Air handling unit controller (Carel uPC3) · BACnet points list

FläktGroup vQ Stream unit with Carel uPC3 controller BACnet points list

Updated 12 November 2026

Short answer

The vQ Stream unit's Carel uPC3 controller publishes one variable list for Modbus, BACnet IP and OPC-UA. The BACnet side has Analog, Binary, Positive Integer and Integer Values: probe readings, outputs, setpoints, fan monitoring (up to 10 supply and 10 return fans), scheduler entries, unit configuration parameters, energy values and about 1,500 alarm flags (trigger and active bits per alarm).

This page lists 2422 BACnet objects for the FläktGroup vQ Stream unit with Carel uPC3 controller — 595 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FläktGroup’s own free documentation, linked below.

Manufacturer
FläktGroup
Model
vQ Stream unit with Carel uPC3 controller
Equipment
Air handling unit controller (Carel uPC3)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
2422 (595 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
vQ Stream, vQ Stream uPC3, Flakt vQ Stream BMS list, Carel uPC3 vQ Stream
Source document
vQ Stream - Communication list for BMS (uPC3 - BMS Variable)
Download CSV 2422 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against FläktGroup’s current documentation and the live device before use. Not official FläktGroup information. Terms of use.

BMS integration notes: FläktGroup vQ Stream unit with Carel uPC3 controller

Integration in brief

Select the BACnet port (BV 1680: Ethernet or pLAN) and network settings in the controller, then command the unit with PIV 397 SetTyp work mode and the per-mode setpoints, and read supply and return temperatures, fan running flags and the global alarm. BV 845 resets alarms from the BMS.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 397SetTypWork mode: 0 Off, 1 Eco, 2 Optimal, 3 Comfort, 5 AutoWrite
AV 207UnitSetP.RoomTempSetP.ComfortComfort room temperature setpoint, °CWrite
BV 845AlarmMng.AlrmResByBmsAlarm reset from the BMS (1 = reset)Write
AV 194RegTempCurrent temperature setpoint value, °CWrite
BV 24RunSupplyFanSupply fan runningRead
AV 36SupplyTemp.ValSupply air temperature, °CRead
AV 32RetTemp.ValReturn / room air temperature, °CRead
AV 6ExtTemp.ValOutdoor (external) air temperature, °CRead
AV 191SupplyFanValSupply fan output, %Read
BV 18SrsAlrm.ValGlobal alarm output (printed 0 = ON)Read

Enable & remote start

PIV 397 SetTyp (ReadWrite) is the work-mode selection; 5 = Auto follows the unit's scheduler. The setpoints used in each mode are the UnitSetP.* AVs (Economy, Optimal/PreComfort, Comfort, Standby).

Network setup

Watch out for

FläktGroup vQ Stream unit with Carel uPC3 controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

