8 - Drive temperature (USA) | °C | Read | |
| AV | 101 | ExhFan_8.Freq | MO - Fan - Return 8 - Frequence | Hz | Read | |
| AV | 102 | ExhFan_8.kWh | MO - Fan - Return 8 - Consumption (USA) | kWh | Read | |
| AV | 103 | ExhFan_8.Power | MO - Fan - Return 8 - Power | W | Read | |
| AV | 104 | ExhFan_8.Rpm | MO - Fan - Return 8 - Speed | RPM | Read | |
| AV | 105 | ExhFan_8.Voltage | MO - Fan - Return 8 - Voltage | V | Read | |
| AV | 106 | ExhFan_9.Current | MO - Fan - Return 9 - Current | A | Read | |
| AV | 107 | ExhFan_9.DriveTemp | MO - Fan - Return 9 - Drive temperature (USA) | °C | Read | |
| AV | 108 | ExhFan_9.Freq | MO - Fan - Return 9 - Frequence | Hz | Read | |
| AV | 109 | ExhFan_9.kWh | MO - Fan - Return 9 - Consumption (USA) | kWh | Read | |
| AV | 110 | ExhFan_9.Power | MO - Fan - Return 9 - Power | W | Read | |
| AV | 111 | ExhFan_9.Rpm | MO - Fan - Return 9 - Speed | RPM | Read | |
| AV | 112 | ExhFan_9.Voltage | MO - Fan - Return 9 - Voltage | V | Read | |
| AV | 113 | ExhFanVal | MO - Fan - Return - Value (0 - 100 %) | % | Read | |
| BV | 22 | MixAirDamp_On | MO - Damper Mixing - On | Read | ||
| AV | 114 | Rotary.Current | MO - Recovery - Rotary - Current | A | Read | |
| AV | 115 | Rotary.DriveTemp | MO - Recovery - Rotary - Drive temperature (USA) | °C | Read | |
| AV | 116 | Rotary.Freq | MO - Recovery - Rotary - Frequence | Hz | Read | |
| AV | 117 | Rotary.kWh | MO - Recovery - Rotary - Consumption (USA) | kWh | Read | |
| AV | 118 | Rotary.Power | MO - Recovery - Rotary - Power | W | Read | |
| AV | 119 | Rotary.Rpm | MO - Recovery - Rotary - Speed | RPM | Read | |
| AV | 120 | Rotary.Voltage | MO - Recovery - Rotary - Voltage | V | Read | |
| BV | 23 | RunExhFan | MO - Fan - Return - On | Read | ||
| BVmin | 24 | RunSupplyFan | MO - Fan - Supply - On | Read | ||
| AV | 121 | SupplyFan_1.Current | MO - Fan - Supply 1 - Current | A | Read | |
| AV | 122 | SupplyFan_1.DriveTemp | MO - Fan - Supply 1 - Drive temperature (USA) | °C | Read | |
| AV | 123 | SupplyFan_1.Freq | MO - Fan - Supply 1 - Frequence | Hz | Read | |
| AV | 124 | SupplyFan_1.kWh | MO - Fan - Supply 1 - Consumption (USA) | kWh | Read | |
| AV | 125 | SupplyFan_1.Power | MO - Fan - Supply 1 - Power | W | Read | |
| AV | 126 | SupplyFan_1.Rpm | MO - Fan - Supply 1 - Speed | RPM | Read | |
| AV | 127 | SupplyFan_1.Voltage | MO - Fan - Supply 1 - Voltage | V | Read | |
| AV | 128 | SupplyFan_10.Current | MO - Fan - Supply 10 - Current | A | Read | |
| AV | 129 | SupplyFan_10.DriveTemp | MO - Fan - Supply 10 - Drive temperature (USA) | °C | Read | |
| AV | 130 | SupplyFan_10.Freq | MO - Fan - Supply 10 - Frequence | Hz | Read | |
| AV | 131 | SupplyFan_10.kWh | MO - Fan - Supply 10 - Consumption (USA) | kWh | Read | |
| AV | 132 | SupplyFan_10.Power | MO - Fan - Supply 10 - Power | W | Read | |
| AV | 133 | SupplyFan_10.Rpm | MO - Fan - Supply 10 - Speed | RPM | Read | |
| AV | 134 | SupplyFan_10.Voltage | MO - Fan - Supply 10 - Voltage | V | Read | |
| AV | 135 | SupplyFan_2.Current | MO - Fan - Supply 2 - Current | A | Read | |
| AV | 136 | SupplyFan_2.DriveTemp | MO - Fan - Supply 2 - Drive temperature (USA) | °C | Read | |
| AV | 137 | SupplyFan_2.Freq | MO - Fan - Supply 2 - Frequence | Hz | Read | |
| AV | 138 | SupplyFan_2.kWh | MO - Fan - Supply 2 - Consumption (USA) | kWh | Read | |
| AV | 139 | SupplyFan_2.Power | MO - Fan - Supply 2 - Power | W | Read | |
| AV | 140 | SupplyFan_2.Rpm | MO - Fan - Supply 2 - Speed | RPM | Read | |
| AV | 141 | SupplyFan_2.Voltage | MO - Fan - Supply 2 - Voltage | V | Read | |
| AV | 142 | SupplyFan_3.Current | MO - Fan - Supply 3 - Current | A | Read | |
| AV | 143 | SupplyFan_3.DriveTemp | MO - Fan - Supply 3 - Drive temperature (USA) | °C | Read | |
| AV | 144 | SupplyFan_3.Freq | MO - Fan - Supply 3 - Frequence | Hz | Read | |
| AV | 145 | SupplyFan_3.kWh | MO - Fan - Supply 3 - Consumption (USA) | kWh | Read | |
| AV | 146 | SupplyFan_3.Power | MO - Fan - Supply 3 - Power | W | Read | |
| AV | 147 | SupplyFan_3.Rpm | MO - Fan - Supply 3 - Speed | RPM | Read | |
| AV | 148 | SupplyFan_3.Voltage | MO - Fan - Supply 3 - Voltage | V | Read | |
| AV | 149 | SupplyFan_4.Current | MO - Fan - Supply 4 - Current | A | Read | |
| AV | 150 | SupplyFan_4.DriveTemp | MO - Fan - Supply 4 - Drive temperature (USA) | °C | Read | |
| AV | 151 | SupplyFan_4.Freq | MO - Fan - Supply 4 - Frequence | Hz | Read | |
| AV | 152 | SupplyFan_4.kWh | MO - Fan - Supply 4 - Consumption (USA) | kWh | Read | |
| AV | 153 | SupplyFan_4.Power | MO - Fan - Supply 4 - Power | W | Read | |
| AV | 154 | SupplyFan_4.Rpm | MO - Fan - Supply 4 - Speed | RPM | Read | |
| AV | 155 | SupplyFan_4.Voltage | MO - Fan - Supply 4 - Voltage | V | Read | |
| AV | 156 | SupplyFan_5.Current | MO - Fan - Supply 5 - Current | A | Read | |
| AV | 157 | SupplyFan_5.DriveTemp | MO - Fan - Supply 5 - Drive temperature (USA) | °C | Read | |
| AV | 158 | SupplyFan_5.Freq | MO - Fan - Supply 5 - Frequence | Hz | Read | |
| AV | 159 | SupplyFan_5.kWh | MO - Fan - Supply 5 - Consumption (USA) | kWh | Read | |
| AV | 160 | SupplyFan_5.Power | MO - Fan - Supply 5 - Power | W | Read | |
| AV | 161 | SupplyFan_5.Rpm | MO - Fan - Supply 5 - Speed | RPM | Read | |
| AV | 162 | SupplyFan_5.Voltage | MO - Fan - Supply 5 - Voltage | V | Read | |
| AV | 163 | SupplyFan_6.Current | MO - Fan - Supply 6 - Current | A | Read | |
| AV | 164 | SupplyFan_6.DriveTemp | MO - Fan - Supply 6 - Drive temperature (USA) | °C | Read | |
| AV | 165 | SupplyFan_6.Freq | MO - Fan - Supply 6 - Frequence | Hz | Read | |
| AV | 166 | SupplyFan_6.kWh | MO - Fan - Supply 6 - Consumption (USA) | kWh | Read | |
| AV | 167 | SupplyFan_6.Power | MO - Fan - Supply 6 - Power | W | Read | |
| AV | 168 | SupplyFan_6.Rpm | MO - Fan - Supply 6 - Speed | RPM | Read | |
| AV | 169 | SupplyFan_6.Voltage | MO - Fan - Supply 6 - Voltage | V | Read | |
| AV | 170 | SupplyFan_7.Current | MO - Fan - Supply 7 - Current | A | Read | |
| AV | 171 | SupplyFan_7.DriveTemp | MO - Fan - Supply 7 - Drive temperature (USA) | °C | Read | |
| AV | 172 | SupplyFan_7.Freq | MO - Fan - Supply 7 - Frequence | Hz | Read | |
| AV | 173 | SupplyFan_7.kWh | MO - Fan - Supply 7 - Consumption (USA) | kWh | Read | |
| AV | 174 | SupplyFan_7.Power | MO - Fan - Supply 7 - Power | W | Read | |
| AV | 175 | SupplyFan_7.Rpm | MO - Fan - Supply 7 - Speed | RPM | Read | |
| AV | 176 | SupplyFan_7.Voltage | MO - Fan - Supply 7 - Voltage | V | Read | |
| AV | 177 | SupplyFan_8.Current | MO - Fan - Supply 8 - Current | A | Read | |
| AV | 178 | SupplyFan_8.DriveTemp | MO - Fan - Supply 8 - Drive temperature (USA) | °C | Read | |
| AV | 179 | SupplyFan_8.Freq | MO - Fan - Supply 8 - Frequence | Hz | Read | |
| AV | 180 | SupplyFan_8.kWh | MO - Fan - Supply 8 - Consumption (USA) | kWh | Read | |
| AV | 181 | SupplyFan_8.Power | MO - Fan - Supply 8 - Power | W | Read | |
| AV | 182 | SupplyFan_8.Rpm | MO - Fan - Supply 8 - Speed | RPM | Read | |
| AV | 183 | SupplyFan_8.Voltage | MO - Fan - Supply 8 - Voltage | V | Read | |
| AV | 184 | SupplyFan_9.Current | MO - Fan - Supply 9 - Current | A | Read | |
| AV | 185 | SupplyFan_9.DriveTemp | MO - Fan - Supply 9 - Drive temperature (USA) | °C | Read | |
| AV | 186 | SupplyFan_9.Freq | MO - Fan - Supply 9 - Frequence | Hz | Read | |
| AV | 187 | SupplyFan_9.kWh | MO - Fan - Supply 9 - Consumption (USA) | kWh | Read | |
| AV | 188 | SupplyFan_9.Power | MO - Fan - Supply 9 - Power | W | Read | |
| AV | 189 | SupplyFan_9.Rpm | MO - Fan - Supply 9 - Speed | RPM | Read | |
| AV | 190 | SupplyFan_9.Voltage | MO - Fan - Supply 9 - Voltage | V | Read | |
| AVmin | 191 | SupplyFanVal | MO - Fan - Supply - Value (0 - 100 %) | % | Read | |
| BV | 25 | UnitOff | MO - Unit - On | Read | ||
| BV | 26 | UnitOn | MO - Unit - Off | Read | ||
| AV | 192 | ExhFan_1_Power | MO - Fan - Return - Power | W | Read | |
| AV | 193 | SupplyFan_1_Power | MO - Fan - Supply - Power | W | Read | |
| PIV | 384 | HC_Cool_1.Hrs | CT - Counter - Cooling - Device 1 (0 - 999999) | h | Read | |
| PIV | 385 | HC_Cool_2.Hrs | CT - Counter - Cooling - Device 2 (0 - 999999) | h | Read | |
| PIV | 386 | HC_ExhFan_1.Hrs | CT - Counter - Fan - Return 1 (0 - 999999) | h | Read | |
| PIV | 387 | HC_ExhFan_2.Hrs | CT - Counter - Fan - Return 2 (0 - 999999) | h | Read | |
| PIV | 388 | HC_Heat_1.Hrs | CT - Counter - Heating - Device 1 (0 - 999999) | h | Read | |
| PIV | 389 | HC_Heat_2.Hrs | CT - Counter - Heating - Device 2 (0 - 999999) | h | Read | |
| PIV | 390 | HC_Heat_Mod.Hrs | CT - Counter - Heating - Modulation (0 - 999999) | h | Read | |
| PIV | 391 | HC_Hum.Hrs | CT - Counter - Humidity (0 - 999999) | h | Read | |
| PIV | 392 | HC_PreHeat.Hrs | CT - Counter - PreHeating (0 - 999999) | h | Read | |
| PIV | 393 | HC_RecoveryPump.Hrs | CT - Counter - Recovery (0 - 999999) | h | Read | |
| PIV | 394 | HC_ReHeat.Hrs | CT - Counter - ReHeating (0 - 999999) | h | Read | |
| PIV | 395 | HC_SupplyFan_1.Hrs | CT - Counter - Fan - Supply 1 (0 - 999999) | h | Read | |
| PIV | 396 | HC_SupplyFan_2.Hrs | CT - Counter - Fan - Supply 2 (0 - 999999) | h | Read | |
| AVmin | 194 | RegTemp | SP - Setpoint - Temperature - Current - Value | °C | Write | |
| PIVmin | 397 | SetTyp | SP - Work Mode | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT; 4=STANDBY; 5=AUTO | |
| AV | 195 | UnitSetP.AirFlwSetP.Comfort | SP - Setpoint - Air Flow - Supply - 3 - Comfort (0 - 100 %) | % | Write | |
| AV | 196 | UnitSetP.AirFlwSetP.Economy | SP - Setpoint - Air Flow - Supply - 1 - Economy (0 - 100 %) | % | Write | |
| AV | 197 | UnitSetP.AirFlwSetP.PreComfort | SP - Setpoint - Air Flow - Supply - 2 - Optimal (0 - 100 %) | % | Write | |
| AV | 198 | UnitSetP.AirQualitySetP.Comfort | SP - Setpoint - Air Quality - 3 - Comfort | ppm | Write | |
| AV | 199 | UnitSetP.AirQualitySetP.Economy | SP - Setpoint - Air Quality - 1 - Economy | ppm | Write | |
| AV | 200 | UnitSetP.AirQualitySetP.PreComfort | SP - Setpoint - Air Quality - 2 - Optimal | ppm | Write | |
| AV | 201 | UnitSetP.HumSetP.Comfort | SP - Setpoint - Humidity - 3 - Comfort (0 - 100 %) | % | Write | |
| AV | 202 | UnitSetP.HumSetP.Economy | SP - Setpoint - Humidity - 1 - Economy (0 - 100 %) | % | Write | |
| AV | 203 | UnitSetP.HumSetP.PreComfort | SP - Setpoint - Humidity - 2 - Optimal (0 - 100 %) | % | Write | |
| AV | 204 | UnitSetP.RetAirFlwSetP.Comfort | SP - Setpoint - Air Flow - Return - 3 - Comfort (0 - 100 %) | % | Write | |
| AV | 205 | UnitSetP.RetAirFlwSetP.Economy | SP - Setpoint - Air Flow - Return - 1 - Economy (0 - 100 %) | % | Write | |
| AV | 206 | UnitSetP.RetAirFlwSetP.PreComfort | SP - Setpoint - Air Flow - Return - 2 - Optimal (0 - 100 %) | % | Write | |
| AVmin | 207 | UnitSetP.RoomTempSetP.Comfort | SP - Setpoint - Temperature - Room - 3 - Comfort | °C | Write | |
| AV | 208 | UnitSetP.RoomTempSetP.Economy | SP - Setpoint - Temperature - Room - 1 - Economy | °C | Write | |
| AV | 209 | UnitSetP.RoomTempSetP.PreComfort | SP - Setpoint - Temperature - Room - 2 - Optimal | °C | Write | |
| AV | 210 | ActualSet | SP - Setpoint - Temperature - Actual | °C | Read | |
| AV | 211 | CurrAirFlwSetP_Val | SP - Setpoint - Air Flow - Supply - Current - Value (0 - 100 %) | % | Read | |
| AV | 212 | CurrAirQualitySetP_Val | SP - Setpoint - Air Quality - Current - Value | ppm | Read | |
| AV | 213 | CurrHumSetP_Val | SP - Setpoint - Humidity - Current - Value (0 - 100 %) | % | Read | |
| AV | 214 | CurrRetAirFlwSetP_Val | SP - Setpoint - Air Flow - Return - Current - Value (0 - 100 %) | % | Read | |
| AV | 215 | CurrRoomTempSetP_Val | SP - Setpoint - Temperature - Room - Current - Value | °C | Read | |
| AV | 216 | UnitSetP_AirFlwSetP_Comfort | SP - Setpoint - Air Flow - Supply - 3 - Comfort (Actual) (0 - 100 | % | Read | |
| AV | 217 | UnitSetP_AirFlwSetP_Comfort_2 | SP - Setpoint - Air Flow - Return - 3 - Comfort (Actual) (0 - 100 | % | Read | |
| AV | 218 | UnitSetP_AirFlwSetP_Economy | SP - Setpoint - Air Flow - Supply - 1 - Economy (Actual) (0 - 100 | % | Read | |
| AV | 219 | UnitSetP_AirFlwSetP_Economy_2 | SP - Setpoint - Air Flow - Return - 1 - Economy (Actual) (0 - 100 | % | Read | |
| AV | 220 | UnitSetP_AirFlwSetP_PreComfort | SP - Setpoint - Air Flow - Supply - 2 - Optimal (Actual) (0 - 100 | % | Read | |
| AV | 221 | UnitSetP_AirFlwSetP_PreComfort_2 | SP - Setpoint - Air Flow - Return - 2 - Optimal (Actual) (0 - 100 | % | Read | |
| AV | 222 | RecHeat_PowerTemp_T_kWh | ECO - Power Cool | kW | Read | |
| AV | 223 | RecCool_PowerTemp_T_kWh | ECO - Power Cool | kWh | Read | |
| AV | 224 | Heat_PowerTemp_T_kWh | ECO - Power Cost - Constant | kWh | Read | |
| AV | 225 | Cool_PowerTemp_T_kWh | ECO - Power Cost - Constant - Mode ECO | kWh | Read | |
| AV | 226 | PowerElect_T_kWh_ECO | ECO - Power Cost - Constant - Mode Optimal | kWh | Read | |
| AV | 227 | PowerElect_T_kWh_Optimal | ECO - Power Cost - Constant - Mode Comfort | kWh | Read | |
| AV | 228 | PowerElect_T_kWh_Comfort | ECO - Power Cost | kWh | Read | |
| AV | 229 | SupplyFan_Power_E1 | ECO - Power Cost - Mode ECO | kWh | Read | |
| AV | 230 | ReturnFan_Power_E1 | ECO - Power Cost - Mode Optimal | kWh | Read | |
| PIV | 398 | HC_Mode_ECO | ECO - Power Cost - Mode Comfort | kWh | Read | |
| PIV | 399 | HC_Mode_Comfort | ECO - Power Heat | kW | Read | |
| PIV | 400 | HC_Mode_Optimal | ECO - Power Heat kWh | kWh | Read | |
| AV | 231 | RecHeat_PowerTemp | ECO | kWh | Read | |
| AV | 232 | RecCool_PowerTemp | ECO | kWh | Read | |
| AV | 233 | Heat_PowerTemp | ECO | kWh | Read | |
| AV | 234 | Cool_PowerTemp | ECO | kWh | Read | |
| AV | 235 | RecHeat_PowerTemp_kWh | ECO | kWh | Read | |
| AV | 236 | RecCool_PowerTemp_kWh | ECO | kW | Read | |
| AV | 237 | Heat_PowerTemp_kWh | ECO | kWh | Read | |
| AV | 238 | Cool_PowerTemp_kWh | ECO | kW | Read | |
| AV | 239 | Recovery_Efficency | ECO | kWh | Read | |
| BV | 27 | SchedOn | SCH - Scheduller - On | Write | 0=OFF; 1=ON | |
| IV | 401 | Scheduler_OnOffUnit.Scheduler_1.CopyTo_Day | SCH - Scheduller - Time Band - Copy to Day | Write | 0=MON; 1=TUE; 2=WED; 3=THU; 4=FRI; 5=SAT; 6=SUN; 7=ALL | |
| IV | 402 | Scheduler_OnOffUnit.Scheduler_1.Day | SCH - Scheduller - Time Band - Day | Write | 0=MON; 1=TUE; 2=WED; 3=THU; 4=FRI; 5=SAT; 6=SUN | |
| BV | 28 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].Enabled | SCH - Scheduller - Monday - 1 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 29 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].Flag_Enabled | SCH - Scheduller - Monday - 1 - Flag_Enabled | Write | ||
| PIV | 403 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].Hours | SCH - Scheduller - Monday - 1 - Hours (00-23) | h | Write | |
| PIV | 404 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].Mins | SCH - Scheduller - Monday - 1 - Mins (0 - 59) | min. | Write | |
| PIV | 405 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].UnitStatus | SCH - Scheduller - Monday - 1 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 30 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].Enabled | SCH - Scheduller - Monday - 2 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 31 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].Flag_Enabled | SCH - Scheduller - Monday - 2 - Flag_Enabled | Write | ||
| PIV | 406 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].Hours | SCH - Scheduller - Monday - 2 - Hours (0 - 23) | h | Write | |
| PIV | 407 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].Mins | SCH - Scheduller - Monday - 2 - Mins (0 - 59) | min. | Write | |
| PIV | 408 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].UnitStatus | SCH - Scheduller - Monday - 2 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 32 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].Enabled | SCH - Scheduller - Monday - 3 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 33 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].Flag_Enabled | SCH - Scheduller - Monday - 3 - Flag_Enabled | Write | ||
| PIV | 409 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].Hours | SCH - Scheduller - Monday - 3 - Hours (0 - 23) | h | Write | |
| PIV | 410 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].Mins | SCH - Scheduller - Monday - 3 - Mins (0 - 59) | min. | Write | |
| PIV | 411 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].UnitStatus | SCH - Scheduller - Monday - 3 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 34 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].Enabled | SCH - Scheduller - Monday - 4 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 35 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].Flag_Enabled | SCH - Scheduller - Monday - 4 - Flag_Enabled | Write | ||
| PIV | 412 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].Hours | SCH - Scheduller - Monday - 4 - Hours (0 - 23) | h | Write | |
| PIV | 413 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].Mins | SCH - Scheduller - Monday - 4 - Mins (0 - 59) | min. | Write | |
| PIV | 414 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].UnitStatus | SCH - Scheduller - Monday - 4 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 36 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].Enabled | SCH - Scheduller - Tuesday - 1 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 37 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].Flag_Enabled | SCH - Scheduller - Tuesday - 1 - Flag_Enabled | Write | ||
| PIV | 415 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].Hours | SCH - Scheduller - Tuesday - 1 - Hours (0 - 23) | h | Write | |
| PIV | 416 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].Mins | SCH - Scheduller - Tuesday - 1 - Mins (0 - 59) | min. | Write | |
| PIV | 417 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].UnitStatus | SCH - Scheduller - Tuesday - 1 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 38 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].Enabled | SCH - Scheduller - Tuesday - 2 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 39 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].Flag_Enabled | SCH - Scheduller - Tuesday - 2 - Flag_Enabled | Write | ||
| PIV | 418 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].Hours | SCH - Scheduller - Tuesday - 2 - Hours (0 - 23) | h | Write | |
| PIV | 419 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].Mins | SCH - Scheduller - Tuesday - 2 - Mins (0 - 59) | min. | Write | |
| PIV | 420 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].UnitStatus | SCH - Scheduller - Tuesday - 2 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 40 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].Enabled | SCH - Scheduller - Tuesday - 3 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 41 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].Flag_Enabled | SCH - Scheduller - Tuesday - 3 - Flag_Enabled | Write | ||
| PIV | 421 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].Hours | SCH - Scheduller - Tuesday - 3 - Hours (0 - 23) | h | Write | |
| PIV | 422 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].Mins | SCH - Scheduller - Tuesday - 3 - Mins (0 - 59) | min. | Write | |
| PIV | 423 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].UnitStatus | SCH - Scheduller - Tuesday - 3 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 42 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].Enabled | SCH - Scheduller - Tuesday - 4 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 43 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].Flag_Enabled | SCH - Scheduller - Tuesday - 4 - Flag_Enabled | Write | ||
| PIV | 424 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].Hours | SCH - Scheduller - Tuesday - 4 - Hours (0 - 23) | h | Write | |
| PIV | 425 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].Mins | SCH - Scheduller - Tuesday - 4 - Mins (0 - 59) | min. | Write | |
| PIV | 426 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].UnitStatus | SCH - Scheduller - Tuesday - 4 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 44 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].Enabled | SCH - Scheduller - Wednesday - 1 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 45 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].Flag_Enabled | SCH - Scheduller - Wednesday - 1 - Flag_Enabled | Write | ||
| PIV | 427 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].Hours | SCH - Scheduller - Wednesday - 1 - Hours (0 - 23) | h | Write | |
| PIV | 428 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].Mins | SCH - Scheduller - Wednesday - 1 - Mins (0 - 59) | min. | Write | |
| PIV | 429 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].UnitStatus | SCH - Scheduller - Wednesday - 1 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 46 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].Enabled | SCH - Scheduller - Wednesday - 2 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 47 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].Flag_Enabled | SCH - Scheduller - Wednesday - 2 - Flag_Enabled | Write | ||
| PIV | 430 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].Hours | SCH - Scheduller - Wednesday - 2 - Hours (0 - 23) | h | Write | |
| PIV | 431 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].Mins | SCH - Scheduller - Wednesday - 2 - Mins (0 - 59) | min. | Write | |
| PIV | 432 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].UnitStatus | SCH - Scheduller - Wednesday - 2 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 48 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].Enabled | SCH - Scheduller - Wednesday - 3 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 49 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].Flag_Enabled | SCH - Scheduller - Wednesday - 3 - Flag_Enabled | Write | ||
| PIV | 433 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].Hours | SCH - Scheduller - Wednesday - 3 - Hours (0 - 23) | h | Write | |
| PIV | 434 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].Mins | SCH - Scheduller - Wednesday - 3 - Mins (0 - 59) | min. | Write | |
| PIV | 435 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].UnitStatus | SCH - Scheduller - Wednesday - 3 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 50 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].Enabled | SCH - Scheduller - Wednesday - 4 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 51 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].Flag_Enabled | SCH - Scheduller - Wednesday - 4 - Flag_Enabled | Write | ||
| PIV | 436 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].Hours | SCH - Scheduller - Wednesday - 4 - Hours (0 - 23) | h | Write | |
| PIV | 437 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].Mins | SCH - Scheduller - Wednesday - 4 - Mins (0 - 59) | min. | Write | |
| PIV | 438 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].UnitStatus | SCH - Scheduller - Wednesday - 4 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 52 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].Enabled | SCH - Scheduller - Thursday - 1 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 53 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].Flag_Enabled | SCH - Scheduller - Thursday - 1 - Flag_Enabled | Write | ||
| PIV | 439 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].Hours | SCH - Scheduller - Thursday - 1 - Hours (0 - 23) | h | Write | |
| PIV | 440 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].Mins | SCH - Scheduller - Thursday - 1 - Mins (0 - 59) | min. | Write | |
| PIV | 441 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].UnitStatus | SCH - Scheduller - Thursday - 1 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 54 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].Enabled | SCH - Scheduller - Thursday - 2 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 55 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].Flag_Enabled | SCH - Scheduller - Thursday - 2 - Flag_Enabled | Write | ||
| PIV | 442 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].Hours | SCH - Scheduller - Thursday - 2 - Hours (0 - 23) | h | Write | |
| PIV | 443 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].Mins | SCH - Scheduller - Thursday - 2 - Mins (0 - 59) | min. | Write | |
| PIV | 444 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].UnitStatus | SCH - Scheduller - Thursday - 2 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 56 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].Enabled | SCH - Scheduller - Thursday - 3 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 57 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].Flag_Enabled | SCH - Scheduller - Thursday - 3 - Flag_Enabled | Write | ||
| PIV | 445 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].Hours | SCH - Scheduller - Thursday - 3 - Hours (0 - 23) | h | Write | |
| PIV | 446 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].Mins | SCH - Scheduller - Thursday - 3 - Mins (0 - 59) | min. | Write | |
| PIV | 447 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].UnitStatus | SCH - Scheduller - Thursday - 3 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 58 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].Enabled | SCH - Scheduller - Thursday - 4 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 59 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].Flag_Enabled | SCH - Scheduller - Thursday - 4 - Flag_Enabled | Write | ||
| PIV | 448 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].Hours | SCH - Scheduller - Thursday - 4 - Hours (0 - 23) | h | Write | |
| PIV | 449 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].Mins | SCH - Scheduller - Thursday - 4 - Mins (0 - 59) | min. | Write | |
| PIV | 450 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].UnitStatus | SCH - Scheduller - Thursday - 4 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 60 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].Enabled | SCH - Scheduller - Friday - 1 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 61 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].Flag_Enabled | SCH - Scheduller - Friday - 1 - Flag_Enabled | Write | ||
| PIV | 451 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].Hours | SCH - Scheduller - Friday - 1 - Hours (0 - 23) | h | Write | |
| PIV | 452 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].Mins | SCH - Scheduller - Friday - 1 - Mins (0 - 59) | min. | Write | |
| PIV | 453 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].UnitStatus | SCH - Scheduller - Friday - 1 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 62 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].Enabled | SCH - Scheduller - Friday - 2 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 63 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].Flag_Enabled | SCH - Scheduller - Friday - 2 - Flag_Enabled | Write | ||
| PIV | 454 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].Hours | SCH - Scheduller - Friday - 2 - Hours (0 - 23) | h | Write | |
| PIV | 455 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].Mins | SCH - Scheduller - Friday - 2 - Mins (0 - 59) | min. | Write | |
| PIV | 456 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].UnitStatus | SCH - Scheduller - Friday - 2 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 64 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].Enabled | SCH - Scheduller - Friday - 3 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 65 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].Flag_Enabled | SCH - Scheduller - Friday - 3 - Flag_Enabled | Write | ||
| PIV | 457 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].Hours | SCH - Scheduller - Friday - 3 - Hours (0 - 23) | h | Write | |
| PIV | 458 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].Mins | SCH - Scheduller - Friday - 3 - Mins (0 - 59) | min. | Write | |
| PIV | 459 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].UnitStatus | SCH - Scheduller - Friday - 3 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 66 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].Enabled | SCH - Scheduller - Friday - 4 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 67 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].Flag_Enabled | SCH - Scheduller - Friday - 4 - Flag_Enabled | Write | ||
| PIV | 460 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].Hours | SCH - Scheduller - Friday - 4 - Hours (0 - 23) | h | Write | |
| PIV | 461 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].Mins | SCH - Scheduller - Friday - 4 - Mins (0 - 59) | min. | Write | |
| PIV | 462 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].UnitStatus | SCH - Scheduller - Friday - 4 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 68 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].Enabled | SCH - Scheduller - Saturday - 1 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 69 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].Flag_Enabled | SCH - Scheduller - Saturday - 1 - Flag_Enabled | Write | ||
| PIV | 463 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].Hours | SCH - Scheduller - Saturday - 1 - Hours (0 - 23) | h | Write | |
| PIV | 464 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].Mins | SCH - Scheduller - Saturday - 1 - Mins (0 - 59) | min. | Write | |
| PIV | 465 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].UnitStatus | SCH - Scheduller - Saturday - 1 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 70 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].Enabled | SCH - Scheduller - Saturday - 2 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 71 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].Flag_Enabled | SCH - Scheduller - Saturday - 2 - Flag_Enabled | Write | ||
| PIV | 466 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].Hours | SCH - Scheduller - Saturday - 2 - Hours (0 - 23) | h | Write | |
| PIV | 467 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].Mins | SCH - Scheduller - Saturday - 2 - Mins (0 - 59) | min. | Write | |
| PIV | 468 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].UnitStatus | SCH - Scheduller - Saturday - 2 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 72 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].Enabled | SCH - Scheduller - Saturday - 3 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 73 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].Flag_Enabled | SCH - Scheduller - Saturday - 3 - Flag_Enabled | Write | ||
| PIV | 469 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].Hours | SCH - Scheduller - Saturday - 3 - Hours (0 - 23) | h | Write | |
| PIV | 470 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].Mins | SCH - Scheduller - Saturday - 3 - Mins (0 - 59) | min. | Write | |
| PIV | 471 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].UnitStatus | SCH - Scheduller - Saturday - 3 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 74 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].Enabled | SCH - Scheduller - Saturday - 4 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 75 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].Flag_Enabled | SCH - Scheduller - Saturday - 4 - Flag_Enabled | Write | ||
| PIV | 472 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].Hours | SCH - Scheduller - Saturday - 4 - Hours (0 - 23) | h | Write | |
| PIV | 473 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].Mins | SCH - Scheduller - Saturday - 4 - Mins (0 - 59) | min. | Write | |
| PIV | 474 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].UnitStatus | SCH - Scheduller - Saturday - 4 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 76 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].Enabled | SCH - Scheduller - Sunday - 1 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 77 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].Flag_Enabled | SCH - Scheduller - Sunday - 1 - Flag_Enabled | Write | ||
| PIV | 475 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].Hours | SCH - Scheduller - Sunday - 1 - Hours (0 - 23) | h | Write | |
| PIV | 476 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].Mins | SCH - Scheduller - Sunday - 1 - Mins (0 - 59) | min. | Write | |
| PIV | 477 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].UnitStatus | SCH - Scheduller - Sunday - 1 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 78 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].Enabled | SCH - Scheduller - Sunday - 2 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 79 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].Flag_Enabled | SCH - Scheduller - Sunday - 2 - Flag_Enabled | Write | ||
| PIV | 478 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].Hours | SCH - Scheduller - Sunday - 2 - Hours (0 - 23) | h | Write | |
| PIV | 479 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].Mins | SCH - Scheduller - Sunday - 2 - Mins (0 - 59) | min. | Write | |
| PIV | 480 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].UnitStatus | SCH - Scheduller - Sunday - 2 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 80 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].Enabled | SCH - Scheduller - Sunday - 3 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 81 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].Flag_Enabled | SCH - Scheduller - Sunday - 3 - Flag_Enabled | Write | ||
| PIV | 481 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].Hours | SCH - Scheduller - Sunday - 3 - Hours (0 - 23) | h | Write | |
| PIV | 482 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].Mins | SCH - Scheduller - Sunday - 3 - Mins (0 - 59) | min. | Write | |
| PIV | 483 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].UnitStatus | SCH - Scheduller - Sunday - 3 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 82 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].Enabled | SCH - Scheduller - Sunday - 4 - Enabled | Write | 0=OFF; 1=ON | |
| BV | 83 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].Flag_Enabled | SCH - Scheduller - Sunday - 4 - Flag_Enabled | Write | ||
| PIV | 484 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].Hours | SCH - Scheduller - Sunday - 4 - Hours (0 - 23) | h | Write | |
| PIV | 485 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].Mins | SCH - Scheduller - Sunday - 4 - Mins (0 - 59) | min. | Write | |
| PIV | 486 | Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].UnitStatus | SCH - Scheduller - Sunday - 4 - UnitStatus | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| PIV | 487 | Scheduler_OnOffUnit.Scheduler_1.EnDayCopy | SCH - Scheduller - Time Band - Enable Copy to Day | Write | 0=NO; 1=YES | |
| PIV | 488 | Scheduler_OnOffUnit.Scheduler_1.SaveData | SCH - Scheduller - Time Band - Save Data | Write | 0=NO; 1=YES | |
| BV | 84 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].Enabled | SCH - Scheduller - Special Days 1 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 489 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].SpecialDay | SCH - Scheduller - Special Days 1 - Day (1 - 31) | Write | ||
| PIV | 490 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].SpecialMonth | SCH - Scheduller - Special Days 1 - Month (1 - 12) | Write | ||
| PIV | 491 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].UnitStatus | SCH - Scheduller - Special Days 1 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 85 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].Enabled | SCH - Scheduller - Special Days 2 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 492 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].SpecialDay | SCH - Scheduller - Special Days 2 - Day (1 - 31) | Write | ||
| PIV | 493 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].SpecialMonth | SCH - Scheduller - Special Days 2 - Month (1 - 12) | Write | ||
| PIV | 494 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].UnitStatus | SCH - Scheduller - Special Days 2 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 86 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].Enabled | SCH - Scheduller - Special Days 3 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 495 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].SpecialDay | SCH - Scheduller - Special Days 3 - Day (1 - 31) | Write | ||
| PIV | 496 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].SpecialMonth | SCH - Scheduller - Special Days 3 - Month (1 - 12) | Write | ||
| PIV | 497 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].UnitStatus | SCH - Scheduller - Special Days 3 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 87 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].Enabled | SCH - Scheduller - Special Days 4 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 498 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].SpecialDay | SCH - Scheduller - Special Days 4 - Day (1 - 31) | Write | ||
| PIV | 499 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].SpecialMonth | SCH - Scheduller - Special Days 4 - Month (1 - 12) | Write | ||
| PIV | 500 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].UnitStatus | SCH - Scheduller - Special Days 4 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 88 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].Enabled | SCH - Scheduller - Special Days 5 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 501 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].SpecialDay | SCH - Scheduller - Special Days 5 - Day (1 - 31) | Write | ||
| PIV | 502 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].SpecialMonth | SCH - Scheduller - Special Days 5 - Month (1 - 12) | Write | ||
| PIV | 503 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].UnitStatus | SCH - Scheduller - Special Days 5 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 89 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].Enabled | SCH - Scheduller - Special Days 6 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 504 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].SpecialDay | SCH - Scheduller - Special Days 6 - Day (1 - 31) | Write | ||
| PIV | 505 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].SpecialMonth | SCH - Scheduller - Special Days 6 - Month (1 - 12) | Write | ||
| PIV | 506 | Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].UnitStatus | SCH - Scheduller - Special Days 6 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| BV | 90 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].Enabled | SCH - Scheduller - Time Band 1 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 507 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].Hours | SCH - Scheduller - Time Band 1 - Hours (0 - 23) | h | Write | |
| PIV | 508 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].Mins | SCH - Scheduller - Time Band 1 - Minute (0 - 59) | min. | Write | |
| PIV | 509 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].UnitStatus | SCH - Scheduller - Time Band 1 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT | |
| BV | 91 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].Enabled | SCH - Scheduller - Time Band 2 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 510 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].Hours | SCH - Scheduller - Time Band 2 - Hours (0 - 23) | h | Write | |
| PIV | 511 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].Mins | SCH - Scheduller - Time Band 2 - Minute (0 - 59) | min. | Write | |
| PIV | 512 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].UnitStatus | SCH - Scheduller - Time Band 2 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT | |
| BV | 92 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].Enabled | SCH - Scheduller - Time Band 3 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 513 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].Hours | SCH - Scheduller - Time Band 3 - Hours (0 - 23) | h | Write | |
| PIV | 514 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].Mins | SCH - Scheduller - Time Band 3 - Minute (0 - 59) | min. | Write | |
| PIV | 515 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].UnitStatus | SCH - Scheduller - Time Band 3 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT | |
| BV | 93 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].Enabled | SCH - Scheduller - Time Band 4 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 516 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].Hours | SCH - Scheduller - Time Band 4 - Hours (0 - 23) | h | Write | |
| PIV | 517 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].Mins | SCH - Scheduller - Time Band 4 - Minute (0 - 59) | min. | Write | |
| PIV | 518 | Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].UnitStatus | SCH - Scheduller - Time Band 4 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT | |
| BV | 94 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].Enabled | SCH - Scheduller - Periods 1 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 519 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EndDay | SCH - Scheduller - Periods 1 - End Day (1 - 31) | Write | ||
| PIV | 520 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EndMonth | SCH - Scheduller - Periods 1 - End Month (1 - 12) | Write | ||
| PIV | 521 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].StartDay | SCH - Scheduller - Periods 1 - Start Day (1 - 31) | Write | ||
| PIV | 522 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].StartMonth | SCH - Scheduller - Periods 1 - Start Month (1 - 12) | Write | ||
| PIV | 523 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].UnitStatus | SCH - Scheduller - Periods 1 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT | |
| BV | 95 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].Enabled | SCH - Scheduller - Periods 2 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 524 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EndDay | SCH - Scheduller - Periods 2 - End Day (1 - 31) | Write | ||
| PIV | 525 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EndMonth | SCH - Scheduller - Periods 2 - End Month (1 - 12) | Write | ||
| PIV | 526 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].StartDay | SCH - Scheduller - Periods 2 - Start Day (1 - 31) | Write | ||
| PIV | 527 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].StartMonth | SCH - Scheduller - Periods 2 - Start Month (1 - 12) | Write | ||
| PIV | 528 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].UnitStatus | SCH - Scheduller - Periods 2 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT | |
| BV | 96 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].Enabled | SCH - Scheduller - Periods 3 - Enabled | Write | 0=OFF; 1=ON | |
| PIV | 529 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EndDay | SCH - Scheduller - Periods 3 - End Day (1 - 31) | Write | ||
| PIV | 530 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EndMonth | SCH - Scheduller - Periods 3 - End Month (1 - 12) | Write | ||
| PIV | 531 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].StartDay | SCH - Scheduller - Periods 3 - Start Day (1 - 31) | Write | ||
| PIV | 532 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].StartMonth | SCH - Scheduller - Periods 3 - Start Month (1 - 12) | Write | ||
| PIV | 533 | Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].UnitStatus | SCH - Scheduller - Periods 3 - Unit Status | Write | 0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT | |
| PIV | 534 | SetTypSched | SP - WorkMode - Actual | Read | ||
| PIV | 535 | TypScheduler | SCH - Scheduller - Type | Write | 0=NONE; 1=BOARD; 2=HMI | |
| BV | 97 | SchedActive | SCH - Scheduller - Active | Read | 0=NO; 1=YES | |
| PIV | 536 | CurrUnitStatus | SCH - Scheduller - Actual mode from scheduller | Read | 0=OFF; 1=ECO; 2=Optimal; 3=Comfort | |
| BV | 98 | Al_ABB_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 | Read | ||
| BV | 99 | Al_ABB_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 | Read | ||
| BV | 100 | Al_ABB_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 | Read | ||
| BV | 101 | Al_ABB_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 | Read | ||
| BV | 102 | Al_ABB_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 | Read | ||
| BV | 103 | Al_ABB_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 | Read | ||
| BV | 104 | Al_ABB_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 | Read | ||
| BV | 105 | Al_ABB_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 | Read | ||
| BV | 106 | Al_ABB_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 | Read | ||
| BV | 107 | Al_ABB_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 | Read | ||
| BV | 108 | Al_ABB_Rotary.Trigger | AL - Alarm - Rotary | Read | ||
| BV | 109 | Al_ABB_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 | Read | ||
| BV | 110 | Al_ABB_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 | Read | ||
| BV | 111 | Al_ABB_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 | Read | ||
| BV | 112 | Al_ABB_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 | Read | ||
| BV | 113 | Al_ABB_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 | Read | ||
| BV | 114 | Al_ABB_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 | Read | ||
| BV | 115 | Al_ABB_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 | Read | ||
| BV | 116 | Al_ABB_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 | Read | ||
| BV | 117 | Al_ABB_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 | Read | ||
| BV | 118 | Al_ABB_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 | Read | ||
| BV | 119 | Al_AFreezeDIN.Trigger | AL - Alarm - Antifreeze - Digital Input | Read | ||
| BV | 120 | Al_AFreezePRB.Trigger | AL - Alarm - Antifreeze - Back Water Temperature | Read | ||
| BV | 121 | Al_AFreezePreHeatPRB.Trigger | AL - Alarm - Antifreeze - PreHeat Back Water Temperature | Read | ||
| BV | 122 | Al_AfterPreHeatCoilTempPrb.Trigger | AL - Alarm - Probe - After preheating coil temperature | Read | ||
| BV | 123 | Al_BMS_Offline.Trigger | AL - Alarm - BMS - Offline | Read | ||
| BV | 124 | Al_CfgError_cpCOe.Trigger | AL - Alarm - Module IO - cPCOE - Configuration error | Read | ||
| BV | 125 | Al_CircuitFault_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - Circuit Fault | Read | ||
| BV | 126 | Al_CircuitFault_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - Circuit Fault | Read | ||
| BV | 127 | Al_CircuitFault_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - Circuit Fault | Read | ||
| BV | 128 | Al_CircuitFault_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - Circuit Fault | Read | ||
| BV | 129 | Al_CircuitFault_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - Circuit Fault | Read | ||
| BV | 130 | Al_CircuitFault_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - Circuit Fault | Read | ||
| BV | 131 | Al_CircuitFault_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - Circuit Fault | Read | ||
| BV | 132 | Al_CircuitFault_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - Circuit Fault | Read | ||
| BV | 133 | Al_CircuitFault_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - Circuit Fault | Read | ||
| BV | 134 | Al_CircuitFault_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - Circuit Fault | Read | ||
| BV | 135 | Al_CircuitFault_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - Circuit Fault | Read | ||
| BV | 136 | Al_CircuitFault_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - Circuit Fault | Read | ||
| BV | 137 | Al_CircuitFault_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - Circuit Fault | Read | ||
| BV | 138 | Al_CircuitFault_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - Circuit Fault | Read | ||
| BV | 139 | Al_CircuitFault_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - Circuit Fault | Read | ||
| BV | 140 | Al_CircuitFault_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - Circuit Fault | Read | ||
| BV | 141 | Al_CircuitFault_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - Circuit Fault | Read | ||
| BV | 142 | Al_CircuitFault_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - Circuit Fault | Read | ||
| BV | 143 | Al_CircuitFault_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - Circuit Fault | Read | ||