2422 of 2422 shown
Type
AnalogBinary
Access
Show
FläktGroup vQ Stream unit with Carel uPC3 controller BACnet Points List
DescriptionStates
AV1AfterPreHeatCoilTemp.ValIO - Probe - Temperature - After PreHeat°CRead
BV1Cool_1.ValIO - Digital Output - Cooler - Stage 1Read0=ON; 1=OFF
BV2Cool_2.ValIO - Digital Output - Cooler - Stage 2Read0=ON; 1=OFF
BV3CoolAlrm.ValIO - Digital Input - Cooler - AlarmRead
BV4CoolHeat.ValIO - Digital Output - Heating - SignalRead0=ON; 1=OFF
AV2CoolVlv.ValIO - Analog Output - Cooling (0 - 100 %)%Read
BV5DoubleDamp.ValIO - Digital Output - Damper - RedundantRead0=ON; 1=OFF
BV6ExhAirDamp.ValIO - Digital Output - Damper - SupplyRead0=ON; 1=OFF
AV3ExhAirFlowIO - Probe - Air Flow - Return (For airflow < 32767)m3/hRead
AV4ExhAirP_ValIO - Probe - Pressure - ReturnPaRead
AV5ExhTemp.ValIO - Probe - Temperature - Recovery°CRead
AVmin6ExtTemp.ValIO - Probe - Temperature - External°CRead
BV7FireAlrm.ValIO - Digital Input - Fire - AlarmRead
BV8Heat_1.ValIO - Digital Output - Heater - Stage 1Read0=ON; 1=OFF
BV9Heat_2.ValIO - Digital Output - Heater - Stage 2Read0=ON; 1=OFF
AV7HeatRecovery_ValIO - Analog Output - Rotary - Value (0 - 100 %)%Read
AV8HeatVlv.ValIO - Analog Output - Heater (0 - 100 %)%Read
BV10Hum.ValIO - Digital Output - HumidifierRead0=ON; 1=OFF
AV9Hum_THTN_1IO - Probe - Humidity - TH Room (0 - 100 %)%Read
BV11HumAlrm.ValIO - Digital Input - Humidifier - AlarmRead
BV12ID2_Alrm.ValIO - Digital Input - Freeze - AlarmRead
AV10MB_Devices.MB_MainBoard_1.AI_Temp_Fan_ReturnIO - Module IO - Temperature Fan Return°CRead
AV11MB_Devices.MB_MainBoard_1.AI_Temp_Fan_SupplyIO - Module IO - Temperature Fan Supply°CRead
AV12MB_Devices.MB_MainBoard_1.AO_01_ReadIO - Module IO - Analog output 1%Read
AV13MB_Devices.MB_MainBoard_1.AO_02_ReadIO - Module IO - Analog output 2%Read
AV14MB_Devices.MB_MainBoard_1.AO_03_ReadIO - Module IO - Analog output 3%Read
AV15MB_Devices.MB_MainBoard_1.AO_04_ReadIO - Module IO - Analog output 4%Read
AV16MB_Devices.MB_MainBoard_1.Humid_ReturnIO - Module IO - Humidity Return%Read
AV17MB_Devices.MB_MainBoard_1.Pressure_Fan_ReturnIO - Module IO - Pressure Fan ReturnPaRead
AV18MB_Devices.MB_MainBoard_1.Pressure_Fan_SupplyIO - Module IO - Pressure Fan SupplyPaRead
AV19MB_Devices.MB_MainBoard_1.Pressure_Filter_ReturnIO - Module IO - Pressure Filter ReturnPaRead
AV20MB_Devices.MB_MainBoard_1.Pressure_Filter_SupplyIO - Module IO - Pressure Filter SupplyPaRead
AV21MB_Devices.MB_MainBoard_1.Supply_24V_ReadIO - Module IO - Supply 24VVRead
AV22MB_Devices.MB_MainBoard_1.Supply_Control_ReadIO - Module IO - Supply ControllerVRead
AV23MB_Devices.MB_MainBoard_1.Temp_ReturnIO - Module IO - Temperature Return°CRead
AV24MixDampReq_FreshIO - Analog Output - Damper - External (0 - 100 %)%Read
AV25ModulHum.ValIO - Analog Output - Humidifier (0 - 100 %)%Read
AV26ModulMixDamp_ValIO - Analog Output - Damper - Mixing (0 - 100 %)%Read
AV27ModulPreHeat.ValIO - Analog Output - PreHeater (0 - 100 %)%Read
BV13PreHeaterPump.ValIO - Digital Output - PreHeaterRead0=ON; 1=OFF
BV14RecoveryPump.ValIO - Digital Output - RecoveryRead0=ON; 1=OFF
AV28RecSupplyTemp.ValIO - Probe - Temperature - Supply after recovery°CRead
BV15ReHeat.ValIO - Digital Output - ReHeaterRead0=ON; 1=OFF
AV29ReHeatVlv.ValIO - Analog Output - ReHeater (0 - 100 %)%Read
BV16RemoteOn.ValIO - Digital Input - Remote - ONRead
AV30RetAir_CO2_ValIO - Probe - CO2 - ReturnppmRead
BV17RetFilter.ValIO - Digital Input - Filter - ReturnRead
AV31RetHum_ValIO - Probe - Humidity - Return (0 - 100 %)%Read