| BV | 144 | Al_CircuitFault_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - Circuit Fault | Read | ||
| BV | 145 | Al_CommErr_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Communication Error | Read | ||
| BV | 146 | Al_CommErr_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Communication Error | Read | ||
| BV | 147 | Al_CommErr_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Communication Error | Read | ||
| BV | 148 | Al_CommErr_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Communication Error | Read | ||
| BV | 149 | Al_CommErr_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Communication Error | Read | ||
| BV | 150 | Al_CommErr_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Communication Error | Read | ||
| BV | 151 | Al_CommErr_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Communication Error | Read | ||
| BV | 152 | Al_CommErr_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Communication Error | Read | ||
| BV | 153 | Al_CommErr_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Communication Error | Read | ||
| BV | 154 | Al_CommErr_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Communication Error | Read | ||
| BV | 155 | Al_CommErr_Rotary.Trigger | AL - Alarm - Rotary - CommUnitation Error | Read | ||
| BV | 156 | Al_CommErr_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Communication Error | Read | ||
| BV | 157 | Al_CommErr_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Communication Error | Read | ||
| BV | 158 | Al_CommErr_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Communication Error | Read | ||
| BV | 159 | Al_CommErr_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Communication Error | Read | ||
| BV | 160 | Al_CommErr_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Communication Error | Read | ||
| BV | 161 | Al_CommErr_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Communication Error | Read | ||
| BV | 162 | Al_CommErr_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Communication Error | Read | ||
| BV | 163 | Al_CommErr_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Communication Error | Read | ||
| BV | 164 | Al_CommErr_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Communication Error | Read | ||
| BV | 165 | Al_CommErr_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Communication Error | Read | ||
| BV | 166 | Al_Cool.Trigger | AL - Alarm - Cooling - Device Alarm | Read | ||
| BV | 167 | Al_CoolFanFault_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Cooling Fan Fault | Read | ||
| BV | 168 | Al_CoolFanFault_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Cooling Fan Fault | Read | ||
| BV | 169 | Al_CoolFanFault_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Cooling Fan Fault | Read | ||
| BV | 170 | Al_CoolFanFault_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Cooling Fan Fault | Read | ||
| BV | 171 | Al_CoolFanFault_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Cooling Fan Fault | Read | ||
| BV | 172 | Al_CoolFanFault_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Cooling Fan Fault | Read | ||
| BV | 173 | Al_CoolFanFault_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Cooling Fan Fault | Read | ||
| BV | 174 | Al_CoolFanFault_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Cooling Fan Fault | Read | ||
| BV | 175 | Al_CoolFanFault_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Cooling Fan Fault | Read | ||
| BV | 176 | Al_CoolFanFault_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Cooling Fan Fault | Read | ||
| BV | 177 | Al_CoolFanFault_Rotary.Trigger | AL - Alarm - Rotary - Cooling Fan Fault | Read | ||
| BV | 178 | Al_CoolFanFault_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Cooling Fan Fault | Read | ||
| BV | 179 | Al_CoolFanFault_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Cooling Fan Fault | Read | ||
| BV | 180 | Al_CoolFanFault_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Cooling Fan Fault | Read | ||
| BV | 181 | Al_CoolFanFault_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Cooling Fan Fault | Read | ||
| BV | 182 | Al_CoolFanFault_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Cooling Fan Fault | Read | ||
| BV | 183 | Al_CoolFanFault_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Cooling Fan Fault | Read | ||
| BV | 184 | Al_CoolFanFault_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Cooling Fan Fault | Read | ||
| BV | 185 | Al_CoolFanFault_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Cooling Fan Fault | Read | ||
| BV | 186 | Al_CoolFanFault_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Cooling Fan Fault | Read | ||
| BV | 187 | Al_CoolFanFault_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Cooling Fan Fault | Read | ||
| BV | 188 | Al_CutOff_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - CutOff | Read | ||
| BV | 189 | Al_CutOff_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - CutOff | Read | ||
| BV | 190 | Al_CutOff_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - CutOff | Read | ||
| BV | 191 | Al_CutOff_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - CutOff | Read | ||
| BV | 192 | Al_CutOff_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - CutOff | Read | ||
| BV | 193 | Al_CutOff_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - CutOff | Read | ||
| BV | 194 | Al_CutOff_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - CutOff | Read | ||
| BV | 195 | Al_CutOff_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - CutOff | Read | ||
| BV | 196 | Al_CutOff_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - CutOff | Read | ||
| BV | 197 | Al_CutOff_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - CutOff | Read | ||
| BV | 198 | Al_CutOff_Rotary.Trigger | AL - Alarm - Rotary - CutOff | Read | ||
| BV | 199 | Al_CutOff_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - CutOff | Read | ||
| BV | 200 | Al_CutOff_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - CutOff | Read | ||
| BV | 201 | Al_CutOff_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - CutOff | Read | ||
| BV | 202 | Al_CutOff_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - CutOff | Read | ||
| BV | 203 | Al_CutOff_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - CutOff | Read | ||
| BV | 204 | Al_CutOff_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - CutOff | Read | ||
| BV | 205 | Al_CutOff_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - CutOff | Read | ||
| BV | 206 | Al_CutOff_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - CutOff | Read | ||
| BV | 207 | Al_CutOff_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - CutOff | Read | ||
| BV | 208 | Al_CutOff_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - CutOff | Read | ||
| BV | 209 | Al_DC_Ovld_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - DC Over load | Read | ||
| BV | 210 | Al_DC_Ovld_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - DC Over load | Read | ||
| BV | 211 | Al_DC_Ovld_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - DC Over load | Read | ||
| BV | 212 | Al_DC_Ovld_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - DC Over load | Read | ||
| BV | 213 | Al_DC_Ovld_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - DC Over load | Read | ||
| BV | 214 | Al_DC_Ovld_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - DC Over load | Read | ||
| BV | 215 | Al_DC_Ovld_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - DC Over load | Read | ||
| BV | 216 | Al_DC_Ovld_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - DC Over load | Read | ||
| BV | 217 | Al_DC_Ovld_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - DC Over load | Read | ||
| BV | 218 | Al_DC_Ovld_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - DC Over load | Read | ||
| BV | 219 | Al_DC_Ovld_Rotary.Trigger | AL - Alarm - Rotary - DC Overload | Read | ||
| BV | 220 | Al_DC_Ovld_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - DC Over load | Read | ||
| BV | 221 | Al_DC_Ovld_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - DC Over load | Read | ||
| BV | 222 | Al_DC_Ovld_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - DC Over load | Read | ||
| BV | 223 | Al_DC_Ovld_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - DC Over load | Read | ||
| BV | 224 | Al_DC_Ovld_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - DC Over load | Read | ||
| BV | 225 | Al_DC_Ovld_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - DC Over load | Read | ||
| BV | 226 | Al_DC_Ovld_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - DC Over load | Read | ||
| BV | 227 | Al_DC_Ovld_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - DC Over load | Read | ||
| BV | 228 | Al_DC_Ovld_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - DC Over load | Read | ||
| BV | 229 | Al_DC_Ovld_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - DC Over load | Read | ||
| BV | 230 | Al_ElectTherm_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Electric Thermal | Read | ||
| BV | 231 | Al_ElectTherm_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Electric Thermal | Read | ||
| BV | 232 | Al_ElectTherm_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Electric Thermal | Read | ||
| BV | 233 | Al_ElectTherm_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Electric Thermal | Read | ||
| BV | 234 | Al_ElectTherm_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Electric Thermal | Read | ||
| BV | 235 | Al_ElectTherm_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Electric Thermal | Read | ||
| BV | 236 | Al_ElectTherm_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Electric Thermal | Read | ||
| BV | 237 | Al_ElectTherm_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Electric Thermal | Read | ||
| BV | 238 | Al_ElectTherm_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Electric Thermal | Read | ||
| BV | 239 | Al_ElectTherm_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Electric Thermal | Read | ||
| BV | 240 | Al_ElectTherm_Rotary.Trigger | AL - Alarm - Rotary - Electric Thermal | Read | ||
| BV | 241 | Al_ElectTherm_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Electric Thermal | Read | ||
| BV | 242 | Al_ElectTherm_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Electric Thermal | Read | ||
| BV | 243 | Al_ElectTherm_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Electric Thermal | Read | ||
| BV | 244 | Al_ElectTherm_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Electric Thermal | Read | ||
| BV | 245 | Al_ElectTherm_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Electric Thermal | Read | ||
| BV | 246 | Al_ElectTherm_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Electric Thermal | Read | ||
| BV | 247 | Al_ElectTherm_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Electric Thermal | Read | ||
| BV | 248 | Al_ElectTherm_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Electric Thermal | Read | ||
| BV | 249 | Al_ElectTherm_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Electric Thermal | Read | ||
| BV | 250 | Al_ElectTherm_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Electric Thermal | Read | ||
| BV | 251 | Al_Err_retain_write.Trigger | AL - Alarm - Error retain write | Read | ||
| BV | 252 | Al_ExhTempPrb.Trigger | AL - Alarm - Probe - Temperature Exhaust | Read | ||
| BV | 253 | Al_ExtFaultA_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - External Fault A | Read | ||
| BV | 254 | Al_ExtFaultA_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - External Fault A | Read | ||
| BV | 255 | Al_ExtFaultA_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - External Fault A | Read | ||
| BV | 256 | Al_ExtFaultA_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - External Fault A | Read | ||
| BV | 257 | Al_ExtFaultA_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - External Fault A | Read | ||
| BV | 258 | Al_ExtFaultA_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - External Fault A | Read | ||
| BV | 259 | Al_ExtFaultA_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - External Fault A | Read | ||
| BV | 260 | Al_ExtFaultA_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - External Fault A | Read | ||
| BV | 261 | Al_ExtFaultA_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - External Fault A | Read | ||
| BV | 262 | Al_ExtFaultA_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - External Fault A | Read | ||
| BV | 263 | Al_ExtFaultA_Rotary.Trigger | AL - Alarm - Rotary - External Fault A | Read | ||
| BV | 264 | Al_ExtFaultA_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - External Fault A | Read | ||
| BV | 265 | Al_ExtFaultA_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - External Fault A | Read | ||
| BV | 266 | Al_ExtFaultA_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - External Fault A | Read | ||
| BV | 267 | Al_ExtFaultA_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - External Fault A | Read | ||
| BV | 268 | Al_ExtFaultA_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - External Fault A | Read | ||
| BV | 269 | Al_ExtFaultA_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - External Fault A | Read | ||
| BV | 270 | Al_ExtFaultA_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - External Fault A | Read | ||
| BV | 271 | Al_ExtFaultA_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - External Fault A | Read | ||
| BV | 272 | Al_ExtFaultA_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - External Fault A | Read | ||
| BV | 273 | Al_ExtFaultA_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - External Fault A | Read | ||
| BV | 274 | Al_ExtFaultB_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - External Fault B | Read | ||
| BV | 275 | Al_ExtFaultB_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - External Fault B | Read | ||
| BV | 276 | Al_ExtFaultB_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - External Fault B | Read | ||
| BV | 277 | Al_ExtFaultB_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - External Fault B | Read | ||
| BV | 278 | Al_ExtFaultB_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - External Fault B | Read | ||
| BV | 279 | Al_ExtFaultB_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - External Fault B | Read | ||
| BV | 280 | Al_ExtFaultB_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - External Fault B | Read | ||
| BV | 281 | Al_ExtFaultB_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - External Fault B | Read | ||
| BV | 282 | Al_ExtFaultB_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - External Fault B | Read | ||
| BV | 283 | Al_ExtFaultB_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - External Fault B | Read | ||
| BV | 284 | Al_ExtFaultB_Rotary.Trigger | AL - Alarm - Rotary - External Fault B | Read | ||
| BV | 285 | Al_ExtFaultB_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - External Fault B | Read | ||
| BV | 286 | Al_ExtFaultB_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - External Fault B | Read | ||
| BV | 287 | Al_ExtFaultB_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - External Fault B | Read | ||
| BV | 288 | Al_ExtFaultB_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - External Fault B | Read | ||
| BV | 289 | Al_ExtFaultB_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - External Fault B | Read | ||
| BV | 290 | Al_ExtFaultB_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - External Fault B | Read | ||
| BV | 291 | Al_ExtFaultB_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - External Fault B | Read | ||
| BV | 292 | Al_ExtFaultB_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - External Fault B | Read | ||
| BV | 293 | Al_ExtFaultB_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - External Fault B | Read | ||
| BV | 294 | Al_ExtFaultB_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - External Fault B | Read | ||
| BV | 295 | Al_ExtTempPrb.Trigger | AL - Alarm - Probe - Temperature External | Read | ||
| BV | 296 | Al_Fire.Trigger | AL - Alarm - Fire | Read | ||
| BV | 297 | Al_FireExh.Trigger | AL - Alarm - Fire - Return Temperature | Read | ||
| BV | 298 | Al_GroundFault_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Ground Fault | Read | ||
| BV | 299 | Al_GroundFault_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Ground Fault | Read | ||
| BV | 300 | Al_GroundFault_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Ground Fault | Read | ||
| BV | 301 | Al_GroundFault_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Ground Fault | Read | ||
| BV | 302 | Al_GroundFault_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Ground Fault | Read | ||
| BV | 303 | Al_GroundFault_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Ground Fault | Read | ||
| BV | 304 | Al_GroundFault_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Ground Fault | Read | ||
| BV | 305 | Al_GroundFault_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Ground Fault | Read | ||
| BV | 306 | Al_GroundFault_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Ground Fault | Read | ||
| BV | 307 | Al_GroundFault_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Ground Fault | Read | ||
| BV | 308 | Al_GroundFault_Rotary.Trigger | AL - Alarm - Rotary - Ground Fault | Read | ||
| BV | 309 | Al_GroundFault_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Ground Fault | Read | ||
| BV | 310 | Al_GroundFault_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Ground Fault | Read | ||
| BV | 311 | Al_GroundFault_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Ground Fault | Read | ||
| BV | 312 | Al_GroundFault_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Ground Fault | Read | ||
| BV | 313 | Al_GroundFault_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Ground Fault | Read | ||
| BV | 314 | Al_GroundFault_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Ground Fault | Read | ||
| BV | 315 | Al_GroundFault_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Ground Fault | Read | ||
| BV | 316 | Al_GroundFault_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Ground Fault | Read | ||
| BV | 317 | Al_GroundFault_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Ground Fault | Read | ||
| BV | 318 | Al_GroundFault_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Ground Fault | Read | ||
| BV | 319 | Al_Heat.Trigger | AL - Alarm - Heating - Device Alarm | Read | ||
| BV | 320 | Al_HeatCoilTempPrb.Trigger | AL - Alarm - Probe - Temperature Water Heating coil | Read | ||
| BV | 321 | Al_HeatExchgWorkHrsWarn.Trigger | AL - Alarm - HeatExchanger - HeatExchanger Works Hour Warning | Read | ||
| BV | 322 | Al_HeatSink_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - HeatSink | Read | ||
| BV | 323 | Al_HeatSink_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - HeatSink | Read | ||
| BV | 324 | Al_HeatSink_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - HeatSink | Read | ||
| BV | 325 | Al_HeatSink_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - HeatSink | Read | ||
| BV | 326 | Al_HeatSink_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - HeatSink | Read | ||
| BV | 327 | Al_HeatSink_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - HeatSink | Read | ||
| BV | 328 | Al_HeatSink_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - HeatSink | Read | ||
| BV | 329 | Al_HeatSink_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - HeatSink | Read | ||
| BV | 330 | Al_HeatSink_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - HeatSink | Read | ||
| BV | 331 | Al_HeatSink_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - HeatSink | Read | ||
| BV | 332 | Al_HeatSink_Rotary.Trigger | AL - Alarm - Rotary - HeatSink | Read | ||
| BV | 333 | Al_HeatSink_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - HeatSink | Read | ||
| BV | 334 | Al_HeatSink_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - HeatSink | Read | ||
| BV | 335 | Al_HeatSink_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - HeatSink | Read | ||
| BV | 336 | Al_HeatSink_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - HeatSink | Read | ||
| BV | 337 | Al_HeatSink_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - HeatSink | Read | ||
| BV | 338 | Al_HeatSink_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - HeatSink | Read | ||
| BV | 339 | Al_HeatSink_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - HeatSink | Read | ||
| BV | 340 | Al_HeatSink_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - HeatSink | Read | ||
| BV | 341 | Al_HeatSink_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - HeatSink | Read | ||
| BV | 342 | Al_HeatSink_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - HeatSink | Read | ||
| BV | 343 | AL_Hot_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - Hot | Read | ||
| BV | 344 | AL_Hot_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - Hot | Read | ||
| BV | 345 | AL_Hot_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - Hot | Read | ||
| BV | 346 | AL_Hot_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - Hot | Read | ||
| BV | 347 | AL_Hot_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - Hot | Read | ||
| BV | 348 | AL_Hot_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - Hot | Read | ||
| BV | 349 | AL_Hot_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - Hot | Read | ||
| BV | 350 | AL_Hot_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - Hot | Read | ||
| BV | 351 | AL_Hot_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - Hot | Read | ||
| BV | 352 | AL_Hot_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - Hot | Read | ||
| BV | 353 | AL_Hot_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - Hot | Read | ||
| BV | 354 | AL_Hot_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - Hot | Read | ||
| BV | 355 | AL_Hot_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - Hot | Read | ||
| BV | 356 | AL_Hot_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - Hot | Read | ||
| BV | 357 | AL_Hot_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - Hot | Read | ||
| BV | 358 | AL_Hot_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - Hot | Read | ||
| BV | 359 | AL_Hot_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - Hot | Read | ||
| BV | 360 | AL_Hot_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - Hot | Read | ||
| BV | 361 | AL_Hot_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - Hot | Read | ||
| BV | 362 | AL_Hot_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - Hot | Read | ||
| BV | 363 | Al_Hum.Trigger | AL - Alarm - Humidifier | Read | ||
| BV | 364 | Al_HumWorkHrsWarn.Trigger | AL - Alarm - Humidity - Works Hour Warning | Read | ||
| BV | 365 | Al_HW_Fault_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Hardware Fault | Read | ||
| BV | 366 | Al_HW_Fault_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Hardware Fault | Read | ||
| BV | 367 | Al_HW_Fault_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Hardware Fault | Read | ||
| BV | 368 | Al_HW_Fault_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Hardware Fault | Read | ||
| BV | 369 | Al_HW_Fault_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Hardware Fault | Read | ||
| BV | 370 | Al_HW_Fault_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Hardware Fault | Read | ||
| BV | 371 | Al_HW_Fault_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Hardware Fault | Read | ||
| BV | 372 | Al_HW_Fault_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Hardware Fault | Read | ||
| BV | 373 | Al_HW_Fault_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Hardware Fault | Read | ||
| BV | 374 | Al_HW_Fault_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Hardware Fault | Read | ||
| BV | 375 | Al_HW_Fault_Rotary.Trigger | AL - Alarm - Rotary - Hardware Fault | Read | ||
| BV | 376 | Al_HW_Fault_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Hardware Fault | Read | ||
| BV | 377 | Al_HW_Fault_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Hardware Fault | Read | ||
| BV | 378 | Al_HW_Fault_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Hardware Fault | Read | ||
| BV | 379 | Al_HW_Fault_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Hardware Fault | Read | ||
| BV | 380 | Al_HW_Fault_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Hardware Fault | Read | ||
| BV | 381 | Al_HW_Fault_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Hardware Fault | Read | ||
| BV | 382 | Al_HW_Fault_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Hardware Fault | Read | ||
| BV | 383 | Al_HW_Fault_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Hardware Fault | Read | ||
| BV | 384 | Al_HW_Fault_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Hardware Fault | Read | ||
| BV | 385 | Al_HW_Fault_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Hardware Fault | Read | ||
| BV | 386 | Al_I2RIGBTFault_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - I2RIGBT Fault | Read | ||
| BV | 387 | Al_I2RIGBTFault_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - I2RIGBT Fault | Read | ||
| BV | 388 | Al_I2RIGBTFault_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - I2RIGBT Fault | Read | ||
| BV | 389 | Al_I2RIGBTFault_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - I2RIGBT Fault | Read | ||
| BV | 390 | Al_I2RIGBTFault_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - I2RIGBT Fault | Read | ||
| BV | 391 | Al_I2RIGBTFault_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - I2RIGBT Fault | Read | ||
| BV | 392 | Al_I2RIGBTFault_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - I2RIGBT Fault | Read | ||
| BV | 393 | Al_I2RIGBTFault_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - I2RIGBT Fault | Read | ||
| BV | 394 | Al_I2RIGBTFault_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - I2RIGBT Fault | Read | ||
| BV | 395 | Al_I2RIGBTFault_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - I2RIGBT Fault | Read | ||
| BV | 396 | Al_I2RIGBTFault_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - I2RIGBT Fault | Read | ||
| BV | 397 | Al_I2RIGBTFault_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - I2RIGBT Fault | Read | ||
| BV | 398 | Al_I2RIGBTFault_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - I2RIGBT Fault | Read | ||
| BV | 399 | Al_I2RIGBTFault_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - I2RIGBT Fault | Read | ||
| BV | 400 | Al_I2RIGBTFault_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - I2RIGBT Fault | Read | ||
| BV | 401 | Al_I2RIGBTFault_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - I2RIGBT Fault | Read | ||
| BV | 402 | Al_I2RIGBTFault_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - I2RIGBT Fault | Read | ||
| BV | 403 | Al_I2RIGBTFault_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - I2RIGBT Fault | Read | ||
| BV | 404 | Al_I2RIGBTFault_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - I2RIGBT Fault | Read | ||
| BV | 405 | Al_I2RIGBTFault_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - I2RIGBT Fault | Read | ||
| BV | 406 | AL_IGBTOvercurrent_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - IGBT Over current | Read | ||
| BV | 407 | AL_IGBTOvercurrent_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - IGBT Over current | Read | ||
| BV | 408 | AL_IGBTOvercurrent_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - IGBT Over current | Read | ||
| BV | 409 | AL_IGBTOvercurrent_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - IGBT Over current | Read | ||
| BV | 410 | AL_IGBTOvercurrent_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - IGBT Over current | Read | ||
| BV | 411 | AL_IGBTOvercurrent_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - IGBT Over current | Read | ||
| BV | 412 | AL_IGBTOvercurrent_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - IGBT Over current | Read | ||
| BV | 413 | AL_IGBTOvercurrent_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - IGBT Over current | Read | ||
| BV | 414 | AL_IGBTOvercurrent_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - IGBT Over current | Read | ||
| BV | 415 | AL_IGBTOvercurrent_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - IGBT Over current | Read | ||
| BV | 416 | AL_IGBTOvercurrent_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - IGBT Over current | Read | ||
| BV | 417 | AL_IGBTOvercurrent_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - IGBT Over current | Read | ||
| BV | 418 | AL_IGBTOvercurrent_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - IGBT Over current | Read | ||
| BV | 419 | AL_IGBTOvercurrent_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - IGBT Over current | Read | ||
| BV | 420 | AL_IGBTOvercurrent_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - IGBT Over current | Read | ||
| BV | 421 | AL_IGBTOvercurrent_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - IGBT Over current | Read | ||
| BV | 422 | AL_IGBTOvercurrent_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - IGBT Over current | Read | ||
| BV | 423 | AL_IGBTOvercurrent_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - IGBT Over current | Read | ||
| BV | 424 | AL_IGBTOvercurrent_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - IGBT Over current | Read | ||
| BV | 425 | AL_IGBTOvercurrent_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - IGBT Over current | Read | ||
| BV | 426 | Al_InvOverheat_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Inverter Over Heat | Read | ||
| BV | 427 | Al_InvOverheat_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Inverter Over Heat | Read | ||
| BV | 428 | Al_InvOverheat_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Inverter Over Heat | Read | ||
| BV | 429 | Al_InvOverheat_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Inverter Over Heat | Read | ||
| BV | 430 | Al_InvOverheat_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Inverter Over Heat | Read | ||
| BV | 431 | Al_InvOverheat_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Inverter Over Heat | Read | ||
| BV | 432 | Al_InvOverheat_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Inverter Over Heat | Read | ||
| BV | 433 | Al_InvOverheat_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Inverter Over Heat | Read | ||
| BV | 434 | Al_InvOverheat_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Inverter Over Heat | Read | ||
| BV | 435 | Al_InvOverheat_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Inverter Over Heat | Read | ||
| BV | 436 | Al_InvOverheat_Rotary.Trigger | AL - Alarm - Rotary - Inverter OverHeat | Read | ||
| BV | 437 | Al_InvOverheat_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Inverter Over Heat | Read | ||
| BV | 438 | Al_InvOverheat_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Inverter Over Heat | Read | ||
| BV | 439 | Al_InvOverheat_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Inverter Over Heat | Read | ||
| BV | 440 | Al_InvOverheat_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Inverter Over Heat | Read | ||
| BV | 441 | Al_InvOverheat_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Inverter Over Heat | Read | ||
| BV | 442 | Al_InvOverheat_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Inverter Over Heat | Read | ||
| BV | 443 | Al_InvOverheat_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Inverter Over Heat | Read | ||
| BV | 444 | Al_InvOverheat_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Inverter Over Heat | Read | ||
| BV | 445 | Al_InvOverheat_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Inverter Over Heat | Read | ||
| BV | 446 | Al_InvOverheat_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Inverter Over Heat | Read | ||
| BV | 447 | Al_InvOvld_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Inverter Over Load | Read | ||
| BV | 448 | Al_InvOvld_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Inverter Over Load | Read | ||
| BV | 449 | Al_InvOvld_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Inverter Over Load | Read | ||
| BV | 450 | Al_InvOvld_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Inverter Over Load | Read | ||
| BV | 451 | Al_InvOvld_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Inverter Over Load | Read | ||
| BV | 452 | Al_InvOvld_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Inverter Over Load | Read | ||
| BV | 453 | Al_InvOvld_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Inverter Over Load | Read | ||
| BV | 454 | Al_InvOvld_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Inverter Over Load | Read | ||
| BV | 455 | Al_InvOvld_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Inverter Over Load | Read | ||
| BV | 456 | Al_InvOvld_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Inverter Over Load | Read | ||
| BV | 457 | Al_InvOvld_Rotary.Trigger | AL - Alarm - Rotary - Inverter OverLoad | Read | ||
| BV | 458 | Al_InvOvld_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Inverter Over Load | Read | ||
| BV | 459 | Al_InvOvld_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Inverter Over Load | Read | ||
| BV | 460 | Al_InvOvld_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Inverter Over Load | Read | ||
| BV | 461 | Al_InvOvld_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Inverter Over Load | Read | ||
| BV | 462 | Al_InvOvld_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Inverter Over Load | Read | ||
| BV | 463 | Al_InvOvld_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Inverter Over Load | Read | ||
| BV | 464 | Al_InvOvld_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Inverter Over Load | Read | ||
| BV | 465 | Al_InvOvld_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Inverter Over Load | Read | ||
| BV | 466 | Al_InvOvld_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Inverter Over Load | Read | ||
| BV | 467 | Al_InvOvld_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Inverter Over Load | Read | ||
| BV | 468 | Al_LowSupplyTemp.Trigger | AL - Alarm - Probe - Low Supply Temperature | Read | ||
| BV | 469 | Al_LowVolt_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Low Voltage | Read | ||
| BV | 470 | Al_LowVolt_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Low Voltage | Read | ||
| BV | 471 | Al_LowVolt_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Low Voltage | Read | ||
| BV | 472 | Al_LowVolt_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Low Voltage | Read | ||
| BV | 473 | Al_LowVolt_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Low Voltage | Read | ||
| BV | 474 | Al_LowVolt_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Low Voltage | Read | ||
| BV | 475 | Al_LowVolt_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Low Voltage | Read | ||
| BV | 476 | Al_LowVolt_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Low Voltage | Read | ||
| BV | 477 | Al_LowVolt_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Low Voltage | Read | ||
| BV | 478 | Al_LowVolt_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Low Voltage | Read | ||
| BV | 479 | Al_LowVolt_Rotary.Trigger | AL - Alarm - Rotary - Low Voltage | Read | ||
| BV | 480 | Al_LowVolt_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Low Voltage | Read | ||
| BV | 481 | Al_LowVolt_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Low Voltage | Read | ||
| BV | 482 | Al_LowVolt_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Low Voltage | Read | ||
| BV | 483 | Al_LowVolt_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Low Voltage | Read | ||
| BV | 484 | Al_LowVolt_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Low Voltage | Read | ||
| BV | 485 | Al_LowVolt_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Low Voltage | Read | ||
| BV | 486 | Al_LowVolt_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Low Voltage | Read | ||
| BV | 487 | Al_LowVolt_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Low Voltage | Read | ||
| BV | 488 | Al_LowVolt_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Low Voltage | Read | ||
| BV | 489 | Al_LowVolt_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Low Voltage | Read | ||
| BV | 490 | Al_MB_AO1.Trigger | AL - Alarm - Control Circuit - AO1 | Read | ||
| BV | 491 | Al_MB_AO1_AO4_PWM.Trigger | AL - Alarm - Control Circuit - AO1_AO4_PWM | Read | ||
| BV | 492 | Al_MB_AO2.Trigger | AL - Alarm - Control Circuit - AO2 | Read | ||
| BV | 493 | Al_MB_AO3.Trigger | AL - Alarm - Control Circuit - AO3 | Read | ||
| BV | 494 | Al_MB_AO4.Trigger | AL - Alarm - Control Circuit - AO4 | Read | ||
| BV | 495 | Al_MB_Control_Supply.Trigger | AL - Alarm - Control Circuit - Control_Supply | Read | ||
| BV | 496 | Al_MB_Control_Temp.Trigger | AL - Alarm - Control Circuit - Control_Temp | Read | ||
| BV | 497 | Al_MB_Humidity.Trigger | AL - Alarm - Control Circuit - Humidity | Read | ||
| BV | 498 | Al_MB_Press_Fan_Return.Trigger | AL - Alarm - Control Circuit - Press_Fan_Return | Read | ||
| BV | 499 | Al_MB_Press_Fan_Supply.Trigger | AL - Alarm - Control Circuit - Press_Fan_Supply | Read | ||
| BV | 500 | Al_MB_Press_Filter_Return.Trigger | AL - Alarm - Control Circuit - Press_Filter_Return | Read | ||
| BV | 501 | Al_MB_Press_Filter_Supply.Trigger | AL - Alarm - Control Circuit - Press_Filter_Supply | Read | ||
| BV | 502 | Al_MB_Supply24.Trigger | AL - Alarm - Control Circuit - Supply24 | Read | ||
| BV | 503 | Al_MB_Temp_Fan_Return.Trigger | AL - Alarm - Control Circuit - Temp_Fan_Return | Read | ||
| BV | 504 | Al_MB_Temp_Fan_Supply.Trigger | AL - Alarm - Control Circuit - Temp_Fan_Supply | Read | ||
| BV | 505 | Al_MB_Temp_Filter_Return.Trigger | AL - Alarm - Control Circuit - Temp_Filter_Return | Read | ||
| BV | 506 | Al_MB_Temp_Filter_Supply.Trigger | AL - Alarm - Control Circuit - Temp_Filter_Supply | Read | ||
| BV | 507 | Al_MB_Temperature.Trigger | AL - Alarm - Control Circuit - Temperature | Read | ||
| BV | 508 | Al_MotorFault_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - Motor Fault | Read | ||
| BV | 509 | Al_MotorFault_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - Motor Fault | Read | ||
| BV | 510 | Al_MotorFault_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - Motor Fault | Read | ||
| BV | 511 | Al_MotorFault_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - Motor Fault | Read | ||
| BV | 512 | Al_MotorFault_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - Motor Fault | Read | ||
| BV | 513 | Al_MotorFault_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - Motor Fault | Read | ||
| BV | 514 | Al_MotorFault_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - Motor Fault | Read | ||
| BV | 515 | Al_MotorFault_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - Motor Fault | Read | ||
| BV | 516 | Al_MotorFault_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - Motor Fault | Read | ||
| BV | 517 | Al_MotorFault_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - Motor Fault | Read | ||
| BV | 518 | Al_MotorFault_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - Motor Fault | Read | ||
| BV | 519 | Al_MotorFault_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - Motor Fault | Read | ||
| BV | 520 | Al_MotorFault_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - Motor Fault | Read | ||
| BV | 521 | Al_MotorFault_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - Motor Fault | Read | ||
| BV | 522 | Al_MotorFault_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - Motor Fault | Read | ||
| BV | 523 | Al_MotorFault_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - Motor Fault | Read | ||
| BV | 524 | Al_MotorFault_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - Motor Fault | Read | ||
| BV | 525 | Al_MotorFault_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - Motor Fault | Read | ||
| BV | 526 | Al_MotorFault_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - Motor Fault | Read | ||
| BV | 527 | Al_MotorOverheat_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Motor Over heat | Read | ||
| BV | 528 | Al_MotorOverheat_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Motor Over heat | Read | ||
| BV | 529 | Al_MotorOverheat_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Motor Over heat | Read | ||
| BV | 530 | Al_MotorOverheat_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Motor Over heat | Read | ||
| BV | 531 | Al_MotorOverheat_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Motor Over heat | Read | ||
| BV | 532 | Al_MotorOverheat_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Motor Over heat | Read | ||
| BV | 533 | Al_MotorOverheat_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Motor Over heat | Read | ||
| BV | 534 | Al_MotorOverheat_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Motor Over heat | Read | ||
| BV | 535 | Al_MotorOverheat_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Motor Over heat | Read | ||
| BV | 536 | Al_MotorOverheat_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Motor Over heat | Read | ||
| BV | 537 | Al_MotorOverheat_Rotary.Trigger | AL - Alarm - Rotary - Motor Overheat | Read | ||
| BV | 538 | Al_MotorOverheat_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Motor Over heat | Read | ||
| BV | 539 | Al_MotorOverheat_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Motor Over heat | Read | ||
| BV | 540 | Al_MotorOverheat_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Motor Over heat | Read | ||
| BV | 541 | Al_MotorOverheat_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Motor Over heat | Read | ||
| BV | 542 | Al_MotorOverheat_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Motor Over heat | Read | ||
| BV | 543 | Al_MotorOverheat_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Motor Over heat | Read | ||
| BV | 544 | Al_MotorOverheat_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Motor Over heat | Read | ||
| BV | 545 | Al_MotorOverheat_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Motor Over heat | Read | ||
| BV | 546 | Al_MotorOverheat_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Motor Over heat | Read | ||
| BV | 547 | Al_MotorOverheat_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Motor Over heat | Read | ||
| BV | 548 | Al_Offline_cpCOe.Trigger | AL - Alarm - Module IO - cPCOE - Offline | Read | ||
| BV | 549 | Al_Offline_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Offline | Read | ||
| BV | 550 | Al_Offline_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Offline | Read | ||
| BV | 551 | Al_Offline_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Offline | Read | ||
| BV | 552 | Al_Offline_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Offline | Read | ||
| BV | 553 | Al_Offline_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Offline | Read | ||
| BV | 554 | Al_Offline_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Offline | Read | ||
| BV | 555 | Al_Offline_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Offline | Read | ||
| BV | 556 | Al_Offline_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Offline | Read | ||
| BV | 557 | Al_Offline_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Offline | Read | ||
| BV | 558 | Al_Offline_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Offline | Read | ||
| BV | 559 | Al_Offline_MainBoard.Trigger | AL - Alarm - Control Circuit - Offline | Read | ||
| BV | 560 | Al_Offline_Rotary.Trigger | AL - Alarm - Rotary - Offline | Read | ||
| BV | 561 | Al_Offline_SP_ExhHum.Trigger | AL - Alarm - Probe - Return Humidity - Offline | Read | ||
| BV | 562 | Al_Offline_SP_ExhPress.Trigger | AL - Alarm - Probe - Return Air Pressure - Offline | Read | ||
| BV | 563 | Al_Offline_SP_SupplyHum.Trigger | AL - Alarm - Probe - Supply humidity - Offline | Read | ||
| BV | 564 | Al_Offline_SP_SupplyPress.Trigger | AL - Alarm - Probe - Supply Air Pressure - Offline | Read | ||
| BV | 565 | Al_Offline_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Offline | Read | ||
| BV | 566 | Al_Offline_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Offline | Read | ||
| BV | 567 | Al_Offline_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Offline | Read | ||
| BV | 568 | Al_Offline_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Offline | Read | ||
| BV | 569 | Al_Offline_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Offline | Read | ||
| BV | 570 | Al_Offline_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Offline | Read | ||
| BV | 571 | Al_Offline_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Offline | Read | ||
| BV | 572 | Al_Offline_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Offline | Read | ||
| BV | 573 | Al_Offline_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Offline | Read | ||
| BV | 574 | Al_Offline_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Offline | Read | ||
| BV | 575 | Al_Offline_THTN_1.Trigger | AL - Alarm - HMI Basic - Offline | Read | ||
| BV | 576 | Al_Option_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Option | Read | ||
| BV | 577 | Al_Option_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Option | Read | ||
| BV | 578 | Al_Option_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Option | Read | ||
| BV | 579 | Al_Option_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Option | Read | ||
| BV | 580 | Al_Option_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Option | Read | ||
| BV | 581 | Al_Option_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Option | Read | ||
| BV | 582 | Al_Option_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Option | Read | ||
| BV | 583 | Al_Option_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Option | Read | ||
| BV | 584 | Al_Option_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Option | Read | ||
| BV | 585 | Al_Option_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Option | Read | ||
| BV | 586 | Al_Option_Rotary.Trigger | AL - Alarm - Rotary - Option | Read | ||
| BV | 587 | Al_Option_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Option | Read | ||
| BV | 588 | Al_Option_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Option | Read | ||
| BV | 589 | Al_Option_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Option | Read | ||
| BV | 590 | Al_Option_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Option | Read | ||
| BV | 591 | Al_Option_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Option | Read | ||
| BV | 592 | Al_Option_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Option | Read | ||
| BV | 593 | Al_Option_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Option | Read | ||
| BV | 594 | Al_Option_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Option | Read | ||
| BV | 595 | Al_Option_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Option | Read | ||
| BV | 596 | Al_Option_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Option | Read | ||
| BV | 597 | Al_Overcurrent_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Over Current | Read | ||
| BV | 598 | Al_Overcurrent_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Over Current | Read | ||
| BV | 599 | Al_Overcurrent_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Over Current | Read | ||
| BV | 600 | Al_Overcurrent_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Over Current | Read | ||
| BV | 601 | Al_Overcurrent_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Over Current | Read | ||
| BV | 602 | Al_Overcurrent_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Over current | Read | ||
| BV | 603 | Al_Overcurrent_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Over Current | Read | ||
| BV | 604 | Al_Overcurrent_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Over Current | Read | ||
| BV | 605 | Al_Overcurrent_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Over Current | Read | ||
| BV | 606 | Al_Overcurrent_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Over Current | Read | ||
| BV | 607 | Al_Overcurrent_Rotary.Trigger | AL - Alarm - Rotary - OverCurrent | Read | ||
| BV | 608 | Al_Overcurrent_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Over current | Read | ||
| BV | 609 | Al_Overcurrent_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Over Current | Read | ||
| BV | 610 | Al_Overcurrent_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Over Current | Read | ||
| BV | 611 | Al_Overcurrent_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Over Current | Read | ||
| BV | 612 | Al_Overcurrent_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Over Current | Read | ||
| BV | 613 | Al_Overcurrent_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Over current | Read | ||
| BV | 614 | Al_Overcurrent_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Over Current | Read | ||
| BV | 615 | Al_Overcurrent_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Over Current | Read | ||
| BV | 616 | Al_Overcurrent_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Over Current | Read | ||
| BV | 617 | Al_Overcurrent_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Over Current | Read | ||
| BV | 618 | Al_OverVolt_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Over Voltage | Read | ||
| BV | 619 | Al_OverVolt_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Over Voltage | Read | ||
| BV | 620 | Al_OverVolt_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Over Voltage | Read | ||
| BV | 621 | Al_OverVolt_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Over Voltage | Read | ||
| BV | 622 | Al_OverVolt_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Over Voltage | Read | ||
| BV | 623 | Al_OverVolt_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Over voltage | Read | ||
| BV | 624 | Al_OverVolt_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Over Voltage | Read | ||
| BV | 625 | Al_OverVolt_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Over Voltage | Read | ||
| BV | 626 | Al_OverVolt_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Over Voltage | Read | ||
| BV | 627 | Al_OverVolt_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Over Voltage | Read | ||
| BV | 628 | Al_OverVolt_Rotary.Trigger | AL - Alarm - Rotary - OverVoltage | Read | ||
| BV | 629 | Al_OverVolt_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Over voltage | Read | ||
| BV | 630 | Al_OverVolt_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Over Voltage | Read | ||
| BV | 631 | Al_OverVolt_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Over Voltage | Read | ||
| BV | 632 | Al_OverVolt_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Over Voltage | Read | ||
| BV | 633 | Al_OverVolt_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Over Voltage | Read | ||
| BV | 634 | Al_OverVolt_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Over voltage | Read | ||
| BV | 635 | Al_OverVolt_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Over Voltage | Read | ||
| BV | 636 | Al_OverVolt_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Over Voltage | Read | ||
| BV | 637 | Al_OverVolt_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Over Voltage | Read | ||
| BV | 638 | Al_OverVolt_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Over Voltage | Read | ||
| BV | 639 | AL_Overvoltage_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - Over voltage | Read | ||
| BV | 640 | AL_Overvoltage_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - Over voltage | Read | ||
| BV | 641 | AL_Overvoltage_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - Over voltage | Read | ||
| BV | 642 | AL_Overvoltage_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - Over voltage | Read | ||
| BV | 643 | AL_Overvoltage_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - Over voltage | Read | ||
| BV | 644 | AL_Overvoltage_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - Over voltage | Read | ||
| BV | 645 | AL_Overvoltage_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - Over voltage | Read | ||
| BV | 646 | AL_Overvoltage_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - Over voltage | Read | ||
| BV | 647 | AL_Overvoltage_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - Over voltage | Read | ||
| BV | 648 | AL_Overvoltage_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - Over voltage | Read | ||
| BV | 649 | AL_Overvoltage_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - Over voltage | Read | ||
| BV | 650 | AL_Overvoltage_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - Over voltage | Read | ||
| BV | 651 | AL_Overvoltage_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - Over voltage | Read | ||
| BV | 652 | AL_Overvoltage_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - Over voltage | Read | ||
| BV | 653 | AL_Overvoltage_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - Over voltage | Read | ||
| BV | 654 | AL_Overvoltage_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - Over voltage | Read | ||
| BV | 655 | AL_Overvoltage_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - Over voltage | Read | ||
| BV | 656 | AL_Overvoltage_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - Over voltage | Read | ||
| BV | 657 | AL_Overvoltage_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - Over voltage | Read | ||
| BV | 658 | AL_Overvoltage_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - Over voltage | Read | ||
| BV | 659 | Al_Ovld_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Over Load | Read | ||
| BV | 660 | Al_Ovld_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Over Load | Read | ||
| BV | 661 | Al_Ovld_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Over Load | Read | ||
| BV | 662 | Al_Ovld_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Over Load | Read | ||
| BV | 663 | Al_Ovld_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Over Load | Read | ||
| BV | 664 | Al_Ovld_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Over load | Read | ||
| BV | 665 | Al_Ovld_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Over Load | Read | ||
| BV | 666 | Al_Ovld_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Over Load | Read | ||
| BV | 667 | Al_Ovld_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Over Load | Read | ||
| BV | 668 | Al_Ovld_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Over Load | Read | ||
| BV | 669 | Al_Ovld_Rotary.Trigger | AL - Alarm - Rotary - OverLoad | Read | ||
| BV | 670 | Al_Ovld_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Over load | Read | ||
| BV | 671 | Al_Ovld_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Over Load | Read | ||
| BV | 672 | Al_Ovld_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Over Load | Read | ||
| BV | 673 | Al_Ovld_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Over Load | Read | ||
| BV | 674 | Al_Ovld_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Over Load | Read | ||
| BV | 675 | Al_Ovld_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Over load | Read | ||
| BV | 676 | Al_Ovld_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Over Load | Read | ||
| BV | 677 | Al_Ovld_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Over Load | Read | ||
| BV | 678 | Al_Ovld_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Over Load | Read | ||
| BV | 679 | Al_Ovld_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Over Load | Read | ||
| BV | 680 | Al_ParamErr_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Parameters Error | Read | ||
| BV | 681 | Al_ParamErr_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Parameters Error | Read | ||
| BV | 682 | Al_ParamErr_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Parameters Error | Read | ||
| BV | 683 | Al_ParamErr_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Parameters Error | Read | ||
| BV | 684 | Al_ParamErr_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Parameters Error | Read | ||
| BV | 685 | Al_ParamErr_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Parameter save Error | Read | ||
| BV | 686 | Al_ParamErr_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Parameters Error | Read | ||
| BV | 687 | Al_ParamErr_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Parameters Error | Read | ||
| BV | 688 | Al_ParamErr_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Parameters Error | Read | ||
| BV | 689 | Al_ParamErr_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Parameters Error | Read | ||
| BV | 690 | Al_ParamErr_Rotary.Trigger | AL - Alarm - Rotary - Parameters Error | Read | ||
| BV | 691 | Al_ParamErr_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Parameter save Error | Read | ||
| BV | 692 | Al_ParamErr_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Parameters Error | Read | ||
| BV | 693 | Al_ParamErr_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Parameters Error | Read | ||
| BV | 694 | Al_ParamErr_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Parameters Error | Read | ||
| BV | 695 | Al_ParamErr_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Parameters Error | Read | ||
| BV | 696 | Al_ParamErr_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Parameter save Error | Read | ||
| BV | 697 | Al_ParamErr_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Parameters Error | Read | ||
| BV | 698 | Al_ParamErr_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Parameters Error | Read | ||
| BV | 699 | Al_ParamErr_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Parameters Error | Read | ||
| BV | 700 | Al_ParamErr_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Parameters Error | Read | ||
| BV | 701 | AL_ParametersCRC_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - Parameters CRC | Read | ||
| BV | 702 | AL_ParametersCRC_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - Parameters CRC | Read | ||
| BV | 703 | AL_ParametersCRC_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - Parameters CRC | Read | ||
| BV | 704 | AL_ParametersCRC_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - Parameters CRC | Read | ||
| BV | 705 | AL_ParametersCRC_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - Parameters CRC | Read | ||
| BV | 706 | AL_ParametersCRC_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - Parameters CRC | Read | ||
| BV | 707 | AL_ParametersCRC_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - Parameters CRC | Read | ||
| BV | 708 | AL_ParametersCRC_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - Parameters CRC | Read | ||
| BV | 709 | AL_ParametersCRC_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - Parameters CRC | Read | ||
| BV | 710 | AL_ParametersCRC_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - Parameters CRC | Read | ||
| BV | 711 | AL_ParametersCRC_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - Parameters CRC | Read | ||
| BV | 712 | AL_ParametersCRC_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - Parameters CRC | Read | ||
| BV | 713 | AL_ParametersCRC_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - Parameters CRC | Read | ||
| BV | 714 | AL_ParametersCRC_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - Parameters CRC | Read | ||
| BV | 715 | AL_ParametersCRC_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - Parameters CRC | Read | ||
| BV | 716 | AL_ParametersCRC_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - Parameters CRC | Read | ||
| BV | 717 | AL_ParametersCRC_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - Parameters CRC | Read | ||
| BV | 718 | AL_ParametersCRC_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - Parameters CRC | Read | ||
| BV | 719 | AL_ParametersCRC_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - Parameters CRC | Read | ||
| BV | 720 | AL_ParametersCRC_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - Parameters CRC | Read | ||
| BV | 721 | AL_PhaseLoss_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - Phase Loss | Read | ||
| BV | 722 | AL_PhaseLoss_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - Phase Loss | Read | ||
| BV | 723 | AL_PhaseLoss_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - Phase Loss | Read | ||
| BV | 724 | AL_PhaseLoss_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - Phase Loss | Read | ||
| BV | 725 | AL_PhaseLoss_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - Phase Loss | Read | ||
| BV | 726 | AL_PhaseLoss_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - Phase Loss | Read | ||
| BV | 727 | AL_PhaseLoss_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - Phase Loss | Read | ||
| BV | 728 | AL_PhaseLoss_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - Phase Loss | Read | ||
| BV | 729 | AL_PhaseLoss_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - Phase Loss | Read | ||
| BV | 730 | AL_PhaseLoss_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - Phase Loss | Read | ||
| BV | 731 | AL_PhaseLoss_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - Phase Loss | Read | ||
| BV | 732 | AL_PhaseLoss_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - Phase Loss | Read | ||
| BV | 733 | AL_PhaseLoss_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - Phase Loss | Read | ||
| BV | 734 | AL_PhaseLoss_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - Phase Loss | Read | ||
| BV | 735 | AL_PhaseLoss_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - Phase Loss | Read | ||
| BV | 736 | AL_PhaseLoss_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - Phase Loss | Read | ||
| BV | 737 | AL_PhaseLoss_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - Phase Loss | Read | ||
| BV | 738 | AL_PhaseLoss_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - Phase Loss | Read | ||
| BV | 739 | AL_PhaseLoss_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - Phase Loss | Read | ||
| BV | 740 | AL_PhaseLoss_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - Phase Loss | Read | ||
| BV | 741 | Al_PhLost_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Phase Lost | Read | ||
| BV | 742 | Al_PhLost_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Phase Lost | Read | ||
| BV | 743 | Al_PhLost_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Phase Lost | Read | ||
| BV | 744 | Al_PhLost_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Phase Lost | Read | ||
| BV | 745 | Al_PhLost_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Phase Lost | Read | ||
| BV | 746 | Al_PhLost_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Phase Lost | Read | ||
| BV | 747 | Al_PhLost_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Phase Lost | Read | ||
| BV | 748 | Al_PhLost_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Phase Lost | Read | ||
| BV | 749 | Al_PhLost_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Phase Lost | Read | ||
| BV | 750 | Al_PhLost_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Phase Lost | Read | ||
| BV | 751 | Al_PhLost_Rotary.Trigger | AL - Alarm - Rotary - Phase Lost | Read | ||
| BV | 752 | Al_PhLost_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Phase Lost | Read | ||
| BV | 753 | Al_PhLost_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Phase Lost | Read | ||
| BV | 754 | Al_PhLost_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Phase Lost | Read | ||
| BV | 755 | Al_PhLost_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Phase Lost | Read | ||
| BV | 756 | Al_PhLost_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Phase Lost | Read | ||
| BV | 757 | Al_PhLost_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Phase Lost | Read | ||
| BV | 758 | Al_PhLost_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Phase Lost | Read | ||
| BV | 759 | Al_PhLost_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Phase Lost | Read | ||
| BV | 760 | Al_PhLost_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Phase Lost | Read | ||
| BV | 761 | Al_PhLost_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Phase Lost | Read | ||
| BV | 762 | Al_PhOpen_ExhFan_1.Trigger | AL - Alarm - Fan Return 1 - Phase Open | Read | ||
| BV | 763 | Al_PhOpen_ExhFan_10.Trigger | AL - Alarm - Fan Return 10 - Phase Open | Read | ||
| BV | 764 | Al_PhOpen_ExhFan_2.Trigger | AL - Alarm - Fan Return 2 - Phase Open | Read | ||
| BV | 765 | Al_PhOpen_ExhFan_3.Trigger | AL - Alarm - Fan Return 3 - Phase Open | Read | ||
| BV | 766 | Al_PhOpen_ExhFan_4.Trigger | AL - Alarm - Fan Return 4 - Phase Open | Read | ||
| BV | 767 | Al_PhOpen_ExhFan_5.Trigger | AL - Alarm - Fan Return 5 - Phase Open | Read | ||
| BV | 768 | Al_PhOpen_ExhFan_6.Trigger | AL - Alarm - Fan Return 6 - Phase Open | Read | ||
| BV | 769 | Al_PhOpen_ExhFan_7.Trigger | AL - Alarm - Fan Return 7 - Phase Open | Read | ||
| BV | 770 | Al_PhOpen_ExhFan_8.Trigger | AL - Alarm - Fan Return 8 - Phase Open | Read | ||
| BV | 771 | Al_PhOpen_ExhFan_9.Trigger | AL - Alarm - Fan Return 9 - Phase Open | Read | ||
| BV | 772 | Al_PhOpen_Rotary.Trigger | AL - Alarm - Rotary - Phase Open | Read | ||
| BV | 773 | Al_PhOpen_SupFan_1.Trigger | AL - Alarm - Fan Supply 1 - Phase Open | Read | ||
| BV | 774 | Al_PhOpen_SupFan_10.Trigger | AL - Alarm - Fan Supply 10 - Phase Open | Read | ||
| BV | 775 | Al_PhOpen_SupFan_2.Trigger | AL - Alarm - Fan Supply 2 - Phase Open | Read | ||
| BV | 776 | Al_PhOpen_SupFan_3.Trigger | AL - Alarm - Fan Supply 3 - Phase Open | Read | ||
| BV | 777 | Al_PhOpen_SupFan_4.Trigger | AL - Alarm - Fan Supply 4 - Phase Open | Read | ||
| BV | 778 | Al_PhOpen_SupFan_5.Trigger | AL - Alarm - Fan Supply 5 - Phase Open | Read | ||
| BV | 779 | Al_PhOpen_SupFan_6.Trigger | AL - Alarm - Fan Supply 6 - Phase Open | Read | ||
| BV | 780 | Al_PhOpen_SupFan_7.Trigger | AL - Alarm - Fan Supply 7 - Phase Open | Read | ||
| BV | 781 | Al_PhOpen_SupFan_8.Trigger | AL - Alarm - Fan Supply 8 - Phase Open | Read | ||
| BV | 782 | Al_PhOpen_SupFan_9.Trigger | AL - Alarm - Fan Supply 9 - Phase Open | Read | ||
| BV | 783 | Al_PreHeatCoilTempPrb.Trigger | AL - Alarm - Probe - Temperature Water PreHeating Coil | Read | ||
| BV | 784 | Al_RDT_Fan.Trigger | AL - Alarm - Fan Group | Read | ||
| BV | 785 | Al_RecSupplyTemp.Trigger | AL - Alarm - Probe - Supply Recovery Temperature | Read | ||
| BV | 786 | Al_ReheatCoilWorkHrsWarn.Trigger | AL - Alarm - ReHeatCoil - Works Hour Warning | Read | ||
| BV | 787 | Al_retain.Trigger | AL - Alarm - Retain | Read | ||
| BV | 788 | Al_RetAir_CO2_Lev_Prb.Trigger | AL - Alarm - Probe - CO2 Return Level Probe | Read | ||
| BV | 789 | Al_RetAirFlwSwWarn.Trigger | AL - Alarm - Probe - Air Flow Return SW Warning | Read | ||
| BV | 790 | Al_RetAirP_Prb.Trigger | AL - Alarm - Probe - Pressure Return Air | Read | ||
| BV | 791 | Al_RetFanWorkHrsWarn.Trigger | AL - Alarm - Fan Return - Works Hour Warning | Read | ||
| BV | 792 | Al_RetFilt.Trigger | AL - Alarm - Filter - Return | Read | ||
| BV | 793 | Al_RetTempPrb.Trigger | AL - Alarm - Probe - Return Temperature | Read | ||
| BV | 794 | Al_SupplyAirFlwSwWarn.Trigger | AL - Alarm - Probe - Supply Air Flow SW Warning | Read | ||
| BV | 795 | Al_SupplyAirP_Prb.Trigger | AL - Alarm - Probe - Supply Air Pressure | Read | ||
| BV | 796 | Al_SupplyFanWorkHrsWarn.Trigger | AL - Alarm - Fan Supply - Works Hour Warning | Read | ||
| BV | 797 | Al_SupplyFilt.Trigger | AL - Alarm - Filter - Supply | Read | ||
| BV | 798 | Al_SupplyTempPrb.Trigger | AL - Alarm - Probe - Supply Temperature | Read | ||
| BV | 799 | Al_SwPrototype.Trigger | AL - Alarm - Software Version - Prototype | Read | ||
| BV | 800 | Al_ThTune_ClkBrd.Trigger | AL - Alarm - HMI Basic - Clock Board | Read | ||
| BV | 801 | Al_ThTune_HumPrb.Trigger | AL - Alarm - HMI Basic - Humidity Probe | Read | ||
| BV | 802 | Al_ThTune_TempPrb.Trigger | AL - Alarm - HMI Basic - Temperature Probe | Read | ||
| BV | 803 | Al_TooHot_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - TooHot | Read | ||
| BV | 804 | Al_TooHot_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - TooHot | Read | ||
| BV | 805 | Al_TooHot_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - TooHot | Read | ||
| BV | 806 | Al_TooHot_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - TooHot | Read | ||
| BV | 807 | Al_TooHot_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - TooHot | Read | ||
| BV | 808 | Al_TooHot_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - TooHot | Read | ||
| BV | 809 | Al_TooHot_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - TooHot | Read | ||
| BV | 810 | Al_TooHot_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - TooHot | Read | ||
| BV | 811 | Al_TooHot_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - TooHot | Read | ||
| BV | 812 | Al_TooHot_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - TooHot | Read | ||
| BV | 813 | Al_TooHot_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - TooHot | Read | ||
| BV | 814 | Al_TooHot_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - TooHot | Read | ||
| BV | 815 | Al_TooHot_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - TooHot | Read | ||
| BV | 816 | Al_TooHot_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - TooHot | Read | ||
| BV | 817 | Al_TooHot_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - TooHot | Read | ||
| BV | 818 | Al_TooHot_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - TooHot | Read | ||
| BV | 819 | Al_TooHot_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - TooHot | Read | ||
| BV | 820 | Al_TooHot_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - TooHot | Read | ||
| BV | 821 | Al_TooHot_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - TooHot | Read | ||
| BV | 822 | Al_TooHot_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - TooHot | Read | ||
| BV | 823 | Al_Undervoltage_EC_ExhFan1.Trigger | AL - Alarm - Fan Return 1 EC - Undervoltage | Read | ||
| BV | 824 | Al_Undervoltage_EC_ExhFan10.Trigger | AL - Alarm - Fan Return 10 EC - Undervoltage | Read | ||
| BV | 825 | Al_Undervoltage_EC_ExhFan2.Trigger | AL - Alarm - Fan Return 2 EC - Undervoltage | Read | ||
| BV | 826 | Al_Undervoltage_EC_ExhFan3.Trigger | AL - Alarm - Fan Return 3 EC - Undervoltage | Read | ||
| BV | 827 | Al_Undervoltage_EC_ExhFan4.Trigger | AL - Alarm - Fan Return 4 EC - Undervoltage | Read | ||
| BV | 828 | Al_Undervoltage_EC_ExhFan5.Trigger | AL - Alarm - Fan Return 5 EC - Undervoltage | Read | ||
| BV | 829 | Al_Undervoltage_EC_ExhFan6.Trigger | AL - Alarm - Fan Return 6 EC - Undervoltage | Read | ||
| BV | 830 | Al_Undervoltage_EC_ExhFan7.Trigger | AL - Alarm - Fan Return 7 EC - Undervoltage | Read | ||
| BV | 831 | Al_Undervoltage_EC_ExhFan8.Trigger | AL - Alarm - Fan Return 8 EC - Undervoltage | Read | ||
| BV | 832 | Al_Undervoltage_EC_ExhFan9.Trigger | AL - Alarm - Fan Return 9 EC - Undervoltage | Read | ||
| BV | 833 | Al_Undervoltage_EC_SupFan1.Trigger | AL - Alarm - Fan Supply 1 EC - Undervoltage | Read | ||
| BV | 834 | Al_Undervoltage_EC_SupFan10.Trigger | AL - Alarm - Fan Supply 10 EC - Undervoltage | Read | ||
| BV | 835 | Al_Undervoltage_EC_SupFan2.Trigger | AL - Alarm - Fan Supply 2 EC - Undervoltage | Read | ||
| BV | 836 | Al_Undervoltage_EC_SupFan3.Trigger | AL - Alarm - Fan Supply 3 EC - Undervoltage | Read | ||
| BV | 837 | Al_Undervoltage_EC_SupFan4.Trigger | AL - Alarm - Fan Supply 4 EC - Undervoltage | Read | ||
| BV | 838 | Al_Undervoltage_EC_SupFan5.Trigger | AL - Alarm - Fan Supply 5 EC - Undervoltage | Read | ||
| BV | 839 | Al_Undervoltage_EC_SupFan6.Trigger | AL - Alarm - Fan Supply 6 EC - Undervoltage | Read | ||
| BV | 840 | Al_Undervoltage_EC_SupFan7.Trigger | AL - Alarm - Fan Supply 7 EC - Undervoltage | Read | ||
| BV | 841 | Al_Undervoltage_EC_SupFan8.Trigger | AL - Alarm - Fan Supply 8 EC - Undervoltage | Read | ||
| BV | 842 | Al_Undervoltage_EC_SupFan9.Trigger | AL - Alarm - Fan Supply 9 EC - Undervoltage | Read | ||
| BV | 843 | CfgErrAlrm.Trigger | AL - Alarm - Device - Wrong configuration | Read | ||
| BV | 844 | OfflineAlrm.Trigger | AL - Alarm - Device - Offline | Read | ||
| BVmin | 845 | AlarmMng.AlrmResByBms | AL - Alarm - BMS - Reset | Write | 0=; 1=RESET | |
| BV | 846 | Al_ABB_ExhFan_1.Active | AL - Alarm - Fan Return 1 | Read | ||
| BV | 847 | Al_ABB_ExhFan_10.Active | AL - Alarm - Fan Return 10 | Read | ||
| BV | 848 | Al_ABB_ExhFan_2.Active | AL - Alarm - Fan Return 2 | Read | ||
| BV | 849 | Al_ABB_ExhFan_3.Active | AL - Alarm - Fan Return 3 | Read | ||
| BV | 850 | Al_ABB_ExhFan_4.Active | AL - Alarm - Fan Return 4 | Read | ||
| BV | 851 | Al_ABB_ExhFan_5.Active | AL - Alarm - Fan Return 5 | Read | ||
| BV | 852 | Al_ABB_ExhFan_6.Active | AL - Alarm - Fan Return 6 | Read | ||
| BV | 853 | Al_ABB_ExhFan_7.Active | AL - Alarm - Fan Return 7 | Read | ||
| BV | 854 | Al_ABB_ExhFan_8.Active | AL - Alarm - Fan Return 8 | Read | ||
| BV | 855 | Al_ABB_ExhFan_9.Active | AL - Alarm - Fan Return 9 | Read | ||
| BV | 856 | Al_ABB_Rotary.Active | AL - Alarm - Rotary | Read | ||
| BV | 857 | Al_ABB_SupFan_1.Active | AL - Alarm - Fan Supply 1 | Read | ||
| BV | 858 | Al_ABB_SupFan_10.Active | AL - Alarm - Fan Supply 10 | Read | ||
| BV | 859 | Al_ABB_SupFan_2.Active | AL - Alarm - Fan Supply 2 | Read | ||
| BV | 860 | Al_ABB_SupFan_3.Active | AL - Alarm - Fan Supply 3 | Read | ||
| BV | 861 | Al_ABB_SupFan_4.Active | AL - Alarm - Fan Supply 4 | Read | ||
| BV | 862 | Al_ABB_SupFan_5.Active | AL - Alarm - Fan Supply 5 | Read | ||
| BV | 863 | Al_ABB_SupFan_6.Active | AL - Alarm - Fan Supply 6 | Read | ||
| BV | 864 | Al_ABB_SupFan_7.Active | AL - Alarm - Fan Supply 7 | Read | ||
| BV | 865 | Al_ABB_SupFan_8.Active | AL - Alarm - Fan Supply 8 | Read | ||
| BV | 866 | Al_ABB_SupFan_9.Active | AL - Alarm - Fan Supply 9 | Read | ||
| BV | 867 | Al_AFreezeDIN.Active | AL - Alarm - Antifreeze - Digital Input | Read | ||
| BV | 868 | Al_AFreezePRB.Active | AL - Alarm - Antifreeze - Back Water Temperature | Read | ||
| BV | 869 | Al_AFreezePreHeatPRB.Active | AL - Alarm - Antifreeze - PreHeat Back Water Temperature | Read | ||
| BV | 870 | Al_AfterPreHeatCoilTempPrb.Active | AL - Alarm - Probe - After preheating coil temperature | Read | ||
| BV | 871 | Al_BMS_Offline.Active | AL - Alarm - BMS - Offline | Read | ||
| BV | 872 | Al_CfgError_cpCOe.Active | AL - Alarm - Module IO - cPCOE - Configuration error | Read | ||
| BV | 873 | Al_CircuitFault_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - Circuit Fault | Read | ||
| BV | 874 | Al_CircuitFault_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - Circuit Fault | Read | ||
| BV | 875 | Al_CircuitFault_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - Circuit Fault | Read | ||
| BV | 876 | Al_CircuitFault_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - Circuit Fault | Read | ||
| BV | 877 | Al_CircuitFault_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - Circuit Fault | Read | ||
| BV | 878 | Al_CircuitFault_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - Circuit Fault | Read | ||
| BV | 879 | Al_CircuitFault_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - Circuit Fault | Read | ||
| BV | 880 | Al_CircuitFault_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - Circuit Fault | Read | ||
| BV | 881 | Al_CircuitFault_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - Circuit Fault | Read | ||
| BV | 882 | Al_CircuitFault_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - Circuit Fault | Read | ||
| BV | 883 | Al_CircuitFault_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - Circuit Fault | Read | ||
| BV | 884 | Al_CircuitFault_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - Circuit Fault | Read | ||
| BV | 885 | Al_CircuitFault_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - Circuit Fault | Read | ||
| BV | 886 | Al_CircuitFault_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - Circuit Fault | Read | ||
| BV | 887 | Al_CircuitFault_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - Circuit Fault | Read | ||
| BV | 888 | Al_CircuitFault_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - Circuit Fault | Read | ||
| BV | 889 | Al_CircuitFault_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - Circuit Fault | Read | ||
| BV | 890 | Al_CircuitFault_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - Circuit Fault | Read | ||
| BV | 891 | Al_CircuitFault_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - Circuit Fault | Read | ||
| BV | 892 | Al_CircuitFault_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - Circuit Fault | Read | ||
| BV | 893 | Al_CommErr_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Communication Error | Read | ||
| BV | 894 | Al_CommErr_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Communication Error | Read | ||
| BV | 895 | Al_CommErr_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Communication Error | Read | ||
| BV | 896 | Al_CommErr_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Communication Error | Read | ||
| BV | 897 | Al_CommErr_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Communication Error | Read | ||
| BV | 898 | Al_CommErr_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Communication Error | Read | ||
| BV | 899 | Al_CommErr_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Communication Error | Read | ||
| BV | 900 | Al_CommErr_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Communication Error | Read | ||
| BV | 901 | Al_CommErr_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Communication Error | Read | ||
| BV | 902 | Al_CommErr_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Communication Error | Read | ||
| BV | 903 | Al_CommErr_Rotary.Active | AL - Alarm - Rotary - CommUnitation Error | Read | ||
| BV | 904 | Al_CommErr_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Communication Error | Read | ||
| BV | 905 | Al_CommErr_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Communication Error | Read | ||
| BV | 906 | Al_CommErr_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Communication Error | Read | ||
| BV | 907 | Al_CommErr_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Communication Error | Read | ||
| BV | 908 | Al_CommErr_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Communication Error | Read | ||
| BV | 909 | Al_CommErr_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Communication Error | Read | ||
| BV | 910 | Al_CommErr_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Communication Error | Read | ||
| BV | 911 | Al_CommErr_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Communication Error | Read | ||
| BV | 912 | Al_CommErr_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Communication Error | Read | ||
| BV | 913 | Al_CommErr_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Communication Error | Read | ||
| BV | 914 | Al_Cool.Active | AL - Alarm - Cooling - Device Alarm | Read | ||
| BV | 915 | Al_CoolFanFault_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Cooling Fan Fault | Read | ||
| BV | 916 | Al_CoolFanFault_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Cooling Fan Fault | Read | ||
| BV | 917 | Al_CoolFanFault_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Cooling Fan Fault | Read | ||
| BV | 918 | Al_CoolFanFault_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Cooling Fan Fault | Read | ||
| BV | 919 | Al_CoolFanFault_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Cooling Fan Fault | Read | ||
| BV | 920 | Al_CoolFanFault_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Cooling Fan Fault | Read | ||
| BV | 921 | Al_CoolFanFault_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Cooling Fan Fault | Read | ||
| BV | 922 | Al_CoolFanFault_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Cooling Fan Fault | Read | ||
| BV | 923 | Al_CoolFanFault_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Cooling Fan Fault | Read | ||
| BV | 924 | Al_CoolFanFault_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Cooling Fan Fault | Read | ||
| BV | 925 | Al_CoolFanFault_Rotary.Active | AL - Alarm - Rotary - Cooling Fan Fault | Read | ||
| BV | 926 | Al_CoolFanFault_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Cooling Fan Fault | Read | ||
| BV | 927 | Al_CoolFanFault_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Cooling Fan Fault | Read | ||
| BV | 928 | Al_CoolFanFault_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Cooling Fan Fault | Read | ||
| BV | 929 | Al_CoolFanFault_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Cooling Fan Fault | Read | ||
| BV | 930 | Al_CoolFanFault_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Cooling Fan Fault | Read | ||
| BV | 931 | Al_CoolFanFault_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Cooling Fan Fault | Read | ||
| BV | 932 | Al_CoolFanFault_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Cooling Fan Fault | Read | ||
| BV | 933 | Al_CoolFanFault_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Cooling Fan Fault | Read | ||
| BV | 934 | Al_CoolFanFault_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Cooling Fan Fault | Read | ||
| BV | 935 | Al_CoolFanFault_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Cooling Fan Fault | Read | ||
| BV | 936 | Al_CutOff_ExhFan_1.Active | AL - Alarm - Fan Return 1 - CutOff | Read | ||
| BV | 937 | Al_CutOff_ExhFan_10.Active | AL - Alarm - Fan Return 10 - CutOff | Read | ||
| BV | 938 | Al_CutOff_ExhFan_2.Active | AL - Alarm - Fan Return 2 - CutOff | Read | ||
| BV | 939 | Al_CutOff_ExhFan_3.Active | AL - Alarm - Fan Return 3 - CutOff | Read | ||
| BV | 940 | Al_CutOff_ExhFan_4.Active | AL - Alarm - Fan Return 4 - CutOff | Read | ||
| BV | 941 | Al_CutOff_ExhFan_5.Active | AL - Alarm - Fan Return 5 - CutOff | Read | ||
| BV | 942 | Al_CutOff_ExhFan_6.Active | AL - Alarm - Fan Return 6 - CutOff | Read | ||
| BV | 943 | Al_CutOff_ExhFan_7.Active | AL - Alarm - Fan Return 7 - CutOff | Read | ||
| BV | 944 | Al_CutOff_ExhFan_8.Active | AL - Alarm - Fan Return 8 - CutOff | Read | ||
| BV | 945 | Al_CutOff_ExhFan_9.Active | AL - Alarm - Fan Return 9 - CutOff | Read | ||
| BV | 946 | Al_CutOff_Rotary.Active | AL - Alarm - Rotary - CutOff | Read | ||
| BV | 947 | Al_CutOff_SupFan_1.Active | AL - Alarm - Fan Supply 1 - CutOff | Read | ||
| BV | 948 | Al_CutOff_SupFan_10.Active | AL - Alarm - Fan Supply 10 - CutOff | Read | ||
| BV | 949 | Al_CutOff_SupFan_2.Active | AL - Alarm - Fan Supply 2 - CutOff | Read | ||
| BV | 950 | Al_CutOff_SupFan_3.Active | AL - Alarm - Fan Supply 3 - CutOff | Read | ||
| BV | 951 | Al_CutOff_SupFan_4.Active | AL - Alarm - Fan Supply 4 - CutOff | Read | ||
| BV | 952 | Al_CutOff_SupFan_5.Active | AL - Alarm - Fan Supply 5 - CutOff | Read | ||
| BV | 953 | Al_CutOff_SupFan_6.Active | AL - Alarm - Fan Supply 6 - CutOff | Read | ||
| BV | 954 | Al_CutOff_SupFan_7.Active | AL - Alarm - Fan Supply 7 - CutOff | Read | ||
| BV | 955 | Al_CutOff_SupFan_8.Active | AL - Alarm - Fan Supply 8 - CutOff | Read | ||
| BV | 956 | Al_CutOff_SupFan_9.Active | AL - Alarm - Fan Supply 9 - CutOff | Read | ||
| BV | 957 | Al_DC_Ovld_ExhFan_1.Active | AL - Alarm - Fan Return 1 - DC Over load | Read | ||
| BV | 958 | Al_DC_Ovld_ExhFan_10.Active | AL - Alarm - Fan Return 10 - DC Over load | Read | ||
| BV | 959 | Al_DC_Ovld_ExhFan_2.Active | AL - Alarm - Fan Return 2 - DC Over load | Read | ||
| BV | 960 | Al_DC_Ovld_ExhFan_3.Active | AL - Alarm - Fan Return 3 - DC Over load | Read | ||
| BV | 961 | Al_DC_Ovld_ExhFan_4.Active | AL - Alarm - Fan Return 4 - DC Over load | Read | ||
| BV | 962 | Al_DC_Ovld_ExhFan_5.Active | AL - Alarm - Fan Return 5 - DC Over load | Read | ||
| BV | 963 | Al_DC_Ovld_ExhFan_6.Active | AL - Alarm - Fan Return 6 - DC Over load | Read | ||
| BV | 964 | Al_DC_Ovld_ExhFan_7.Active | AL - Alarm - Fan Return 7 - DC Over load | Read | ||
| BV | 965 | Al_DC_Ovld_ExhFan_8.Active | AL - Alarm - Fan Return 8 - DC Over load | Read | ||
| BV | 966 | Al_DC_Ovld_ExhFan_9.Active | AL - Alarm - Fan Return 9 - DC Over load | Read | ||
| BV | 967 | Al_DC_Ovld_Rotary.Active | AL - Alarm - Rotary - DC Overload | Read | ||
| BV | 968 | Al_DC_Ovld_SupFan_1.Active | AL - Alarm - Fan Supply 1 - DC Over load | Read | ||
| BV | 969 | Al_DC_Ovld_SupFan_10.Active | AL - Alarm - Fan Supply 10 - DC Over load | Read | ||
| BV | 970 | Al_DC_Ovld_SupFan_2.Active | AL - Alarm - Fan Supply 2 - DC Over load | Read | ||
| BV | 971 | Al_DC_Ovld_SupFan_3.Active | AL - Alarm - Fan Supply 3 - DC Over load | Read | ||
| BV | 972 | Al_DC_Ovld_SupFan_4.Active | AL - Alarm - Fan Supply 4 - DC Over load | Read | ||
| BV | 973 | Al_DC_Ovld_SupFan_5.Active | AL - Alarm - Fan Supply 5 - DC Over load | Read | ||
| BV | 974 | Al_DC_Ovld_SupFan_6.Active | AL - Alarm - Fan Supply 6 - DC Over load | Read | ||
| BV | 975 | Al_DC_Ovld_SupFan_7.Active | AL - Alarm - Fan Supply 7 - DC Over load | Read | ||
| BV | 976 | Al_DC_Ovld_SupFan_8.Active | AL - Alarm - Fan Supply 8 - DC Over load | Read | ||
| BV | 977 | Al_DC_Ovld_SupFan_9.Active | AL - Alarm - Fan Supply 9 - DC Over load | Read | ||
| BV | 978 | Al_ElectTherm_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Electric Thermal | Read | ||
| BV | 979 | Al_ElectTherm_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Electric Thermal | Read | ||
| BV | 980 | Al_ElectTherm_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Electric Thermal | Read | ||
| BV | 981 | Al_ElectTherm_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Electric Thermal | Read | ||
| BV | 982 | Al_ElectTherm_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Electric Thermal | Read | ||
| BV | 983 | Al_ElectTherm_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Electric Thermal | Read | ||
| BV | 984 | Al_ElectTherm_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Electric Thermal | Read | ||
| BV | 985 | Al_ElectTherm_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Electric Thermal | Read | ||
| BV | 986 | Al_ElectTherm_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Electric Thermal | Read | ||
| BV | 987 | Al_ElectTherm_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Electric Thermal | Read | ||
| BV | 988 | Al_ElectTherm_Rotary.Active | AL - Alarm - Rotary - Electric Thermal | Read | ||
| BV | 989 | Al_ElectTherm_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Electric Thermal | Read | ||
| BV | 990 | Al_ElectTherm_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Electric Thermal | Read | ||
| BV | 991 | Al_ElectTherm_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Electric Thermal | Read | ||
| BV | 992 | Al_ElectTherm_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Electric Thermal | Read | ||
| BV | 993 | Al_ElectTherm_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Electric Thermal | Read | ||
| BV | 994 | Al_ElectTherm_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Electric Thermal | Read | ||
| BV | 995 | Al_ElectTherm_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Electric Thermal | Read | ||
| BV | 996 | Al_ElectTherm_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Electric Thermal | Read | ||
| BV | 997 | Al_ElectTherm_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Electric Thermal | Read | ||
| BV | 998 | Al_ElectTherm_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Electric Thermal | Read | ||
| BV | 999 | Al_Err_retain_write.Active | AL - Alarm - Error retain write | Read | ||
| BV | 1000 | Al_ExhTempPrb.Active | AL - Alarm - Probe - Temperature Exhaust | Read | ||
| BV | 1001 | Al_ExtFaultA_ExhFan_1.Active | AL - Alarm - Fan Return 1 - External Fault A | Read | ||
| BV | 1002 | Al_ExtFaultA_ExhFan_10.Active | AL - Alarm - Fan Return 10 - External Fault A | Read | ||
| BV | 1003 | Al_ExtFaultA_ExhFan_2.Active | AL - Alarm - Fan Return 2 - External Fault A | Read | ||
| BV | 1004 | Al_ExtFaultA_ExhFan_3.Active | AL - Alarm - Fan Return 3 - External Fault A | Read | ||
| BV | 1005 | Al_ExtFaultA_ExhFan_4.Active | AL - Alarm - Fan Return 4 - External Fault A | Read | ||
| BV | 1006 | Al_ExtFaultA_ExhFan_5.Active | AL - Alarm - Fan Return 5 - External Fault A | Read | ||
| BV | 1007 | Al_ExtFaultA_ExhFan_6.Active | AL - Alarm - Fan Return 6 - External Fault A | Read | ||
| BV | 1008 | Al_ExtFaultA_ExhFan_7.Active | AL - Alarm - Fan Return 7 - External Fault A | Read | ||
| BV | 1009 | Al_ExtFaultA_ExhFan_8.Active | AL - Alarm - Fan Return 8 - External Fault A | Read | ||
| BV | 1010 | Al_ExtFaultA_ExhFan_9.Active | AL - Alarm - Fan Return 9 - External Fault A | Read | ||
| BV | 1011 | Al_ExtFaultA_Rotary.Active | AL - Alarm - Rotary - External Fault A | Read | ||
| BV | 1012 | Al_ExtFaultA_SupFan_1.Active | AL - Alarm - Fan Supply 1 - External Fault A | Read | ||
| BV | 1013 | Al_ExtFaultA_SupFan_10.Active | AL - Alarm - Fan Supply 10 - External Fault A | Read | ||
| BV | 1014 | Al_ExtFaultA_SupFan_2.Active | AL - Alarm - Fan Supply 2 - External Fault A | Read | ||
| BV | 1015 | Al_ExtFaultA_SupFan_3.Active | AL - Alarm - Fan Supply 3 - External Fault A | Read | ||
| BV | 1016 | Al_ExtFaultA_SupFan_4.Active | AL - Alarm - Fan Supply 4 - External Fault A | Read | ||
| BV | 1017 | Al_ExtFaultA_SupFan_5.Active | AL - Alarm - Fan Supply 5 - External Fault A | Read | ||
| BV | 1018 | Al_ExtFaultA_SupFan_6.Active | AL - Alarm - Fan Supply 6 - External Fault A | Read | ||
| BV | 1019 | Al_ExtFaultA_SupFan_7.Active | AL - Alarm - Fan Supply 7 - External Fault A | Read | ||
| BV | 1020 | Al_ExtFaultA_SupFan_8.Active | AL - Alarm - Fan Supply 8 - External Fault A | Read | ||
| BV | 1021 | Al_ExtFaultA_SupFan_9.Active | AL - Alarm - Fan Supply 9 - External Fault A | Read | ||
| BV | 1022 | Al_ExtFaultB_ExhFan_1.Active | AL - Alarm - Fan Return 1 - External Fault B | Read | ||
| BV | 1023 | Al_ExtFaultB_ExhFan_10.Active | AL - Alarm - Fan Return 10 - External Fault B | Read | ||
| BV | 1024 | Al_ExtFaultB_ExhFan_2.Active | AL - Alarm - Fan Return 2 - External Fault B | Read | ||
| BV | 1025 | Al_ExtFaultB_ExhFan_3.Active | AL - Alarm - Fan Return 3 - External Fault B | Read | ||
| BV | 1026 | Al_ExtFaultB_ExhFan_4.Active | AL - Alarm - Fan Return 4 - External Fault B | Read | ||
| BV | 1027 | Al_ExtFaultB_ExhFan_5.Active | AL - Alarm - Fan Return 5 - External Fault B | Read | ||
| BV | 1028 | Al_ExtFaultB_ExhFan_6.Active | AL - Alarm - Fan Return 6 - External Fault B | Read | ||
| BV | 1029 | Al_ExtFaultB_ExhFan_7.Active | AL - Alarm - Fan Return 7 - External Fault B | Read | ||
| BV | 1030 | Al_ExtFaultB_ExhFan_8.Active | AL - Alarm - Fan Return 8 - External Fault B | Read | ||
| BV | 1031 | Al_ExtFaultB_ExhFan_9.Active | AL - Alarm - Fan Return 9 - External Fault B | Read | ||
| BV | 1032 | Al_ExtFaultB_Rotary.Active | AL - Alarm - Rotary - External Fault B | Read | ||
| BV | 1033 | Al_ExtFaultB_SupFan_1.Active | AL - Alarm - Fan Supply 1 - External Fault B | Read | ||
| BV | 1034 | Al_ExtFaultB_SupFan_10.Active | AL - Alarm - Fan Supply 10 - External Fault B | Read | ||
| BV | 1035 | Al_ExtFaultB_SupFan_2.Active | AL - Alarm - Fan Supply 2 - External Fault B | Read | ||
| BV | 1036 | Al_ExtFaultB_SupFan_3.Active | AL - Alarm - Fan Supply 3 - External Fault B | Read | ||
| BV | 1037 | Al_ExtFaultB_SupFan_4.Active | AL - Alarm - Fan Supply 4 - External Fault B | Read | ||
| BV | 1038 | Al_ExtFaultB_SupFan_5.Active | AL - Alarm - Fan Supply 5 - External Fault B | Read | ||
| BV | 1039 | Al_ExtFaultB_SupFan_6.Active | AL - Alarm - Fan Supply 6 - External Fault B | Read | ||
| BV | 1040 | Al_ExtFaultB_SupFan_7.Active | AL - Alarm - Fan Supply 7 - External Fault B | Read | ||
| BV | 1041 | Al_ExtFaultB_SupFan_8.Active | AL - Alarm - Fan Supply 8 - External Fault B | Read | ||
| BV | 1042 | Al_ExtFaultB_SupFan_9.Active | AL - Alarm - Fan Supply 9 - External Fault B | Read | ||
| BV | 1043 | Al_ExtTempPrb.Active | AL - Alarm - Probe - Temperature External | Read | ||
| BV | 1044 | Al_Fire.Active | AL - Alarm - Fire | Read | ||
| BV | 1045 | Al_FireExh.Active | AL - Alarm - Fire - Return Temperature | Read | ||
| BV | 1046 | Al_GroundFault_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Ground Fault | Read | ||
| BV | 1047 | Al_GroundFault_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Ground Fault | Read | ||
| BV | 1048 | Al_GroundFault_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Ground Fault | Read | ||
| BV | 1049 | Al_GroundFault_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Ground Fault | Read | ||
| BV | 1050 | Al_GroundFault_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Ground Fault | Read | ||
| BV | 1051 | Al_GroundFault_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Ground Fault | Read | ||
| BV | 1052 | Al_GroundFault_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Ground Fault | Read | ||
| BV | 1053 | Al_GroundFault_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Ground Fault | Read | ||
| BV | 1054 | Al_GroundFault_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Ground Fault | Read | ||
| BV | 1055 | Al_GroundFault_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Ground Fault | Read | ||
| BV | 1056 | Al_GroundFault_Rotary.Active | AL - Alarm - Rotary - Ground Fault | Read | ||
| BV | 1057 | Al_GroundFault_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Ground Fault | Read | ||
| BV | 1058 | Al_GroundFault_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Ground Fault | Read | ||
| BV | 1059 | Al_GroundFault_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Ground Fault | Read | ||
| BV | 1060 | Al_GroundFault_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Ground Fault | Read | ||
| BV | 1061 | Al_GroundFault_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Ground Fault | Read | ||
| BV | 1062 | Al_GroundFault_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Ground Fault | Read | ||
| BV | 1063 | Al_GroundFault_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Ground Fault | Read | ||
| BV | 1064 | Al_GroundFault_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Ground Fault | Read | ||
| BV | 1065 | Al_GroundFault_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Ground Fault | Read | ||
| BV | 1066 | Al_GroundFault_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Ground Fault | Read | ||
| BV | 1067 | Al_Heat.Active | AL - Alarm - Heating - Device Alarm | Read | ||
| BV | 1068 | Al_HeatCoilTempPrb.Active | AL - Alarm - Probe - Temperature Water Heating coil | Read | ||
| BV | 1069 | Al_HeatExchgWorkHrsWarn.Active | AL - Alarm - HeatExchanger - HeatExchanger Works Hour Warning | Read | ||
| BV | 1070 | Al_HeatSink_ExhFan_1.Active | AL - Alarm - Fan Return 1 - HeatSink | Read | ||
| BV | 1071 | Al_HeatSink_ExhFan_10.Active | AL - Alarm - Fan Return 10 - HeatSink | Read | ||
| BV | 1072 | Al_HeatSink_ExhFan_2.Active | AL - Alarm - Fan Return 2 - HeatSink | Read | ||
| BV | 1073 | Al_HeatSink_ExhFan_3.Active | AL - Alarm - Fan Return 3 - HeatSink | Read | ||
| BV | 1074 | Al_HeatSink_ExhFan_4.Active | AL - Alarm - Fan Return 4 - HeatSink | Read | ||
| BV | 1075 | Al_HeatSink_ExhFan_5.Active | AL - Alarm - Fan Return 5 - HeatSink | Read | ||
| BV | 1076 | Al_HeatSink_ExhFan_6.Active | AL - Alarm - Fan Return 6 - HeatSink | Read | ||
| BV | 1077 | Al_HeatSink_ExhFan_7.Active | AL - Alarm - Fan Return 7 - HeatSink | Read | ||
| BV | 1078 | Al_HeatSink_ExhFan_8.Active | AL - Alarm - Fan Return 8 - HeatSink | Read | ||
| BV | 1079 | Al_HeatSink_ExhFan_9.Active | AL - Alarm - Fan Return 9 - HeatSink | Read | ||
| BV | 1080 | Al_HeatSink_Rotary.Active | AL - Alarm - Rotary - HeatSink | Read | ||
| BV | 1081 | Al_HeatSink_SupFan_1.Active | AL - Alarm - Fan Supply 1 - HeatSink | Read | ||
| BV | 1082 | Al_HeatSink_SupFan_10.Active | AL - Alarm - Fan Supply 10 - HeatSink | Read | ||
| BV | 1083 | Al_HeatSink_SupFan_2.Active | AL - Alarm - Fan Supply 2 - HeatSink | Read | ||
| BV | 1084 | Al_HeatSink_SupFan_3.Active | AL - Alarm - Fan Supply 3 - HeatSink | Read | ||
| BV | 1085 | Al_HeatSink_SupFan_4.Active | AL - Alarm - Fan Supply 4 - HeatSink | Read | ||
| BV | 1086 | Al_HeatSink_SupFan_5.Active | AL - Alarm - Fan Supply 5 - HeatSink | Read | ||
| BV | 1087 | Al_HeatSink_SupFan_6.Active | AL - Alarm - Fan Supply 6 - HeatSink | Read | ||
| BV | 1088 | Al_HeatSink_SupFan_7.Active | AL - Alarm - Fan Supply 7 - HeatSink | Read | ||
| BV | 1089 | Al_HeatSink_SupFan_8.Active | AL - Alarm - Fan Supply 8 - HeatSink | Read | ||
| BV | 1090 | Al_HeatSink_SupFan_9.Active | AL - Alarm - Fan Supply 9 - HeatSink | Read | ||
| BV | 1091 | AL_Hot_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - Hot | Read | ||