AVmin32RetTemp.ValIO - Probe - Temperature - Return / Room°CRead
BVmin18SrsAlrm.ValIO - Digital Output - Alarm - GlobalRead0=ON; 1=OFF
AV33SupplyAirFlowIO - Probe - Air Flow - Supply (For airflow < 32767)m3/hRead
AV34SupplyAirP_ValIO - Probe - Pressure - SupplyPaRead
BV19SupplyFilter.ValIO - Digital Input - Filter - SupplyRead
AV35SupplyHum_ValIO - Probe - Humidity - Supply (0 - 100 %)%Read
AVmin36SupplyTemp.ValIO - Probe - Temperature - Supply°CRead
AV37Temp_THTN_1IO - Probe - Temperature - TH Room°CRead
AV38W_HeatCoilTemp.ValIO - Probe - Temperature - Water Heat°CRead
AV39W_PreHeatCoilTemp.ValIO - Probe - Temperature - Water PreHeat°CRead
BV20WinSum.ValIO - Digital Input - Winter / SummerRead
AV40Y1Out_HWIO - Analog Output - Y1 (0 - 100 %)%Read
AV41Y2Out_HWIO - Analog Output - Y2 (0 - 100 %)%Read
AV42Y3Out_HWIO - Analog Output - Y3 (0 - 100 %)%Read
BV21UnitCoolHeatModeMO - Unit - Cooling / HeatingWrite0=Cooling; 1=Heating
AV43ExhFan_1.CurrentMO - Fan - Return 1 - CurrentARead
AV44ExhFan_1.DriveTempMO - Fan - Return 1 - Drive temperature (USA)°CRead
AV45ExhFan_1.FreqMO - Fan - Return 1 - FrequenceHzRead
AV46ExhFan_1.kWhMO - Fan - Return 1 - Consumption (USA)kWhRead
AV47ExhFan_1.PowerMO - Fan - Return 1 - PowerWRead
AV48ExhFan_1.RpmMO - Fan - Return 1 - SpeedRPMRead
AV49ExhFan_1.VoltageMO - Fan - Return 1 - VoltageVRead
AV50ExhFan_10.CurrentMO - Fan - Return 10 - CurrentARead
AV51ExhFan_10.DriveTempMO - Fan - Return 10 - Drive temperature (USA)°CRead
AV52ExhFan_10.FreqMO - Fan - Return 10 - FrequenceHzRead
AV53ExhFan_10.kWhMO - Fan - Return 10 - Consumption (USA)kWhRead
AV54ExhFan_10.PowerMO - Fan - Return 10 - PowerWRead
AV55ExhFan_10.RpmMO - Fan - Return 10 - SpeedRPMRead
AV56ExhFan_10.VoltageMO - Fan - Return 10 - VoltageVRead
AV57ExhFan_2.CurrentMO - Fan - Return 2 - CurrentARead
AV58ExhFan_2.DriveTempMO - Fan - Return 2 - Drive temperature (USA)°CRead
AV59ExhFan_2.FreqMO - Fan - Return 2 - FrequenceHzRead
AV60ExhFan_2.kWhMO - Fan - Return 2 - Consumption (USA)kWhRead
AV61ExhFan_2.PowerMO - Fan - Return 2 - PowerWRead
AV62ExhFan_2.RpmMO - Fan - Return 2 - SpeedRPMRead
AV63ExhFan_2.VoltageMO - Fan - Return 2 - VoltageVRead
AV64ExhFan_3.CurrentMO - Fan - Return 3 - CurrentARead
AV65ExhFan_3.DriveTempMO - Fan - Return 3 - Drive temperature (USA)°CRead
AV66ExhFan_3.FreqMO - Fan - Return 3 - FrequenceHzRead
AV67ExhFan_3.kWhMO - Fan - Return 3 - Consumption (USA)kWhRead
AV68ExhFan_3.PowerMO - Fan - Return 3 - PowerWRead
AV69ExhFan_3.RpmMO - Fan - Return 3 - SpeedRPMRead
AV70ExhFan_3.VoltageMO - Fan - Return 3 - VoltageVRead
AV71ExhFan_4.CurrentMO - Fan - Return 4 - CurrentARead
AV72ExhFan_4.DriveTempMO - Fan - Return 4 - Drive temperature (USA)°CRead
AV73ExhFan_4.FreqMO - Fan - Return 4 - FrequenceHzRead
AV74ExhFan_4.kWhMO - Fan - Return 4 - Consumption (USA)kWhRead
AV75ExhFan_4.PowerMO - Fan - Return 4 - PowerWRead
AV76ExhFan_4.RpmMO - Fan - Return 4 - SpeedRPMRead
AV77ExhFan_4.VoltageMO - Fan - Return 4 - VoltageVRead
AV78ExhFan_5.CurrentMO - Fan - Return 5 - CurrentARead
AV79ExhFan_5.DriveTempMO - Fan - Return 5 - Drive temperature (USA)°CRead
AV80ExhFan_5.FreqMO - Fan - Return 5 - FrequenceHzRead
AV81ExhFan_5.kWhMO - Fan - Return 5 - Consumption (USA)kWhRead
AV82ExhFan_5.PowerMO - Fan - Return 5 - PowerWRead
AV83ExhFan_5.RpmMO - Fan - Return 5 - SpeedRPMRead
AV84ExhFan_5.VoltageMO - Fan - Return 5 - VoltageVRead
AV85ExhFan_6.CurrentMO - Fan - Return 6 - CurrentARead
AV86ExhFan_6.DriveTempMO - Fan - Return 6 - Drive temperature (USA)°CRead
AV87ExhFan_6.FreqMO - Fan - Return 6 - FrequenceHzRead