| BV | 1092 | AL_Hot_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - Hot | Read | ||
| BV | 1093 | AL_Hot_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - Hot | Read | ||
| BV | 1094 | AL_Hot_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - Hot | Read | ||
| BV | 1095 | AL_Hot_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - Hot | Read | ||
| BV | 1096 | AL_Hot_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - Hot | Read | ||
| BV | 1097 | AL_Hot_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - Hot | Read | ||
| BV | 1098 | AL_Hot_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - Hot | Read | ||
| BV | 1099 | AL_Hot_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - Hot | Read | ||
| BV | 1100 | AL_Hot_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - Hot | Read | ||
| BV | 1101 | AL_Hot_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - Hot | Read | ||
| BV | 1102 | AL_Hot_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - Hot | Read | ||
| BV | 1103 | AL_Hot_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - Hot | Read | ||
| BV | 1104 | AL_Hot_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - Hot | Read | ||
| BV | 1105 | AL_Hot_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - Hot | Read | ||
| BV | 1106 | AL_Hot_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - Hot | Read | ||
| BV | 1107 | AL_Hot_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - Hot | Read | ||
| BV | 1108 | AL_Hot_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - Hot | Read | ||
| BV | 1109 | AL_Hot_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - Hot | Read | ||
| BV | 1110 | AL_Hot_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - Hot | Read | ||
| BV | 1111 | Al_Hum.Active | AL - Alarm - Humidifier | Read | ||
| BV | 1112 | Al_HumWorkHrsWarn.Active | AL - Alarm - Humidity - Works Hour Warning | Read | ||
| BV | 1113 | Al_HW_Fault_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Hardware Fault | Read | ||
| BV | 1114 | Al_HW_Fault_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Hardware Fault | Read | ||
| BV | 1115 | Al_HW_Fault_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Hardware Fault | Read | ||
| BV | 1116 | Al_HW_Fault_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Hardware Fault | Read | ||
| BV | 1117 | Al_HW_Fault_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Hardware Fault | Read | ||
| BV | 1118 | Al_HW_Fault_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Hardware Fault | Read | ||
| BV | 1119 | Al_HW_Fault_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Hardware Fault | Read | ||
| BV | 1120 | Al_HW_Fault_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Hardware Fault | Read | ||
| BV | 1121 | Al_HW_Fault_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Hardware Fault | Read | ||
| BV | 1122 | Al_HW_Fault_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Hardware Fault | Read | ||
| BV | 1123 | Al_HW_Fault_Rotary.Active | AL - Alarm - Rotary - Hardware Fault | Read | ||
| BV | 1124 | Al_HW_Fault_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Hardware Fault | Read | ||
| BV | 1125 | Al_HW_Fault_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Hardware Fault | Read | ||
| BV | 1126 | Al_HW_Fault_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Hardware Fault | Read | ||
| BV | 1127 | Al_HW_Fault_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Hardware Fault | Read | ||
| BV | 1128 | Al_HW_Fault_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Hardware Fault | Read | ||
| BV | 1129 | Al_HW_Fault_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Hardware Fault | Read | ||
| BV | 1130 | Al_HW_Fault_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Hardware Fault | Read | ||
| BV | 1131 | Al_HW_Fault_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Hardware Fault | Read | ||
| BV | 1132 | Al_HW_Fault_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Hardware Fault | Read | ||
| BV | 1133 | Al_HW_Fault_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Hardware Fault | Read | ||
| BV | 1134 | Al_I2RIGBTFault_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - I2RIGBT Fault | Read | ||
| BV | 1135 | Al_I2RIGBTFault_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - I2RIGBT Fault | Read | ||
| BV | 1136 | Al_I2RIGBTFault_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - I2RIGBT Fault | Read | ||
| BV | 1137 | Al_I2RIGBTFault_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - I2RIGBT Fault | Read | ||
| BV | 1138 | Al_I2RIGBTFault_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - I2RIGBT Fault | Read | ||
| BV | 1139 | Al_I2RIGBTFault_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - I2RIGBT Fault | Read | ||
| BV | 1140 | Al_I2RIGBTFault_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - I2RIGBT Fault | Read | ||
| BV | 1141 | Al_I2RIGBTFault_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - I2RIGBT Fault | Read | ||
| BV | 1142 | Al_I2RIGBTFault_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - I2RIGBT Fault | Read | ||
| BV | 1143 | Al_I2RIGBTFault_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - I2RIGBT Fault | Read | ||
| BV | 1144 | Al_I2RIGBTFault_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - I2RIGBT Fault | Read | ||
| BV | 1145 | Al_I2RIGBTFault_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - I2RIGBT Fault | Read | ||
| BV | 1146 | Al_I2RIGBTFault_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - I2RIGBT Fault | Read | ||
| BV | 1147 | Al_I2RIGBTFault_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - I2RIGBT Fault | Read | ||
| BV | 1148 | Al_I2RIGBTFault_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - I2RIGBT Fault | Read | ||
| BV | 1149 | Al_I2RIGBTFault_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - I2RIGBT Fault | Read | ||
| BV | 1150 | Al_I2RIGBTFault_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - I2RIGBT Fault | Read | ||
| BV | 1151 | Al_I2RIGBTFault_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - I2RIGBT Fault | Read | ||
| BV | 1152 | Al_I2RIGBTFault_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - I2RIGBT Fault | Read | ||
| BV | 1153 | Al_I2RIGBTFault_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - I2RIGBT Fault | Read | ||
| BV | 1154 | AL_IGBTOvercurrent_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - IGBT Over current | Read | ||
| BV | 1155 | AL_IGBTOvercurrent_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - IGBT Over current | Read | ||
| BV | 1156 | AL_IGBTOvercurrent_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - IGBT Over current | Read | ||
| BV | 1157 | AL_IGBTOvercurrent_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - IGBT Over current | Read | ||
| BV | 1158 | AL_IGBTOvercurrent_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - IGBT Over current | Read | ||
| BV | 1159 | AL_IGBTOvercurrent_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - IGBT Over current | Read | ||
| BV | 1160 | AL_IGBTOvercurrent_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - IGBT Over current | Read | ||
| BV | 1161 | AL_IGBTOvercurrent_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - IGBT Over current | Read | ||
| BV | 1162 | AL_IGBTOvercurrent_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - IGBT Over current | Read | ||
| BV | 1163 | AL_IGBTOvercurrent_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - IGBT Over current | Read | ||
| BV | 1164 | AL_IGBTOvercurrent_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - IGBT Over current | Read | ||
| BV | 1165 | AL_IGBTOvercurrent_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - IGBT Over current | Read | ||
| BV | 1166 | AL_IGBTOvercurrent_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - IGBT Over current | Read | ||
| BV | 1167 | AL_IGBTOvercurrent_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - IGBT Over current | Read | ||
| BV | 1168 | AL_IGBTOvercurrent_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - IGBT Over current | Read | ||
| BV | 1169 | AL_IGBTOvercurrent_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - IGBT Over current | Read | ||
| BV | 1170 | AL_IGBTOvercurrent_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - IGBT Over current | Read | ||
| BV | 1171 | AL_IGBTOvercurrent_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - IGBT Over current | Read | ||
| BV | 1172 | AL_IGBTOvercurrent_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - IGBT Over current | Read | ||
| BV | 1173 | AL_IGBTOvercurrent_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - IGBT Over current | Read | ||
| BV | 1174 | Al_InvOverheat_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Inverter Over Heat | Read | ||
| BV | 1175 | Al_InvOverheat_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Inverter Over Heat | Read | ||
| BV | 1176 | Al_InvOverheat_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Inverter Over Heat | Read | ||
| BV | 1177 | Al_InvOverheat_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Inverter Over Heat | Read | ||
| BV | 1178 | Al_InvOverheat_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Inverter Over Heat | Read | ||
| BV | 1179 | Al_InvOverheat_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Inverter Over Heat | Read | ||
| BV | 1180 | Al_InvOverheat_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Inverter Over Heat | Read | ||
| BV | 1181 | Al_InvOverheat_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Inverter Over Heat | Read | ||
| BV | 1182 | Al_InvOverheat_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Inverter Over Heat | Read | ||
| BV | 1183 | Al_InvOverheat_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Inverter Over Heat | Read | ||
| BV | 1184 | Al_InvOverheat_Rotary.Active | AL - Alarm - Rotary - Inverter OverHeat | Read | ||
| BV | 1185 | Al_InvOverheat_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Inverter Over Heat | Read | ||
| BV | 1186 | Al_InvOverheat_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Inverter Over Heat | Read | ||
| BV | 1187 | Al_InvOverheat_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Inverter Over Heat | Read | ||
| BV | 1188 | Al_InvOverheat_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Inverter Over Heat | Read | ||
| BV | 1189 | Al_InvOverheat_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Inverter Over Heat | Read | ||
| BV | 1190 | Al_InvOverheat_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Inverter Over Heat | Read | ||
| BV | 1191 | Al_InvOverheat_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Inverter Over Heat | Read | ||
| BV | 1192 | Al_InvOverheat_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Inverter Over Heat | Read | ||
| BV | 1193 | Al_InvOverheat_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Inverter Over Heat | Read | ||
| BV | 1194 | Al_InvOverheat_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Inverter Over Heat | Read | ||
| BV | 1195 | Al_InvOvld_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Inverter Over Load | Read | ||
| BV | 1196 | Al_InvOvld_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Inverter Over Load | Read | ||
| BV | 1197 | Al_InvOvld_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Inverter Over Load | Read | ||
| BV | 1198 | Al_InvOvld_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Inverter Over Load | Read | ||
| BV | 1199 | Al_InvOvld_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Inverter Over Load | Read | ||
| BV | 1200 | Al_InvOvld_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Inverter Over Load | Read | ||
| BV | 1201 | Al_InvOvld_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Inverter Over Load | Read | ||
| BV | 1202 | Al_InvOvld_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Inverter Over Load | Read | ||
| BV | 1203 | Al_InvOvld_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Inverter Over Load | Read | ||
| BV | 1204 | Al_InvOvld_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Inverter Over Load | Read | ||
| BV | 1205 | Al_InvOvld_Rotary.Active | AL - Alarm - Rotary - Inverter OverLoad | Read | ||
| BV | 1206 | Al_InvOvld_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Inverter Over Load | Read | ||
| BV | 1207 | Al_InvOvld_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Inverter Over Load | Read | ||
| BV | 1208 | Al_InvOvld_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Inverter Over Load | Read | ||
| BV | 1209 | Al_InvOvld_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Inverter Over Load | Read | ||
| BV | 1210 | Al_InvOvld_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Inverter Over Load | Read | ||
| BV | 1211 | Al_InvOvld_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Inverter Over Load | Read | ||
| BV | 1212 | Al_InvOvld_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Inverter Over Load | Read | ||
| BV | 1213 | Al_InvOvld_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Inverter Over Load | Read | ||
| BV | 1214 | Al_InvOvld_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Inverter Over Load | Read | ||
| BV | 1215 | Al_InvOvld_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Inverter Over Load | Read | ||
| BV | 1216 | Al_LowSupplyTemp.Active | AL - Alarm - Probe - Low Supply Temperature | Read | ||
| BV | 1217 | Al_LowVolt_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Low Voltage | Read | ||
| BV | 1218 | Al_LowVolt_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Low Voltage | Read | ||
| BV | 1219 | Al_LowVolt_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Low Voltage | Read | ||
| BV | 1220 | Al_LowVolt_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Low Voltage | Read | ||
| BV | 1221 | Al_LowVolt_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Low Voltage | Read | ||
| BV | 1222 | Al_LowVolt_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Low Voltage | Read | ||
| BV | 1223 | Al_LowVolt_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Low Voltage | Read | ||
| BV | 1224 | Al_LowVolt_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Low Voltage | Read | ||
| BV | 1225 | Al_LowVolt_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Low Voltage | Read | ||
| BV | 1226 | Al_LowVolt_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Low Voltage | Read | ||
| BV | 1227 | Al_LowVolt_Rotary.Active | AL - Alarm - Rotary - Low Voltage | Read | ||
| BV | 1228 | Al_LowVolt_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Low Voltage | Read | ||
| BV | 1229 | Al_LowVolt_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Low Voltage | Read | ||
| BV | 1230 | Al_LowVolt_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Low Voltage | Read | ||
| BV | 1231 | Al_LowVolt_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Low Voltage | Read | ||
| BV | 1232 | Al_LowVolt_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Low Voltage | Read | ||
| BV | 1233 | Al_LowVolt_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Low Voltage | Read | ||
| BV | 1234 | Al_LowVolt_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Low Voltage | Read | ||
| BV | 1235 | Al_LowVolt_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Low Voltage | Read | ||
| BV | 1236 | Al_LowVolt_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Low Voltage | Read | ||
| BV | 1237 | Al_LowVolt_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Low Voltage | Read | ||
| BV | 1238 | Al_MB_AO1.Active | AL - Alarm - Control Circuit - AO1 | Read | ||
| BV | 1239 | Al_MB_AO1_AO4_PWM.Active | AL - Alarm - Control Circuit - AO1_AO4_PWM | Read | ||
| BV | 1240 | Al_MB_AO2.Active | AL - Alarm - Control Circuit - AO2 | Read | ||
| BV | 1241 | Al_MB_AO3.Active | AL - Alarm - Control Circuit - AO3 | Read | ||
| BV | 1242 | Al_MB_AO4.Active | AL - Alarm - Control Circuit - AO4 | Read | ||
| BV | 1243 | Al_MB_Control_Supply.Active | AL - Alarm - Control Circuit - Control_Supply | Read | ||
| BV | 1244 | Al_MB_Control_Temp.Active | AL - Alarm - Control Circuit - Control_Temp | Read | ||
| BV | 1245 | Al_MB_Humidity.Active | AL - Alarm - Control Circuit - Humidity | Read | ||
| BV | 1246 | Al_MB_Press_Fan_Return.Active | AL - Alarm - Control Circuit - Press_Fan_Return | Read | ||
| BV | 1247 | Al_MB_Press_Fan_Supply.Active | AL - Alarm - Control Circuit - Press_Fan_Supply | Read | ||
| BV | 1248 | Al_MB_Press_Filter_Return.Active | AL - Alarm - Control Circuit - Press_Filter_Return | Read | ||
| BV | 1249 | Al_MB_Press_Filter_Supply.Active | AL - Alarm - Control Circuit - Press_Filter_Supply | Read | ||
| BV | 1250 | Al_MB_Supply24.Active | AL - Alarm - Control Circuit - Supply24 | Read | ||
| BV | 1251 | Al_MB_Temp_Fan_Return.Active | AL - Alarm - Control Circuit - Temp_Fan_Return | Read | ||
| BV | 1252 | Al_MB_Temp_Fan_Supply.Active | AL - Alarm - Control Circuit - Temp_Fan_Supply | Read | ||
| BV | 1253 | Al_MB_Temp_Filter_Return.Active | AL - Alarm - Control Circuit - Temp_Filter_Return | Read | ||
| BV | 1254 | Al_MB_Temp_Filter_Supply.Active | AL - Alarm - Control Circuit - Temp_Filter_Supply | Read | ||
| BV | 1255 | Al_MB_Temperature.Active | AL - Alarm - Control Circuit - Temperature | Read | ||
| BV | 1256 | Al_MotorFault_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - Motor Fault | Read | ||
| BV | 1257 | Al_MotorFault_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - Motor Fault | Read | ||
| BV | 1258 | Al_MotorFault_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - Motor Fault | Read | ||
| BV | 1259 | Al_MotorFault_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - Motor Fault | Read | ||
| BV | 1260 | Al_MotorFault_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - Motor Fault | Read | ||
| BV | 1261 | Al_MotorFault_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - Motor Fault | Read | ||
| BV | 1262 | Al_MotorFault_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - Motor Fault | Read | ||
| BV | 1263 | Al_MotorFault_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - Motor Fault | Read | ||
| BV | 1264 | Al_MotorFault_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - Motor Fault | Read | ||
| BV | 1265 | Al_MotorFault_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - Motor Fault | Read | ||
| BV | 1266 | Al_MotorFault_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - Motor Fault | Read | ||
| BV | 1267 | Al_MotorFault_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - Motor Fault | Read | ||
| BV | 1268 | Al_MotorFault_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - Motor Fault | Read | ||
| BV | 1269 | Al_MotorFault_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - Motor Fault | Read | ||
| BV | 1270 | Al_MotorFault_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - Motor Fault | Read | ||
| BV | 1271 | Al_MotorFault_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - Motor Fault | Read | ||
| BV | 1272 | Al_MotorFault_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - Motor Fault | Read | ||
| BV | 1273 | Al_MotorFault_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - Motor Fault | Read | ||
| BV | 1274 | Al_MotorFault_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - Motor Fault | Read | ||
| BV | 1275 | Al_MotorOverheat_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Motor Over heat | Read | ||
| BV | 1276 | Al_MotorOverheat_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Motor Over heat | Read | ||
| BV | 1277 | Al_MotorOverheat_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Motor Over heat | Read | ||
| BV | 1278 | Al_MotorOverheat_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Motor Over heat | Read | ||
| BV | 1279 | Al_MotorOverheat_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Motor Over heat | Read | ||
| BV | 1280 | Al_MotorOverheat_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Motor Over heat | Read | ||
| BV | 1281 | Al_MotorOverheat_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Motor Over heat | Read | ||
| BV | 1282 | Al_MotorOverheat_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Motor Over heat | Read | ||
| BV | 1283 | Al_MotorOverheat_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Motor Over heat | Read | ||
| BV | 1284 | Al_MotorOverheat_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Motor Over heat | Read | ||
| BV | 1285 | Al_MotorOverheat_Rotary.Active | AL - Alarm - Rotary - Motor Overheat | Read | ||
| BV | 1286 | Al_MotorOverheat_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Motor Over heat | Read | ||
| BV | 1287 | Al_MotorOverheat_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Motor Over heat | Read | ||
| BV | 1288 | Al_MotorOverheat_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Motor Over heat | Read | ||
| BV | 1289 | Al_MotorOverheat_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Motor Over heat | Read | ||
| BV | 1290 | Al_MotorOverheat_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Motor Over heat | Read | ||
| BV | 1291 | Al_MotorOverheat_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Motor Over heat | Read | ||
| BV | 1292 | Al_MotorOverheat_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Motor Over heat | Read | ||
| BV | 1293 | Al_MotorOverheat_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Motor Over heat | Read | ||
| BV | 1294 | Al_MotorOverheat_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Motor Over heat | Read | ||
| BV | 1295 | Al_MotorOverheat_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Motor Over heat | Read | ||
| BV | 1296 | Al_Offline_cpCOe.Active | AL - Alarm - Module IO - cPCOE - Offline | Read | ||
| BV | 1297 | Al_Offline_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Offline | Read | ||
| BV | 1298 | Al_Offline_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Offline | Read | ||
| BV | 1299 | Al_Offline_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Offline | Read | ||
| BV | 1300 | Al_Offline_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Offline | Read | ||
| BV | 1301 | Al_Offline_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Offline | Read | ||
| BV | 1302 | Al_Offline_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Offline | Read | ||
| BV | 1303 | Al_Offline_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Offline | Read | ||
| BV | 1304 | Al_Offline_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Offline | Read | ||
| BV | 1305 | Al_Offline_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Offline | Read | ||
| BV | 1306 | Al_Offline_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Offline | Read | ||
| BV | 1307 | Al_Offline_MainBoard.Active | AL - Alarm - Control Circuit - Offline | Read | ||
| BV | 1308 | Al_Offline_Rotary.Active | AL - Alarm - Rotary - Offline | Read | ||
| BV | 1309 | Al_Offline_SP_ExhHum.Active | AL - Alarm - Probe - Return Humidity - Offline | Read | ||
| BV | 1310 | Al_Offline_SP_ExhPress.Active | AL - Alarm - Probe - Return Air Pressure - Offline | Read | ||
| BV | 1311 | Al_Offline_SP_SupplyHum.Active | AL - Alarm - Probe - Supply humidity - Offline | Read | ||
| BV | 1312 | Al_Offline_SP_SupplyPress.Active | AL - Alarm - Probe - Supply Air Pressure - Offline | Read | ||
| BV | 1313 | Al_Offline_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Offline | Read | ||
| BV | 1314 | Al_Offline_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Offline | Read | ||
| BV | 1315 | Al_Offline_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Offline | Read | ||
| BV | 1316 | Al_Offline_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Offline | Read | ||
| BV | 1317 | Al_Offline_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Offline | Read | ||
| BV | 1318 | Al_Offline_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Offline | Read | ||
| BV | 1319 | Al_Offline_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Offline | Read | ||
| BV | 1320 | Al_Offline_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Offline | Read | ||
| BV | 1321 | Al_Offline_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Offline | Read | ||
| BV | 1322 | Al_Offline_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Offline | Read | ||
| BV | 1323 | Al_Offline_THTN_1.Active | AL - Alarm - HMI Basic - Offline | Read | ||
| BV | 1324 | Al_Option_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Option | Read | ||
| BV | 1325 | Al_Option_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Option | Read | ||
| BV | 1326 | Al_Option_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Option | Read | ||
| BV | 1327 | Al_Option_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Option | Read | ||
| BV | 1328 | Al_Option_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Option | Read | ||
| BV | 1329 | Al_Option_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Option | Read | ||
| BV | 1330 | Al_Option_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Option | Read | ||
| BV | 1331 | Al_Option_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Option | Read | ||
| BV | 1332 | Al_Option_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Option | Read | ||
| BV | 1333 | Al_Option_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Option | Read | ||
| BV | 1334 | Al_Option_Rotary.Active | AL - Alarm - Rotary - Option | Read | ||
| BV | 1335 | Al_Option_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Option | Read | ||
| BV | 1336 | Al_Option_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Option | Read | ||
| BV | 1337 | Al_Option_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Option | Read | ||
| BV | 1338 | Al_Option_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Option | Read | ||
| BV | 1339 | Al_Option_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Option | Read | ||
| BV | 1340 | Al_Option_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Option | Read | ||
| BV | 1341 | Al_Option_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Option | Read | ||
| BV | 1342 | Al_Option_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Option | Read | ||
| BV | 1343 | Al_Option_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Option | Read | ||
| BV | 1344 | Al_Option_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Option | Read | ||
| BV | 1345 | Al_Overcurrent_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Over Current | Read | ||
| BV | 1346 | Al_Overcurrent_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Over Current | Read | ||
| BV | 1347 | Al_Overcurrent_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Over Current | Read | ||
| BV | 1348 | Al_Overcurrent_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Over Current | Read | ||
| BV | 1349 | Al_Overcurrent_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Over Current | Read | ||
| BV | 1350 | Al_Overcurrent_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Over current | Read | ||
| BV | 1351 | Al_Overcurrent_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Over Current | Read | ||
| BV | 1352 | Al_Overcurrent_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Over Current | Read | ||
| BV | 1353 | Al_Overcurrent_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Over Current | Read | ||
| BV | 1354 | Al_Overcurrent_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Over Current | Read | ||
| BV | 1355 | Al_Overcurrent_Rotary.Active | AL - Alarm - Rotary - OverCurrent | Read | ||
| BV | 1356 | Al_Overcurrent_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Over current | Read | ||
| BV | 1357 | Al_Overcurrent_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Over Current | Read | ||
| BV | 1358 | Al_Overcurrent_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Over Current | Read | ||
| BV | 1359 | Al_Overcurrent_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Over Current | Read | ||
| BV | 1360 | Al_Overcurrent_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Over Current | Read | ||
| BV | 1361 | Al_Overcurrent_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Over current | Read | ||
| BV | 1362 | Al_Overcurrent_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Over Current | Read | ||
| BV | 1363 | Al_Overcurrent_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Over Current | Read | ||
| BV | 1364 | Al_Overcurrent_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Over Current | Read | ||
| BV | 1365 | Al_Overcurrent_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Over Current | Read | ||
| BV | 1366 | Al_OverVolt_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Over Voltage | Read | ||
| BV | 1367 | Al_OverVolt_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Over Voltage | Read | ||
| BV | 1368 | Al_OverVolt_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Over Voltage | Read | ||
| BV | 1369 | Al_OverVolt_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Over Voltage | Read | ||
| BV | 1370 | Al_OverVolt_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Over Voltage | Read | ||
| BV | 1371 | Al_OverVolt_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Over voltage | Read | ||
| BV | 1372 | Al_OverVolt_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Over Voltage | Read | ||
| BV | 1373 | Al_OverVolt_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Over Voltage | Read | ||
| BV | 1374 | Al_OverVolt_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Over Voltage | Read | ||
| BV | 1375 | Al_OverVolt_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Over Voltage | Read | ||
| BV | 1376 | Al_OverVolt_Rotary.Active | AL - Alarm - Rotary - OverVoltage | Read | ||
| BV | 1377 | Al_OverVolt_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Over voltage | Read | ||
| BV | 1378 | Al_OverVolt_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Over Voltage | Read | ||
| BV | 1379 | Al_OverVolt_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Over Voltage | Read | ||
| BV | 1380 | Al_OverVolt_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Over Voltage | Read | ||
| BV | 1381 | Al_OverVolt_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Over Voltage | Read | ||
| BV | 1382 | Al_OverVolt_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Over voltage | Read | ||
| BV | 1383 | Al_OverVolt_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Over Voltage | Read | ||
| BV | 1384 | Al_OverVolt_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Over Voltage | Read | ||
| BV | 1385 | Al_OverVolt_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Over Voltage | Read | ||
| BV | 1386 | Al_OverVolt_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Over Voltage | Read | ||
| BV | 1387 | AL_Overvoltage_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - Over voltage | Read | ||
| BV | 1388 | AL_Overvoltage_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - Over voltage | Read | ||
| BV | 1389 | AL_Overvoltage_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - Over voltage | Read | ||
| BV | 1390 | AL_Overvoltage_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - Over voltage | Read | ||
| BV | 1391 | AL_Overvoltage_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - Over voltage | Read | ||
| BV | 1392 | AL_Overvoltage_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - Over voltage | Read | ||
| BV | 1393 | AL_Overvoltage_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - Over voltage | Read | ||
| BV | 1394 | AL_Overvoltage_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - Over voltage | Read | ||
| BV | 1395 | AL_Overvoltage_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - Over voltage | Read | ||
| BV | 1396 | AL_Overvoltage_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - Over voltage | Read | ||
| BV | 1397 | AL_Overvoltage_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - Over voltage | Read | ||
| BV | 1398 | AL_Overvoltage_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - Over voltage | Read | ||
| BV | 1399 | AL_Overvoltage_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - Over voltage | Read | ||
| BV | 1400 | AL_Overvoltage_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - Over voltage | Read | ||
| BV | 1401 | AL_Overvoltage_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - Over voltage | Read | ||
| BV | 1402 | AL_Overvoltage_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - Over voltage | Read | ||
| BV | 1403 | AL_Overvoltage_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - Over voltage | Read | ||
| BV | 1404 | AL_Overvoltage_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - Over voltage | Read | ||
| BV | 1405 | AL_Overvoltage_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - Over voltage | Read | ||
| BV | 1406 | AL_Overvoltage_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - Over voltage | Read | ||
| BV | 1407 | Al_Ovld_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Over Load | Read | ||
| BV | 1408 | Al_Ovld_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Over Load | Read | ||
| BV | 1409 | Al_Ovld_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Over Load | Read | ||
| BV | 1410 | Al_Ovld_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Over Load | Read | ||
| BV | 1411 | Al_Ovld_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Over Load | Read | ||
| BV | 1412 | Al_Ovld_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Over load | Read | ||
| BV | 1413 | Al_Ovld_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Over Load | Read | ||
| BV | 1414 | Al_Ovld_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Over Load | Read | ||
| BV | 1415 | Al_Ovld_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Over Load | Read | ||
| BV | 1416 | Al_Ovld_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Over Load | Read | ||
| BV | 1417 | Al_Ovld_Rotary.Active | AL - Alarm - Rotary - OverLoad | Read | ||
| BV | 1418 | Al_Ovld_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Over load | Read | ||
| BV | 1419 | Al_Ovld_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Over Load | Read | ||
| BV | 1420 | Al_Ovld_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Over Load | Read | ||
| BV | 1421 | Al_Ovld_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Over Load | Read | ||
| BV | 1422 | Al_Ovld_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Over Load | Read | ||
| BV | 1423 | Al_Ovld_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Over load | Read | ||
| BV | 1424 | Al_Ovld_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Over Load | Read | ||
| BV | 1425 | Al_Ovld_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Over Load | Read | ||
| BV | 1426 | Al_Ovld_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Over Load | Read | ||
| BV | 1427 | Al_Ovld_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Over Load | Read | ||
| BV | 1428 | Al_ParamErr_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Parameters Error | Read | ||
| BV | 1429 | Al_ParamErr_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Parameters Error | Read | ||
| BV | 1430 | Al_ParamErr_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Parameters Error | Read | ||
| BV | 1431 | Al_ParamErr_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Parameters Error | Read | ||
| BV | 1432 | Al_ParamErr_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Parameters Error | Read | ||
| BV | 1433 | Al_ParamErr_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Parameter save Error | Read | ||
| BV | 1434 | Al_ParamErr_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Parameters Error | Read | ||
| BV | 1435 | Al_ParamErr_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Parameters Error | Read | ||
| BV | 1436 | Al_ParamErr_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Parameters Error | Read | ||
| BV | 1437 | Al_ParamErr_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Parameters Error | Read | ||
| BV | 1438 | Al_ParamErr_Rotary.Active | AL - Alarm - Rotary - Parameters Error | Read | ||
| BV | 1439 | Al_ParamErr_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Parameter save Error | Read | ||
| BV | 1440 | Al_ParamErr_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Parameters Error | Read | ||
| BV | 1441 | Al_ParamErr_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Parameters Error | Read | ||
| BV | 1442 | Al_ParamErr_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Parameters Error | Read | ||
| BV | 1443 | Al_ParamErr_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Parameters Error | Read | ||
| BV | 1444 | Al_ParamErr_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Parameter save Error | Read | ||
| BV | 1445 | Al_ParamErr_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Parameters Error | Read | ||
| BV | 1446 | Al_ParamErr_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Parameters Error | Read | ||
| BV | 1447 | Al_ParamErr_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Parameters Error | Read | ||
| BV | 1448 | Al_ParamErr_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Parameters Error | Read | ||
| BV | 1449 | AL_ParametersCRC_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - Parameters CRC | Read | ||
| BV | 1450 | AL_ParametersCRC_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - Parameters CRC | Read | ||
| BV | 1451 | AL_ParametersCRC_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - Parameters CRC | Read | ||
| BV | 1452 | AL_ParametersCRC_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - Parameters CRC | Read | ||
| BV | 1453 | AL_ParametersCRC_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - Parameters CRC | Read | ||
| BV | 1454 | AL_ParametersCRC_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - Parameters CRC | Read | ||
| BV | 1455 | AL_ParametersCRC_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - Parameters CRC | Read | ||
| BV | 1456 | AL_ParametersCRC_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - Parameters CRC | Read | ||
| BV | 1457 | AL_ParametersCRC_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - Parameters CRC | Read | ||
| BV | 1458 | AL_ParametersCRC_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - Parameters CRC | Read | ||
| BV | 1459 | AL_ParametersCRC_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - Parameters CRC | Read | ||
| BV | 1460 | AL_ParametersCRC_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - Parameters CRC | Read | ||
| BV | 1461 | AL_ParametersCRC_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - Parameters CRC | Read | ||
| BV | 1462 | AL_ParametersCRC_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - Parameters CRC | Read | ||
| BV | 1463 | AL_ParametersCRC_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - Parameters CRC | Read | ||
| BV | 1464 | AL_ParametersCRC_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - Parameters CRC | Read | ||
| BV | 1465 | AL_ParametersCRC_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - Parameters CRC | Read | ||
| BV | 1466 | AL_ParametersCRC_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - Parameters CRC | Read | ||
| BV | 1467 | AL_ParametersCRC_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - Parameters CRC | Read | ||
| BV | 1468 | AL_ParametersCRC_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - Parameters CRC | Read | ||
| BV | 1469 | AL_PhaseLoss_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - Phase Loss | Read | ||
| BV | 1470 | AL_PhaseLoss_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - Phase Loss | Read | ||
| BV | 1471 | AL_PhaseLoss_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - Phase Loss | Read | ||
| BV | 1472 | AL_PhaseLoss_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - Phase Loss | Read | ||
| BV | 1473 | AL_PhaseLoss_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - Phase Loss | Read | ||
| BV | 1474 | AL_PhaseLoss_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - Phase Loss | Read | ||
| BV | 1475 | AL_PhaseLoss_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - Phase Loss | Read | ||
| BV | 1476 | AL_PhaseLoss_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - Phase Loss | Read | ||
| BV | 1477 | AL_PhaseLoss_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - Phase Loss | Read | ||
| BV | 1478 | AL_PhaseLoss_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - Phase Loss | Read | ||
| BV | 1479 | AL_PhaseLoss_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - Phase Loss | Read | ||
| BV | 1480 | AL_PhaseLoss_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - Phase Loss | Read | ||
| BV | 1481 | AL_PhaseLoss_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - Phase Loss | Read | ||
| BV | 1482 | AL_PhaseLoss_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - Phase Loss | Read | ||
| BV | 1483 | AL_PhaseLoss_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - Phase Loss | Read | ||
| BV | 1484 | AL_PhaseLoss_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - Phase Loss | Read | ||
| BV | 1485 | AL_PhaseLoss_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - Phase Loss | Read | ||
| BV | 1486 | AL_PhaseLoss_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - Phase Loss | Read | ||
| BV | 1487 | AL_PhaseLoss_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - Phase Loss | Read | ||
| BV | 1488 | AL_PhaseLoss_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - Phase Loss | Read | ||
| BV | 1489 | Al_PhLost_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Phase Lost | Read | ||
| BV | 1490 | Al_PhLost_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Phase Lost | Read | ||
| BV | 1491 | Al_PhLost_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Phase Lost | Read | ||
| BV | 1492 | Al_PhLost_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Phase Lost | Read | ||
| BV | 1493 | Al_PhLost_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Phase Lost | Read | ||
| BV | 1494 | Al_PhLost_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Phase Lost | Read | ||
| BV | 1495 | Al_PhLost_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Phase Lost | Read | ||
| BV | 1496 | Al_PhLost_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Phase Lost | Read | ||
| BV | 1497 | Al_PhLost_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Phase Lost | Read | ||
| BV | 1498 | Al_PhLost_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Phase Lost | Read | ||
| BV | 1499 | Al_PhLost_Rotary.Active | AL - Alarm - Rotary - Phase Lost | Read | ||
| BV | 1500 | Al_PhLost_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Phase Lost | Read | ||
| BV | 1501 | Al_PhLost_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Phase Lost | Read | ||
| BV | 1502 | Al_PhLost_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Phase Lost | Read | ||
| BV | 1503 | Al_PhLost_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Phase Lost | Read | ||
| BV | 1504 | Al_PhLost_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Phase Lost | Read | ||
| BV | 1505 | Al_PhLost_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Phase Lost | Read | ||
| BV | 1506 | Al_PhLost_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Phase Lost | Read | ||
| BV | 1507 | Al_PhLost_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Phase Lost | Read | ||
| BV | 1508 | Al_PhLost_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Phase Lost | Read | ||
| BV | 1509 | Al_PhLost_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Phase Lost | Read | ||
| BV | 1510 | Al_PhOpen_ExhFan_1.Active | AL - Alarm - Fan Return 1 - Phase Open | Read | ||
| BV | 1511 | Al_PhOpen_ExhFan_10.Active | AL - Alarm - Fan Return 10 - Phase Open | Read | ||
| BV | 1512 | Al_PhOpen_ExhFan_2.Active | AL - Alarm - Fan Return 2 - Phase Open | Read | ||
| BV | 1513 | Al_PhOpen_ExhFan_3.Active | AL - Alarm - Fan Return 3 - Phase Open | Read | ||
| BV | 1514 | Al_PhOpen_ExhFan_4.Active | AL - Alarm - Fan Return 4 - Phase Open | Read | ||
| BV | 1515 | Al_PhOpen_ExhFan_5.Active | AL - Alarm - Fan Return 5 - Phase Open | Read | ||
| BV | 1516 | Al_PhOpen_ExhFan_6.Active | AL - Alarm - Fan Return 6 - Phase Open | Read | ||
| BV | 1517 | Al_PhOpen_ExhFan_7.Active | AL - Alarm - Fan Return 7 - Phase Open | Read | ||
| BV | 1518 | Al_PhOpen_ExhFan_8.Active | AL - Alarm - Fan Return 8 - Phase Open | Read | ||
| BV | 1519 | Al_PhOpen_ExhFan_9.Active | AL - Alarm - Fan Return 9 - Phase Open | Read | ||
| BV | 1520 | Al_PhOpen_Rotary.Active | AL - Alarm - Rotary - Phase Open | Read | ||
| BV | 1521 | Al_PhOpen_SupFan_1.Active | AL - Alarm - Fan Supply 1 - Phase Open | Read | ||
| BV | 1522 | Al_PhOpen_SupFan_10.Active | AL - Alarm - Fan Supply 10 - Phase Open | Read | ||
| BV | 1523 | Al_PhOpen_SupFan_2.Active | AL - Alarm - Fan Supply 2 - Phase Open | Read | ||
| BV | 1524 | Al_PhOpen_SupFan_3.Active | AL - Alarm - Fan Supply 3 - Phase Open | Read | ||
| BV | 1525 | Al_PhOpen_SupFan_4.Active | AL - Alarm - Fan Supply 4 - Phase Open | Read | ||
| BV | 1526 | Al_PhOpen_SupFan_5.Active | AL - Alarm - Fan Supply 5 - Phase Open | Read | ||
| BV | 1527 | Al_PhOpen_SupFan_6.Active | AL - Alarm - Fan Supply 6 - Phase Open | Read | ||
| BV | 1528 | Al_PhOpen_SupFan_7.Active | AL - Alarm - Fan Supply 7 - Phase Open | Read | ||
| BV | 1529 | Al_PhOpen_SupFan_8.Active | AL - Alarm - Fan Supply 8 - Phase Open | Read | ||
| BV | 1530 | Al_PhOpen_SupFan_9.Active | AL - Alarm - Fan Supply 9 - Phase Open | Read | ||
| BV | 1531 | Al_PreHeatCoilTempPrb.Active | AL - Alarm - Probe - Temperature Water PreHeating Coil | Read | ||
| BV | 1532 | Al_RDT_Fan.Active | AL - Alarm - Fan Group | Read | ||
| BV | 1533 | Al_RecSupplyTemp.Active | AL - Alarm - Probe - Supply Recovery Temperature | Read | ||
| BV | 1534 | Al_ReheatCoilWorkHrsWarn.Active | AL - Alarm - ReHeatCoil - Works Hour Warning | Read | ||
| BV | 1535 | Al_retain.Active | AL - Alarm - Retain | Read | ||
| BV | 1536 | Al_RetAir_CO2_Lev_Prb.Active | AL - Alarm - Probe - CO2 Return Level Probe | Read | ||
| BV | 1537 | Al_RetAirFlwSwWarn.Active | AL - Alarm - Probe - Air Flow Return SW Warning | Read | ||
| BV | 1538 | Al_RetAirP_Prb.Active | AL - Alarm - Probe - Pressure Return Air | Read | ||
| BV | 1539 | Al_RetFanWorkHrsWarn.Active | AL - Alarm - Fan Return - Works Hour Warning | Read | ||
| BV | 1540 | Al_RetFilt.Active | AL - Alarm - Filter - Return | Read | ||
| BV | 1541 | Al_RetTempPrb.Active | AL - Alarm - Probe - Return Temperature | Read | ||
| BV | 1542 | Al_SupplyAirFlwSwWarn.Active | AL - Alarm - Probe - Supply Air Flow SW Warning | Read | ||
| BV | 1543 | Al_SupplyAirP_Prb.Active | AL - Alarm - Probe - Supply Air Pressure | Read | ||
| BV | 1544 | Al_SupplyFanWorkHrsWarn.Active | AL - Alarm - Fan Supply - Works Hour Warning | Read | ||
| BV | 1545 | Al_SupplyFilt.Active | AL - Alarm - Filter - Supply | Read | ||
| BV | 1546 | Al_SupplyTempPrb.Active | AL - Alarm - Probe - Supply Temperature | Read | ||
| BV | 1547 | Al_SwPrototype.Active | AL - Alarm - Software Version - Prototype | Read | ||
| BV | 1548 | Al_ThTune_ClkBrd.Active | AL - Alarm - HMI Basic - Clock Board | Read | ||
| BV | 1549 | Al_ThTune_HumPrb.Active | AL - Alarm - HMI Basic - Humidity Probe | Read | ||
| BV | 1550 | Al_ThTune_TempPrb.Active | AL - Alarm - HMI Basic - Temperature Probe | Read | ||
| BV | 1551 | Al_TooHot_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - TooHot | Read | ||
| BV | 1552 | Al_TooHot_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - TooHot | Read | ||
| BV | 1553 | Al_TooHot_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - TooHot | Read | ||
| BV | 1554 | Al_TooHot_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - TooHot | Read | ||
| BV | 1555 | Al_TooHot_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - TooHot | Read | ||
| BV | 1556 | Al_TooHot_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - TooHot | Read | ||
| BV | 1557 | Al_TooHot_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - TooHot | Read | ||
| BV | 1558 | Al_TooHot_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - TooHot | Read | ||
| BV | 1559 | Al_TooHot_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - TooHot | Read | ||
| BV | 1560 | Al_TooHot_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - TooHot | Read | ||
| BV | 1561 | Al_TooHot_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - TooHot | Read | ||
| BV | 1562 | Al_TooHot_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - TooHot | Read | ||
| BV | 1563 | Al_TooHot_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - TooHot | Read | ||
| BV | 1564 | Al_TooHot_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - TooHot | Read | ||
| BV | 1565 | Al_TooHot_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - TooHot | Read | ||
| BV | 1566 | Al_TooHot_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - TooHot | Read | ||
| BV | 1567 | Al_TooHot_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - TooHot | Read | ||
| BV | 1568 | Al_TooHot_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - TooHot | Read | ||
| BV | 1569 | Al_TooHot_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - TooHot | Read | ||
| BV | 1570 | Al_TooHot_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - TooHot | Read | ||
| BV | 1571 | Al_Undervoltage_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - Undervoltage | Read | ||
| BV | 1572 | Al_Undervoltage_EC_ExhFan10.Active | AL - Alarm - Fan Return 10 EC - Undervoltage | Read | ||
| BV | 1573 | Al_Undervoltage_EC_ExhFan2.Active | AL - Alarm - Fan Return 2 EC - Undervoltage | Read | ||
| BV | 1574 | Al_Undervoltage_EC_ExhFan3.Active | AL - Alarm - Fan Return 3 EC - Undervoltage | Read | ||
| BV | 1575 | Al_Undervoltage_EC_ExhFan4.Active | AL - Alarm - Fan Return 4 EC - Undervoltage | Read | ||
| BV | 1576 | Al_Undervoltage_EC_ExhFan5.Active | AL - Alarm - Fan Return 5 EC - Undervoltage | Read | ||
| BV | 1577 | Al_Undervoltage_EC_ExhFan6.Active | AL - Alarm - Fan Return 6 EC - Undervoltage | Read | ||
| BV | 1578 | Al_Undervoltage_EC_ExhFan7.Active | AL - Alarm - Fan Return 7 EC - Undervoltage | Read | ||
| BV | 1579 | Al_Undervoltage_EC_ExhFan8.Active | AL - Alarm - Fan Return 8 EC - Undervoltage | Read | ||
| BV | 1580 | Al_Undervoltage_EC_ExhFan9.Active | AL - Alarm - Fan Return 9 EC - Undervoltage | Read | ||
| BV | 1581 | Al_Undervoltage_EC_SupFan1.Active | AL - Alarm - Fan Supply 1 EC - Undervoltage | Read | ||
| BV | 1582 | Al_Undervoltage_EC_SupFan10.Active | AL - Alarm - Fan Supply 10 EC - Undervoltage | Read | ||
| BV | 1583 | Al_Undervoltage_EC_SupFan2.Active | AL - Alarm - Fan Supply 2 EC - Undervoltage | Read | ||
| BV | 1584 | Al_Undervoltage_EC_SupFan3.Active | AL - Alarm - Fan Supply 3 EC - Undervoltage | Read | ||
| BV | 1585 | Al_Undervoltage_EC_SupFan4.Active | AL - Alarm - Fan Supply 4 EC - Undervoltage | Read | ||
| BV | 1586 | Al_Undervoltage_EC_SupFan5.Active | AL - Alarm - Fan Supply 5 EC - Undervoltage | Read | ||
| BV | 1587 | Al_Undervoltage_EC_SupFan6.Active | AL - Alarm - Fan Supply 6 EC - Undervoltage | Read | ||
| BV | 1588 | Al_Undervoltage_EC_SupFan7.Active | AL - Alarm - Fan Supply 7 EC - Undervoltage | Read | ||
| BV | 1589 | Al_Undervoltage_EC_SupFan8.Active | AL - Alarm - Fan Supply 8 EC - Undervoltage | Read | ||
| BV | 1590 | Al_Undervoltage_EC_SupFan9.Active | AL - Alarm - Fan Supply 9 EC - Undervoltage | Read | ||
| BV | 1591 | CfgErrAlrm.Active | AL - Alarm - Device - Wrong configuration | Read | ||
| BV | 1592 | Al_MotorFault_EC_ExhFan1.Active | AL - Alarm - Fan Return 1 EC - Motor Fault | Read | ||
| BV | 1593 | OfflineAlrm.Active | AL - Alarm - Device - Offline | Read | ||
| BV | 1594 | Al_Offline_IO_PCB.Active | AL - Alarm - Module IO - EC-PCB - Offline | Read | ||
| BV | 1595 | Al_DXRev.Active | AL - Alarm - Reverse unit | Read | ||
| BV | 1596 | Al_WarningFilterHigh.Active | AL - Alarm - Filter - High pressure | Read | ||
| BV | 1597 | Al_RRG_WorkConfirm.Active | AL - Alarm - Recovery - Rotary - Work confirm | Read | ||
| BV | 1598 | Al_ClkBrd_THTN_1.Active | AL - Alarm - HMI Basic - Clock Board | Read | ||
| BV | 1599 | Al_ClkBrd_THTN_1.Trigger | AL - Alarm - HMI Basic - Clock Board | Read | ||
| BV | 1600 | Al_DXRev.Trigger | AL - Alarm - Reverse unit | Read | ||
| BV | 1601 | Al_HumPrb_THTN_1.Active | AL - Alarm - HMI Basic - Humidity sensor | Read | ||
| BV | 1602 | Al_HumPrb_THTN_1.Trigger | AL - Alarm - HMI Basic - Humidity sensor | Read | ||
| BV | 1603 | Al_Offline_IO_PCB.Trigger | AL - Alarm - Module IO - EC-PCB - Offline | Read | ||
| BV | 1604 | Al_RRG_WorkConfirm.Trigger | AL - Alarm - Recovery - Rotary - Work confirm | Read | ||
| BV | 1605 | Al_TempPrb_THTN_1.Active | AL - Alarm - HMI Basic - Temperature sensor | Read | ||
| BV | 1606 | Al_TempPrb_THTN_1.Trigger | AL - Alarm - HMI Basic - Temperature sensor | Read | ||
| BV | 1607 | Al_WarningFilterHigh.Trigger | AL - Alarm - Filter - Pressure High | Read | ||
| BV | 1608 | CfgErrAlrm_CPCOE_1.Active | AL - Alarm - Module IO - cPCOE - Configuration | Read | ||
| BV | 1609 | CfgErrAlrm_CPCOE_1.Trigger | AL - Alarm - Module IO - cPCOE - Configuration | Read | ||
| BV | 1610 | OfflineAlrm_CPCOE_1.Active | AL - Alarm - Module IO - cPCOE - Offline | Read | ||
| BV | 1611 | OfflineAlrm_CPCOE_1.Trigger | AL - Alarm - Module IO - cPCOE - Offline | Read | ||
| PIV | 537 | DayIn | CLK - Time - Setting - Day (1 - 31) | Write | ||
| BV | 1612 | EnDate | CLK - Time - Setting - Change Enable | Write | 0=NO; 1=YES | |
| PIV | 538 | GeneralMng.Zone_TZ | CLK - Time - Setting - Zone | Write | ||
| PIV | 539 | HourIn | CLK - Time - Setting - Hour | h | Write | |
| PIV | 540 | MinuteIn | CLK - Time - Setting - Minute | min. | Write | |
| PIV | 541 | MonthIn | CLK - Time - Setting - Month (1 - 12) | Write | ||
| PIV | 542 | SecondIn | CLK - Time - Setting - Second | sec. | Write | |
| PIV | 543 | YearIn | CLK - Time - Setting - Year (0 - 99) | Write | ||
| PIV | 544 | Day | CLK - Time - Day (1 - 31) | Read | ||
| PIV | 545 | DayOfWeek | CLK - Time - Setting - Day of Week | Read | 1=MON; 2=TUE; 3=WED; 4=THU; 5=FRI; 6=SAT; 7=SUN | |
| PIV | 546 | Hour | CLK - Time - Hour | h | Read | |
| PIV | 547 | Minute | CLK - Time - Minute | min. | Read | |
| PIV | 548 | Month | CLK - Time - Month (1 - 12) | Read | ||
| PIV | 549 | Second | CLK - Time - Second | sec. | Read | |
| PIV | 550 | Year | CLK - Time - Year (0 - 99) | Read | ||
| AV | 240 | AlrmExhAirP_Msk | PAR - Fan - Return - Warning Threshold Air Pressure | Pa | Write | |
| AV | 241 | AlrmSupplyAirP_Msk | PAR - Fan - Supply - Warning Threshold Air Pressure | Pa | Write | |
| AV | 242 | AFreezeExtMaxTemp | PAR - Heating - Antifreeze - External Temperature - Maximum | °C | Write | |
| AV | 243 | AFreezeExtMinTemp | PAR - Heating - Antifreeze - External Temperature - Minimum | °C | Write | |
| AV | 244 | AfreezeHeatMax | PAR - Heating - Antifreeze - Valve Open - Maximum (0 - 100 %) | % | Write | |
| PIV | 551 | AFreezeHeatMaxT | PAR - Heating - Antifreeze - Time - Maximum | sec. | Write | |
| AV | 245 | AfreezeHeatMin | PAR - Heating - Antifreeze - Valve Open - Minimum (0 - 100 %) | % | Write | |
| PIV | 552 | AFreezeHeatMinT | PAR - Heating - Antifreeze - Time - Minimum | sec. | Write | |
| AV | 246 | AlrmExhAirP | PAR - Fan - Return - Warning Threshold Pressure | Pa | Write | |
| AV | 247 | AlrmSupplyAirP | PAR - Fan - Supply - Warning Threshold Pressure | Pa | Write | |
| BV | 1613 | Cool_1.Logic | PAR - Cooling - Main Cooler - Logic | Write | 0=NC; 1=NO | |
| PIV | 553 | Cool_1.Man | PAR - Cooling - Main Cooler - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1614 | Cool_2.Logic | PAR - Cooling - Main Cooler DX - Logic | Write | 0=NC; 1=NO | |
| PIV | 554 | Cool_2.Man | PAR - Cooling - Main Cooler DX - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| PIV | 555 | CoolDX_ResTyp | PAR - Cooling - Main Cooler DX - Operating Block | Write | 0=NONE; 1=ECO; 2=ECO + OPTIMAL | |
| AV | 248 | CoolExtTempThrsh | PAR - Regulation - ChangeOver - External Temperature - Cool Threshold | °C | Write | |
| PIV | 556 | CoolMinOffT | PAR - Cooling - Main Cooler DX - Time - Minimum OFF | sec. | Write | |
| PIV | 557 | CoolMinOnOnSameT | PAR - Cooling - Main Cooler DX - Time - Between starts | sec. | Write | |
| PIV | 558 | CoolMinOnT | PAR - Cooling - Main Cooler DX - Time - Minimum ON | sec. | Write | |
| PIV | 559 | CoolVlv.Man | PAR - Cooling - Main Cooler - Manual Analog (0 - 100 %) | % | Write | |
| AV | 249 | DeltaDew_PID.Kp | PAR - Regulation PID - Humidity - Dewpoint - Proportional gain | Kp | Write | |
| PIV | 560 | DeltaDew_PID.Ti | PAR - Regulation PID - Humidity - Dewpoint - Integral time | Ti - sec. | Write | |
| AV | 250 | DeltaDewTemp | PAR - Regulation PID - Humidity - Dewpoint - Delta (0 - 100 %) | % | Write | |
| AV | 251 | DevCfg_PID_Seq_CO2[0].Kp | PAR - Regulation PID - CO2 Mixing - Proportional gain | Kp | Write | |
| PIV | 561 | DevCfg_PID_Seq_CO2[0].Ti | PAR - Regulation PID - CO2 Mixing - Integral time | Ti - sec. | Write | |
| AV | 252 | DevCfg_PID_Seq_CO2[1].Kp | PAR - Regulation PID - CO2 Fan Compensation - Proportional gain | Kp | Write | |
| PIV | 562 | DevCfg_PID_Seq_CO2[1].Ti | PAR - Regulation PID - CO2 Fan Compensation - Integral time | Ti - sec. | Write | |
| AV | 253 | DevCfg_PID_Seq_Cool[2].Kp | PAR - Regulation PID - Recovery - Cooling - Proportional gain | Kp | Write | |
| PIV | 563 | DevCfg_PID_Seq_Cool[2].Ti | PAR - Regulation PID - Recovery - Cooling - Integral time | Ti - sec. | Write | |
| AV | 254 | DevCfg_PID_Seq_Cool[4].Kp | PAR - Regulation PID - Main Cooler - Proportional gain | Kp | Write | |
| PIV | 564 | DevCfg_PID_Seq_Cool[4].Ti | PAR - Regulation PID - Main Cooler - Integral time | Ti - sec. | Write | |
| AV | 255 | DevCfg_PID_Seq_Cool[5].Kp | PAR - Regulation PID - Mixing - Cooling - Proportional gain | Kp | Write | |
| PIV | 565 | DevCfg_PID_Seq_Cool[5].Ti | PAR - Regulation PID - Mixing - Cooling - Integral time | Ti - sec. | Write | |
| AV | 256 | DevCfg_PID_Seq_Heat[2].Kp | PAR - Regulation PID - Recovery - Heating - Proportional gain | Kp | Write | |
| PIV | 566 | DevCfg_PID_Seq_Heat[2].Ti | PAR - Regulation PID - Recovery - Heating - Integral time | Ti - sec. | Write | |
| AV | 257 | DevCfg_PID_Seq_Heat[4].Kp | PAR - Regulation PID - Main Heater - Proportional gain | Kp | Write | |
| PIV | 567 | DevCfg_PID_Seq_Heat[4].Ti | PAR - Regulation PID - Main Heater - Integral time | Ti - sec. | Write | |
| AV | 258 | DevCfg_PID_Seq_Heat[5].Kp | PAR - Regulation PID - Mixing - Heating - Proportional gain | Kp | Write | |
| PIV | 568 | DevCfg_PID_Seq_Heat[5].Ti | PAR - Regulation PID - Mixing - Heating - Integral time | Ti - sec. | Write | |
| AV | 259 | DevCfg_PID_Seq_Heat[6].Kp | PAR - Regulation PID - ReHeating - Proportional gain | Kp | Write | |
| PIV | 569 | DevCfg_PID_Seq_Heat[6].Ti | PAR - Regulation PID - ReHeating - Integral time | Ti - sec. | Write | |
| PIV | 570 | DOff_ExhFan | PAR - Fan - Return - Time - OFF Delay | sec. | Write | |
| PIV | 571 | DOff_SupplyFan | PAR - Fan - Supply - Time - OFF Delay | sec. | Write | |
| PIV | 572 | DT_ChangeHum | PAR - Humidity - Time - Change Delay | sec. | Write | |
| PIV | 573 | DT_Dmp | PAR - Fan - Supply - Time - OFF Damper | sec. | Write | |
| PIV | 574 | DT_ExhFan | PAR - Fan - Return - Time - ON Delay | sec. | Write | |
| PIV | 575 | DT_SupplyFan | PAR - Fan - Supply - Time - ON Delay | sec. | Write | |
| BV | 1615 | En_CoolRec | PAR - Recovery - Cooling - Enable | Write | 0=NO; 1=YES | |
| BV | 1616 | En_FreeCoolHeat | PAR - System - Free Cool/Heat - Enable | Write | 0=NO; 1=YES | |
| BV | 1617 | En_Rev_MixDamper | PAR - Mixing damper - Reverse signal | Write | 0=NO; 1=YES | |
| BV | 1618 | En_Rev_Recovery | PAR - Recovery - Reverse signal | Write | 0=NO; 1=YES | |
| AV | 260 | ExhAirFlowSet_Msk | PAR - Fan - Return - Flow - Maximum (For airflow < 32767) | m3/h | Write | |
| AV | 261 | ExhAirPSet_Msk | PAR - Fan - Return - Pressure - Maximum | Pa | Write | |
| AV | 262 | FastCoolThrsh | PAR - Recovery - Cooling Limit (0 - 100 %) | % | Write | |
| BV | 1619 | FastHeatEn | PAR - Recovery - Fast Heating - Enable | Write | 0=NO; 1=YES | |
| BV | 1620 | FastHeatStop | PAR - Recovery - Stop Fast Heat - Enable | Write | 0=NO; 1=YES | |
| PIV | 576 | FastHeatT | PAR - Recovery - Startup Time | sec. | Write | |
| AV | 263 | FastHeatThrsh | PAR - Recovery - Heating Limit (0 - 100 %) | % | Write | |
| BV | 1621 | FastHeatTrig | PAR - Recovery - Start Fast Heat - Enable | Write | 0=NO; 1=YES | |
| AV | 264 | FilterF7_Max | PAR - Filter - Maximum pressure F7 | Pa | Write | |
| AV | 265 | FilterF9_Max | PAR - Filter - Maximum pressure F9 | Pa | Write | |
| AV | 266 | FilterPG4_Max | PAR - Filter - Maximum pressure PG4 | Pa | Write | |
| IV | 577 | FilterRet_Type | PAR - Filter - Return type | Write | 0=None; 1=PG4/G4; 2=M5/F7; 3=F9 | |
| IV | 578 | FilterSup_Type | PAR - Filter - Supply type | Write | 0=None; 1=PG4/G4; 2=M5/F7; 3=F9 | |
| AV | 267 | FireExhSpeed | PAR - Fan - Fire Setting - Return Speed (0 - 100 %) | % | Write | |
| AV | 268 | FireSupplySpeed | PAR - Fan - Fire Setting - Supply Speed (0 - 100 %) | % | Write | |
| AV | 269 | FireThrsh | PAR - Fan - Fire Setting - Threshold | °C | Write | |
| BV | 1622 | HC_Cool_1.Res | PAR - Cooling - Main Cooler - Reset | Write | 0=NO; 1=YES | |
| BV | 1623 | HC_Cool_2.Res | PAR - Cooling - Main Cooler DX - Reset | Write | 0=NO; 1=YES | |
| BV | 1624 | HC_ExhFan_1.Res | PAR - Fan - Return 1 - Reset | Write | 0=NO; 1=YES | |
| BV | 1625 | HC_ExhFan_2.Res | PAR - Fan - Return 2 - Reset | Write | 0=NO; 1=YES | |
| BV | 1626 | HC_Heat_1.Res | PAR - Heating - Main Heater - Reset | Write | 0=NO; 1=YES | |
| BV | 1627 | HC_Heat_2.Res | PAR - Heating - Main Device 2 - Reset | Write | 0=NO; 1=YES | |
| BV | 1628 | HC_Hum.Res | PAR - Humidity - Reset | Write | 0=NO; 1=YES | |
| BV | 1629 | HC_PreHeat.Res | PAR - Heating - PreHeating - Reset | Write | 0=NO; 1=YES | |
| BV | 1630 | HC_RecoveryPump.Res | PAR - Recovery - Reset | Write | 0=NO; 1=YES | |
| BV | 1631 | HC_ReHeat.Res | PAR - Heating - ReHeating - Reset | Write | 0=NO; 1=YES | |
| BV | 1632 | HC_SupplyFan_1.Res | PAR - Fan - Supply 1 - Reset | Write | 0=NO; 1=YES | |
| BV | 1633 | HC_SupplyFan_2.Res | PAR - Fan - Supply 2 - Reset | Write | 0=NO; 1=YES | |
| AV | 270 | HE_Pwr[0] | PAR - Heating - Main Heater - Maximum Power Modulating (0 - 100 %) | % | Write | |
| AV | 271 | HE_Pwr[1] | PAR - Heating - Main Heater - Maximum Power 1 Stage (0 - 100 %) | % | Write | |
| AV | 272 | HE_Pwr[2] | PAR - Heating - Main Heater - Maximum Power 2 Stage (0 - 100 %) | % | Write | |
| BV | 1634 | Heat_1.Logic | PAR - Heating - Main Heater - Logic | Write | 0=NC; 1=NO | |
| PIV | 579 | Heat_2.Man | PAR - Heating - Main Device 2 - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| AV | 273 | HeatExtTempThrsh | PAR - Regulation - ChangeOver - External Temperature - Heat Threshold | °C | Write | |
| PIV | 580 | HeatMinOffT | PAR - Heating - Main Heater DX - Time - Minimum OFF | sec. | Write | |
| PIV | 581 | HeatMinOnOnSameT | PAR - Heating - Main Heater DX - Time - Between starts | sec. | Write | |
| PIV | 582 | HeatMinOnT | PAR - Heating - Main Heater DX - Time - Minimum ON | sec. | Write | |
| PIV | 583 | HeatRecovery.Man | PAR - Recovery - Manual Analog (0 - 100 %) | % | Write | |
| PIV | 584 | HeatVlv.Man | PAR - Heating - Main Heater - Manual Analog (0 - 100 %) | % | Write | |
| BV | 1635 | Hum.Logic | PAR - Humidity - Logic | Write | 0=NC; 1=NO | |
| PIV | 585 | Hum.Man | PAR - Humidity - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| AV | 274 | Hum_PID.DeadBand | PAR - Regulation PID - Humidity - DeadBand | g/m3 | Write | |
| AV | 275 | Hum_PID.Kp | PAR - Regulation PID - Humidity - Proportional gain | Kp | Write | |
| PIV | 586 | Hum_PID.Ti | PAR - Regulation PID - Humidity - Integral time | Ti - sec. | Write | |
| AV | 276 | HW_Set | PAR - Heating - Main Water - SetPoint | °C | Write | |
| PIV | 587 | IdleT_ExhFan | PAR - Fan - Return - Idle Time | sec. | Write | |
| PIV | 588 | IdleT_SupplyFan | PAR - Fan - Supply - Idle Time | sec. | Write | |
| AV | 277 | K_FactorExh | PAR - Fan - Return - K-Factor | Write | ||
| PIV | 589 | K_FactorExhCode | PAR - Fan - Return - Fan Code | Write | 0=CUSTOM; 1=VS-225; 2=VS-250; 3=VS-315; 4=VS-355; 5=VS-400; 6=VS-450; 7=VS-500; 8=VS-560; 9=VS-630 | |
| AV | 278 | K_FactorSupply | PAR - Fan - Supply - K-Factor | Write | ||
| PIV | 590 | K_FactorSupplyCode | PAR - Fan - Supply - Fan Code | Write | 0=CUSTOM; 1=VS-225; 2=VS-250; 3=VS-315; 4=VS-355; 5=VS-400; 6=VS-450; 7=VS-500; 8=VS-560; 9=VS-630 | |
| AV | 279 | LowSupplyTempThrsh | PAR - Heating - Supply Limit - Threshold | °C | Write | |
| AV | 280 | MainCoolMin | PAR - Cooling - Main Cooler - Minimum Power (0 - 100 %) | % | Write | |
| AV | 281 | MainCW_MinPID | PAR - Cooling - Main Cooler Water - Minimum Valve Signal (0 - 100 %) | % | Write | |
| AV | 282 | MainHeatMin | PAR - Heating - Main Heater - Minimum Power (0 - 100 %) | % | Write | |
| AV | 283 | MainHW_MinPID | PAR - Heating - Main Water - Minimum Valve Singal (0 - 100 %) | % | Write | |
| AV | 284 | ManExhFanIdle | PAR - Fan - Return - Idle Power (0 - 100 %) | % | Write | |
| AV | 285 | ManSupplyFanIdle | PAR - Fan - Supply - Idle Power (0 - 100 %) | % | Write | |
| AV | 286 | MinHeatRec | PAR - Recovery - Heating - Minimum Power (0 - 100 %) | % | Write | |
| PIV | 591 | ModulHum.Man | PAR - Humidity - Manual Analog (0 - 100 %) | % | Write | |
| PIV | 592 | ModulMixDamp.Man | PAR - Mix Damper - Manual Analog (0 - 100 %) | % | Write | |
| AV | 287 | ModulMixDampMaxVal | PAR - Mix Damper - Limits - Maximum Openning (0 - 100 %) | % | Write | |
| AV | 288 | ModulMixDampMinVal | PAR - Mix Damper - Limits - Minimum Openning (0 - 100 %) | % | Write | |
| PIV | 593 | ModulPreHeat.Man | PAR - Heating - PreHeating - Manual Analog (0 - 100 %) | % | Write | |
| PIV | 594 | NightKickHour | PAR - System - Night Kick Time - Hour | h | Write | |
| PIV | 595 | NightKickMinute | PAR - System - Night Kick Time - Minute | min. | Write | |
| AV | 289 | PID_Exh.Kp | PAR - Regulation PID - Fan Return - Proportional gain | Kp | Write | |
| PIV | 596 | PID_Exh.Td | PAR - Regulation PID - Fan Return - Derivative time | Td - sec. | Write | |
| PIV | 597 | PID_Exh.Ti | PAR - Regulation PID - Fan Return - Integral time | Ti - sec. | Write | |
| AV | 290 | PID_FrostProt.Kp | PAR - Regulation PID - Recovery - Frost - Proportional gain | Kp | Write | |
| AV | 291 | PID_FrostProt.SetP | PAR - Recovery - Frost Protection - SetPoint | °C | Write | |
| PIV | 598 | PID_FrostProt.Ti | PAR - Regulation PID - Recovery - Frost - Integral time | Ti - sec. | Write | |
| AV | 292 | PID_HeatHW.Kp | PAR - Regulation PID - Main Water - Proportional gain | Kp | Write | |
| PIV | 599 | PID_HeatHW.Ti | PAR - Regulation PID - Main Water - Integral time | Ti - sec. | Write | |
| AV | 293 | PID_PreHeatCoil.Kp | PAR - Regulation PID - PreHeating - Proportional gain | Kp | Write | |
| PIV | 600 | PID_PreHeatCoil.Ti | PAR - Regulation PID - PreHeating - Integral time | Ti - sec. | Write | |
| AV | 294 | PID_PreHeatHW.Kp | PAR - Regulation PID - PreHeater Water - Proportional gain | Kp | Write | |
| PIV | 601 | PID_PreHeatHW.Ti | PAR - Regulation PID - PreHeater Water - Integral time | Ti - sec. | Write | |
| AV | 295 | PID_Supply.Kp | PAR - Regulation PID - Fan Supply - Proportional gain | Kp | Write | |
| PIV | 602 | PID_Supply.Td | PAR - Regulation PID - Fan Supply - Derivative time | Td - sec. | Write | |
| PIV | 603 | PID_Supply.Ti | PAR - Regulation PID - Fan Supply - Integral time | Ti - sec. | Write | |
| BV | 1636 | PreHeaterPump.Logic | PAR - Heating - PreHeating - Logic | Write | 0=NC; 1=NO | |
| PIV | 604 | PreHeaterPump.Man | PAR - Heating - PreHeating - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| AV | 296 | PreHeatHE_Pwr[0] | PAR - Heating - PreHeating - Maximum Power Modulating (0 - 100 %) | % | Write | |
| AV | 297 | PreHeatHE_Pwr[1] | PAR - Heating - PreHeating - Maximum Power 1 Stage (0 - 100 %) | % | Write | |
| AV | 298 | PreHeatMin | PAR - Heating - PreHeating - Minimum Power (0 - 100 %) | % | Write | |
| PIV | 605 | PreHeatMinOffT | PAR - Heating - PreHeating DX - Time - Minimum OFF | sec. | Write | |
| PIV | 606 | PreheatMinOnOnSameT | PAR - Heating - PreHeating DX - Time - Between starts | sec. | Write | |
| PIV | 607 | PreHeatMinOnT | PAR - Heating - PreHeating DX - Time - Minimum ON | sec. | Write | |
| IV | 608 | PreHeatRotConf.DevNoPerCirc | PAR - Heating - PreHeating - Type | Write | 1=MODULATING; 2=MOD. + 1 STAGE | |
| AV | 299 | PreHeatSet | PAR - Heating - PreHeater Water - SetPoint | °C | Write | |
| AV | 300 | PreHW_MinPID | PAR - Heating - PreHeater Water - Minimum Valve Signal (0 - 100 %) | % | Write | |
| AV | 301 | Rec_MinPID | PAR - Recovery - Heating - Minimum Recovery (0 - 100 %) | % | Write | |
| BV | 1637 | RecoveryPump.Logic | PAR - Recovery - Logic | Write | 0=NC; 1=NO | |
| PIV | 609 | RecoveryPump.Man | PAR - Recovery - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1638 | ReHeat.Logic | PAR - Heating - ReHeating - Logic | Write | 0=NC; 1=NO | |
| PIV | 610 | ReHeat.Man | PAR - Heating - ReHeating - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| AV | 302 | ReHeatHE_Pwr[0] | PAR - Heating - ReHeating - Maximum Power Modulating (0 - 100 %) | % | Write | |
| AV | 303 | ReHeatHE_Pwr[1] | PAR - Heating - ReHeating - Maximum Power 1 Stage (0 - 100 %) | % | Write | |
| AV | 304 | ReHeatMin | PAR - Heating - ReHeating - Minimum Power (0 - 100 %) | % | Write | |
| PIV | 611 | ReHeatMinOffT | PAR - Heating - ReHeater DX - Time - Minimum OFF | sec. | Write | |
| PIV | 612 | ReHeatMinOnOnSameT | PAR - Heating - ReHeater DX - Time - Between starts | sec. | Write | |
| PIV | 613 | ReHeatMinOnT | PAR - Heating - ReHeater DX - Time - Minimum ON | sec. | Write | |
| IV | 614 | ReHeatRotConf.CompMinPwr | PAR - Heating - ReHeating - Minimum Power (0 - 100 %) | % | Write | |
| IV | 615 | ReHeatRotConf.DevNoPerCirc | PAR - Heating - ReHeating - Type | Write | 1=MODULATING; 2=MOD. + 1 STAGE | |
| PIV | 616 | ReHeatVlv.Man | PAR - Heating - ReHeating - Manual Analog (0 - 100 %) | % | Write | |
| AV | 305 | ReHW_MinPID | PAR - Heating - ReHeating - Minimum Valve Signal (0 - 100 %) | % | Write | |
| AV | 306 | Ret_NrPole | PAR - Fan - Return - Number of pole | Write | ||
| BV | 1639 | RevOut_1.Logic | PAR - Heating - Reverse Device 1 - Logic | Write | 0=NC; 1=NO | |
| PIV | 617 | RevOut_1.Man | PAR - Heating - Reverse Device 1 - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1640 | RevOut_2.Logic | PAR - Heating - Reverse Device 2 - Logic | Write | 0=NC; 1=NO | |
| PIV | 618 | RevOut_2.Man | PAR - Heating - Reverse Device 2 - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| PIV | 619 | RevOutVlv.Man | PAR - Heating - Reverse Device 1 - Manual Analog (0 - 100 %) | % | Write | |
| AV | 307 | RoomReg_SetP_Offs_Kp | PAR - Regulation PID - Room Compnsation - Proportional gain | Kp | Write | |
| PIV | 620 | RoomReg_SetP_Offs_Ti | PAR - Regulation PID - Room Compnsation - Integral time | sec. | Write | |
| IV | 621 | RotConf.CompMinPwr | PAR - Heating - Main Heater - Minimum Power (0 - 100 %) | % | Write | |
| IV | 622 | RotConf.DevNoPerCirc | PAR - Heating - Main Heater - Type | Write | 1=MODULATING; 2=MOD. + 1 STAGE; 3=MOD. + 2 STAGES | |
| AV | 308 | RRG_NrPole | PAR - Recovery - Rotary - Numver of pole | Write | ||
| AV | 309 | SetMaxLimit | PAR - Regulation - Limits - Return / Room - Maximum | °C | Write | |
| AV | 310 | SetMinLimit | PAR - Regulation - Limits - Return / Room - Minimum | °C | Write | |
| PIV | 623 | StandbyT | PAR - System - StandBy - Time | sec. | Write | |
| AV | 311 | StartHumPerc | PAR - Humidity - Digital - Start (0 - 100 %) | % | Write | |
| AV | 312 | StopHumPerc | PAR - Humidity - Digital - Stop (0 - 100 %) | % | Write | |
| AV | 313 | Sup_NrPole | PAR - Fan - Supply - Number of pole | Write | ||
| AV | 314 | SupplyAirFlowSet_Msk | PAR - Fan - Supply - Flow - Maximum (For airflow < 32767) | m3/h | Write | |
| AV | 315 | SupplyAirPSet_Msk | PAR - Fan - Supply - Pressure - Maximum | Pa | Write | |
| AV | 316 | SupplyDewPoint | PAR - Humidity - Supply Dewpoint | °C | Write | |
| AV | 317 | SupplyFanMax | PAR - CO2 - Fan Compensation - Max Air-Flow Quality (0 - 100 %) | % | Write | |
| AV | 318 | SupplyMaxSet | PAR - Regulation - Limits - Temperature Supply - Maximum | °C | Write | |
| AV | 319 | SupplyMinSet | PAR - Regulation - Limits - Temperature Supply - Minimum | °C | Write | |
| PIV | 624 | SupplyTemp_CoolHeatDT | PAR - Regulation - ChangeOver - External Temperature - Time Delay | sec. | Write | |
| AV | 320 | ThrshOffCool_1 | PAR - Cooling - Main Cooler DX - Stop Step 1 (0 - 100 %) | % | Write | |
| AV | 321 | ThrshOffCool_2 | PAR - Cooling - Main Cooler DX - Stop Step 2 (0 - 100 %) | % | Write | |
| AV | 322 | ThrshOffHeat_1 | PAR - Heating - Main Heater DX - Stop Step 1 (0 - 100 %) | % | Write | |
| AV | 323 | ThrshOffHeat_2 | PAR - Heating - Main Heater DX - Stop Step 2 (0 - 100 %) | % | Write | |
| AV | 324 | ThrshOnCool_1 | PAR - Cooling - Main Cooler DX - Start Step 1 (0 - 100 %) | % | Write | |
| AV | 325 | ThrshOnCool_2 | PAR - Cooling - Main Cooler DX - Start Step 2 (0 - 100 %) | % | Write | |
| AV | 326 | ThrshOnHeat_1 | PAR - Heating - Main Heater DX - Start Step 1 (0 - 100 %) | % | Write | |
| AV | 327 | ThrshOnHeat_2 | PAR - Heating - Main Heater DX - Start Step 2 (0 - 100 %) | % | Write | |
| AV | 328 | W_HeatFreezeSet | PAR - Heating - Main Water - Frreeze SetPoint | °C | Write | |
| AV | 329 | W_PreHeatFreezeSet | PAR - Heating - PreHeater Water - Freeze SetPoint | °C | Write | |
| PIV | 625 | WakeUpT | PAR - System - Wake Up - Time | sec. | Write | |
| AV | 330 | WarnThrshExhFlw_Msk | PAR - Fan - Return - Warning Threshold Air Flow | m3/h | Write | |
| AV | 331 | WarnThrshSupplyFlw_Msk | PAR - Fan - Supply - Warning Threshold Air Flow | m3/h | Write | |
| AV | 332 | AbsHum | PAR - Humidity - ABS Humidity | g/m3 | Read | |
| AV | 333 | AbsHumSet | PAR - Humidity - ABS SetPoint | g/m3 | Read | |
| AV | 334 | AfterPreHeatReq | PAR - Regulation PID - PreHeating - Output (0 - 100 %) | % | Read | |
| AV | 335 | AirQualFan | PAR - Regulation PID - CO2 Fan Compensation - Output (0 - 100 %) | % | Read | |
| AV | 336 | AirQualReq_1 | PAR - Regulation PID - CO2 Mixing - Output (0 - 100 %) | % | Read | |
| AV | 337 | Cooling_PID_Seq[2] | PAR - Regulation PID - Recovery - Cooling - Output (0 - 100 %) | % | Read | |
| AV | 338 | Cooling_PID_Seq[3] | PAR - Regulation PID - Reverse - Cooling - Output (0 - 100 %) | % | Read | |
| AV | 339 | Cooling_PID_Seq[4] | PAR - Regulation PID - Main Cooler - Output (0 - 100 %) | % | Read | |
| AV | 340 | Cooling_PID_Seq[5] | PAR - Regulation PID - Mixing - Cooling - Output (0 - 100 %) | % | Read | |
| AV | 341 | FrostProtReq | PAR - Regulation PID - Recovery - Frost - Output (0 - 100 %) | % | Read | |
| AV | 342 | Heating_PID_Seq[2] | PAR - Regulation PID - Recovery - Heating - Output (0 - 100 %) | % | Read | |
| AV | 343 | Heating_PID_Seq[3] | PAR - Regulation PID - Reverse - Heating - Output (0 - 100 %) | % | Read | |
| AV | 344 | Heating_PID_Seq[4] | PAR - Regulation PID - Main Heater - Output (0 - 100 %) | % | Read | |
| AV | 345 | Heating_PID_Seq[5] | PAR - Regulation PID - Mixing - Heating - Output (0 - 100 %) | % | Read | |
| AV | 346 | Heating_PID_Seq[6] | PAR - Regulation PID - ReHeating - Output (0 - 100 %) | % | Read | |
| AV | 347 | Heating_PID_Seq[7] | PAR - Regulation PID - Fan Heating - Output (0 - 100 %) | % | Read | |
| AV | 348 | HumDehumReq | PAR - Regulation PID - Humidity - Output (0 - 100 %) | % | Read | |
| AV | 349 | HW_AfreezeReq | PAR - Regulation PID - Main Water - Output (0 - 100 %) | % | Read | |
| AV | 350 | PID_DewCompens | PAR - Regulation PID - Humidity - Dewpoint - Output (0 - 100 %) | % | Read | |
| AV | 351 | PID_RegCompens | PAR - Regulation PID - Room Compnsation - Output (0 - 100 %) | % | Read | |
| AV | 352 | PreW_AfreezeReq | PAR - Regulation PID - PreHeater Water - Output (0 - 100 %) | % | Read | |
| AV | 353 | MainHeatMax | PAR - Heating - Main Heater - Maximum Power (0 - 100 %) | % | Write | |
| AV | 354 | RevHeat_Sig_Min | PAR - Heating - Reverse Device 1 - Heating - Minimum signal (0 - 100 %) | % | Write | |
| AV | 355 | RevHeat_Sig_Max | PAR - Heating - Reverse Device 1 - Heating - Maximum signal (0 - 100 %) | % | Write | |
| AV | 356 | RevCool_Sig_Min | PAR - Heating - Reverse Device 1 - Cooling - Minimum signal (0 - 100 %) | % | Write | |
| AV | 357 | RevCool_Sig_Max | PAR - Heating - Reverse Device 1 - Cooling - Maximum signal (0 - 100 %) | % | Write | |
| AV | 358 | RevTemp_En | PAR - Heating - Reverse Device 1 - Permistion from external temperature | °C | Write | |
| AV | 359 | ReHeatMax | PAR - Heating - ReHeating - Maximum Power (0 - 100 %) | % | Write | |
| AV | 360 | PreHeatMax | PAR - Heating - PreHeating - Maximum Power (0 - 100 %) | % | Write | |
| PIV | 626 | LowTempAlrmDT_Run | PAR - Heating - Supply Limit - Threshold delay | sec. | Write | |
| BV | 1641 | LowSupplyTemp_Off | PAR - Heating - Supply Limit - Threshold unit STOP | Write | 0=NO; 1=YES | |
| BV | 1642 | PreHeat_Always | PAR - Heating - Main Heater HW - Pre-Heat always start | Write | 0=NO; 1=YES | |
| AV | 361 | MainStartupValue | PAR - Heating - Main Heater HW - Pre-Heat always start - Minimum signal (0 - | % | Write | |
| PIV | 627 | HE_Alarm_Delay | PAR - Heating - Main Heater HE - Alarm delay | sec. | Write | |
| AV | 362 | Pump_ExtTemp | PAR - Heating - Main Heater HW - Active pump when external temp lower | °C | Write | |
| AV | 363 | Valve_ExtTemp | PAR - Heating - Main Heater HW - Active vavlve when external temp lower | °C | Write | |
| AV | 364 | MainHW_MinPID_Text | PAR - Heating - Main Heater HW - Minimum signal for winter valve (0 - 100 | % | Write | |
| IV | 628 | FanFlowAlarm_Delay | PAR - Fan - Supply - Warning Threshold Pressure delay | sec. | Write | |
| PIV | 629 | DoubleFanRotT | PAR - Fan - Redundant - Time rotation | h | Write | |
| BV | 1643 | DoubleFanRot_Manual | PAR - Fan - Redundant - Manual rotation | Write | 0=NO; 1=YES | |
| PIV | 630 | DoubleDamp.Man | PAR - Fan - Redundant - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1644 | FanTempReg | PAR - Fan - Temperature regulation - Enable | Write | 0=NO; 1=YES | |
| AV | 365 | FanTempReg_Sig | PAR - Fan - Temperature regulation - Output (0 - 100 %) | % | Write | |
| AV | 366 | DevCfg_PID_Seq_Heat[7].Kp | PAR - Fan - Temperature regulation - Proportional gain | Kp | Write | |
| PIV | 631 | DevCfg_PID_Seq_Heat[7].Ti | PAR - Fan - Temperature regulation - Integral time | Ti - sec. | Write | |
| AV | 367 | FanTempReg_Max | PAR - Fan - Temperature regulation - Maximum fan signal correction (0 - 100 %) | % | Write | |
| BV | 1645 | RRG_0_10V | PAR - Recovery - Rotery - Enable 0-10V on Y3 for RRG | Write | 0=NO; 1=YES | |
| BV | 1646 | En_RRG_Alarm | PAR - Recovery - Rotery - Alarm enable | Write | 0=NO; 1=YES | |
| AV | 368 | RRG_MinValueFor_Al | PAR - Recovery - Rotery - Minium signal for active power (0 - 100 %) | % | Write | |
| AV | 369 | RRG_MinPower_Al | PAR - Recovery - Rotery - Minimum power for alarm | W | Write | |
| IV | 632 | RRG_Alarm_Delay | PAR - Recovery - Rotery - Dlarm delay | sec. | Write | |
| BV | 1647 | Mix_Mode_ECO | PAR - Mixing - Manual mode ECO - Enable | Write | 0=NO; 1=YES | |
| AV | 370 | Mix_Val_ECO | PAR - Mixing - Manual mode ECO - Signal (0 - 100 %) | % | Write | |
| BV | 1648 | Mix_Mode_OPTIMAL | PAR - Mixing - Manual mode Optimal - Enable | Write | 0=NO; 1=YES | |
| AV | 371 | Mix_Val_OPTIMAL | PAR - Mixing - Manual mode Optimal - Signal (0 - 100 %) | % | Write | |
| BV | 1649 | Mix_Mode_COMFORT | PAR - Mixing - Manual mode Comfort - Enable | Write | 0=NO; 1=YES | |
| AV | 372 | Mix_Val_COMFORT | PAR - Mixing - Manual mode Comfort - Signal (0 - 100 %) | % | Write | |
| AV | 373 | AFreezeHeatOut | PAR - Heater - Antifreeze - Output (0 - 100 %) | % | Write | |
| PIV | 633 | AFreezeHeatOutT | PAR - Heater - Antifreeze - Output T (0 - 100 %) | % | Write | |
| PIV | 634 | __SYSVA_BEEP_ON | SYS - Hardware - Activate Buzzer for a while (Virtual HMI) | Write | ||
| IV | 635 | __SYSVA_CURSOR_COLUMN | SYS - Hardware - Display cursor current X coordinate (Virtual HMI) | Write | ||
| IV | 636 | __SYSVA_CURSOR_ROW | SYS - Hardware - Display cursor current Y coordinate (Virtual HMI) | Write | ||
| IV | 637 | __SYSVA_CURSOR_VAR | SYS - Hardware - Display cursor for scrolling lists (Virtual HMI) | Write | ||
| IV | 638 | __SYSVA_KEY_COUNTER | SYS - Hardware - Key pressed time (Virtual HMI) | Write | ||
| PIV | 639 | __SYSVA_KEY_PRESSED | SYS - Hardware - Key pressed flag (Virtual HMI) | Write | ||
| PIV | 640 | __SYSVA_MANUAL_BUZZER_OFF | SYS - Hardware - Deactivates the alarm buzzer (Virtual HMI) | Write | ||
| PIV | 641 | __SYSVA_MANUAL_BUZZER_ON | SYS - Hardware - Activate Buzzer when controlled manually (Virtual HMI) | Write | ||
| PIV | 642 | __SYSVA_TMP_VALUE | SYS - Hardware - Temp value for field editing (Virtual HMI) | Write | ||
| BV | 1650 | AfterPreHeatCoilTemp.Enabled | SYS - IO Setting - Enable Inputs - Temperature - After PreHeat | Write | 0=NO; 1=YES | |
| PIV | 643 | AfterPreHeatCoilTemp.Man | SYS - IO Setting - Manual - Temperature - After PreHeat | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 374 | AfterPreHeatCoilTemp.Offset | SYS - IO Setting - Offset - Temperature - After PreHeat | °C | Write | |
| PIV | 644 | AppCode_Board | SYS - Application Code - Board - _ _ - _ . _ . _ . | Write | 0=uPC3 XS; 1=uPC3 XS; 2=uPC3 Small; 3=uPC3 XS; 4=uPC3 XS; 5=uPC3 XS; 6=uPC3 XS | |
| PIV | 645 | AppCode_Cool | SYS - Application Code - Cooling - _ _ - _ . X . _ . | Write | 0=None; 1=Chilled water; 2=DX | |
| PIV | 646 | AppCode_Eco | SYS - Application Code - ECO - _ _ - _ . _ . _ . | Write | 0=NO; 1=YES | |
| PIV | 647 | AppCode_Heat | SYS - Application Code - Heating - _ _ - X . _ . _ . | Write | 0=None; 1=Hot water; 2=DX; 3=Electric heater; 4=Steam | |
| PIV | 648 | AppCode_Hum | SYS - Application Code - Humidity - _ _ - _ . _ . _ . | Write | 0=None; 1=Evaporative; 2=Steam | |
| PIV | 649 | AppCode_PreHeat | SYS - Application Code - PreHeating - _ _ - _ . _ . _ . | Write | 0=None; 1=Hot water; 2=DX; 3=Electric heater | |
| PIV | 650 | AppCode_Rec | SYS - Application Code - Recirculation - XX - _ . _ . _ . _ | Write | 0=AS:Supply; 1=AD: S+E; 2=AR: S/E & Rotary; 3=AP: S/E + Cross; 4=AG: S/E + Glycol | |
| PIV | 651 | AppCode_ReHeat | SYS - Application Code - Recirculation Heating - _ _ - _ . _ . _ | Write | 0=None; 1=Hot water; 2=DX; 3=Electric heater | |
| PIV | 652 | AppCode_Rev | SYS - Application Code - Rev - _ _ - _ . _ . X . | Write | 0=None; 1=Hydronic; 2=DX | |
| BV | 1651 | AppCool_CW | SYS - Application Code - Cooling coil | Write | 0=NO; 1=YES | |
| BV | 1652 | AppCool_DX | SYS - Application Code - Direct Expansion | Write | 0=NO; 1=YES | |
| BV | 1653 | AppEco | SYS - Application Code - Mixing damper | Write | 0=NO; 1=YES | |
| BV | 1654 | AppHeat_DX | SYS - Application Code - Heat - Direct Expansion | Write | 0=NO; 1=YES | |
| BV | 1655 | AppHeat_HE | SYS - Application Code - Electric Heating | Write | 0=NO; 1=YES | |
| BV | 1656 | AppHeat_HW | SYS - Application Code - Heating Coil | Write | 0=NO; 1=YES | |
| BV | 1657 | AppHeat_Steam | SYS - Application Code - Heating Steam | Write | 0=NO; 1=YES | |
| BV | 1658 | AppHum_Evap | SYS - Application Code - Humidity - Evap | Write | 0=NO; 1=YES | |
| BV | 1659 | AppHum_Steam | SYS - Application Code - Humidity - Steam | Write | 0=NO; 1=YES | |
| PIV | 653 | AppHumReg | SYS - Unit Configuration - Humidity Regulation | Write | 0=NONE; 1=SUPPLY; 2=RETURN; 3=ROOM | |
| BV | 1660 | AppPreHeat_DX | SYS - Application Code - PreHeat_DX | Write | 0=NO; 1=YES | |
| BV | 1661 | AppPreHeat_HE | SYS - Application Code - PreHeat_HE | Write | 0=NO; 1=YES | |
| BV | 1662 | AppPreHeat_HW | SYS - Application Code - PreHeat_HW | Write | 0=NO; 1=YES | |
| BV | 1663 | AppRec_EnExh | SYS - Application Code - Return | Write | 0=NO; 1=YES | |
| BV | 1664 | AppRec_Glycol | SYS - Application Code - Rec_Glycol | Write | 0=NO; 1=YES | |
| BV | 1665 | AppRec_Plate | SYS - Application Code - Rec_Plate | Write | 0=NO; 1=YES | |
| BV | 1666 | AppRec_Rotary | SYS - Application Code - Recovery - Rotary | Write | 0=NO; 1=YES | |
| BV | 1667 | AppRec_SupplyOnly | SYS - Application Code - Rec_SupplyOnly | Write | 0=NO; 1=YES | |
| BV | 1668 | AppReg_Ret | SYS - Application Code - Reg_Ret | Write | 0=NO; 1=YES | |
| BV | 1669 | AppReg_Room | SYS - Application Code - Reg_Room | Write | 0=NO; 1=YES | |
| BV | 1670 | AppReg_Supply | SYS - Application Code - Reg_Supply | Write | 0=NO; 1=YES | |
| BV | 1671 | AppReHeat_DX | SYS - Application Code - ReHeat_DX | Write | 0=NO; 1=YES | |
| BV | 1672 | AppReHeat_HE | SYS - Application Code - ReHeat_HE | Write | 0=NO; 1=YES | |
| BV | 1673 | AppReHeat_HW | SYS - Application Code - ReHeat_HW | Write | 0=NO; 1=YES | |
| BV | 1674 | AppRev_DX | SYS - Application Code - Rev_DX | Write | 0=NO; 1=YES | |
| BV | 1675 | AppRev_W | SYS - Application Code - Rev_W | Write | 0=NO; 1=YES | |
| BV | 1676 | AppRevCoolDX | SYS - Application Code - RevCoolDX | Write | 0=NO; 1=YES | |
| BV | 1677 | AppRevCoolW | SYS - Application Code - RevCoolW | Write | 0=NO; 1=YES | |
| BV | 1678 | AppRevHeatDX | SYS - Application Code - RevHeatDX | Write | 0=NO; 1=YES | |
| BV | 1679 | AppRevHeatW | SYS - Application Code - RevHeatW | Write | 0=NO; 1=YES | |
| PIV | 654 | AppTempReg | SYS - Unit Configuration - Temperature Regulation | Write | 0=SUPPLY; 1=RETURN; 2=ROOM | |
| BV | 1680 | BacNetSel | SYS - Unit Configuration - BacNet Port | Write | 0=ETHERNET; 1=PLAN | |
| PIV | 655 | BMS_Addr | SYS - Unit Configuration - BMS port - Address (1 - 32) | Write | ||
| BV | 1681 | CO2_Simulation_En | SYS - IO Setting - CO2 Simulate - Enabled | Write | 0=NO; 1=YES | |
| IV | 656 | CO2_Simulation_Var | SYS - IO Setting - CO2 Simulate - Value | ppm | Write | |
| BV | 1682 | CoolAlrm.Logic | SYS - IO Setting - Digital Input - Logic - Alarm - Cool | Write | 0=NC; 1=NO | |
| PIV | 657 | CoolAlrm.Man | SYS - IO Setting - Digital Input - Manual - Alarm - Cool | Write | 0=AUTO; 1=OFF; 2=ON | |
| PIV | 658 | DriveTyp | SYS - Unit Configuration - Import / Export - Memory Type | Write | 0=FLASH MEMORY; 1=USB | |
| BV | 1684 | En_Buzz | SYS - Unit Configuration - Enable Buzzer | Write | 0=NO; 1=YES | |
| BV | 1685 | En_HumTHTN_1 | SYS - Unit Configuration - HMI Basic - Humidity Probe | Write | 0=NO; 1=YES | |
| BV | 1686 | En_RetAir_CO2 | SYS - IO Setting - Enable Modbus - CO2 | Write | 0=NO; 1=YES | |
| BV | 1687 | En_RetAirP | SYS - IO Setting - Enable Modbus - Pressure - Return | Write | 0=NO; 1=YES | |
| BV | 1688 | En_RetHum | SYS - IO Setting - Enable Modbus - Humidity - Return | Write | 0=NO; 1=YES | |
| BV | 1689 | En_SupplyAirP | SYS - IO Setting - Enable Modbus - Pressure - Supply | Write | 0=NO; 1=YES | |
| BV | 1690 | En_SupplyHum | SYS - IO Setting - Enable Modbus - Humidity - Supply | Write | 0=NO; 1=YES | |
| BV | 1691 | ExhAirDamp.Logic | SYS - IO Setting - Digital Output - Logic - Damper - Supply | Write | 0=NC; 1=NO | |
| PIV | 659 | ExhFanRegTyp | SYS - Unit Configuration - Regulation Return | Write | 0=NONE; 1=VAV; 2=CAV | |
| PIV | 660 | ExhMulti | SYS - Unit Configuration - Config Return | Write | 0=1 FAN; 1=REDUNDANT; 2=2 FANS; 3=3 FANS; 4=4 FANS; 5=5 FANS; 6=6 FANS; 7=7 FANS; 8=8 FANS; 9=9 FANS; 10=10 FANS | |
| PIV | 661 | ExhTemp.Man | SYS - IO Setting - Manual - Temperature Exhaust | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 375 | ExhTemp.Offset | SYS - IO Setting - Offset - Temperature Exhaust | °C | Write | |
| BV | 1692 | ExtTemp.Enabled | SYS - IO Setting - Enable Inputs - Temperature - External | Write | 0=NO; 1=YES | |
| PIV | 662 | ExtTemp.Man | SYS - IO Setting - Manual - Temperature - External | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 376 | ExtTemp.Offset | SYS - IO Setting - Offset - Temperature - External | °C | Write | |
| IV | 663 | FB_Baud_msk | SYS - Unit Configuration - FieldBus Port - Baudrate | Write | 0=4800; 1=9600; 2=19200; 3=38400 | |
| BV | 1693 | FireAlrm.Logic | SYS - IO Setting - Digital Input - Logic - Alarm Fire | Write | 0=NC; 1=NO | |
| PIV | 664 | FireAlrm.Man | SYS - IO Setting - Digital Input - Manual - Alarm Fire | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1694 | Heat_2.Logic | SYS - IO Setting - Digital Output - Logic - Heating 2 | Write | 0=NC; 1=NO | |
| BV | 1696 | HumAlrm.Logic | SYS - IO Setting - Digital Input - Logic - Alarm - Humidifier | Write | 0=NC; 1=NO | |
| PIV | 665 | HumAlrm.Man | SYS - IO Setting - Digital Input - Manual - Alarm - Humidifier | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1697 | ID2_Alrm.Logic | SYS - IO Setting - Digital Input - Logic - Alarm - Heat | Write | 0=NC; 1=NO | |
| PIV | 666 | ID2_Alrm.Man | SYS - IO Setting - Digital Input - Manual - Alarm - Heat | Write | 0=AUTO; 1=OFF; 2=ON | |
| IV | 667 | ImpExpFileName | SYS - Unit Configuration - Import / Export - File Name (0 - 99) | Write | ||
| IV | 668 | LangChange | SYS - Unit Configuration - Language | Write | 0=EN; 1=PL | |
| AV | 377 | MinFanPwrRet | SYS - Unit Configuration - Minimum Speed - Return (0 - 100 %) | % | Write | |
| AV | 378 | MinFanPwrSup | SYS - Unit Configuration - Minimum Speed - Supply (0 - 100 %) | % | Write | |
| PIV | 669 | OffTotMinutes | SYS - Hardware - Time last blackout | min. | Write | |
| PIV | 670 | OnOffStatus | SYS - Hardware - Machine Status | msec. | Write | |
| PIV | 671 | PrgCycleMs | SYS - Hardware - Cycle | msec. | Write | |
| BV | 1699 | RecSupplyTemp.Enabled | SYS - IO Setting - Enable Inputs - Temperature - Supply Recovery | Write | 0=NO; 1=YES | |
| PIV | 672 | RecSupplyTemp.Man | SYS - IO Setting - Manual - Temperature - Supply Recovery | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 379 | RecSupplyTemp.Offset | SYS - IO Setting - Offset - Temperature - Supply Recovery | °C | Write | |
| BV | 1701 | RemoteOn.Logic | SYS - IO Setting - Digital Input - Logic - Remote ON | Write | 0=NC; 1=NO | |
| PIV | 673 | RemoteOn.Man | SYS - IO Setting - Digital Input - Manual - Remote ON | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1702 | RetFilter.Logic | SYS - IO Setting - Digital Input - Logic - Filter - Return | Write | 0=NC; 1=NO | |
| PIV | 674 | RetFilter.Man | SYS - IO Setting - Digital Input - Manual - Filter - Return | Write | 0=AUTO; 1=OFF; 2=ON | |
| BV | 1703 | RetTemp.Enabled | SYS - IO Setting - Enable Inputs - Temperature - Return | Write | 0=NO; 1=YES | |
| PIV | 675 | RetTemp.Man | SYS - IO Setting - Manual - Temperature - Return | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 380 | RetTemp.Offset | SYS - IO Setting - Offset - Temperature - Return | °C | Write | |
| BV | 1704 | SrsAlrm.Logic | SYS - IO Setting - Digital Output - Logic - Global Alarm | Write | 0=NC; 1=NO | |
| PIV | 676 | SupplyFanRegTyp | SYS - Unit Configuration - Regulation Supply | Write | 0=NONE; 1=VAV; 2=CAV | |
| BV | 1705 | SupplyFilter.Logic | SYS - IO Setting - Digital Input - Logic - Filter - Supply | Write | 0=NC; 1=NO | |
| PIV | 677 | SupplyFilter.Man | SYS - IO Setting - Digital Input - Manual - Filter - Supply | Write | 0=AUTO; 1=OFF; 2=ON | |
| PIV | 678 | SupplyMulti | SYS - Unit Configuration - Config Supply | Write | 0=1 FAN; 1=REDUNDANT; 2=2 FANS; 3=3 FANS; 4=4 FANS; 5=5 FANS; 6=6 FANS; 7=7 FANS; 8=8 FANS; 9=9 FANS; 10=10 FANS | |
| PIV | 679 | SupplyTemp.Man | SYS - IO Setting - Manual - Temperature - Supply | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 381 | SupplyTemp.Offset | SYS - IO Setting - Offset - Temperature - Supply | °C | Write | |
| PIV | 680 | Typ_SP_CO2 | SYS - IO Setting - Modbus Probe Type - CO2 | Write | 0=TYPE 1; 1=TYPE 2 | |
| PIV | 681 | Typ_SP_Hum | SYS - IO Setting - Modbus Probe Type - Humidity | Write | 0=TYPE 1; 1=TYPE 2 | |
| PIV | 682 | Typ_SP_Pressure | SYS - IO Setting - Modbus Probe Type - Pressure | Write | 0=TYPE 1; 1=TYPE 2 | |
| PIV | 683 | TypVFD | SYS - Unit Configuration - Supply Fan VFD Type | Write | 0=iC5; 1=iG5; 2=ABB; 3=EC; 4=DFI; 5=M100; 6=None | |
| PIV | 684 | TypVFD_2 | SYS - Unit Configuration - Return Fan VFD Type | Write | 0=iC5; 1=iG5; 2=ABB; 3=EC; 4=DFI; 5=M100; 6=None | |
| PIV | 685 | TypVFD_Rotor | SYS - Unit Configuration - Rotor Fan VFD Type | Write | 0=iC5; 1=iG5; 2=ABB; 3=EC; 4=DFI; 5=M100; 6=None | |
| BV | 1706 | UnitConfigured | SYS - Unit Configuration - Enabled | Write | 0=NO; 1=YES | |
| IV | 686 | Uom_Msk | SYS - Unit Configuration - Unit of Measure | Write | 1=INTERNATIONAL; 2=USA | |
| BV | 1707 | W_HeatCoilTemp.Enabled | SYS - IO Setting - Enable Inputs - Temperature - Water Heat | Write | 0=NO; 1=YES | |
| PIV | 687 | W_HeatCoilTemp.Man | SYS - IO Setting - Manual - Temperature - Water Heat | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 382 | W_HeatCoilTemp.Offset | SYS - IO Setting - Offset - Temperature - Water Heat | °C | Write | |
| BV | 1708 | W_PreHeatCoilTemp.Enabled | SYS - IO Setting - Enable Inputs - Temperature - Water PreHeat | Write | 0=NO; 1=YES | |
| PIV | 688 | W_PreHeatCoilTemp.Man | SYS - IO Setting - Manual - Temperature - Water PreHeat | °C | Write | 0=AUTO; OR 1 - 100% |
| AV | 383 | W_PreHeatCoilTemp.Offset | SYS - IO Setting - Offset - Temperature - Water PreHeat | °C | Write | |
| BV | 1709 | WinSum.Enabled | SYS - IO Setting - Enable Inputs - Summer / Winter | Write | 0=NO; 1=YES | |
| BV | 1710 | WinSum.Logic | SYS - IO Setting - Digital Input - Logic - Winter / Summer | Write | 0=NC; 1=NO | |
| PIV | 689 | WinSum.Man | SYS - IO Setting - Digital Input - Manual - Winter / Summer | Write | 0=AUTO; 1=OFF; 2=ON | |
| PIV | 690 | CurrVer.D | SYS - System - Application Version - _ . _ . _ _ _ _ D | Read | ||
| BV | 1711 | CurrVer.IsBeta | SYS - System - Application Version - _ . _ . _ _ _ B _ | Read | ||
| PIV | 691 | CurrVer.X | SYS - System - Application Version - X . _ . _ _ _ _ _ | Read | ||
| PIV | 692 | CurrVer.Y | SYS - System - Application Version - _ . Y . _ _ _ _ _ | Read | ||
| PIV | 693 | CurrVer.Z | SYS - System - Application Version - _ . _ . Z Z Z _ _ | Read | ||
| BV | 1712 | ExhTemp.Enabled | SYS - IO Setting - Enable Inputs - Temperature Exhaust | Read | 0=NO; 1=YES | |
| BV | 1713 | Manual_PreHeat | SYS - PreHeater - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1714 | Manual_Recovery | SYS - Recovery - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1715 | Manual_Heat | SYS - Heater - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1716 | Manual_Cool | SYS - Cooler - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1717 | Manual_ReHeat | SYS - ReHeater - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1718 | Manual_Reverse | SYS - Reverse unit - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1719 | Manual_Mix | SYS - Mixing damper - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1720 | Manual_Humidity | SYS - Humidifier - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1721 | Manual_RedDamp | SYS - Redundant Damper - Manual mode active | Read | 0=NO; 1=YES | |
| BV | 1722 | Manual_Active | SYS - Manual mode active | Read | 0=NO; 1=YES | |
| AV | 694 | Reverse_Val_AO | IO - Analog Output - Reverse unit (0 - 100 %) | % | Read | |
| AV | 698 | UnitSetP.AirFlwSetP.StandBy | SP - Setpoint - Air Flow - Supply - 4 - Standby (0 - 100 %) | % | Write | |
| AV | 697 | UnitSetP.AirQualitySetP.StandBy | SP - Setpoint - Air Quality - 3 - Standby | ppm | Write | |
| AV | 696 | UnitSetP.HumSetP.StandBy | SP - Setpoint - Humidity - 4 - Standby (0 - 100 %) | % | Write | |
| AV | 699 | UnitSetP.RetAirFlwSetP.StandBy | SP - Setpoint - Air Flow - Return - 4 - Standby (0 - 100 %) | % | Write | |
| AV | 695 | UnitSetP.RoomTempSetP.StandBy | SP - Setpoint - Temperature - Room - 4 - Standby | °C | Write | |
| PIV | 700 | Heat_1.Man | PAR - Heating - Main Device 1 - Manual Digital | Write | 0=AUTO; 1=OFF; 2=ON | |
| AV | 712 | SupplyAirFlow_2 | IO - Probe - Air Flow - Supply (For airflow > 32767) | m3/h | Read | |
| AV | 713 | ExhAirFlow_2 | IO - Probe - Air Flow - Return (For airflow > 32767) | m3/h | Read | |
| AV | 714 | ExhAirFlowSet_Msk_2 | PAR - Fan - Return - Flow - Maximum (For airflow > 32767) | m3/h | Write | |
| AV | 715 | SupplyAirFlowSet_Msk_2 | PAR - Fan - Supply - Flow - Maximum (For airflow > 32767) | m3/h | Write |
No points match these filters.