AV88ExhFan_6.kWhMO - Fan - Return 6 - Consumption (USA)kWhRead
AV89ExhFan_6.PowerMO - Fan - Return 6 - PowerWRead
AV90ExhFan_6.RpmMO - Fan - Return 6 - SpeedRPMRead
AV91ExhFan_6.VoltageMO - Fan - Return 6 - VoltageVRead
AV92ExhFan_7.CurrentMO - Fan - Return 7 - CurrentARead
AV93ExhFan_7.DriveTempMO - Fan - Return 7 - Drive temperature (USA)°CRead
AV94ExhFan_7.FreqMO - Fan - Return 7 - FrequenceHzRead
AV95ExhFan_7.kWhMO - Fan - Return 7 - Consumption (USA)kWhRead
AV96ExhFan_7.PowerMO - Fan - Return 7 - PowerWRead
AV97ExhFan_7.RpmMO - Fan - Return 7 - SpeedRPMRead
AV98ExhFan_7.VoltageMO - Fan - Return 7 - VoltageVRead
AV99ExhFan_8.CurrentMO - Fan - Return 8 - CurrentARead
AV100ExhFan_8.DriveTempMO - Fan - Return 8 - Drive temperature (USA)°CRead
AV101ExhFan_8.FreqMO - Fan - Return 8 - FrequenceHzRead
AV102ExhFan_8.kWhMO - Fan - Return 8 - Consumption (USA)kWhRead
AV103ExhFan_8.PowerMO - Fan - Return 8 - PowerWRead
AV104ExhFan_8.RpmMO - Fan - Return 8 - SpeedRPMRead
AV105ExhFan_8.VoltageMO - Fan - Return 8 - VoltageVRead
AV106ExhFan_9.CurrentMO - Fan - Return 9 - CurrentARead
AV107ExhFan_9.DriveTempMO - Fan - Return 9 - Drive temperature (USA)°CRead
AV108ExhFan_9.FreqMO - Fan - Return 9 - FrequenceHzRead
AV109ExhFan_9.kWhMO - Fan - Return 9 - Consumption (USA)kWhRead
AV110ExhFan_9.PowerMO - Fan - Return 9 - PowerWRead
AV111ExhFan_9.RpmMO - Fan - Return 9 - SpeedRPMRead
AV112ExhFan_9.VoltageMO - Fan - Return 9 - VoltageVRead
AV113ExhFanValMO - Fan - Return - Value (0 - 100 %)%Read
BV22MixAirDamp_OnMO - Damper Mixing - OnRead
AV114Rotary.CurrentMO - Recovery - Rotary - CurrentARead
AV115Rotary.DriveTempMO - Recovery - Rotary - Drive temperature (USA)°CRead
AV116Rotary.FreqMO - Recovery - Rotary - FrequenceHzRead
AV117Rotary.kWhMO - Recovery - Rotary - Consumption (USA)kWhRead
AV118Rotary.PowerMO - Recovery - Rotary - PowerWRead
AV119Rotary.RpmMO - Recovery - Rotary - SpeedRPMRead
AV120Rotary.VoltageMO - Recovery - Rotary - VoltageVRead
BV23RunExhFanMO - Fan - Return - OnRead
BVmin24RunSupplyFanMO - Fan - Supply - OnRead
AV121SupplyFan_1.CurrentMO - Fan - Supply 1 - CurrentARead
AV122SupplyFan_1.DriveTempMO - Fan - Supply 1 - Drive temperature (USA)°CRead
AV123SupplyFan_1.FreqMO - Fan - Supply 1 - FrequenceHzRead
AV124SupplyFan_1.kWhMO - Fan - Supply 1 - Consumption (USA)kWhRead
AV125SupplyFan_1.PowerMO - Fan - Supply 1 - PowerWRead
AV126SupplyFan_1.RpmMO - Fan - Supply 1 - SpeedRPMRead
AV127SupplyFan_1.VoltageMO - Fan - Supply 1 - VoltageVRead
AV128SupplyFan_10.CurrentMO - Fan - Supply 10 - CurrentARead
AV129SupplyFan_10.DriveTempMO - Fan - Supply 10 - Drive temperature (USA)°CRead
AV130SupplyFan_10.FreqMO - Fan - Supply 10 - FrequenceHzRead
AV131SupplyFan_10.kWhMO - Fan - Supply 10 - Consumption (USA)kWhRead
AV132SupplyFan_10.PowerMO - Fan - Supply 10 - PowerWRead
AV133SupplyFan_10.RpmMO - Fan - Supply 10 - SpeedRPMRead
AV134SupplyFan_10.VoltageMO - Fan - Supply 10 - VoltageVRead
AV135SupplyFan_2.CurrentMO - Fan - Supply 2 - CurrentARead
AV136SupplyFan_2.DriveTempMO - Fan - Supply 2 - Drive temperature (USA)°CRead
AV137SupplyFan_2.FreqMO - Fan - Supply 2 - FrequenceHzRead
AV138SupplyFan_2.kWhMO - Fan - Supply 2 - Consumption (USA)kWhRead
AV139SupplyFan_2.PowerMO - Fan - Supply 2 - PowerWRead
AV140SupplyFan_2.RpmMO - Fan - Supply 2 - SpeedRPMRead
AV141SupplyFan_2.VoltageMO - Fan - Supply 2 - VoltageVRead
AV142SupplyFan_3.CurrentMO - Fan - Supply 3 - CurrentARead
AV143SupplyFan_3.DriveTempMO - Fan - Supply 3 - Drive temperature (USA)°CRead