Object ID lookup: FläktGroup vQ Stream unit with Carel uPC3 controller point IDs by name
AV1AfterPreHeatCoilTemp.ValBV1Cool_1.ValBV2Cool_2.ValBV3CoolAlrm.ValBV4CoolHeat.ValAV2CoolVlv.ValBV5DoubleDamp.ValBV6ExhAirDamp.ValAV3ExhAirFlowAV4ExhAirP_ValAV5ExhTemp.ValAV6ExtTemp.ValBV7FireAlrm.ValBV8Heat_1.ValBV9Heat_2.ValAV7HeatRecovery_ValAV8HeatVlv.ValBV10Hum.ValAV9Hum_THTN_1BV11HumAlrm.ValBV12ID2_Alrm.ValAV10MB_Devices.MB_MainBoard_1.AI_Temp_Fan_ReturnAV11MB_Devices.MB_MainBoard_1.AI_Temp_Fan_SupplyAV12MB_Devices.MB_MainBoard_1.AO_01_ReadAV13MB_Devices.MB_MainBoard_1.AO_02_ReadAV14MB_Devices.MB_MainBoard_1.AO_03_ReadAV15MB_Devices.MB_MainBoard_1.AO_04_ReadAV16MB_Devices.MB_MainBoard_1.Humid_ReturnAV17MB_Devices.MB_MainBoard_1.Pressure_Fan_ReturnAV18MB_Devices.MB_MainBoard_1.Pressure_Fan_SupplyAV19MB_Devices.MB_MainBoard_1.Pressure_Filter_ReturnAV20MB_Devices.MB_MainBoard_1.Pressure_Filter_SupplyAV21MB_Devices.MB_MainBoard_1.Supply_24V_ReadAV22MB_Devices.MB_MainBoard_1.Supply_Control_ReadAV23MB_Devices.MB_MainBoard_1.Temp_ReturnAV24MixDampReq_FreshAV25ModulHum.ValAV26ModulMixDamp_ValAV27ModulPreHeat.ValBV13PreHeaterPump.ValBV14RecoveryPump.ValAV28RecSupplyTemp.ValBV15ReHeat.ValAV29ReHeatVlv.ValBV16RemoteOn.ValAV30RetAir_CO2_ValBV17RetFilter.ValAV31RetHum_ValAV32RetTemp.ValBV18SrsAlrm.ValAV33SupplyAirFlowAV34SupplyAirP_ValBV19SupplyFilter.ValAV35SupplyHum_ValAV36SupplyTemp.ValAV37Temp_THTN_1AV38W_HeatCoilTemp.ValAV39W_PreHeatCoilTemp.ValBV20WinSum.ValAV40Y1Out_HWAV41Y2Out_HWAV42Y3Out_HWBV21UnitCoolHeatModeAV43ExhFan_1.CurrentAV44ExhFan_1.DriveTempAV45ExhFan_1.FreqAV46ExhFan_1.kWhAV47ExhFan_1.PowerAV48ExhFan_1.RpmAV49ExhFan_1.VoltageAV50ExhFan_10.CurrentAV51ExhFan_10.DriveTempAV52ExhFan_10.FreqAV53ExhFan_10.kWhAV54ExhFan_10.PowerAV55ExhFan_10.RpmAV56ExhFan_10.VoltageAV57ExhFan_2.CurrentAV58ExhFan_2.DriveTempAV59ExhFan_2.FreqAV60ExhFan_2.kWhAV61ExhFan_2.PowerAV62ExhFan_2.RpmAV63ExhFan_2.VoltageAV64ExhFan_3.CurrentAV65ExhFan_3.DriveTempAV66ExhFan_3.FreqAV67ExhFan_3.kWhAV68ExhFan_3.PowerAV69ExhFan_3.RpmAV70ExhFan_3.VoltageAV71ExhFan_4.CurrentAV72ExhFan_4.DriveTempAV73ExhFan_4.FreqAV74ExhFan_4.kWhAV75ExhFan_4.PowerAV76ExhFan_4.RpmAV77ExhFan_4.VoltageAV78ExhFan_5.CurrentAV79ExhFan_5.DriveTempAV80ExhFan_5.FreqAV81ExhFan_5.kWhAV82ExhFan_5.PowerAV83ExhFan_5.RpmAV84ExhFan_5.VoltageAV85ExhFan_6.CurrentAV86ExhFan_6.DriveTempAV87ExhFan_6.FreqAV88ExhFan_6.kWhAV89ExhFan_6.PowerAV90ExhFan_6.RpmAV91ExhFan_6.VoltageAV92ExhFan_7.CurrentAV93ExhFan_7.DriveTempAV94ExhFan_7.FreqAV95ExhFan_7.kWhAV96ExhFan_7.PowerAV97ExhFan_7.RpmAV98ExhFan_7.VoltageAV99ExhFan_8.CurrentAV100ExhFan_8.DriveTempAV101ExhFan_8.FreqAV102ExhFan_8.kWhAV103ExhFan_8.PowerAV104ExhFan_8.RpmAV105ExhFan_8.VoltageAV106ExhFan_9.CurrentAV107ExhFan_9.DriveTempAV108ExhFan_9.FreqAV109ExhFan_9.kWhAV110ExhFan_9.PowerAV111ExhFan_9.RpmAV112ExhFan_9.VoltageAV113ExhFanValBV22MixAirDamp_OnAV114Rotary.CurrentAV115Rotary.DriveTempAV116Rotary.FreqAV117Rotary.kWhAV118Rotary.PowerAV119Rotary.RpmAV120Rotary.VoltageBV23RunExhFanBV24RunSupplyFanAV121SupplyFan_1.CurrentAV122SupplyFan_1.DriveTempAV123SupplyFan_1.FreqAV124SupplyFan_1.kWhAV125SupplyFan_1.PowerAV126SupplyFan_1.RpmAV127SupplyFan_1.VoltageAV128SupplyFan_10.CurrentAV129SupplyFan_10.DriveTempAV130SupplyFan_10.FreqAV131SupplyFan_10.kWhAV132SupplyFan_10.PowerAV133SupplyFan_10.RpmAV134SupplyFan_10.VoltageAV135SupplyFan_2.CurrentAV136SupplyFan_2.DriveTempAV137SupplyFan_2.FreqAV138SupplyFan_2.kWhAV139SupplyFan_2.PowerAV140SupplyFan_2.RpmAV141SupplyFan_2.VoltageAV142SupplyFan_3.CurrentAV143SupplyFan_3.DriveTempAV144SupplyFan_3.FreqAV145SupplyFan_3.kWhAV146SupplyFan_3.PowerAV147SupplyFan_3.RpmAV148SupplyFan_3.VoltageAV149SupplyFan_4.CurrentAV150SupplyFan_4.DriveTempAV151SupplyFan_4.FreqAV152SupplyFan_4.kWhAV153SupplyFan_4.PowerAV154SupplyFan_4.RpmAV155SupplyFan_4.VoltageAV156SupplyFan_5.CurrentAV157SupplyFan_5.DriveTempAV158SupplyFan_5.FreqAV159SupplyFan_5.kWhAV160SupplyFan_5.PowerAV161SupplyFan_5.RpmAV162SupplyFan_5.VoltageAV163SupplyFan_6.CurrentAV164SupplyFan_6.DriveTempAV165SupplyFan_6.FreqAV166SupplyFan_6.kWhAV167SupplyFan_6.PowerAV168SupplyFan_6.RpmAV169SupplyFan_6.VoltageAV170SupplyFan_7.CurrentAV171SupplyFan_7.DriveTempAV172SupplyFan_7.FreqAV173SupplyFan_7.kWhAV174SupplyFan_7.PowerAV175SupplyFan_7.RpmAV176SupplyFan_7.VoltageAV177SupplyFan_8.CurrentAV178SupplyFan_8.DriveTempAV179SupplyFan_8.FreqAV180SupplyFan_8.kWhAV181SupplyFan_8.PowerAV182SupplyFan_8.RpmAV183SupplyFan_8.VoltageAV184SupplyFan_9.CurrentAV185SupplyFan_9.DriveTempAV186SupplyFan_9.FreqAV187SupplyFan_9.kWhAV188SupplyFan_9.PowerAV189SupplyFan_9.RpmAV190SupplyFan_9.VoltageAV191SupplyFanValBV25UnitOffBV26UnitOnAV192ExhFan_1_PowerAV193SupplyFan_1_PowerPIV384HC_Cool_1.HrsPIV385HC_Cool_2.HrsPIV386HC_ExhFan_1.HrsPIV387HC_ExhFan_2.HrsPIV388HC_Heat_1.HrsPIV389HC_Heat_2.HrsPIV390HC_Heat_Mod.HrsPIV391HC_Hum.HrsPIV392HC_PreHeat.HrsPIV393HC_RecoveryPump.HrsPIV394HC_ReHeat.HrsPIV395HC_SupplyFan_1.HrsPIV396HC_SupplyFan_2.HrsAV194RegTempPIV397SetTypAV195UnitSetP.AirFlwSetP.ComfortAV196UnitSetP.AirFlwSetP.EconomyAV197UnitSetP.AirFlwSetP.PreComfortAV198UnitSetP.AirQualitySetP.ComfortAV199UnitSetP.AirQualitySetP.EconomyAV200UnitSetP.AirQualitySetP.PreComfortAV201UnitSetP.HumSetP.ComfortAV202UnitSetP.HumSetP.EconomyAV203UnitSetP.HumSetP.PreComfortAV204UnitSetP.RetAirFlwSetP.ComfortAV205UnitSetP.RetAirFlwSetP.EconomyAV206UnitSetP.RetAirFlwSetP.PreComfortAV207UnitSetP.RoomTempSetP.ComfortAV208UnitSetP.RoomTempSetP.EconomyAV209UnitSetP.RoomTempSetP.PreComfortAV210ActualSetAV211CurrAirFlwSetP_ValAV212CurrAirQualitySetP_ValAV213CurrHumSetP_ValAV214CurrRetAirFlwSetP_ValAV215CurrRoomTempSetP_ValAV216UnitSetP_AirFlwSetP_ComfortAV217UnitSetP_AirFlwSetP_Comfort_2AV218UnitSetP_AirFlwSetP_EconomyAV219UnitSetP_AirFlwSetP_Economy_2AV220UnitSetP_AirFlwSetP_PreComfortAV221UnitSetP_AirFlwSetP_PreComfort_2AV222RecHeat_PowerTemp_T_kWhAV223RecCool_PowerTemp_T_kWhAV224Heat_PowerTemp_T_kWhAV225Cool_PowerTemp_T_kWhAV226PowerElect_T_kWh_ECOAV227PowerElect_T_kWh_OptimalAV228PowerElect_T_kWh_ComfortAV229SupplyFan_Power_E1AV230ReturnFan_Power_E1PIV398HC_Mode_ECOPIV399HC_Mode_ComfortPIV400HC_Mode_OptimalAV231RecHeat_PowerTempAV232RecCool_PowerTempAV233Heat_PowerTempAV234Cool_PowerTempAV235RecHeat_PowerTemp_kWhAV236RecCool_PowerTemp_kWhAV237Heat_PowerTemp_kWhAV238Cool_PowerTemp_kWhAV239Recovery_EfficencyBV27SchedOnIV401Scheduler_OnOffUnit.Scheduler_1.CopyTo_DayIV402Scheduler_OnOffUnit.Scheduler_1.DayBV28Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].EnabledBV29Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].Flag_EnabledPIV403Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].HoursPIV404Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].MinsPIV405Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].UnitStatusBV30Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].EnabledBV31Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].Flag_EnabledPIV406Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].HoursPIV407Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].MinsPIV408Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].UnitStatusBV32Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].EnabledBV33Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].Flag_EnabledPIV409Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].HoursPIV410Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].MinsPIV411Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].UnitStatusBV34Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].EnabledBV35Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].Flag_EnabledPIV412Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].HoursPIV413Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].MinsPIV414Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].UnitStatusBV36Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].EnabledBV37Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].Flag_EnabledPIV415Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].HoursPIV416Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].MinsPIV417Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].UnitStatusBV38Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].EnabledBV39Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].Flag_EnabledPIV418Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].HoursPIV419Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].MinsPIV420Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].UnitStatusBV40Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].EnabledBV41Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].Flag_EnabledPIV421Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].HoursPIV422Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].MinsPIV423Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].UnitStatusBV42Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].EnabledBV43Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].Flag_EnabledPIV424Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].HoursPIV425Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].MinsPIV426Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].UnitStatusBV44Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].EnabledBV45Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].Flag_EnabledPIV427Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].HoursPIV428Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].MinsPIV429Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].UnitStatusBV46Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].EnabledBV47Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].Flag_EnabledPIV430Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].HoursPIV431Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].MinsPIV432Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].UnitStatusBV48Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].EnabledBV49Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].Flag_EnabledPIV433Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].HoursPIV434Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].MinsPIV435Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].UnitStatusBV50Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].EnabledBV51Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].Flag_EnabledPIV436Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].HoursPIV437Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].MinsPIV438Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].UnitStatusBV52Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].EnabledBV53Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].Flag_EnabledPIV439Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].HoursPIV440Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].MinsPIV441Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].UnitStatusBV54Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].EnabledBV55Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].Flag_EnabledPIV442Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].HoursPIV443Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].MinsPIV444Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].UnitStatusBV56Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].EnabledBV57Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].Flag_EnabledPIV445Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].HoursPIV446Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].MinsPIV447Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].UnitStatusBV58Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].EnabledBV59Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].Flag_EnabledPIV448Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].HoursPIV449Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].MinsPIV450Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].UnitStatusBV60Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].EnabledBV61Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].Flag_EnabledPIV451Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].HoursPIV452Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].MinsPIV453Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].UnitStatusBV62Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].EnabledBV63Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].Flag_EnabledPIV454Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].HoursPIV455Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].MinsPIV456Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].UnitStatusBV64Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].EnabledBV65Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].Flag_EnabledPIV457Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].HoursPIV458Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].MinsPIV459Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].UnitStatusBV66Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].EnabledBV67Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].Flag_EnabledPIV460Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].HoursPIV461Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].MinsPIV462Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].UnitStatusBV68Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].EnabledBV69Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].Flag_EnabledPIV463Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].HoursPIV464Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].MinsPIV465Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].UnitStatusBV70Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].EnabledBV71Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].Flag_EnabledPIV466Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].HoursPIV467Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].MinsPIV468Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].UnitStatusBV72Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].EnabledBV73Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].Flag_EnabledPIV469Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].HoursPIV470Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].MinsPIV471Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].UnitStatusBV74Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].EnabledBV75Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].Flag_EnabledPIV472Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].HoursPIV473Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].MinsPIV474Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].UnitStatusBV76Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].EnabledBV77Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].Flag_EnabledPIV475Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].HoursPIV476Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].MinsPIV477Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].UnitStatusBV78Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].EnabledBV79Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].Flag_EnabledPIV478Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].HoursPIV479Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].MinsPIV480Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].UnitStatusBV80Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].EnabledBV81Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].Flag_EnabledPIV481Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].HoursPIV482Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].MinsPIV483Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].UnitStatusBV82Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].EnabledBV83Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].Flag_EnabledPIV484Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].HoursPIV485Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].MinsPIV486Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].UnitStatusPIV487Scheduler_OnOffUnit.Scheduler_1.EnDayCopyPIV488Scheduler_OnOffUnit.Scheduler_1.SaveDataBV84Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].EnabledPIV489Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].SpecialDayPIV490Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].SpecialMonthPIV491Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].UnitStatusBV85Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].EnabledPIV492Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].SpecialDayPIV493Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].SpecialMonthPIV494Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].UnitStatusBV86Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].EnabledPIV495Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].SpecialDayPIV496Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].SpecialMonthPIV497Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].UnitStatusBV87Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].EnabledPIV498Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].SpecialDayPIV499Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].SpecialMonthPIV500Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].UnitStatusBV88Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].EnabledPIV501Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].SpecialDayPIV502Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].SpecialMonthPIV503Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].UnitStatusBV89Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].EnabledPIV504Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].SpecialDayPIV505Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].SpecialMonthPIV506Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].UnitStatusBV90Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].EnabledPIV507Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].HoursPIV508Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].MinsPIV509Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].UnitStatusBV91Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].EnabledPIV510Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].HoursPIV511Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].MinsPIV512Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].UnitStatusBV92Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].EnabledPIV513Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].HoursPIV514Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].MinsPIV515Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].UnitStatusBV93Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].EnabledPIV516Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].HoursPIV517Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].MinsPIV518Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].UnitStatusBV94Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EnabledPIV519Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EndDayPIV520Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EndMonthPIV521Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].StartDayPIV522Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].StartMonthPIV523Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].UnitStatusBV95Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EnabledPIV524Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EndDayPIV525Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EndMonthPIV526Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].StartDayPIV527Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].StartMonthPIV528Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].UnitStatusBV96Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EnabledPIV529Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EndDayPIV530Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EndMonthPIV531Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].StartDayPIV532Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].StartMonthPIV533Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].UnitStatusPIV534SetTypSchedPIV535TypSchedulerBV97SchedActivePIV536CurrUnitStatusBV98Al_ABB_ExhFan_1.TriggerBV99Al_ABB_ExhFan_10.TriggerBV100Al_ABB_ExhFan_2.TriggerBV101Al_ABB_ExhFan_3.TriggerBV102Al_ABB_ExhFan_4.TriggerBV103Al_ABB_ExhFan_5.TriggerBV104Al_ABB_ExhFan_6.TriggerBV105Al_ABB_ExhFan_7.TriggerBV106Al_ABB_ExhFan_8.TriggerBV107Al_ABB_ExhFan_9.TriggerBV108Al_ABB_Rotary.TriggerBV109Al_ABB_SupFan_1.TriggerBV110Al_ABB_SupFan_10.TriggerBV111Al_ABB_SupFan_2.TriggerBV112Al_ABB_SupFan_3.TriggerBV113Al_ABB_SupFan_4.TriggerBV114Al_ABB_SupFan_5.TriggerBV115Al_ABB_SupFan_6.TriggerBV116Al_ABB_SupFan_7.TriggerBV117Al_ABB_SupFan_8.TriggerBV118Al_ABB_SupFan_9.TriggerBV119Al_AFreezeDIN.TriggerBV120Al_AFreezePRB.TriggerBV121Al_AFreezePreHeatPRB.TriggerBV122Al_AfterPreHeatCoilTempPrb.TriggerBV123Al_BMS_Offline.TriggerBV124Al_CfgError_cpCOe.TriggerBV125Al_CircuitFault_EC_ExhFan1.TriggerBV126Al_CircuitFault_EC_ExhFan10.TriggerBV127Al_CircuitFault_EC_ExhFan2.TriggerBV128Al_CircuitFault_EC_ExhFan3.TriggerBV129Al_CircuitFault_EC_ExhFan4.TriggerBV130Al_CircuitFault_EC_ExhFan5.TriggerBV131Al_CircuitFault_EC_ExhFan6.TriggerBV132Al_CircuitFault_EC_ExhFan7.TriggerBV133Al_CircuitFault_EC_ExhFan8.TriggerBV134Al_CircuitFault_EC_ExhFan9.TriggerBV135Al_CircuitFault_EC_SupFan1.TriggerBV136Al_CircuitFault_EC_SupFan10.TriggerBV137Al_CircuitFault_EC_SupFan2.TriggerBV138Al_CircuitFault_EC_SupFan3.TriggerBV139Al_CircuitFault_EC_SupFan4.TriggerBV140Al_CircuitFault_EC_SupFan5.TriggerBV141Al_CircuitFault_EC_SupFan6.TriggerBV142Al_CircuitFault_EC_SupFan7.TriggerBV143Al_CircuitFault_EC_SupFan8.TriggerBV144Al_CircuitFault_EC_SupFan9.TriggerBV145Al_CommErr_ExhFan_1.TriggerBV146Al_CommErr_ExhFan_10.TriggerBV147Al_CommErr_ExhFan_2.TriggerBV148Al_CommErr_ExhFan_3.TriggerBV149Al_CommErr_ExhFan_4.TriggerBV150Al_CommErr_ExhFan_5.TriggerBV151Al_CommErr_ExhFan_6.TriggerBV152Al_CommErr_ExhFan_7.TriggerBV153Al_CommErr_ExhFan_8.TriggerBV154Al_CommErr_ExhFan_9.TriggerBV155Al_CommErr_Rotary.TriggerBV156Al_CommErr_SupFan_1.TriggerBV157Al_CommErr_SupFan_10.TriggerBV158Al_CommErr_SupFan_2.TriggerBV159Al_CommErr_SupFan_3.TriggerBV160Al_CommErr_SupFan_4.TriggerBV161Al_CommErr_SupFan_5.TriggerBV162Al_CommErr_SupFan_6.TriggerBV163Al_CommErr_SupFan_7.TriggerBV164Al_CommErr_SupFan_8.TriggerBV165Al_CommErr_SupFan_9.TriggerBV166Al_Cool.TriggerBV167Al_CoolFanFault_ExhFan_1.TriggerBV168Al_CoolFanFault_ExhFan_10.TriggerBV169Al_CoolFanFault_ExhFan_2.TriggerBV170Al_CoolFanFault_ExhFan_3.TriggerBV171Al_CoolFanFault_ExhFan_4.TriggerBV172Al_CoolFanFault_ExhFan_5.TriggerBV173Al_CoolFanFault_ExhFan_6.TriggerBV174Al_CoolFanFault_ExhFan_7.TriggerBV175Al_CoolFanFault_ExhFan_8.TriggerBV176Al_CoolFanFault_ExhFan_9.TriggerBV177Al_CoolFanFault_Rotary.TriggerBV178Al_CoolFanFault_SupFan_1.TriggerBV179Al_CoolFanFault_SupFan_10.TriggerBV180Al_CoolFanFault_SupFan_2.TriggerBV181Al_CoolFanFault_SupFan_3.TriggerBV182Al_CoolFanFault_SupFan_4.TriggerBV183Al_CoolFanFault_SupFan_5.TriggerBV184Al_CoolFanFault_SupFan_6.TriggerBV185Al_CoolFanFault_SupFan_7.TriggerBV186Al_CoolFanFault_SupFan_8.TriggerBV187Al_CoolFanFault_SupFan_9.TriggerBV188Al_CutOff_ExhFan_1.TriggerBV189Al_CutOff_ExhFan_10.TriggerBV190Al_CutOff_ExhFan_2.TriggerBV191Al_CutOff_ExhFan_3.TriggerBV192Al_CutOff_ExhFan_4.TriggerBV193Al_CutOff_ExhFan_5.TriggerBV194Al_CutOff_ExhFan_6.TriggerBV195Al_CutOff_ExhFan_7.TriggerBV196Al_CutOff_ExhFan_8.TriggerBV197Al_CutOff_ExhFan_9.TriggerBV198Al_CutOff_Rotary.TriggerBV199Al_CutOff_SupFan_1.TriggerBV200Al_CutOff_SupFan_10.TriggerBV201Al_CutOff_SupFan_2.TriggerBV202Al_CutOff_SupFan_3.TriggerBV203Al_CutOff_SupFan_4.TriggerBV204Al_CutOff_SupFan_5.TriggerBV205Al_CutOff_SupFan_6.TriggerBV206Al_CutOff_SupFan_7.TriggerBV207Al_CutOff_SupFan_8.TriggerBV208Al_CutOff_SupFan_9.TriggerBV209Al_DC_Ovld_ExhFan_1.TriggerBV210Al_DC_Ovld_ExhFan_10.TriggerBV211Al_DC_Ovld_ExhFan_2.TriggerBV212Al_DC_Ovld_ExhFan_3.TriggerBV213Al_DC_Ovld_ExhFan_4.TriggerBV214Al_DC_Ovld_ExhFan_5.TriggerBV215Al_DC_Ovld_ExhFan_6.TriggerBV216Al_DC_Ovld_ExhFan_7.TriggerBV217Al_DC_Ovld_ExhFan_8.TriggerBV218Al_DC_Ovld_ExhFan_9.TriggerBV219Al_DC_Ovld_Rotary.TriggerBV220Al_DC_Ovld_SupFan_1.TriggerBV221Al_DC_Ovld_SupFan_10.TriggerBV222Al_DC_Ovld_SupFan_2.TriggerBV223Al_DC_Ovld_SupFan_3.TriggerBV224Al_DC_Ovld_SupFan_4.TriggerBV225Al_DC_Ovld_SupFan_5.TriggerBV226Al_DC_Ovld_SupFan_6.TriggerBV227Al_DC_Ovld_SupFan_7.TriggerBV228Al_DC_Ovld_SupFan_8.TriggerBV229Al_DC_Ovld_SupFan_9.TriggerBV230Al_ElectTherm_ExhFan_1.TriggerBV231Al_ElectTherm_ExhFan_10.TriggerBV232Al_ElectTherm_ExhFan_2.TriggerBV233Al_ElectTherm_ExhFan_3.TriggerBV234Al_ElectTherm_ExhFan_4.TriggerBV235Al_ElectTherm_ExhFan_5.TriggerBV236Al_ElectTherm_ExhFan_6.TriggerBV237Al_ElectTherm_ExhFan_7.TriggerBV238Al_ElectTherm_ExhFan_8.TriggerBV239Al_ElectTherm_ExhFan_9.TriggerBV240Al_ElectTherm_Rotary.TriggerBV241Al_ElectTherm_SupFan_1.TriggerBV242Al_ElectTherm_SupFan_10.TriggerBV243Al_ElectTherm_SupFan_2.TriggerBV244Al_ElectTherm_SupFan_3.TriggerBV245Al_ElectTherm_SupFan_4.TriggerBV246Al_ElectTherm_SupFan_5.TriggerBV247Al_ElectTherm_SupFan_6.TriggerBV248Al_ElectTherm_SupFan_7.TriggerBV249Al_ElectTherm_SupFan_8.TriggerBV250Al_ElectTherm_SupFan_9.TriggerBV251Al_Err_retain_write.TriggerBV252Al_ExhTempPrb.TriggerBV253Al_ExtFaultA_ExhFan_1.TriggerBV254Al_ExtFaultA_ExhFan_10.TriggerBV255Al_ExtFaultA_ExhFan_2.TriggerBV256Al_ExtFaultA_ExhFan_3.TriggerBV257Al_ExtFaultA_ExhFan_4.TriggerBV258Al_ExtFaultA_ExhFan_5.TriggerBV259Al_ExtFaultA_ExhFan_6.TriggerBV260Al_ExtFaultA_ExhFan_7.TriggerBV261Al_ExtFaultA_ExhFan_8.TriggerBV262Al_ExtFaultA_ExhFan_9.TriggerBV263Al_ExtFaultA_Rotary.TriggerBV264Al_ExtFaultA_SupFan_1.TriggerBV265Al_ExtFaultA_SupFan_10.TriggerBV266Al_ExtFaultA_SupFan_2.TriggerBV267Al_ExtFaultA_SupFan_3.TriggerBV268Al_ExtFaultA_SupFan_4.TriggerBV269Al_ExtFaultA_SupFan_5.TriggerBV270Al_ExtFaultA_SupFan_6.TriggerBV271Al_ExtFaultA_SupFan_7.TriggerBV272Al_ExtFaultA_SupFan_8.TriggerBV273Al_ExtFaultA_SupFan_9.TriggerBV274Al_ExtFaultB_ExhFan_1.TriggerBV275Al_ExtFaultB_ExhFan_10.TriggerBV276Al_ExtFaultB_ExhFan_2.TriggerBV277Al_ExtFaultB_ExhFan_3.TriggerBV278Al_ExtFaultB_ExhFan_4.TriggerBV279Al_ExtFaultB_ExhFan_5.TriggerBV280Al_ExtFaultB_ExhFan_6.TriggerBV281Al_ExtFaultB_ExhFan_7.TriggerBV282Al_ExtFaultB_ExhFan_8.TriggerBV283Al_ExtFaultB_ExhFan_9.TriggerBV284Al_ExtFaultB_Rotary.TriggerBV285Al_ExtFaultB_SupFan_1.TriggerBV286Al_ExtFaultB_SupFan_10.TriggerBV287Al_ExtFaultB_SupFan_2.TriggerBV288Al_ExtFaultB_SupFan_3.TriggerBV289Al_ExtFaultB_SupFan_4.TriggerBV290Al_ExtFaultB_SupFan_5.TriggerBV291Al_ExtFaultB_SupFan_6.TriggerBV292Al_ExtFaultB_SupFan_7.TriggerBV293Al_ExtFaultB_SupFan_8.TriggerBV294Al_ExtFaultB_SupFan_9.TriggerBV295Al_ExtTempPrb.TriggerBV296Al_Fire.TriggerBV297Al_FireExh.TriggerBV298Al_GroundFault_ExhFan_1.TriggerBV299Al_GroundFault_ExhFan_10.TriggerBV300Al_GroundFault_ExhFan_2.TriggerBV301Al_GroundFault_ExhFan_3.TriggerBV302Al_GroundFault_ExhFan_4.TriggerBV303Al_GroundFault_ExhFan_5.TriggerBV304Al_GroundFault_ExhFan_6.TriggerBV305Al_GroundFault_ExhFan_7.TriggerBV306Al_GroundFault_ExhFan_8.TriggerBV307Al_GroundFault_ExhFan_9.TriggerBV308Al_GroundFault_Rotary.TriggerBV309Al_GroundFault_SupFan_1.TriggerBV310Al_GroundFault_SupFan_10.TriggerBV311Al_GroundFault_SupFan_2.TriggerBV312Al_GroundFault_SupFan_3.TriggerBV313Al_GroundFault_SupFan_4.TriggerBV314Al_GroundFault_SupFan_5.TriggerBV315Al_GroundFault_SupFan_6.TriggerBV316Al_GroundFault_SupFan_7.TriggerBV317Al_GroundFault_SupFan_8.TriggerBV318Al_GroundFault_SupFan_9.TriggerBV319Al_Heat.TriggerBV320Al_HeatCoilTempPrb.TriggerBV321Al_HeatExchgWorkHrsWarn.TriggerBV322Al_HeatSink_ExhFan_1.TriggerBV323Al_HeatSink_ExhFan_10.TriggerBV324Al_HeatSink_ExhFan_2.TriggerBV325Al_HeatSink_ExhFan_3.TriggerBV326Al_HeatSink_ExhFan_4.TriggerBV327Al_HeatSink_ExhFan_5.TriggerBV328Al_HeatSink_ExhFan_6.TriggerBV329Al_HeatSink_ExhFan_7.TriggerBV330Al_HeatSink_ExhFan_8.TriggerBV331Al_HeatSink_ExhFan_9.TriggerBV332Al_HeatSink_Rotary.TriggerBV333Al_HeatSink_SupFan_1.TriggerBV334Al_HeatSink_SupFan_10.TriggerBV335Al_HeatSink_SupFan_2.TriggerBV336Al_HeatSink_SupFan_3.TriggerBV337Al_HeatSink_SupFan_4.TriggerBV338Al_HeatSink_SupFan_5.TriggerBV339Al_HeatSink_SupFan_6.TriggerBV340Al_HeatSink_SupFan_7.TriggerBV341Al_HeatSink_SupFan_8.TriggerBV342Al_HeatSink_SupFan_9.TriggerBV343AL_Hot_EC_ExhFan1.TriggerBV344AL_Hot_EC_ExhFan10.TriggerBV345AL_Hot_EC_ExhFan2.TriggerBV346AL_Hot_EC_ExhFan3.TriggerBV347AL_Hot_EC_ExhFan4.TriggerBV348AL_Hot_EC_ExhFan5.TriggerBV349AL_Hot_EC_ExhFan6.TriggerBV350AL_Hot_EC_ExhFan7.TriggerBV351AL_Hot_EC_ExhFan8.TriggerBV352AL_Hot_EC_ExhFan9.TriggerBV353AL_Hot_EC_SupFan1.TriggerBV354AL_Hot_EC_SupFan10.TriggerBV355AL_Hot_EC_SupFan2.TriggerBV356AL_Hot_EC_SupFan3.TriggerBV357AL_Hot_EC_SupFan4.TriggerBV358AL_Hot_EC_SupFan5.TriggerBV359AL_Hot_EC_SupFan6.TriggerBV360AL_Hot_EC_SupFan7.TriggerBV361AL_Hot_EC_SupFan8.TriggerBV362AL_Hot_EC_SupFan9.TriggerBV363Al_Hum.TriggerBV364Al_HumWorkHrsWarn.TriggerBV365Al_HW_Fault_ExhFan_1.TriggerBV366Al_HW_Fault_ExhFan_10.TriggerBV367Al_HW_Fault_ExhFan_2.TriggerBV368Al_HW_Fault_ExhFan_3.TriggerBV369Al_HW_Fault_ExhFan_4.TriggerBV370Al_HW_Fault_ExhFan_5.TriggerBV371Al_HW_Fault_ExhFan_6.TriggerBV372Al_HW_Fault_ExhFan_7.TriggerBV373Al_HW_Fault_ExhFan_8.TriggerBV374Al_HW_Fault_ExhFan_9.TriggerBV375Al_HW_Fault_Rotary.TriggerBV376Al_HW_Fault_SupFan_1.TriggerBV377Al_HW_Fault_SupFan_10.TriggerBV378Al_HW_Fault_SupFan_2.TriggerBV379Al_HW_Fault_SupFan_3.TriggerBV380Al_HW_Fault_SupFan_4.TriggerBV381Al_HW_Fault_SupFan_5.TriggerBV382Al_HW_Fault_SupFan_6.TriggerBV383Al_HW_Fault_SupFan_7.TriggerBV384Al_HW_Fault_SupFan_8.TriggerBV385Al_HW_Fault_SupFan_9.TriggerBV386Al_I2RIGBTFault_EC_ExhFan1.TriggerBV387Al_I2RIGBTFault_EC_ExhFan10.TriggerBV388Al_I2RIGBTFault_EC_ExhFan2.TriggerBV389Al_I2RIGBTFault_EC_ExhFan3.TriggerBV390Al_I2RIGBTFault_EC_ExhFan4.TriggerBV391Al_I2RIGBTFault_EC_ExhFan5.TriggerBV392Al_I2RIGBTFault_EC_ExhFan6.TriggerBV393Al_I2RIGBTFault_EC_ExhFan7.TriggerBV394Al_I2RIGBTFault_EC_ExhFan8.TriggerBV395Al_I2RIGBTFault_EC_ExhFan9.TriggerBV396Al_I2RIGBTFault_EC_SupFan1.TriggerBV397Al_I2RIGBTFault_EC_SupFan10.TriggerBV398Al_I2RIGBTFault_EC_SupFan2.TriggerBV399Al_I2RIGBTFault_EC_SupFan3.TriggerBV400Al_I2RIGBTFault_EC_SupFan4.TriggerBV401Al_I2RIGBTFault_EC_SupFan5.TriggerBV402Al_I2RIGBTFault_EC_SupFan6.TriggerBV403Al_I2RIGBTFault_EC_SupFan7.TriggerBV404Al_I2RIGBTFault_EC_SupFan8.TriggerBV405Al_I2RIGBTFault_EC_SupFan9.TriggerBV406AL_IGBTOvercurrent_EC_ExhFan1.TriggerBV407AL_IGBTOvercurrent_EC_ExhFan10.TriggerBV408AL_IGBTOvercurrent_EC_ExhFan2.TriggerBV409AL_IGBTOvercurrent_EC_ExhFan3.TriggerBV410AL_IGBTOvercurrent_EC_ExhFan4.TriggerBV411AL_IGBTOvercurrent_EC_ExhFan5.TriggerBV412AL_IGBTOvercurrent_EC_ExhFan6.TriggerBV413AL_IGBTOvercurrent_EC_ExhFan7.TriggerBV414AL_IGBTOvercurrent_EC_ExhFan8.TriggerBV415AL_IGBTOvercurrent_EC_ExhFan9.TriggerBV416AL_IGBTOvercurrent_EC_SupFan1.TriggerBV417AL_IGBTOvercurrent_EC_SupFan10.TriggerBV418AL_IGBTOvercurrent_EC_SupFan2.TriggerBV419AL_IGBTOvercurrent_EC_SupFan3.TriggerBV420AL_IGBTOvercurrent_EC_SupFan4.TriggerBV421AL_IGBTOvercurrent_EC_SupFan5.TriggerBV422AL_IGBTOvercurrent_EC_SupFan6.TriggerBV423AL_IGBTOvercurrent_EC_SupFan7.TriggerBV424AL_IGBTOvercurrent_EC_SupFan8.TriggerBV425AL_IGBTOvercurrent_EC_SupFan9.TriggerBV426Al_InvOverheat_ExhFan_1.TriggerBV427Al_InvOverheat_ExhFan_10.TriggerBV428Al_InvOverheat_ExhFan_2.TriggerBV429Al_InvOverheat_ExhFan_3.TriggerBV430Al_InvOverheat_ExhFan_4.TriggerBV431Al_InvOverheat_ExhFan_5.TriggerBV432Al_InvOverheat_ExhFan_6.TriggerBV433Al_InvOverheat_ExhFan_7.TriggerBV434Al_InvOverheat_ExhFan_8.TriggerBV435Al_InvOverheat_ExhFan_9.TriggerBV436Al_InvOverheat_Rotary.TriggerBV437Al_InvOverheat_SupFan_1.TriggerBV438Al_InvOverheat_SupFan_10.TriggerBV439Al_InvOverheat_SupFan_2.TriggerBV440Al_InvOverheat_SupFan_3.TriggerBV441Al_InvOverheat_SupFan_4.TriggerBV442Al_InvOverheat_SupFan_5.TriggerBV443Al_InvOverheat_SupFan_6.TriggerBV444Al_InvOverheat_SupFan_7.TriggerBV445Al_InvOverheat_SupFan_8.TriggerBV446Al_InvOverheat_SupFan_9.TriggerBV447Al_InvOvld_ExhFan_1.TriggerBV448Al_InvOvld_ExhFan_10.TriggerBV449Al_InvOvld_ExhFan_2.TriggerBV450Al_InvOvld_ExhFan_3.TriggerBV451Al_InvOvld_ExhFan_4.TriggerBV452Al_InvOvld_ExhFan_5.TriggerBV453Al_InvOvld_ExhFan_6.TriggerBV454Al_InvOvld_ExhFan_7.TriggerBV455Al_InvOvld_ExhFan_8.TriggerBV456Al_InvOvld_ExhFan_9.TriggerBV457Al_InvOvld_Rotary.TriggerBV458Al_InvOvld_SupFan_1.TriggerBV459Al_InvOvld_SupFan_10.TriggerBV460Al_InvOvld_SupFan_2.TriggerBV461Al_InvOvld_SupFan_3.TriggerBV462Al_InvOvld_SupFan_4.TriggerBV463Al_InvOvld_SupFan_5.TriggerBV464Al_InvOvld_SupFan_6.TriggerBV465Al_InvOvld_SupFan_7.TriggerBV466Al_InvOvld_SupFan_8.TriggerBV467Al_InvOvld_SupFan_9.TriggerBV468Al_LowSupplyTemp.TriggerBV469Al_LowVolt_ExhFan_1.TriggerBV470Al_LowVolt_ExhFan_10.TriggerBV471Al_LowVolt_ExhFan_2.TriggerBV472Al_LowVolt_ExhFan_3.TriggerBV473Al_LowVolt_ExhFan_4.TriggerBV474Al_LowVolt_ExhFan_5.TriggerBV475Al_LowVolt_ExhFan_6.TriggerBV476Al_LowVolt_ExhFan_7.TriggerBV477Al_LowVolt_ExhFan_8.TriggerBV478Al_LowVolt_ExhFan_9.TriggerBV479Al_LowVolt_Rotary.TriggerBV480Al_LowVolt_SupFan_1.TriggerBV481Al_LowVolt_SupFan_10.TriggerBV482Al_LowVolt_SupFan_2.TriggerBV483Al_LowVolt_SupFan_3.TriggerBV484Al_LowVolt_SupFan_4.TriggerBV485Al_LowVolt_SupFan_5.TriggerBV486Al_LowVolt_SupFan_6.TriggerBV487Al_LowVolt_SupFan_7.TriggerBV488Al_LowVolt_SupFan_8.TriggerBV489Al_LowVolt_SupFan_9.TriggerBV490Al_MB_AO1.TriggerBV491Al_MB_AO1_AO4_PWM.TriggerBV492Al_MB_AO2.TriggerBV493Al_MB_AO3.TriggerBV494Al_MB_AO4.TriggerBV495Al_MB_Control_Supply.TriggerBV496Al_MB_Control_Temp.TriggerBV497Al_MB_Humidity.TriggerBV498Al_MB_Press_Fan_Return.TriggerBV499Al_MB_Press_Fan_Supply.TriggerBV500Al_MB_Press_Filter_Return.TriggerBV501Al_MB_Press_Filter_Supply.TriggerBV502Al_MB_Supply24.TriggerBV503Al_MB_Temp_Fan_Return.TriggerBV504Al_MB_Temp_Fan_Supply.TriggerBV505Al_MB_Temp_Filter_Return.TriggerBV506Al_MB_Temp_Filter_Supply.TriggerBV507Al_MB_Temperature.TriggerBV508Al_MotorFault_EC_ExhFan10.TriggerBV509Al_MotorFault_EC_ExhFan2.TriggerBV510Al_MotorFault_EC_ExhFan3.TriggerBV511Al_MotorFault_EC_ExhFan4.TriggerBV512Al_MotorFault_EC_ExhFan5.TriggerBV513Al_MotorFault_EC_ExhFan6.TriggerBV514Al_MotorFault_EC_ExhFan7.TriggerBV515Al_MotorFault_EC_ExhFan8.TriggerBV516Al_MotorFault_EC_ExhFan9.TriggerBV517Al_MotorFault_EC_SupFan1.TriggerBV518Al_MotorFault_EC_SupFan10.TriggerBV519Al_MotorFault_EC_SupFan2.TriggerBV520Al_MotorFault_EC_SupFan3.TriggerBV521Al_MotorFault_EC_SupFan4.TriggerBV522Al_MotorFault_EC_SupFan5.TriggerBV523Al_MotorFault_EC_SupFan6.TriggerBV524Al_MotorFault_EC_SupFan7.TriggerBV525Al_MotorFault_EC_SupFan8.TriggerBV526Al_MotorFault_EC_SupFan9.TriggerBV527Al_MotorOverheat_ExhFan_1.TriggerBV528Al_MotorOverheat_ExhFan_10.TriggerBV529Al_MotorOverheat_ExhFan_2.TriggerBV530Al_MotorOverheat_ExhFan_3.TriggerBV531Al_MotorOverheat_ExhFan_4.TriggerBV532Al_MotorOverheat_ExhFan_5.TriggerBV533Al_MotorOverheat_ExhFan_6.TriggerBV534Al_MotorOverheat_ExhFan_7.TriggerBV535Al_MotorOverheat_ExhFan_8.TriggerBV536Al_MotorOverheat_ExhFan_9.TriggerBV537Al_MotorOverheat_Rotary.TriggerBV538Al_MotorOverheat_SupFan_1.TriggerBV539Al_MotorOverheat_SupFan_10.TriggerBV540Al_MotorOverheat_SupFan_2.TriggerBV541Al_MotorOverheat_SupFan_3.TriggerBV542Al_MotorOverheat_SupFan_4.TriggerBV543Al_MotorOverheat_SupFan_5.TriggerBV544Al_MotorOverheat_SupFan_6.TriggerBV545Al_MotorOverheat_SupFan_7.TriggerBV546Al_MotorOverheat_SupFan_8.TriggerBV547Al_MotorOverheat_SupFan_9.TriggerBV548Al_Offline_cpCOe.TriggerBV549Al_Offline_ExhFan_1.TriggerBV550Al_Offline_ExhFan_10.TriggerBV551Al_Offline_ExhFan_2.TriggerBV552Al_Offline_ExhFan_3.TriggerBV553Al_Offline_ExhFan_4.TriggerBV554Al_Offline_ExhFan_5.TriggerBV555Al_Offline_ExhFan_6.TriggerBV556Al_Offline_ExhFan_7.TriggerBV557Al_Offline_ExhFan_8.TriggerBV558Al_Offline_ExhFan_9.TriggerBV559Al_Offline_MainBoard.TriggerBV560Al_Offline_Rotary.TriggerBV561Al_Offline_SP_ExhHum.TriggerBV562Al_Offline_SP_ExhPress.TriggerBV563Al_Offline_SP_SupplyHum.TriggerBV564Al_Offline_SP_SupplyPress.TriggerBV565Al_Offline_SupFan_1.TriggerBV566Al_Offline_SupFan_10.TriggerBV567Al_Offline_SupFan_2.TriggerBV568Al_Offline_SupFan_3.TriggerBV569Al_Offline_SupFan_4.TriggerBV570Al_Offline_SupFan_5.TriggerBV571Al_Offline_SupFan_6.TriggerBV572Al_Offline_SupFan_7.TriggerBV573Al_Offline_SupFan_8.TriggerBV574Al_Offline_SupFan_9.TriggerBV575Al_Offline_THTN_1.TriggerBV576Al_Option_ExhFan_1.TriggerBV577Al_Option_ExhFan_10.TriggerBV578Al_Option_ExhFan_2.TriggerBV579Al_Option_ExhFan_3.TriggerBV580Al_Option_ExhFan_4.TriggerBV581Al_Option_ExhFan_5.TriggerBV582Al_Option_ExhFan_6.TriggerBV583Al_Option_ExhFan_7.TriggerBV584Al_Option_ExhFan_8.TriggerBV585Al_Option_ExhFan_9.TriggerBV586Al_Option_Rotary.TriggerBV587Al_Option_SupFan_1.TriggerBV588Al_Option_SupFan_10.TriggerBV589Al_Option_SupFan_2.TriggerBV590Al_Option_SupFan_3.TriggerBV591Al_Option_SupFan_4.TriggerBV592Al_Option_SupFan_5.TriggerBV593Al_Option_SupFan_6.TriggerBV594Al_Option_SupFan_7.TriggerBV595Al_Option_SupFan_8.TriggerBV596Al_Option_SupFan_9.TriggerBV597Al_Overcurrent_ExhFan_1.TriggerBV598Al_Overcurrent_ExhFan_10.TriggerBV599Al_Overcurrent_ExhFan_2.TriggerBV600Al_Overcurrent_ExhFan_3.TriggerBV601Al_Overcurrent_ExhFan_4.TriggerBV602Al_Overcurrent_ExhFan_5.TriggerBV603Al_Overcurrent_ExhFan_6.TriggerBV604Al_Overcurrent_ExhFan_7.TriggerBV605Al_Overcurrent_ExhFan_8.TriggerBV606Al_Overcurrent_ExhFan_9.TriggerBV607Al_Overcurrent_Rotary.TriggerBV608Al_Overcurrent_SupFan_1.TriggerBV609Al_Overcurrent_SupFan_10.TriggerBV610Al_Overcurrent_SupFan_2.TriggerBV611Al_Overcurrent_SupFan_3.TriggerBV612Al_Overcurrent_SupFan_4.TriggerBV613Al_Overcurrent_SupFan_5.TriggerBV614Al_Overcurrent_SupFan_6.TriggerBV615Al_Overcurrent_SupFan_7.TriggerBV616Al_Overcurrent_SupFan_8.TriggerBV617Al_Overcurrent_SupFan_9.TriggerBV618Al_OverVolt_ExhFan_1.TriggerBV619Al_OverVolt_ExhFan_10.TriggerBV620Al_OverVolt_ExhFan_2.TriggerBV621Al_OverVolt_ExhFan_3.TriggerBV622Al_OverVolt_ExhFan_4.TriggerBV623Al_OverVolt_ExhFan_5.TriggerBV624Al_OverVolt_ExhFan_6.TriggerBV625Al_OverVolt_ExhFan_7.TriggerBV626Al_OverVolt_ExhFan_8.TriggerBV627Al_OverVolt_ExhFan_9.TriggerBV628Al_OverVolt_Rotary.TriggerBV629Al_OverVolt_SupFan_1.TriggerBV630Al_OverVolt_SupFan_10.TriggerBV631Al_OverVolt_SupFan_2.TriggerBV632Al_OverVolt_SupFan_3.TriggerBV633Al_OverVolt_SupFan_4.TriggerBV634Al_OverVolt_SupFan_5.TriggerBV635Al_OverVolt_SupFan_6.TriggerBV636Al_OverVolt_SupFan_7.TriggerBV637Al_OverVolt_SupFan_8.TriggerBV638Al_OverVolt_SupFan_9.TriggerBV639AL_Overvoltage_EC_ExhFan1.TriggerBV640AL_Overvoltage_EC_ExhFan10.TriggerBV641AL_Overvoltage_EC_ExhFan2.TriggerBV642AL_Overvoltage_EC_ExhFan3.TriggerBV643AL_Overvoltage_EC_ExhFan4.TriggerBV644AL_Overvoltage_EC_ExhFan5.TriggerBV645AL_Overvoltage_EC_ExhFan6.TriggerBV646AL_Overvoltage_EC_ExhFan7.TriggerBV647AL_Overvoltage_EC_ExhFan8.TriggerBV648AL_Overvoltage_EC_ExhFan9.TriggerBV649AL_Overvoltage_EC_SupFan1.TriggerBV650AL_Overvoltage_EC_SupFan10.TriggerBV651AL_Overvoltage_EC_SupFan2.TriggerBV652AL_Overvoltage_EC_SupFan3.TriggerBV653AL_Overvoltage_EC_SupFan4.TriggerBV654AL_Overvoltage_EC_SupFan5.TriggerBV655AL_Overvoltage_EC_SupFan6.TriggerBV656AL_Overvoltage_EC_SupFan7.TriggerBV657AL_Overvoltage_EC_SupFan8.TriggerBV658AL_Overvoltage_EC_SupFan9.TriggerBV659Al_Ovld_ExhFan_1.TriggerBV660Al_Ovld_ExhFan_10.TriggerBV661Al_Ovld_ExhFan_2.TriggerBV662Al_Ovld_ExhFan_3.TriggerBV663Al_Ovld_ExhFan_4.TriggerBV664Al_Ovld_ExhFan_5.TriggerBV665Al_Ovld_ExhFan_6.TriggerBV666Al_Ovld_ExhFan_7.TriggerBV667Al_Ovld_ExhFan_8.TriggerBV668Al_Ovld_ExhFan_9.TriggerBV669Al_Ovld_Rotary.TriggerBV670Al_Ovld_SupFan_1.TriggerBV671Al_Ovld_SupFan_10.TriggerBV672Al_Ovld_SupFan_2.TriggerBV673Al_Ovld_SupFan_3.TriggerBV674Al_Ovld_SupFan_4.TriggerBV675Al_Ovld_SupFan_5.TriggerBV676Al_Ovld_SupFan_6.TriggerBV677Al_Ovld_SupFan_7.TriggerBV678Al_Ovld_SupFan_8.TriggerBV679Al_Ovld_SupFan_9.TriggerBV680Al_ParamErr_ExhFan_1.TriggerBV681Al_ParamErr_ExhFan_10.TriggerBV682Al_ParamErr_ExhFan_2.TriggerBV683Al_ParamErr_ExhFan_3.TriggerBV684Al_ParamErr_ExhFan_4.TriggerBV685Al_ParamErr_ExhFan_5.TriggerBV686Al_ParamErr_ExhFan_6.TriggerBV687Al_ParamErr_ExhFan_7.TriggerBV688Al_ParamErr_ExhFan_8.TriggerBV689Al_ParamErr_ExhFan_9.TriggerBV690Al_ParamErr_Rotary.TriggerBV691Al_ParamErr_SupFan_1.TriggerBV692Al_ParamErr_SupFan_10.TriggerBV693Al_ParamErr_SupFan_2.TriggerBV694Al_ParamErr_SupFan_3.TriggerBV695Al_ParamErr_SupFan_4.TriggerBV696Al_ParamErr_SupFan_5.TriggerBV697Al_ParamErr_SupFan_6.TriggerBV698Al_ParamErr_SupFan_7.TriggerBV699Al_ParamErr_SupFan_8.TriggerBV700Al_ParamErr_SupFan_9.TriggerBV701AL_ParametersCRC_EC_ExhFan1.TriggerBV702AL_ParametersCRC_EC_ExhFan10.TriggerBV703AL_ParametersCRC_EC_ExhFan2.TriggerBV704AL_ParametersCRC_EC_ExhFan3.TriggerBV705AL_ParametersCRC_EC_ExhFan4.TriggerBV706AL_ParametersCRC_EC_ExhFan5.TriggerBV707AL_ParametersCRC_EC_ExhFan6.TriggerBV708AL_ParametersCRC_EC_ExhFan7.TriggerBV709AL_ParametersCRC_EC_ExhFan8.TriggerBV710AL_ParametersCRC_EC_ExhFan9.TriggerBV711AL_ParametersCRC_EC_SupFan1.TriggerBV712AL_ParametersCRC_EC_SupFan10.TriggerBV713AL_ParametersCRC_EC_SupFan2.TriggerBV714AL_ParametersCRC_EC_SupFan3.TriggerBV715AL_ParametersCRC_EC_SupFan4.TriggerBV716AL_ParametersCRC_EC_SupFan5.TriggerBV717AL_ParametersCRC_EC_SupFan6.TriggerBV718AL_ParametersCRC_EC_SupFan7.TriggerBV719AL_ParametersCRC_EC_SupFan8.TriggerBV720AL_ParametersCRC_EC_SupFan9.TriggerBV721AL_PhaseLoss_EC_ExhFan1.TriggerBV722AL_PhaseLoss_EC_ExhFan10.TriggerBV723AL_PhaseLoss_EC_ExhFan2.TriggerBV724AL_PhaseLoss_EC_ExhFan3.TriggerBV725AL_PhaseLoss_EC_ExhFan4.TriggerBV726AL_PhaseLoss_EC_ExhFan5.TriggerBV727AL_PhaseLoss_EC_ExhFan6.TriggerBV728AL_PhaseLoss_EC_ExhFan7.TriggerBV729AL_PhaseLoss_EC_ExhFan8.TriggerBV730AL_PhaseLoss_EC_ExhFan9.TriggerBV731AL_PhaseLoss_EC_SupFan1.TriggerBV732AL_PhaseLoss_EC_SupFan10.TriggerBV733AL_PhaseLoss_EC_SupFan2.TriggerBV734AL_PhaseLoss_EC_SupFan3.TriggerBV735AL_PhaseLoss_EC_SupFan4.TriggerBV736AL_PhaseLoss_EC_SupFan5.TriggerBV737AL_PhaseLoss_EC_SupFan6.TriggerBV738AL_PhaseLoss_EC_SupFan7.TriggerBV739AL_PhaseLoss_EC_SupFan8.TriggerBV740AL_PhaseLoss_EC_SupFan9.TriggerBV741Al_PhLost_ExhFan_1.TriggerBV742Al_PhLost_ExhFan_10.TriggerBV743Al_PhLost_ExhFan_2.TriggerBV744Al_PhLost_ExhFan_3.TriggerBV745Al_PhLost_ExhFan_4.TriggerBV746Al_PhLost_ExhFan_5.TriggerBV747Al_PhLost_ExhFan_6.TriggerBV748Al_PhLost_ExhFan_7.TriggerBV749Al_PhLost_ExhFan_8.TriggerBV750Al_PhLost_ExhFan_9.TriggerBV751Al_PhLost_Rotary.TriggerBV752Al_PhLost_SupFan_1.TriggerBV753Al_PhLost_SupFan_10.TriggerBV754Al_PhLost_SupFan_2.TriggerBV755Al_PhLost_SupFan_3.TriggerBV756Al_PhLost_SupFan_4.TriggerBV757Al_PhLost_SupFan_5.TriggerBV758Al_PhLost_SupFan_6.TriggerBV759Al_PhLost_SupFan_7.TriggerBV760Al_PhLost_SupFan_8.TriggerBV761Al_PhLost_SupFan_9.TriggerBV762Al_PhOpen_ExhFan_1.TriggerBV763Al_PhOpen_ExhFan_10.TriggerBV764Al_PhOpen_ExhFan_2.TriggerBV765Al_PhOpen_ExhFan_3.TriggerBV766Al_PhOpen_ExhFan_4.TriggerBV767Al_PhOpen_ExhFan_5.TriggerBV768Al_PhOpen_ExhFan_6.TriggerBV769Al_PhOpen_ExhFan_7.TriggerBV770Al_PhOpen_ExhFan_8.TriggerBV771Al_PhOpen_ExhFan_9.TriggerBV772Al_PhOpen_Rotary.TriggerBV773Al_PhOpen_SupFan_1.TriggerBV774Al_PhOpen_SupFan_10.TriggerBV775Al_PhOpen_SupFan_2.TriggerBV776Al_PhOpen_SupFan_3.TriggerBV777Al_PhOpen_SupFan_4.TriggerBV778Al_PhOpen_SupFan_5.TriggerBV779Al_PhOpen_SupFan_6.TriggerBV780Al_PhOpen_SupFan_7.TriggerBV781Al_PhOpen_SupFan_8.TriggerBV782Al_PhOpen_SupFan_9.TriggerBV783Al_PreHeatCoilTempPrb.TriggerBV784Al_RDT_Fan.TriggerBV785Al_RecSupplyTemp.TriggerBV786Al_ReheatCoilWorkHrsWarn.TriggerBV787Al_retain.TriggerBV788Al_RetAir_CO2_Lev_Prb.TriggerBV789Al_RetAirFlwSwWarn.TriggerBV790Al_RetAirP_Prb.TriggerBV791Al_RetFanWorkHrsWarn.TriggerBV792Al_RetFilt.TriggerBV793Al_RetTempPrb.TriggerBV794Al_SupplyAirFlwSwWarn.TriggerBV795Al_SupplyAirP_Prb.TriggerBV796Al_SupplyFanWorkHrsWarn.TriggerBV797Al_SupplyFilt.TriggerBV798Al_SupplyTempPrb.TriggerBV799Al_SwPrototype.TriggerBV800Al_ThTune_ClkBrd.TriggerBV801Al_ThTune_HumPrb.TriggerBV802Al_ThTune_TempPrb.TriggerBV803Al_TooHot_EC_ExhFan1.TriggerBV804Al_TooHot_EC_ExhFan10.TriggerBV805Al_TooHot_EC_ExhFan2.TriggerBV806Al_TooHot_EC_ExhFan3.TriggerBV807Al_TooHot_EC_ExhFan4.TriggerBV808Al_TooHot_EC_ExhFan5.TriggerBV809Al_TooHot_EC_ExhFan6.TriggerBV810Al_TooHot_EC_ExhFan7.TriggerBV811Al_TooHot_EC_ExhFan8.TriggerBV812Al_TooHot_EC_ExhFan9.TriggerBV813Al_TooHot_EC_SupFan1.TriggerBV814Al_TooHot_EC_SupFan10.TriggerBV815Al_TooHot_EC_SupFan2.TriggerBV816Al_TooHot_EC_SupFan3.TriggerBV817Al_TooHot_EC_SupFan4.TriggerBV818Al_TooHot_EC_SupFan5.TriggerBV819Al_TooHot_EC_SupFan6.TriggerBV820Al_TooHot_EC_SupFan7.TriggerBV821Al_TooHot_EC_SupFan8.TriggerBV822Al_TooHot_EC_SupFan9.TriggerBV823Al_Undervoltage_EC_ExhFan1.TriggerBV824Al_Undervoltage_EC_ExhFan10.TriggerBV825Al_Undervoltage_EC_ExhFan2.TriggerBV826Al_Undervoltage_EC_ExhFan3.TriggerBV827Al_Undervoltage_EC_ExhFan4.TriggerBV828Al_Undervoltage_EC_ExhFan5.TriggerBV829Al_Undervoltage_EC_ExhFan6.TriggerBV830Al_Undervoltage_EC_ExhFan7.TriggerBV831Al_Undervoltage_EC_ExhFan8.TriggerBV832Al_Undervoltage_EC_ExhFan9.TriggerBV833Al_Undervoltage_EC_SupFan1.TriggerBV834Al_Undervoltage_EC_SupFan10.TriggerBV835Al_Undervoltage_EC_SupFan2.TriggerBV836Al_Undervoltage_EC_SupFan3.TriggerBV837Al_Undervoltage_EC_SupFan4.TriggerBV838Al_Undervoltage_EC_SupFan5.TriggerBV839Al_Undervoltage_EC_SupFan6.TriggerBV840Al_Undervoltage_EC_SupFan7.TriggerBV841Al_Undervoltage_EC_SupFan8.TriggerBV842Al_Undervoltage_EC_SupFan9.TriggerBV843CfgErrAlrm.TriggerBV844OfflineAlrm.TriggerBV845AlarmMng.AlrmResByBmsBV846Al_ABB_ExhFan_1.ActiveBV847Al_ABB_ExhFan_10.ActiveBV848Al_ABB_ExhFan_2.ActiveBV849Al_ABB_ExhFan_3.ActiveBV850Al_ABB_ExhFan_4.ActiveBV851Al_ABB_ExhFan_5.ActiveBV852Al_ABB_ExhFan_6.ActiveBV853Al_ABB_ExhFan_7.ActiveBV854Al_ABB_ExhFan_8.ActiveBV855Al_ABB_ExhFan_9.ActiveBV856Al_ABB_Rotary.ActiveBV857Al_ABB_SupFan_1.ActiveBV858Al_ABB_SupFan_10.ActiveBV859Al_ABB_SupFan_2.ActiveBV860Al_ABB_SupFan_3.ActiveBV861Al_ABB_SupFan_4.ActiveBV862Al_ABB_SupFan_5.ActiveBV863Al_ABB_SupFan_6.ActiveBV864Al_ABB_SupFan_7.ActiveBV865Al_ABB_SupFan_8.ActiveBV866Al_ABB_SupFan_9.ActiveBV867Al_AFreezeDIN.ActiveBV868Al_AFreezePRB.ActiveBV869Al_AFreezePreHeatPRB.ActiveBV870Al_AfterPreHeatCoilTempPrb.ActiveBV871Al_BMS_Offline.ActiveBV872Al_CfgError_cpCOe.ActiveBV873Al_CircuitFault_EC_ExhFan1.ActiveBV874Al_CircuitFault_EC_ExhFan10.ActiveBV875Al_CircuitFault_EC_ExhFan2.ActiveBV876Al_CircuitFault_EC_ExhFan3.ActiveBV877Al_CircuitFault_EC_ExhFan4.ActiveBV878Al_CircuitFault_EC_ExhFan5.ActiveBV879Al_CircuitFault_EC_ExhFan6.ActiveBV880Al_CircuitFault_EC_ExhFan7.ActiveBV881Al_CircuitFault_EC_ExhFan8.ActiveBV882Al_CircuitFault_EC_ExhFan9.ActiveBV883Al_CircuitFault_EC_SupFan1.ActiveBV884Al_CircuitFault_EC_SupFan10.ActiveBV885Al_CircuitFault_EC_SupFan2.ActiveBV886Al_CircuitFault_EC_SupFan3.ActiveBV887Al_CircuitFault_EC_SupFan4.ActiveBV888Al_CircuitFault_EC_SupFan5.ActiveBV889Al_CircuitFault_EC_SupFan6.ActiveBV890Al_CircuitFault_EC_SupFan7.ActiveBV891Al_CircuitFault_EC_SupFan8.ActiveBV892Al_CircuitFault_EC_SupFan9.ActiveBV893Al_CommErr_ExhFan_1.ActiveBV894Al_CommErr_ExhFan_10.ActiveBV895Al_CommErr_ExhFan_2.ActiveBV896Al_CommErr_ExhFan_3.ActiveBV897Al_CommErr_ExhFan_4.ActiveBV898Al_CommErr_ExhFan_5.ActiveBV899Al_CommErr_ExhFan_6.ActiveBV900Al_CommErr_ExhFan_7.ActiveBV901Al_CommErr_ExhFan_8.ActiveBV902Al_CommErr_ExhFan_9.ActiveBV903Al_CommErr_Rotary.ActiveBV904Al_CommErr_SupFan_1.ActiveBV905Al_CommErr_SupFan_10.ActiveBV906Al_CommErr_SupFan_2.ActiveBV907Al_CommErr_SupFan_3.ActiveBV908Al_CommErr_SupFan_4.ActiveBV909Al_CommErr_SupFan_5.ActiveBV910Al_CommErr_SupFan_6.ActiveBV911Al_CommErr_SupFan_7.ActiveBV912Al_CommErr_SupFan_8.ActiveBV913Al_CommErr_SupFan_9.ActiveBV914Al_Cool.ActiveBV915Al_CoolFanFault_ExhFan_1.ActiveBV916Al_CoolFanFault_ExhFan_10.ActiveBV917Al_CoolFanFault_ExhFan_2.ActiveBV918Al_CoolFanFault_ExhFan_3.ActiveBV919Al_CoolFanFault_ExhFan_4.ActiveBV920Al_CoolFanFault_ExhFan_5.ActiveBV921Al_CoolFanFault_ExhFan_6.ActiveBV922Al_CoolFanFault_ExhFan_7.ActiveBV923Al_CoolFanFault_ExhFan_8.ActiveBV924Al_CoolFanFault_ExhFan_9.ActiveBV925Al_CoolFanFault_Rotary.ActiveBV926Al_CoolFanFault_SupFan_1.ActiveBV927Al_CoolFanFault_SupFan_10.ActiveBV928Al_CoolFanFault_SupFan_2.ActiveBV929Al_CoolFanFault_SupFan_3.ActiveBV930Al_CoolFanFault_SupFan_4.ActiveBV931Al_CoolFanFault_SupFan_5.ActiveBV932Al_CoolFanFault_SupFan_6.ActiveBV933Al_CoolFanFault_SupFan_7.ActiveBV934Al_CoolFanFault_SupFan_8.ActiveBV935Al_CoolFanFault_SupFan_9.ActiveBV936Al_CutOff_ExhFan_1.ActiveBV937Al_CutOff_ExhFan_10.ActiveBV938Al_CutOff_ExhFan_2.ActiveBV939Al_CutOff_ExhFan_3.ActiveBV940Al_CutOff_ExhFan_4.ActiveBV941Al_CutOff_ExhFan_5.ActiveBV942Al_CutOff_ExhFan_6.ActiveBV943Al_CutOff_ExhFan_7.ActiveBV944Al_CutOff_ExhFan_8.ActiveBV945Al_CutOff_ExhFan_9.ActiveBV946Al_CutOff_Rotary.ActiveBV947Al_CutOff_SupFan_1.ActiveBV948Al_CutOff_SupFan_10.ActiveBV949Al_CutOff_SupFan_2.ActiveBV950Al_CutOff_SupFan_3.ActiveBV951Al_CutOff_SupFan_4.ActiveBV952Al_CutOff_SupFan_5.ActiveBV953Al_CutOff_SupFan_6.ActiveBV954Al_CutOff_SupFan_7.ActiveBV955Al_CutOff_SupFan_8.ActiveBV956Al_CutOff_SupFan_9.ActiveBV957Al_DC_Ovld_ExhFan_1.ActiveBV958Al_DC_Ovld_ExhFan_10.ActiveBV959Al_DC_Ovld_ExhFan_2.ActiveBV960Al_DC_Ovld_ExhFan_3.ActiveBV961Al_DC_Ovld_ExhFan_4.ActiveBV962Al_DC_Ovld_ExhFan_5.ActiveBV963Al_DC_Ovld_ExhFan_6.ActiveBV964Al_DC_Ovld_ExhFan_7.ActiveBV965Al_DC_Ovld_ExhFan_8.ActiveBV966Al_DC_Ovld_ExhFan_9.ActiveBV967Al_DC_Ovld_Rotary.ActiveBV968Al_DC_Ovld_SupFan_1.ActiveBV969Al_DC_Ovld_SupFan_10.ActiveBV970Al_DC_Ovld_SupFan_2.ActiveBV971Al_DC_Ovld_SupFan_3.ActiveBV972Al_DC_Ovld_SupFan_4.ActiveBV973Al_DC_Ovld_SupFan_5.ActiveBV974Al_DC_Ovld_SupFan_6.ActiveBV975Al_DC_Ovld_SupFan_7.ActiveBV976Al_DC_Ovld_SupFan_8.ActiveBV977Al_DC_Ovld_SupFan_9.ActiveBV978Al_ElectTherm_ExhFan_1.ActiveBV979Al_ElectTherm_ExhFan_10.ActiveBV980Al_ElectTherm_ExhFan_2.ActiveBV981Al_ElectTherm_ExhFan_3.ActiveBV982Al_ElectTherm_ExhFan_4.ActiveBV983Al_ElectTherm_ExhFan_5.ActiveBV984Al_ElectTherm_ExhFan_6.ActiveBV985Al_ElectTherm_ExhFan_7.ActiveBV986Al_ElectTherm_ExhFan_8.ActiveBV987Al_ElectTherm_ExhFan_9.ActiveBV988Al_ElectTherm_Rotary.ActiveBV989Al_ElectTherm_SupFan_1.ActiveBV990Al_ElectTherm_SupFan_10.ActiveBV991Al_ElectTherm_SupFan_2.ActiveBV992Al_ElectTherm_SupFan_3.ActiveBV993Al_ElectTherm_SupFan_4.ActiveBV994Al_ElectTherm_SupFan_5.ActiveBV995Al_ElectTherm_SupFan_6.ActiveBV996Al_ElectTherm_SupFan_7.ActiveBV997Al_ElectTherm_SupFan_8.ActiveBV998Al_ElectTherm_SupFan_9.ActiveBV999Al_Err_retain_write.ActiveBV1000Al_ExhTempPrb.ActiveBV1001Al_ExtFaultA_ExhFan_1.ActiveBV1002Al_ExtFaultA_ExhFan_10.ActiveBV1003Al_ExtFaultA_ExhFan_2.ActiveBV1004Al_ExtFaultA_ExhFan_3.ActiveBV1005Al_ExtFaultA_ExhFan_4.ActiveBV1006Al_ExtFaultA_ExhFan_5.ActiveBV1007Al_ExtFaultA_ExhFan_6.ActiveBV1008Al_ExtFaultA_ExhFan_7.ActiveBV1009Al_ExtFaultA_ExhFan_8.ActiveBV1010Al_ExtFaultA_ExhFan_9.ActiveBV1011Al_ExtFaultA_Rotary.ActiveBV1012Al_ExtFaultA_SupFan_1.ActiveBV1013Al_ExtFaultA_SupFan_10.ActiveBV1014Al_ExtFaultA_SupFan_2.ActiveBV1015Al_ExtFaultA_SupFan_3.ActiveBV1016Al_ExtFaultA_SupFan_4.ActiveBV1017Al_ExtFaultA_SupFan_5.ActiveBV1018Al_ExtFaultA_SupFan_6.ActiveBV1019Al_ExtFaultA_SupFan_7.ActiveBV1020Al_ExtFaultA_SupFan_8.ActiveBV1021Al_ExtFaultA_SupFan_9.ActiveBV1022Al_ExtFaultB_ExhFan_1.ActiveBV1023Al_ExtFaultB_ExhFan_10.ActiveBV1024Al_ExtFaultB_ExhFan_2.ActiveBV1025Al_ExtFaultB_ExhFan_3.ActiveBV1026Al_ExtFaultB_ExhFan_4.ActiveBV1027Al_ExtFaultB_ExhFan_5.ActiveBV1028Al_ExtFaultB_ExhFan_6.ActiveBV1029Al_ExtFaultB_ExhFan_7.ActiveBV1030Al_ExtFaultB_ExhFan_8.ActiveBV1031Al_ExtFaultB_ExhFan_9.ActiveBV1032Al_ExtFaultB_Rotary.ActiveBV1033Al_ExtFaultB_SupFan_1.ActiveBV1034Al_ExtFaultB_SupFan_10.ActiveBV1035Al_ExtFaultB_SupFan_2.ActiveBV1036Al_ExtFaultB_SupFan_3.ActiveBV1037Al_ExtFaultB_SupFan_4.ActiveBV1038Al_ExtFaultB_SupFan_5.ActiveBV1039Al_ExtFaultB_SupFan_6.ActiveBV1040Al_ExtFaultB_SupFan_7.ActiveBV1041Al_ExtFaultB_SupFan_8.ActiveBV1042Al_ExtFaultB_SupFan_9.ActiveBV1043Al_ExtTempPrb.ActiveBV1044Al_Fire.ActiveBV1045Al_FireExh.ActiveBV1046Al_GroundFault_ExhFan_1.ActiveBV1047Al_GroundFault_ExhFan_10.ActiveBV1048Al_GroundFault_ExhFan_2.ActiveBV1049Al_GroundFault_ExhFan_3.ActiveBV1050Al_GroundFault_ExhFan_4.ActiveBV1051Al_GroundFault_ExhFan_5.ActiveBV1052Al_GroundFault_ExhFan_6.ActiveBV1053Al_GroundFault_ExhFan_7.ActiveBV1054Al_GroundFault_ExhFan_8.ActiveBV1055Al_GroundFault_ExhFan_9.ActiveBV1056Al_GroundFault_Rotary.ActiveBV1057Al_GroundFault_SupFan_1.ActiveBV1058Al_GroundFault_SupFan_10.ActiveBV1059Al_GroundFault_SupFan_2.ActiveBV1060Al_GroundFault_SupFan_3.ActiveBV1061Al_GroundFault_SupFan_4.ActiveBV1062Al_GroundFault_SupFan_5.ActiveBV1063Al_GroundFault_SupFan_6.ActiveBV1064Al_GroundFault_SupFan_7.ActiveBV1065Al_GroundFault_SupFan_8.ActiveBV1066Al_GroundFault_SupFan_9.ActiveBV1067Al_Heat.ActiveBV1068Al_HeatCoilTempPrb.ActiveBV1069Al_HeatExchgWorkHrsWarn.ActiveBV1070Al_HeatSink_ExhFan_1.ActiveBV1071Al_HeatSink_ExhFan_10.ActiveBV1072Al_HeatSink_ExhFan_2.ActiveBV1073Al_HeatSink_ExhFan_3.ActiveBV1074Al_HeatSink_ExhFan_4.ActiveBV1075Al_HeatSink_ExhFan_5.ActiveBV1076Al_HeatSink_ExhFan_6.ActiveBV1077Al_HeatSink_ExhFan_7.ActiveBV1078Al_HeatSink_ExhFan_8.ActiveBV1079Al_HeatSink_ExhFan_9.ActiveBV1080Al_HeatSink_Rotary.ActiveBV1081Al_HeatSink_SupFan_1.ActiveBV1082Al_HeatSink_SupFan_10.ActiveBV1083Al_HeatSink_SupFan_2.ActiveBV1084Al_HeatSink_SupFan_3.ActiveBV1085Al_HeatSink_SupFan_4.ActiveBV1086Al_HeatSink_SupFan_5.ActiveBV1087Al_HeatSink_SupFan_6.ActiveBV1088Al_HeatSink_SupFan_7.ActiveBV1089Al_HeatSink_SupFan_8.ActiveBV1090Al_HeatSink_SupFan_9.ActiveBV1091AL_Hot_EC_ExhFan1.ActiveBV1092AL_Hot_EC_ExhFan10.ActiveBV1093AL_Hot_EC_ExhFan2.ActiveBV1094AL_Hot_EC_ExhFan3.ActiveBV1095AL_Hot_EC_ExhFan4.ActiveBV1096AL_Hot_EC_ExhFan5.ActiveBV1097AL_Hot_EC_ExhFan6.ActiveBV1098AL_Hot_EC_ExhFan7.ActiveBV1099AL_Hot_EC_ExhFan8.ActiveBV1100AL_Hot_EC_ExhFan9.ActiveBV1101AL_Hot_EC_SupFan1.ActiveBV1102AL_Hot_EC_SupFan10.ActiveBV1103AL_Hot_EC_SupFan2.ActiveBV1104AL_Hot_EC_SupFan3.ActiveBV1105AL_Hot_EC_SupFan4.ActiveBV1106AL_Hot_EC_SupFan5.ActiveBV1107AL_Hot_EC_SupFan6.ActiveBV1108AL_Hot_EC_SupFan7.ActiveBV1109AL_Hot_EC_SupFan8.ActiveBV1110AL_Hot_EC_SupFan9.ActiveBV1111Al_Hum.ActiveBV1112Al_HumWorkHrsWarn.ActiveBV1113Al_HW_Fault_ExhFan_1.ActiveBV1114Al_HW_Fault_ExhFan_10.ActiveBV1115Al_HW_Fault_ExhFan_2.ActiveBV1116Al_HW_Fault_ExhFan_3.ActiveBV1117Al_HW_Fault_ExhFan_4.ActiveBV1118Al_HW_Fault_ExhFan_5.ActiveBV1119Al_HW_Fault_ExhFan_6.ActiveBV1120Al_HW_Fault_ExhFan_7.ActiveBV1121Al_HW_Fault_ExhFan_8.ActiveBV1122Al_HW_Fault_ExhFan_9.ActiveBV1123Al_HW_Fault_Rotary.ActiveBV1124Al_HW_Fault_SupFan_1.ActiveBV1125Al_HW_Fault_SupFan_10.ActiveBV1126Al_HW_Fault_SupFan_2.ActiveBV1127Al_HW_Fault_SupFan_3.ActiveBV1128Al_HW_Fault_SupFan_4.ActiveBV1129Al_HW_Fault_SupFan_5.ActiveBV1130Al_HW_Fault_SupFan_6.ActiveBV1131Al_HW_Fault_SupFan_7.ActiveBV1132Al_HW_Fault_SupFan_8.ActiveBV1133Al_HW_Fault_SupFan_9.ActiveBV1134Al_I2RIGBTFault_EC_ExhFan1.ActiveBV1135Al_I2RIGBTFault_EC_ExhFan10.ActiveBV1136Al_I2RIGBTFault_EC_ExhFan2.ActiveBV1137Al_I2RIGBTFault_EC_ExhFan3.ActiveBV1138Al_I2RIGBTFault_EC_ExhFan4.ActiveBV1139Al_I2RIGBTFault_EC_ExhFan5.ActiveBV1140Al_I2RIGBTFault_EC_ExhFan6.ActiveBV1141Al_I2RIGBTFault_EC_ExhFan7.ActiveBV1142Al_I2RIGBTFault_EC_ExhFan8.ActiveBV1143Al_I2RIGBTFault_EC_ExhFan9.ActiveBV1144Al_I2RIGBTFault_EC_SupFan1.ActiveBV1145Al_I2RIGBTFault_EC_SupFan10.ActiveBV1146Al_I2RIGBTFault_EC_SupFan2.ActiveBV1147Al_I2RIGBTFault_EC_SupFan3.ActiveBV1148Al_I2RIGBTFault_EC_SupFan4.ActiveBV1149Al_I2RIGBTFault_EC_SupFan5.ActiveBV1150Al_I2RIGBTFault_EC_SupFan6.ActiveBV1151Al_I2RIGBTFault_EC_SupFan7.ActiveBV1152Al_I2RIGBTFault_EC_SupFan8.ActiveBV1153Al_I2RIGBTFault_EC_SupFan9.ActiveBV1154AL_IGBTOvercurrent_EC_ExhFan1.ActiveBV1155AL_IGBTOvercurrent_EC_ExhFan10.ActiveBV1156AL_IGBTOvercurrent_EC_ExhFan2.ActiveBV1157AL_IGBTOvercurrent_EC_ExhFan3.ActiveBV1158AL_IGBTOvercurrent_EC_ExhFan4.ActiveBV1159AL_IGBTOvercurrent_EC_ExhFan5.ActiveBV1160AL_IGBTOvercurrent_