AV144SupplyFan_3.FreqMO - Fan - Supply 3 - FrequenceHzRead
AV145SupplyFan_3.kWhMO - Fan - Supply 3 - Consumption (USA)kWhRead
AV146SupplyFan_3.PowerMO - Fan - Supply 3 - PowerWRead
AV147SupplyFan_3.RpmMO - Fan - Supply 3 - SpeedRPMRead
AV148SupplyFan_3.VoltageMO - Fan - Supply 3 - VoltageVRead
AV149SupplyFan_4.CurrentMO - Fan - Supply 4 - CurrentARead
AV150SupplyFan_4.DriveTempMO - Fan - Supply 4 - Drive temperature (USA)°CRead
AV151SupplyFan_4.FreqMO - Fan - Supply 4 - FrequenceHzRead
AV152SupplyFan_4.kWhMO - Fan - Supply 4 - Consumption (USA)kWhRead
AV153SupplyFan_4.PowerMO - Fan - Supply 4 - PowerWRead
AV154SupplyFan_4.RpmMO - Fan - Supply 4 - SpeedRPMRead
AV155SupplyFan_4.VoltageMO - Fan - Supply 4 - VoltageVRead
AV156SupplyFan_5.CurrentMO - Fan - Supply 5 - CurrentARead
AV157SupplyFan_5.DriveTempMO - Fan - Supply 5 - Drive temperature (USA)°CRead
AV158SupplyFan_5.FreqMO - Fan - Supply 5 - FrequenceHzRead
AV159SupplyFan_5.kWhMO - Fan - Supply 5 - Consumption (USA)kWhRead
AV160SupplyFan_5.PowerMO - Fan - Supply 5 - PowerWRead
AV161SupplyFan_5.RpmMO - Fan - Supply 5 - SpeedRPMRead
AV162SupplyFan_5.VoltageMO - Fan - Supply 5 - VoltageVRead
AV163SupplyFan_6.CurrentMO - Fan - Supply 6 - CurrentARead
AV164SupplyFan_6.DriveTempMO - Fan - Supply 6 - Drive temperature (USA)°CRead
AV165SupplyFan_6.FreqMO - Fan - Supply 6 - FrequenceHzRead
AV166SupplyFan_6.kWhMO - Fan - Supply 6 - Consumption (USA)kWhRead
AV167SupplyFan_6.PowerMO - Fan - Supply 6 - PowerWRead
AV168SupplyFan_6.RpmMO - Fan - Supply 6 - SpeedRPMRead
AV169SupplyFan_6.VoltageMO - Fan - Supply 6 - VoltageVRead
AV170SupplyFan_7.CurrentMO - Fan - Supply 7 - CurrentARead
AV171SupplyFan_7.DriveTempMO - Fan - Supply 7 - Drive temperature (USA)°CRead
AV172SupplyFan_7.FreqMO - Fan - Supply 7 - FrequenceHzRead
AV173SupplyFan_7.kWhMO - Fan - Supply 7 - Consumption (USA)kWhRead
AV174SupplyFan_7.PowerMO - Fan - Supply 7 - PowerWRead
AV175SupplyFan_7.RpmMO - Fan - Supply 7 - SpeedRPMRead
AV176SupplyFan_7.VoltageMO - Fan - Supply 7 - VoltageVRead
AV177SupplyFan_8.CurrentMO - Fan - Supply 8 - CurrentARead
AV178SupplyFan_8.DriveTempMO - Fan - Supply 8 - Drive temperature (USA)°CRead
AV179SupplyFan_8.FreqMO - Fan - Supply 8 - FrequenceHzRead
AV180SupplyFan_8.kWhMO - Fan - Supply 8 - Consumption (USA)kWhRead
AV181SupplyFan_8.PowerMO - Fan - Supply 8 - PowerWRead
AV182SupplyFan_8.RpmMO - Fan - Supply 8 - SpeedRPMRead
AV183SupplyFan_8.VoltageMO - Fan - Supply 8 - VoltageVRead
AV184SupplyFan_9.CurrentMO - Fan - Supply 9 - CurrentARead
AV185SupplyFan_9.DriveTempMO - Fan - Supply 9 - Drive temperature (USA)°CRead
AV186SupplyFan_9.FreqMO - Fan - Supply 9 - FrequenceHzRead
AV187SupplyFan_9.kWhMO - Fan - Supply 9 - Consumption (USA)kWhRead
AV188SupplyFan_9.PowerMO - Fan - Supply 9 - PowerWRead
AV189SupplyFan_9.RpmMO - Fan - Supply 9 - SpeedRPMRead
AV190SupplyFan_9.VoltageMO - Fan - Supply 9 - VoltageVRead
AVmin191SupplyFanValMO - Fan - Supply - Value (0 - 100 %)%Read
BV25UnitOffMO - Unit - OnRead
BV26UnitOnMO - Unit - OffRead
AV192ExhFan_1_PowerMO - Fan - Return - PowerWRead
AV193SupplyFan_1_PowerMO - Fan - Supply - PowerWRead
PIV384HC_Cool_1.HrsCT - Counter - Cooling - Device 1 (0 - 999999)hRead
PIV385HC_Cool_2.HrsCT - Counter - Cooling - Device 2 (0 - 999999)hRead
PIV386HC_ExhFan_1.HrsCT - Counter - Fan - Return 1 (0 - 999999)hRead
PIV387HC_ExhFan_2.HrsCT - Counter - Fan - Return 2 (0 - 999999)hRead
PIV388HC_Heat_1.HrsCT - Counter - Heating - Device 1 (0 - 999999)hRead
PIV389HC_Heat_2.HrsCT - Counter - Heating - Device 2 (0 - 999999)hRead