EC_ExhFan6.ActiveBV1161AL_IGBTOvercurrent_EC_ExhFan7.ActiveBV1162AL_IGBTOvercurrent_EC_ExhFan8.ActiveBV1163AL_IGBTOvercurrent_EC_ExhFan9.ActiveBV1164AL_IGBTOvercurrent_EC_SupFan1.ActiveBV1165AL_IGBTOvercurrent_EC_SupFan10.ActiveBV1166AL_IGBTOvercurrent_EC_SupFan2.ActiveBV1167AL_IGBTOvercurrent_EC_SupFan3.ActiveBV1168AL_IGBTOvercurrent_EC_SupFan4.ActiveBV1169AL_IGBTOvercurrent_EC_SupFan5.ActiveBV1170AL_IGBTOvercurrent_EC_SupFan6.ActiveBV1171AL_IGBTOvercurrent_EC_SupFan7.ActiveBV1172AL_IGBTOvercurrent_EC_SupFan8.ActiveBV1173AL_IGBTOvercurrent_EC_SupFan9.ActiveBV1174Al_InvOverheat_ExhFan_1.ActiveBV1175Al_InvOverheat_ExhFan_10.ActiveBV1176Al_InvOverheat_ExhFan_2.ActiveBV1177Al_InvOverheat_ExhFan_3.ActiveBV1178Al_InvOverheat_ExhFan_4.ActiveBV1179Al_InvOverheat_ExhFan_5.ActiveBV1180Al_InvOverheat_ExhFan_6.ActiveBV1181Al_InvOverheat_ExhFan_7.ActiveBV1182Al_InvOverheat_ExhFan_8.ActiveBV1183Al_InvOverheat_ExhFan_9.ActiveBV1184Al_InvOverheat_Rotary.ActiveBV1185Al_InvOverheat_SupFan_1.ActiveBV1186Al_InvOverheat_SupFan_10.ActiveBV1187Al_InvOverheat_SupFan_2.ActiveBV1188Al_InvOverheat_SupFan_3.ActiveBV1189Al_InvOverheat_SupFan_4.ActiveBV1190Al_InvOverheat_SupFan_5.ActiveBV1191Al_InvOverheat_SupFan_6.ActiveBV1192Al_InvOverheat_SupFan_7.ActiveBV1193Al_InvOverheat_SupFan_8.ActiveBV1194Al_InvOverheat_SupFan_9.ActiveBV1195Al_InvOvld_ExhFan_1.ActiveBV1196Al_InvOvld_ExhFan_10.ActiveBV1197Al_InvOvld_ExhFan_2.ActiveBV1198Al_InvOvld_ExhFan_3.ActiveBV1199Al_InvOvld_ExhFan_4.ActiveBV1200Al_InvOvld_ExhFan_5.ActiveBV1201Al_InvOvld_ExhFan_6.ActiveBV1202Al_InvOvld_ExhFan_7.ActiveBV1203Al_InvOvld_ExhFan_8.ActiveBV1204Al_InvOvld_ExhFan_9.ActiveBV1205Al_InvOvld_Rotary.ActiveBV1206Al_InvOvld_SupFan_1.ActiveBV1207Al_InvOvld_SupFan_10.ActiveBV1208Al_InvOvld_SupFan_2.ActiveBV1209Al_InvOvld_SupFan_3.ActiveBV1210Al_InvOvld_SupFan_4.ActiveBV1211Al_InvOvld_SupFan_5.ActiveBV1212Al_InvOvld_SupFan_6.ActiveBV1213Al_InvOvld_SupFan_7.ActiveBV1214Al_InvOvld_SupFan_8.ActiveBV1215Al_InvOvld_SupFan_9.ActiveBV1216Al_LowSupplyTemp.ActiveBV1217Al_LowVolt_ExhFan_1.ActiveBV1218Al_LowVolt_ExhFan_10.ActiveBV1219Al_LowVolt_ExhFan_2.ActiveBV1220Al_LowVolt_ExhFan_3.ActiveBV1221Al_LowVolt_ExhFan_4.ActiveBV1222Al_LowVolt_ExhFan_5.ActiveBV1223Al_LowVolt_ExhFan_6.ActiveBV1224Al_LowVolt_ExhFan_7.ActiveBV1225Al_LowVolt_ExhFan_8.ActiveBV1226Al_LowVolt_ExhFan_9.ActiveBV1227Al_LowVolt_Rotary.ActiveBV1228Al_LowVolt_SupFan_1.ActiveBV1229Al_LowVolt_SupFan_10.ActiveBV1230Al_LowVolt_SupFan_2.ActiveBV1231Al_LowVolt_SupFan_3.ActiveBV1232Al_LowVolt_SupFan_4.ActiveBV1233Al_LowVolt_SupFan_5.ActiveBV1234Al_LowVolt_SupFan_6.ActiveBV1235Al_LowVolt_SupFan_7.ActiveBV1236Al_LowVolt_SupFan_8.ActiveBV1237Al_LowVolt_SupFan_9.ActiveBV1238Al_MB_AO1.ActiveBV1239Al_MB_AO1_AO4_PWM.ActiveBV1240Al_MB_AO2.ActiveBV1241Al_MB_AO3.ActiveBV1242Al_MB_AO4.ActiveBV1243Al_MB_Control_Supply.ActiveBV1244Al_MB_Control_Temp.ActiveBV1245Al_MB_Humidity.ActiveBV1246Al_MB_Press_Fan_Return.ActiveBV1247Al_MB_Press_Fan_Supply.ActiveBV1248Al_MB_Press_Filter_Return.ActiveBV1249Al_MB_Press_Filter_Supply.ActiveBV1250Al_MB_Supply24.ActiveBV1251Al_MB_Temp_Fan_Return.ActiveBV1252Al_MB_Temp_Fan_Supply.ActiveBV1253Al_MB_Temp_Filter_Return.ActiveBV1254Al_MB_Temp_Filter_Supply.ActiveBV1255Al_MB_Temperature.ActiveBV1256Al_MotorFault_EC_ExhFan10.ActiveBV1257Al_MotorFault_EC_ExhFan2.ActiveBV1258Al_MotorFault_EC_ExhFan3.ActiveBV1259Al_MotorFault_EC_ExhFan4.ActiveBV1260Al_MotorFault_EC_ExhFan5.ActiveBV1261Al_MotorFault_EC_ExhFan6.ActiveBV1262Al_MotorFault_EC_ExhFan7.ActiveBV1263Al_MotorFault_EC_ExhFan8.ActiveBV1264Al_MotorFault_EC_ExhFan9.ActiveBV1265Al_MotorFault_EC_SupFan1.ActiveBV1266Al_MotorFault_EC_SupFan10.ActiveBV1267Al_MotorFault_EC_SupFan2.ActiveBV1268Al_MotorFault_EC_SupFan3.ActiveBV1269Al_MotorFault_EC_SupFan4.ActiveBV1270Al_MotorFault_EC_SupFan5.ActiveBV1271Al_MotorFault_EC_SupFan6.ActiveBV1272Al_MotorFault_EC_SupFan7.ActiveBV1273Al_MotorFault_EC_SupFan8.ActiveBV1274Al_MotorFault_EC_SupFan9.ActiveBV1275Al_MotorOverheat_ExhFan_1.ActiveBV1276Al_MotorOverheat_ExhFan_10.ActiveBV1277Al_MotorOverheat_ExhFan_2.ActiveBV1278Al_MotorOverheat_ExhFan_3.ActiveBV1279Al_MotorOverheat_ExhFan_4.ActiveBV1280Al_MotorOverheat_ExhFan_5.ActiveBV1281Al_MotorOverheat_ExhFan_6.ActiveBV1282Al_MotorOverheat_ExhFan_7.ActiveBV1283Al_MotorOverheat_ExhFan_8.ActiveBV1284Al_MotorOverheat_ExhFan_9.ActiveBV1285Al_MotorOverheat_Rotary.ActiveBV1286Al_MotorOverheat_SupFan_1.ActiveBV1287Al_MotorOverheat_SupFan_10.ActiveBV1288Al_MotorOverheat_SupFan_2.ActiveBV1289Al_MotorOverheat_SupFan_3.ActiveBV1290Al_MotorOverheat_SupFan_4.ActiveBV1291Al_MotorOverheat_SupFan_5.ActiveBV1292Al_MotorOverheat_SupFan_6.ActiveBV1293Al_MotorOverheat_SupFan_7.ActiveBV1294Al_MotorOverheat_SupFan_8.ActiveBV1295Al_MotorOverheat_SupFan_9.ActiveBV1296Al_Offline_cpCOe.ActiveBV1297Al_Offline_ExhFan_1.ActiveBV1298Al_Offline_ExhFan_10.ActiveBV1299Al_Offline_ExhFan_2.ActiveBV1300Al_Offline_ExhFan_3.ActiveBV1301Al_Offline_ExhFan_4.ActiveBV1302Al_Offline_ExhFan_5.ActiveBV1303Al_Offline_ExhFan_6.ActiveBV1304Al_Offline_ExhFan_7.ActiveBV1305Al_Offline_ExhFan_8.ActiveBV1306Al_Offline_ExhFan_9.ActiveBV1307Al_Offline_MainBoard.ActiveBV1308Al_Offline_Rotary.ActiveBV1309Al_Offline_SP_ExhHum.ActiveBV1310Al_Offline_SP_ExhPress.ActiveBV1311Al_Offline_SP_SupplyHum.ActiveBV1312Al_Offline_SP_SupplyPress.ActiveBV1313Al_Offline_SupFan_1.ActiveBV1314Al_Offline_SupFan_10.ActiveBV1315Al_Offline_SupFan_2.ActiveBV1316Al_Offline_SupFan_3.ActiveBV1317Al_Offline_SupFan_4.ActiveBV1318Al_Offline_SupFan_5.ActiveBV1319Al_Offline_SupFan_6.ActiveBV1320Al_Offline_SupFan_7.ActiveBV1321Al_Offline_SupFan_8.ActiveBV1322Al_Offline_SupFan_9.ActiveBV1323Al_Offline_THTN_1.ActiveBV1324Al_Option_ExhFan_1.ActiveBV1325Al_Option_ExhFan_10.ActiveBV1326Al_Option_ExhFan_2.ActiveBV1327Al_Option_ExhFan_3.ActiveBV1328Al_Option_ExhFan_4.ActiveBV1329Al_Option_ExhFan_5.ActiveBV1330Al_Option_ExhFan_6.ActiveBV1331Al_Option_ExhFan_7.ActiveBV1332Al_Option_ExhFan_8.ActiveBV1333Al_Option_ExhFan_9.ActiveBV1334Al_Option_Rotary.ActiveBV1335Al_Option_SupFan_1.ActiveBV1336Al_Option_SupFan_10.ActiveBV1337Al_Option_SupFan_2.ActiveBV1338Al_Option_SupFan_3.ActiveBV1339Al_Option_SupFan_4.ActiveBV1340Al_Option_SupFan_5.ActiveBV1341Al_Option_SupFan_6.ActiveBV1342Al_Option_SupFan_7.ActiveBV1343Al_Option_SupFan_8.ActiveBV1344Al_Option_SupFan_9.ActiveBV1345Al_Overcurrent_ExhFan_1.ActiveBV1346Al_Overcurrent_ExhFan_10.ActiveBV1347Al_Overcurrent_ExhFan_2.ActiveBV1348Al_Overcurrent_ExhFan_3.ActiveBV1349Al_Overcurrent_ExhFan_4.ActiveBV1350Al_Overcurrent_ExhFan_5.ActiveBV1351Al_Overcurrent_ExhFan_6.ActiveBV1352Al_Overcurrent_ExhFan_7.ActiveBV1353Al_Overcurrent_ExhFan_8.ActiveBV1354Al_Overcurrent_ExhFan_9.ActiveBV1355Al_Overcurrent_Rotary.ActiveBV1356Al_Overcurrent_SupFan_1.ActiveBV1357Al_Overcurrent_SupFan_10.ActiveBV1358Al_Overcurrent_SupFan_2.ActiveBV1359Al_Overcurrent_SupFan_3.ActiveBV1360Al_Overcurrent_SupFan_4.ActiveBV1361Al_Overcurrent_SupFan_5.ActiveBV1362Al_Overcurrent_SupFan_6.ActiveBV1363Al_Overcurrent_SupFan_7.ActiveBV1364Al_Overcurrent_SupFan_8.ActiveBV1365Al_Overcurrent_SupFan_9.ActiveBV1366Al_OverVolt_ExhFan_1.ActiveBV1367Al_OverVolt_ExhFan_10.ActiveBV1368Al_OverVolt_ExhFan_2.ActiveBV1369Al_OverVolt_ExhFan_3.ActiveBV1370Al_OverVolt_ExhFan_4.ActiveBV1371Al_OverVolt_ExhFan_5.ActiveBV1372Al_OverVolt_ExhFan_6.ActiveBV1373Al_OverVolt_ExhFan_7.ActiveBV1374Al_OverVolt_ExhFan_8.ActiveBV1375Al_OverVolt_ExhFan_9.ActiveBV1376Al_OverVolt_Rotary.ActiveBV1377Al_OverVolt_SupFan_1.ActiveBV1378Al_OverVolt_SupFan_10.ActiveBV1379Al_OverVolt_SupFan_2.ActiveBV1380Al_OverVolt_SupFan_3.ActiveBV1381Al_OverVolt_SupFan_4.ActiveBV1382Al_OverVolt_SupFan_5.ActiveBV1383Al_OverVolt_SupFan_6.ActiveBV1384Al_OverVolt_SupFan_7.ActiveBV1385Al_OverVolt_SupFan_8.ActiveBV1386Al_OverVolt_SupFan_9.ActiveBV1387AL_Overvoltage_EC_ExhFan1.ActiveBV1388AL_Overvoltage_EC_ExhFan10.ActiveBV1389AL_Overvoltage_EC_ExhFan2.ActiveBV1390AL_Overvoltage_EC_ExhFan3.ActiveBV1391AL_Overvoltage_EC_ExhFan4.ActiveBV1392AL_Overvoltage_EC_ExhFan5.ActiveBV1393AL_Overvoltage_EC_ExhFan6.ActiveBV1394AL_Overvoltage_EC_ExhFan7.ActiveBV1395AL_Overvoltage_EC_ExhFan8.ActiveBV1396AL_Overvoltage_EC_ExhFan9.ActiveBV1397AL_Overvoltage_EC_SupFan1.ActiveBV1398AL_Overvoltage_EC_SupFan10.ActiveBV1399AL_Overvoltage_EC_SupFan2.ActiveBV1400AL_Overvoltage_EC_SupFan3.ActiveBV1401AL_Overvoltage_EC_SupFan4.ActiveBV1402AL_Overvoltage_EC_SupFan5.ActiveBV1403AL_Overvoltage_EC_SupFan6.ActiveBV1404AL_Overvoltage_EC_SupFan7.ActiveBV1405AL_Overvoltage_EC_SupFan8.ActiveBV1406AL_Overvoltage_EC_SupFan9.ActiveBV1407Al_Ovld_ExhFan_1.ActiveBV1408Al_Ovld_ExhFan_10.ActiveBV1409Al_Ovld_ExhFan_2.ActiveBV1410Al_Ovld_ExhFan_3.ActiveBV1411Al_Ovld_ExhFan_4.ActiveBV1412Al_Ovld_ExhFan_5.ActiveBV1413Al_Ovld_ExhFan_6.ActiveBV1414Al_Ovld_ExhFan_7.ActiveBV1415Al_Ovld_ExhFan_8.ActiveBV1416Al_Ovld_ExhFan_9.ActiveBV1417Al_Ovld_Rotary.ActiveBV1418Al_Ovld_SupFan_1.ActiveBV1419Al_Ovld_SupFan_10.ActiveBV1420Al_Ovld_SupFan_2.ActiveBV1421Al_Ovld_SupFan_3.ActiveBV1422Al_Ovld_SupFan_4.ActiveBV1423Al_Ovld_SupFan_5.ActiveBV1424Al_Ovld_SupFan_6.ActiveBV1425Al_Ovld_SupFan_7.ActiveBV1426Al_Ovld_SupFan_8.ActiveBV1427Al_Ovld_SupFan_9.ActiveBV1428Al_ParamErr_ExhFan_1.ActiveBV1429Al_ParamErr_ExhFan_10.ActiveBV1430Al_ParamErr_ExhFan_2.ActiveBV1431Al_ParamErr_ExhFan_3.ActiveBV1432Al_ParamErr_ExhFan_4.ActiveBV1433Al_ParamErr_ExhFan_5.ActiveBV1434Al_ParamErr_ExhFan_6.ActiveBV1435Al_ParamErr_ExhFan_7.ActiveBV1436Al_ParamErr_ExhFan_8.ActiveBV1437Al_ParamErr_ExhFan_9.ActiveBV1438Al_ParamErr_Rotary.ActiveBV1439Al_ParamErr_SupFan_1.ActiveBV1440Al_ParamErr_SupFan_10.ActiveBV1441Al_ParamErr_SupFan_2.ActiveBV1442Al_ParamErr_SupFan_3.ActiveBV1443Al_ParamErr_SupFan_4.ActiveBV1444Al_ParamErr_SupFan_5.ActiveBV1445Al_ParamErr_SupFan_6.ActiveBV1446Al_ParamErr_SupFan_7.ActiveBV1447Al_ParamErr_SupFan_8.ActiveBV1448Al_ParamErr_SupFan_9.ActiveBV1449AL_ParametersCRC_EC_ExhFan1.ActiveBV1450AL_ParametersCRC_EC_ExhFan10.ActiveBV1451AL_ParametersCRC_EC_ExhFan2.ActiveBV1452AL_ParametersCRC_EC_ExhFan3.ActiveBV1453AL_ParametersCRC_EC_ExhFan4.ActiveBV1454AL_ParametersCRC_EC_ExhFan5.ActiveBV1455AL_ParametersCRC_EC_ExhFan6.ActiveBV1456AL_ParametersCRC_EC_ExhFan7.ActiveBV1457AL_ParametersCRC_EC_ExhFan8.ActiveBV1458AL_ParametersCRC_EC_ExhFan9.ActiveBV1459AL_ParametersCRC_EC_SupFan1.ActiveBV1460AL_ParametersCRC_EC_SupFan10.ActiveBV1461AL_ParametersCRC_EC_SupFan2.ActiveBV1462AL_ParametersCRC_EC_SupFan3.ActiveBV1463AL_ParametersCRC_EC_SupFan4.ActiveBV1464AL_ParametersCRC_EC_SupFan5.ActiveBV1465AL_ParametersCRC_EC_SupFan6.ActiveBV1466AL_ParametersCRC_EC_SupFan7.ActiveBV1467AL_ParametersCRC_EC_SupFan8.ActiveBV1468AL_ParametersCRC_EC_SupFan9.ActiveBV1469AL_PhaseLoss_EC_ExhFan1.ActiveBV1470AL_PhaseLoss_EC_ExhFan10.ActiveBV1471AL_PhaseLoss_EC_ExhFan2.ActiveBV1472AL_PhaseLoss_EC_ExhFan3.ActiveBV1473AL_PhaseLoss_EC_ExhFan4.ActiveBV1474AL_PhaseLoss_EC_ExhFan5.ActiveBV1475AL_PhaseLoss_EC_ExhFan6.ActiveBV1476AL_PhaseLoss_EC_ExhFan7.ActiveBV1477AL_PhaseLoss_EC_ExhFan8.ActiveBV1478AL_PhaseLoss_EC_ExhFan9.ActiveBV1479AL_PhaseLoss_EC_SupFan1.ActiveBV1480AL_PhaseLoss_EC_SupFan10.ActiveBV1481AL_PhaseLoss_EC_SupFan2.ActiveBV1482AL_PhaseLoss_EC_SupFan3.ActiveBV1483AL_PhaseLoss_EC_SupFan4.ActiveBV1484AL_PhaseLoss_EC_SupFan5.ActiveBV1485AL_PhaseLoss_EC_SupFan6.ActiveBV1486AL_PhaseLoss_EC_SupFan7.ActiveBV1487AL_PhaseLoss_EC_SupFan8.ActiveBV1488AL_PhaseLoss_EC_SupFan9.ActiveBV1489Al_PhLost_ExhFan_1.ActiveBV1490Al_PhLost_ExhFan_10.ActiveBV1491Al_PhLost_ExhFan_2.ActiveBV1492Al_PhLost_ExhFan_3.ActiveBV1493Al_PhLost_ExhFan_4.ActiveBV1494Al_PhLost_ExhFan_5.ActiveBV1495Al_PhLost_ExhFan_6.ActiveBV1496Al_PhLost_ExhFan_7.ActiveBV1497Al_PhLost_ExhFan_8.ActiveBV1498Al_PhLost_ExhFan_9.ActiveBV1499Al_PhLost_Rotary.ActiveBV1500Al_PhLost_SupFan_1.ActiveBV1501Al_PhLost_SupFan_10.ActiveBV1502Al_PhLost_SupFan_2.ActiveBV1503Al_PhLost_SupFan_3.ActiveBV1504Al_PhLost_SupFan_4.ActiveBV1505Al_PhLost_SupFan_5.ActiveBV1506Al_PhLost_SupFan_6.ActiveBV1507Al_PhLost_SupFan_7.ActiveBV1508Al_PhLost_SupFan_8.ActiveBV1509Al_PhLost_SupFan_9.ActiveBV1510Al_PhOpen_ExhFan_1.ActiveBV1511Al_PhOpen_ExhFan_10.ActiveBV1512Al_PhOpen_ExhFan_2.ActiveBV1513Al_PhOpen_ExhFan_3.ActiveBV1514Al_PhOpen_ExhFan_4.ActiveBV1515Al_PhOpen_ExhFan_5.ActiveBV1516Al_PhOpen_ExhFan_6.ActiveBV1517Al_PhOpen_ExhFan_7.ActiveBV1518Al_PhOpen_ExhFan_8.ActiveBV1519Al_PhOpen_ExhFan_9.ActiveBV1520Al_PhOpen_Rotary.ActiveBV1521Al_PhOpen_SupFan_1.ActiveBV1522Al_PhOpen_SupFan_10.ActiveBV1523Al_PhOpen_SupFan_2.ActiveBV1524Al_PhOpen_SupFan_3.ActiveBV1525Al_PhOpen_SupFan_4.ActiveBV1526Al_PhOpen_SupFan_5.ActiveBV1527Al_PhOpen_SupFan_6.ActiveBV1528Al_PhOpen_SupFan_7.ActiveBV1529Al_PhOpen_SupFan_8.ActiveBV1530Al_PhOpen_SupFan_9.ActiveBV1531Al_PreHeatCoilTempPrb.ActiveBV1532Al_RDT_Fan.ActiveBV1533Al_RecSupplyTemp.ActiveBV1534Al_ReheatCoilWorkHrsWarn.ActiveBV1535Al_retain.ActiveBV1536Al_RetAir_CO2_Lev_Prb.ActiveBV1537Al_RetAirFlwSwWarn.ActiveBV1538Al_RetAirP_Prb.ActiveBV1539Al_RetFanWorkHrsWarn.ActiveBV1540Al_RetFilt.ActiveBV1541Al_RetTempPrb.ActiveBV1542Al_SupplyAirFlwSwWarn.ActiveBV1543Al_SupplyAirP_Prb.ActiveBV1544Al_SupplyFanWorkHrsWarn.ActiveBV1545Al_SupplyFilt.ActiveBV1546Al_SupplyTempPrb.ActiveBV1547Al_SwPrototype.ActiveBV1548Al_ThTune_ClkBrd.ActiveBV1549Al_ThTune_HumPrb.ActiveBV1550Al_ThTune_TempPrb.ActiveBV1551Al_TooHot_EC_ExhFan1.ActiveBV1552Al_TooHot_EC_ExhFan10.ActiveBV1553Al_TooHot_EC_ExhFan2.ActiveBV1554Al_TooHot_EC_ExhFan3.ActiveBV1555Al_TooHot_EC_ExhFan4.ActiveBV1556Al_TooHot_EC_ExhFan5.ActiveBV1557Al_TooHot_EC_ExhFan6.ActiveBV1558Al_TooHot_EC_ExhFan7.ActiveBV1559Al_TooHot_EC_ExhFan8.ActiveBV1560Al_TooHot_EC_ExhFan9.ActiveBV1561Al_TooHot_EC_SupFan1.ActiveBV1562Al_TooHot_EC_SupFan10.ActiveBV1563Al_TooHot_EC_SupFan2.ActiveBV1564Al_TooHot_EC_SupFan3.ActiveBV1565Al_TooHot_EC_SupFan4.ActiveBV1566Al_TooHot_EC_SupFan5.ActiveBV1567Al_TooHot_EC_SupFan6.ActiveBV1568Al_TooHot_EC_SupFan7.ActiveBV1569Al_TooHot_EC_SupFan8.ActiveBV1570Al_TooHot_EC_SupFan9.ActiveBV1571Al_Undervoltage_EC_ExhFan1.ActiveBV1572Al_Undervoltage_EC_ExhFan10.ActiveBV1573Al_Undervoltage_EC_ExhFan2.ActiveBV1574Al_Undervoltage_EC_ExhFan3.ActiveBV1575Al_Undervoltage_EC_ExhFan4.ActiveBV1576Al_Undervoltage_EC_ExhFan5.ActiveBV1577Al_Undervoltage_EC_ExhFan6.ActiveBV1578Al_Undervoltage_EC_ExhFan7.ActiveBV1579Al_Undervoltage_EC_ExhFan8.ActiveBV1580Al_Undervoltage_EC_ExhFan9.ActiveBV1581Al_Undervoltage_EC_SupFan1.ActiveBV1582Al_Undervoltage_EC_SupFan10.ActiveBV1583Al_Undervoltage_EC_SupFan2.ActiveBV1584Al_Undervoltage_EC_SupFan3.ActiveBV1585Al_Undervoltage_EC_SupFan4.ActiveBV1586Al_Undervoltage_EC_SupFan5.ActiveBV1587Al_Undervoltage_EC_SupFan6.ActiveBV1588Al_Undervoltage_EC_SupFan7.ActiveBV1589Al_Undervoltage_EC_SupFan8.ActiveBV1590Al_Undervoltage_EC_SupFan9.ActiveBV1591CfgErrAlrm.ActiveBV1592Al_MotorFault_EC_ExhFan1.ActiveBV1593OfflineAlrm.ActiveBV1594Al_Offline_IO_PCB.ActiveBV1595Al_DXRev.ActiveBV1596Al_WarningFilterHigh.ActiveBV1597Al_RRG_WorkConfirm.ActiveBV1598Al_ClkBrd_THTN_1.ActiveBV1599Al_ClkBrd_THTN_1.TriggerBV1600Al_DXRev.TriggerBV1601Al_HumPrb_THTN_1.ActiveBV1602Al_HumPrb_THTN_1.TriggerBV1603Al_Offline_IO_PCB.TriggerBV1604Al_RRG_WorkConfirm.TriggerBV1605Al_TempPrb_THTN_1.ActiveBV1606Al_TempPrb_THTN_1.TriggerBV1607Al_WarningFilterHigh.TriggerBV1608CfgErrAlrm_CPCOE_1.ActiveBV1609CfgErrAlrm_CPCOE_1.TriggerBV1610OfflineAlrm_CPCOE_1.ActiveBV1611OfflineAlrm_CPCOE_1.TriggerPIV537DayInBV1612EnDatePIV538GeneralMng.Zone_TZPIV539HourInPIV540MinuteInPIV541MonthInPIV542SecondInPIV543YearInPIV544DayPIV545DayOfWeekPIV546HourPIV547MinutePIV548MonthPIV549SecondPIV550YearAV240AlrmExhAirP_MskAV241AlrmSupplyAirP_MskAV242AFreezeExtMaxTempAV243AFreezeExtMinTempAV244AfreezeHeatMaxPIV551AFreezeHeatMaxTAV245AfreezeHeatMinPIV552AFreezeHeatMinTAV246AlrmExhAirPAV247AlrmSupplyAirPBV1613Cool_1.LogicPIV553Cool_1.ManBV1614Cool_2.LogicPIV554Cool_2.ManPIV555CoolDX_ResTypAV248CoolExtTempThrshPIV556CoolMinOffTPIV557CoolMinOnOnSameTPIV558CoolMinOnTPIV559CoolVlv.ManAV249DeltaDew_PID.KpPIV560DeltaDew_PID.TiAV250DeltaDewTempAV251DevCfg_PID_Seq_CO2[0].KpPIV561DevCfg_PID_Seq_CO2[0].TiAV252DevCfg_PID_Seq_CO2[1].KpPIV562DevCfg_PID_Seq_CO2[1].TiAV253DevCfg_PID_Seq_Cool[2].KpPIV563DevCfg_PID_Seq_Cool[2].TiAV254DevCfg_PID_Seq_Cool[4].KpPIV564DevCfg_PID_Seq_Cool[4].TiAV255DevCfg_PID_Seq_Cool[5].KpPIV565DevCfg_PID_Seq_Cool[5].TiAV256DevCfg_PID_Seq_Heat[2].KpPIV566DevCfg_PID_Seq_Heat[2].TiAV257DevCfg_PID_Seq_Heat[4].KpPIV567DevCfg_PID_Seq_Heat[4].TiAV258DevCfg_PID_Seq_Heat[5].KpPIV568DevCfg_PID_Seq_Heat[5].TiAV259DevCfg_PID_Seq_Heat[6].KpPIV569DevCfg_PID_Seq_Heat[6].TiPIV570DOff_ExhFanPIV571DOff_SupplyFanPIV572DT_ChangeHumPIV573DT_DmpPIV574DT_ExhFanPIV575DT_SupplyFanBV1615En_CoolRecBV1616En_FreeCoolHeatBV1617En_Rev_MixDamperBV1618En_Rev_RecoveryAV260ExhAirFlowSet_MskAV261ExhAirPSet_MskAV262FastCoolThrshBV1619FastHeatEnBV1620FastHeatStopPIV576FastHeatTAV263FastHeatThrshBV1621FastHeatTrigAV264FilterF7_MaxAV265FilterF9_MaxAV266FilterPG4_MaxIV577FilterRet_TypeIV578FilterSup_TypeAV267FireExhSpeedAV268FireSupplySpeedAV269FireThrshBV1622HC_Cool_1.ResBV1623HC_Cool_2.ResBV1624HC_ExhFan_1.ResBV1625HC_ExhFan_2.ResBV1626HC_Heat_1.ResBV1627HC_Heat_2.ResBV1628HC_Hum.ResBV1629HC_PreHeat.ResBV1630HC_RecoveryPump.ResBV1631HC_ReHeat.ResBV1632HC_SupplyFan_1.ResBV1633HC_SupplyFan_2.ResAV270HE_Pwr[0]AV271HE_Pwr[1]AV272HE_Pwr[2]BV1634Heat_1.LogicPIV579Heat_2.ManAV273HeatExtTempThrshPIV580HeatMinOffTPIV581HeatMinOnOnSameTPIV582HeatMinOnTPIV583HeatRecovery.ManPIV584HeatVlv.ManBV1635Hum.LogicPIV585Hum.ManAV274Hum_PID.DeadBandAV275Hum_PID.KpPIV586Hum_PID.TiAV276HW_SetPIV587IdleT_ExhFanPIV588IdleT_SupplyFanAV277K_FactorExhPIV589K_FactorExhCodeAV278K_FactorSupplyPIV590K_FactorSupplyCodeAV279LowSupplyTempThrshAV280MainCoolMinAV281MainCW_MinPIDAV282MainHeatMinAV283MainHW_MinPIDAV284ManExhFanIdleAV285ManSupplyFanIdleAV286MinHeatRecPIV591ModulHum.ManPIV592ModulMixDamp.ManAV287ModulMixDampMaxValAV288ModulMixDampMinValPIV593ModulPreHeat.ManPIV594NightKickHourPIV595NightKickMinuteAV289PID_Exh.KpPIV596PID_Exh.TdPIV597PID_Exh.TiAV290PID_FrostProt.KpAV291PID_FrostProt.SetPPIV598PID_FrostProt.TiAV292PID_HeatHW.KpPIV599PID_HeatHW.TiAV293PID_PreHeatCoil.KpPIV600PID_PreHeatCoil.TiAV294PID_PreHeatHW.KpPIV601PID_PreHeatHW.TiAV295PID_Supply.KpPIV602PID_Supply.TdPIV603PID_Supply.TiBV1636PreHeaterPump.LogicPIV604PreHeaterPump.ManAV296PreHeatHE_Pwr[0]AV297PreHeatHE_Pwr[1]AV298PreHeatMinPIV605PreHeatMinOffTPIV606PreheatMinOnOnSameTPIV607PreHeatMinOnTIV608PreHeatRotConf.DevNoPerCircAV299PreHeatSetAV300PreHW_MinPIDAV301Rec_MinPIDBV1637RecoveryPump.LogicPIV609RecoveryPump.ManBV1638ReHeat.LogicPIV610ReHeat.ManAV302ReHeatHE_Pwr[0]AV303ReHeatHE_Pwr[1]AV304ReHeatMinPIV611ReHeatMinOffTPIV612ReHeatMinOnOnSameTPIV613ReHeatMinOnTIV614ReHeatRotConf.CompMinPwrIV615ReHeatRotConf.DevNoPerCircPIV616ReHeatVlv.ManAV305ReHW_MinPIDAV306Ret_NrPoleBV1639RevOut_1.LogicPIV617RevOut_1.ManBV1640RevOut_2.LogicPIV618RevOut_2.ManPIV619RevOutVlv.ManAV307RoomReg_SetP_Offs_KpPIV620RoomReg_SetP_Offs_TiIV621RotConf.CompMinPwrIV622RotConf.DevNoPerCircAV308RRG_NrPoleAV309SetMaxLimitAV310SetMinLimitPIV623StandbyTAV311StartHumPercAV312StopHumPercAV313Sup_NrPoleAV314SupplyAirFlowSet_MskAV315SupplyAirPSet_MskAV316SupplyDewPointAV317SupplyFanMaxAV318SupplyMaxSetAV319SupplyMinSetPIV624SupplyTemp_CoolHeatDTAV320ThrshOffCool_1AV321ThrshOffCool_2AV322ThrshOffHeat_1AV323ThrshOffHeat_2AV324ThrshOnCool_1AV325ThrshOnCool_2AV326ThrshOnHeat_1AV327ThrshOnHeat_2AV328W_HeatFreezeSetAV329W_PreHeatFreezeSetPIV625WakeUpTAV330WarnThrshExhFlw_MskAV331WarnThrshSupplyFlw_MskAV332AbsHumAV333AbsHumSetAV334AfterPreHeatReqAV335AirQualFanAV336AirQualReq_1AV337Cooling_PID_Seq[2]AV338Cooling_PID_Seq[3]AV339Cooling_PID_Seq[4]AV340Cooling_PID_Seq[5]AV341FrostProtReqAV342Heating_PID_Seq[2]AV343Heating_PID_Seq[3]AV344Heating_PID_Seq[4]AV345Heating_PID_Seq[5]AV346Heating_PID_Seq[6]AV347Heating_PID_Seq[7]AV348HumDehumReqAV349HW_AfreezeReqAV350PID_DewCompensAV351PID_RegCompensAV352PreW_AfreezeReqAV353MainHeatMaxAV354RevHeat_Sig_MinAV355RevHeat_Sig_MaxAV356RevCool_Sig_MinAV357RevCool_Sig_MaxAV358RevTemp_EnAV359ReHeatMaxAV360PreHeatMaxPIV626LowTempAlrmDT_RunBV1641LowSupplyTemp_OffBV1642PreHeat_AlwaysAV361MainStartupValuePIV627HE_Alarm_DelayAV362Pump_ExtTempAV363Valve_ExtTempAV364MainHW_MinPID_TextIV628FanFlowAlarm_DelayPIV629DoubleFanRotTBV1643DoubleFanRot_ManualPIV630DoubleDamp.ManBV1644FanTempRegAV365FanTempReg_SigAV366DevCfg_PID_Seq_Heat[7].KpPIV631DevCfg_PID_Seq_Heat[7].TiAV367FanTempReg_MaxBV1645RRG_0_10VBV1646En_RRG_AlarmAV368RRG_MinValueFor_AlAV369RRG_MinPower_AlIV632RRG_Alarm_DelayBV1647Mix_Mode_ECOAV370Mix_Val_ECOBV1648Mix_Mode_OPTIMALAV371Mix_Val_OPTIMALBV1649Mix_Mode_COMFORTAV372Mix_Val_COMFORTAV373AFreezeHeatOutPIV633AFreezeHeatOutTPIV634__SYSVA_BEEP_ONIV635__SYSVA_CURSOR_COLUMNIV636__SYSVA_CURSOR_ROWIV637__SYSVA_CURSOR_VARIV638__SYSVA_KEY_COUNTERPIV639__SYSVA_KEY_PRESSEDPIV640__SYSVA_MANUAL_BUZZER_OFFPIV641__SYSVA_MANUAL_BUZZER_ONPIV642__SYSVA_TMP_VALUEBV1650AfterPreHeatCoilTemp.EnabledPIV643AfterPreHeatCoilTemp.ManAV374AfterPreHeatCoilTemp.OffsetPIV644AppCode_BoardPIV645AppCode_CoolPIV646AppCode_EcoPIV647AppCode_HeatPIV648AppCode_HumPIV649AppCode_PreHeatPIV650AppCode_RecPIV651AppCode_ReHeatPIV652AppCode_RevBV1651AppCool_CWBV1652AppCool_DXBV1653AppEcoBV1654AppHeat_DXBV1655AppHeat_HEBV1656AppHeat_HWBV1657AppHeat_SteamBV1658AppHum_EvapBV1659AppHum_SteamPIV653AppHumRegBV1660AppPreHeat_DXBV1661AppPreHeat_HEBV1662AppPreHeat_HWBV1663AppRec_EnExhBV1664AppRec_GlycolBV1665AppRec_PlateBV1666AppRec_RotaryBV1667AppRec_SupplyOnlyBV1668AppReg_RetBV1669AppReg_RoomBV1670AppReg_SupplyBV1671AppReHeat_DXBV1672AppReHeat_HEBV1673AppReHeat_HWBV1674AppRev_DXBV1675AppRev_WBV1676AppRevCoolDXBV1677AppRevCoolWBV1678AppRevHeatDXBV1679AppRevHeatWPIV654AppTempRegBV1680BacNetSelPIV655BMS_AddrBV1681CO2_Simulation_EnIV656CO2_Simulation_VarBV1682CoolAlrm.LogicPIV657CoolAlrm.ManPIV658DriveTypBV1684En_BuzzBV1685En_HumTHTN_1BV1686En_RetAir_CO2BV1687En_RetAirPBV1688En_RetHumBV1689En_SupplyAirPBV1690En_SupplyHumBV1691ExhAirDamp.LogicPIV659ExhFanRegTypPIV660ExhMultiPIV661ExhTemp.ManAV375ExhTemp.OffsetBV1692ExtTemp.EnabledPIV662ExtTemp.ManAV376ExtTemp.OffsetIV663FB_Baud_mskBV1693FireAlrm.LogicPIV664FireAlrm.ManBV1694Heat_2.LogicBV1696HumAlrm.LogicPIV665HumAlrm.ManBV1697ID2_Alrm.LogicPIV666ID2_Alrm.ManIV667ImpExpFileNameIV668LangChangeAV377MinFanPwrRetAV378MinFanPwrSupPIV669OffTotMinutesPIV670OnOffStatusPIV671PrgCycleMsBV1699RecSupplyTemp.EnabledPIV672RecSupplyTemp.ManAV379RecSupplyTemp.OffsetBV1701RemoteOn.LogicPIV673RemoteOn.ManBV1702RetFilter.LogicPIV674RetFilter.ManBV1703RetTemp.EnabledPIV675RetTemp.ManAV380RetTemp.OffsetBV1704SrsAlrm.LogicPIV676SupplyFanRegTypBV1705SupplyFilter.LogicPIV677SupplyFilter.ManPIV678SupplyMultiPIV679SupplyTemp.ManAV381SupplyTemp.OffsetPIV680Typ_SP_CO2PIV681Typ_SP_HumPIV682Typ_SP_PressurePIV683TypVFDPIV684TypVFD_2PIV685TypVFD_RotorBV1706UnitConfiguredIV686Uom_MskBV1707W_HeatCoilTemp.EnabledPIV687W_HeatCoilTemp.ManAV382W_HeatCoilTemp.OffsetBV1708W_PreHeatCoilTemp.EnabledPIV688W_PreHeatCoilTemp.ManAV383W_PreHeatCoilTemp.OffsetBV1709WinSum.EnabledBV1710WinSum.LogicPIV689WinSum.ManPIV690CurrVer.DBV1711CurrVer.IsBetaPIV691CurrVer.XPIV692CurrVer.YPIV693CurrVer.ZBV1712ExhTemp.EnabledBV1713Manual_PreHeatBV1714Manual_RecoveryBV1715Manual_HeatBV1716Manual_CoolBV1717Manual_ReHeatBV1718Manual_ReverseBV1719Manual_MixBV1720Manual_HumidityBV1721Manual_RedDampBV1722Manual_ActiveAV694Reverse_Val_AOAV698UnitSetP.AirFlwSetP.StandByAV697UnitSetP.AirQualitySetP.StandByAV696UnitSetP.HumSetP.StandByAV699UnitSetP.RetAirFlwSetP.StandByAV695UnitSetP.RoomTempSetP.StandByPIV700Heat_1.ManAV712SupplyAirFlow_2AV713ExhAirFlow_2AV714ExhAirFlowSet_Msk_2AV715SupplyAirFlowSet_Msk_2
Integration notes
- Object names are the uPC3 variable names (the workbook's OPC-UA DisplayName repeats them).
- Descriptions start with a group tag: IO inputs/outputs, MO monitoring, SP setpoints, PAR parameters, SCH scheduler, SYS system, CLK clock, CT counters, ECO energy, AL alarms.
- Most alarms have two flags, .Trigger and .Active.
- Objects for fans 2-10, extra coils and options a unit does not have are still listed.
- Access is printed as Read or ReadWrite; ReadWrite is listed as W.
- BV 25 UnitOff is described 'Unit - On' and BV 26 UnitOn 'Unit - Off'; kept as printed. BV 18 SrsAlrm.Val (global alarm output) prints 0=ON, 1=OFF.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the vQ Stream unit with Carel uPC3 controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the FläktGroup vQ Stream unit with Carel uPC3 controller
How many BACnet points does the FläktGroup vQ Stream unit with Carel uPC3 controller have?
This list has 2422 BACnet objects: 393 analog values, 1718 binary values, 20 integer values, 291 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which FläktGroup vQ Stream unit with Carel uPC3 controller BACnet points are writable?
595 of the 2422 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official FläktGroup vQ Stream unit with Carel uPC3 controller BACnet documentation?
The source is vQ Stream - Communication list for BMS (uPC3 - BMS Variable), published free by FläktGroup at https://www.flaktgroup.com/api/v1/Documents/1240712/Download.
What are the minimum BACnet points to integrate the FläktGroup vQ Stream unit with Carel uPC3 controller?
Start with PIV 397 SetTyp (Work mode: 0 Off, 1 Eco, 2 Optimal, 3 Comfort, 5 Auto); AV 207 UnitSetP.RoomTempSetP.Comfort (Comfort room temperature setpoint, °C); BV 845 AlarmMng.AlrmResByBms (Alarm reset from the BMS (1 = reset)); AV 194 RegTemp (Current temperature setpoint value, °C); BV 24 RunSupplyFan (Supply fan running); AV 36 SupplyTemp.Val (Supply air temperature, °C); AV 32 RetTemp.Val (Return / room air temperature, °C); AV 6 ExtTemp.Val (Outdoor (external) air temperature, °C); AV 191 SupplyFanVal (Supply fan output, %); BV 18 SrsAlrm.Val (Global alarm output (printed 0 = ON)).
How do I enable BMS control of the FläktGroup vQ Stream unit with Carel uPC3 controller?
PIV 397 SetTyp (ReadWrite) is the work-mode selection; 5 = Auto follows the unit's scheduler. The setpoints used in each mode are the UnitSetP.* AVs (Economy, Optimal/PreComfort, Comfort, Standby).
How do I check these points on the real vQ Stream unit with Carel uPC3 controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More FläktGroup BACnet points lists
- Air handling unit controller (Climatix)
FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx
FläktGroup eQ air handling units with Siemens Climatix POL6xx controls running the eQ Fläkt AHU application V2.xx.
Also known as: eQ, eQ Flakt V2, eQ Fläkt AHU V2.xx, Climatix eQ, DC_10159GB, POL908, POL904 - Air handling unit controller (Climatix)
FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx
FläktGroup eQ air handling units with Siemens Climatix POL6xx controls running the eQ Fläkt AHU application V3.xx.
Also known as: eQ, eQ Flakt V3, eQ Fläkt AHU V3.xx, Climatix eQ, DC_10159GB, POL908, POL904 - Air handling unit controller
FläktGroup ISYteq 4.0 AHU controls (SW 1.3.0.2)
FläktGroup air handling units controlled by ISYteq 4.0, software version 1.3.0.2.
Also known as: ISYteq 4.0, ISYteq 4, Flakt ISYteq BMS list, DC_10838, BMS Communication list 1.3.0.2 - Air handling unit controller (compact AHU)
FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs
FläktGroup eCO Top and eCO Side compact air handling units with the built-in ISYteq controller (eCO SEC application).
Also known as: ISYteq, eCO Top, eCO Side, eCO SEC, ISYteq eCO, DC_10484GB, Flakt eCO BACnet - Fire / smoke damper controller with airflow measurement
FläktGroup OPTIVENT UltraSafe USFA control unit
FläktGroup OPTIVENT UltraSafe USFA control units for fire and smoke dampers with ultrasonic airflow measurement.
Also known as: UltraSafe USFA, USFA, OPTIVENT UltraSafe, Ultrasafe, DC_10786GB, Flakt UltraSafe BACnet
Source: vQ Stream - Communication list for BMS (uPC3 - BMS Variable). Object names, instances and units are reproduced as published; descriptions are our own.