PIV390HC_Heat_Mod.HrsCT - Counter - Heating - Modulation (0 - 999999)hRead
PIV391HC_Hum.HrsCT - Counter - Humidity (0 - 999999)hRead
PIV392HC_PreHeat.HrsCT - Counter - PreHeating (0 - 999999)hRead
PIV393HC_RecoveryPump.HrsCT - Counter - Recovery (0 - 999999)hRead
PIV394HC_ReHeat.HrsCT - Counter - ReHeating (0 - 999999)hRead
PIV395HC_SupplyFan_1.HrsCT - Counter - Fan - Supply 1 (0 - 999999)hRead
PIV396HC_SupplyFan_2.HrsCT - Counter - Fan - Supply 2 (0 - 999999)hRead
AVmin194RegTempSP - Setpoint - Temperature - Current - Value°CWrite
PIVmin397SetTypSP - Work ModeWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT; 4=STANDBY; 5=AUTO
AV195UnitSetP.AirFlwSetP.ComfortSP - Setpoint - Air Flow - Supply - 3 - Comfort (0 - 100 %)%Write
AV196UnitSetP.AirFlwSetP.EconomySP - Setpoint - Air Flow - Supply - 1 - Economy (0 - 100 %)%Write
AV197UnitSetP.AirFlwSetP.PreComfortSP - Setpoint - Air Flow - Supply - 2 - Optimal (0 - 100 %)%Write
AV198UnitSetP.AirQualitySetP.ComfortSP - Setpoint - Air Quality - 3 - ComfortppmWrite
AV199UnitSetP.AirQualitySetP.EconomySP - Setpoint - Air Quality - 1 - EconomyppmWrite
AV200UnitSetP.AirQualitySetP.PreComfortSP - Setpoint - Air Quality - 2 - OptimalppmWrite
AV201UnitSetP.HumSetP.ComfortSP - Setpoint - Humidity - 3 - Comfort (0 - 100 %)%Write
AV202UnitSetP.HumSetP.EconomySP - Setpoint - Humidity - 1 - Economy (0 - 100 %)%Write
AV203UnitSetP.HumSetP.PreComfortSP - Setpoint - Humidity - 2 - Optimal (0 - 100 %)%Write
AV204UnitSetP.RetAirFlwSetP.ComfortSP - Setpoint - Air Flow - Return - 3 - Comfort (0 - 100 %)%Write
AV205UnitSetP.RetAirFlwSetP.EconomySP - Setpoint - Air Flow - Return - 1 - Economy (0 - 100 %)%Write
AV206UnitSetP.RetAirFlwSetP.PreComfortSP - Setpoint - Air Flow - Return - 2 - Optimal (0 - 100 %)%Write
AVmin207UnitSetP.RoomTempSetP.ComfortSP - Setpoint - Temperature - Room - 3 - Comfort°CWrite
AV208UnitSetP.RoomTempSetP.EconomySP - Setpoint - Temperature - Room - 1 - Economy°CWrite
AV209UnitSetP.RoomTempSetP.PreComfortSP - Setpoint - Temperature - Room - 2 - Optimal°CWrite
AV210ActualSetSP - Setpoint - Temperature - Actual°CRead
AV211CurrAirFlwSetP_ValSP - Setpoint - Air Flow - Supply - Current - Value (0 - 100 %)%Read
AV212CurrAirQualitySetP_ValSP - Setpoint - Air Quality - Current - ValueppmRead
AV213CurrHumSetP_ValSP - Setpoint - Humidity - Current - Value (0 - 100 %)%Read
AV214CurrRetAirFlwSetP_ValSP - Setpoint - Air Flow - Return - Current - Value (0 - 100 %)%Read
AV215CurrRoomTempSetP_ValSP - Setpoint - Temperature - Room - Current - Value°CRead
AV216UnitSetP_AirFlwSetP_ComfortSP - Setpoint - Air Flow - Supply - 3 - Comfort (Actual) (0 - 100%Read
AV217UnitSetP_AirFlwSetP_Comfort_2SP - Setpoint - Air Flow - Return - 3 - Comfort (Actual) (0 - 100%Read
AV218UnitSetP_AirFlwSetP_EconomySP - Setpoint - Air Flow - Supply - 1 - Economy (Actual) (0 - 100%Read
AV219UnitSetP_AirFlwSetP_Economy_2SP - Setpoint - Air Flow - Return - 1 - Economy (Actual) (0 - 100%Read
AV220UnitSetP_AirFlwSetP_PreComfortSP - Setpoint - Air Flow - Supply - 2 - Optimal (Actual) (0 - 100%Read
AV221UnitSetP_AirFlwSetP_PreComfort_2SP - Setpoint - Air Flow - Return - 2 - Optimal (Actual) (0 - 100%Read
AV222RecHeat_PowerTemp_T_kWhECO - Power CoolkWRead
AV223RecCool_PowerTemp_T_kWhECO - Power CoolkWhRead
AV224Heat_PowerTemp_T_kWhECO - Power Cost - ConstantkWhRead
AV225Cool_PowerTemp_T_kWhECO - Power Cost - Constant - Mode ECOkWhRead
AV226PowerElect_T_kWh_ECOECO - Power Cost - Constant - Mode OptimalkWhRead
AV227PowerElect_T_kWh_OptimalECO - Power Cost - Constant - Mode ComfortkWhRead
AV228PowerElect_T_kWh_ComfortECO - Power CostkWhRead
AV229SupplyFan_Power_E1ECO - Power Cost - Mode ECOkWhRead
AV230ReturnFan_Power_E1ECO - Power Cost - Mode OptimalkWhRead
PIV398HC_Mode_ECOECO - Power Cost - Mode ComfortkWhRead
PIV399HC_Mode_ComfortECO - Power HeatkWRead
PIV400HC_Mode_OptimalECO - Power Heat kWhkWhRead
AV231RecHeat_PowerTempECOkWhRead
AV232RecCool_PowerTempECOkWhRead
AV233Heat_PowerTempECOkWhRead
AV234Cool_PowerTempECOkWhRead
AV235RecHeat_PowerTemp_kWhECOkWhRead
AV236RecCool_PowerTemp_kWhECOkWRead
AV237Heat_PowerTemp_kWhECOkWhRead
AV238Cool_PowerTemp_kWhECOkWRead
AV239Recovery_EfficencyECOkWhRead
BV27SchedOnSCH - Scheduller - OnWrite0=OFF; 1=ON
IV401Scheduler_OnOffUnit.Scheduler_1.CopyTo_DaySCH - Scheduller - Time Band - Copy to DayWrite0=MON; 1=TUE; 2=WED; 3=THU; 4=FRI; 5=SAT; 6=SUN; 7=ALL
IV402Scheduler_OnOffUnit.Scheduler_1.DaySCH - Scheduller - Time Band - DayWrite0=MON; 1=TUE; 2=WED; 3=THU; 4=FRI; 5=SAT; 6=SUN
BV28Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].EnabledSCH - Scheduller - Monday - 1 - EnabledWrite0=OFF; 1=ON
BV29Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].Flag_EnabledSCH - Scheduller - Monday - 1 - Flag_EnabledWrite
PIV403Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].HoursSCH - Scheduller - Monday - 1 - Hours (00-23)hWrite
PIV404Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].MinsSCH - Scheduller - Monday - 1 - Mins (0 - 59)min.Write
PIV405Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[0].UnitStatusSCH - Scheduller - Monday - 1 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV30Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].EnabledSCH - Scheduller - Monday - 2 - EnabledWrite0=OFF; 1=ON
BV31Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].Flag_EnabledSCH - Scheduller - Monday - 2 - Flag_EnabledWrite
PIV406Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].HoursSCH - Scheduller - Monday - 2 - Hours (0 - 23)hWrite
PIV407Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].MinsSCH - Scheduller - Monday - 2 - Mins (0 - 59)min.Write
PIV408Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[1].UnitStatusSCH - Scheduller - Monday - 2 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV32Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].EnabledSCH - Scheduller - Monday - 3 - EnabledWrite0=OFF; 1=ON
BV33Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].Flag_EnabledSCH - Scheduller - Monday - 3 - Flag_EnabledWrite
PIV409Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].HoursSCH - Scheduller - Monday - 3 - Hours (0 - 23)hWrite
PIV410Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].MinsSCH - Scheduller - Monday - 3 - Mins (0 - 59)min.Write
PIV411Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[2].UnitStatusSCH - Scheduller - Monday - 3 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV34Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].EnabledSCH - Scheduller - Monday - 4 - EnabledWrite0=OFF; 1=ON
BV35Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].Flag_EnabledSCH - Scheduller - Monday - 4 - Flag_EnabledWrite
PIV412Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].HoursSCH - Scheduller - Monday - 4 - Hours (0 - 23)hWrite
PIV413Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].MinsSCH - Scheduller - Monday - 4 - Mins (0 - 59)min.Write
PIV414Scheduler_OnOffUnit.Scheduler_1.DaysSched[0].EVENT[3].UnitStatusSCH - Scheduller - Monday - 4 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV36Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].EnabledSCH - Scheduller - Tuesday - 1 - EnabledWrite0=OFF; 1=ON
BV37Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].Flag_EnabledSCH - Scheduller - Tuesday - 1 - Flag_EnabledWrite
PIV415Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].HoursSCH - Scheduller - Tuesday - 1 - Hours (0 - 23)hWrite
PIV416Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].MinsSCH - Scheduller - Tuesday - 1 - Mins (0 - 59)min.Write
PIV417Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[0].UnitStatusSCH - Scheduller - Tuesday - 1 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV38Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].EnabledSCH - Scheduller - Tuesday - 2 - EnabledWrite0=OFF; 1=ON
BV39Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].Flag_EnabledSCH - Scheduller - Tuesday - 2 - Flag_EnabledWrite
PIV418Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].HoursSCH - Scheduller - Tuesday - 2 - Hours (0 - 23)hWrite
PIV419Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].MinsSCH - Scheduller - Tuesday - 2 - Mins (0 - 59)min.Write
PIV420Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[1].UnitStatusSCH - Scheduller - Tuesday - 2 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV40Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].EnabledSCH - Scheduller - Tuesday - 3 - EnabledWrite0=OFF; 1=ON
BV41Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].Flag_EnabledSCH - Scheduller - Tuesday - 3 - Flag_EnabledWrite
PIV421Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].HoursSCH - Scheduller - Tuesday - 3 - Hours (0 - 23)hWrite
PIV422Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].MinsSCH - Scheduller - Tuesday - 3 - Mins (0 - 59)min.Write
PIV423Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[2].UnitStatusSCH - Scheduller - Tuesday - 3 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV42Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].EnabledSCH - Scheduller - Tuesday - 4 - EnabledWrite0=OFF; 1=ON
BV43Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].Flag_EnabledSCH - Scheduller - Tuesday - 4 - Flag_EnabledWrite
PIV424Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].HoursSCH - Scheduller - Tuesday - 4 - Hours (0 - 23)hWrite
PIV425Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].MinsSCH - Scheduller - Tuesday - 4 - Mins (0 - 59)min.Write
PIV426Scheduler_OnOffUnit.Scheduler_1.DaysSched[1].EVENT[3].UnitStatusSCH - Scheduller - Tuesday - 4 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV44Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].EnabledSCH - Scheduller - Wednesday - 1 - EnabledWrite0=OFF; 1=ON
BV45Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].Flag_EnabledSCH - Scheduller - Wednesday - 1 - Flag_EnabledWrite
PIV427Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].HoursSCH - Scheduller - Wednesday - 1 - Hours (0 - 23)hWrite
PIV428Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].MinsSCH - Scheduller - Wednesday - 1 - Mins (0 - 59)min.Write
PIV429Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[0].UnitStatusSCH - Scheduller - Wednesday - 1 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV46Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].EnabledSCH - Scheduller - Wednesday - 2 - EnabledWrite0=OFF; 1=ON
BV47Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].Flag_EnabledSCH - Scheduller - Wednesday - 2 - Flag_EnabledWrite
PIV430Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].HoursSCH - Scheduller - Wednesday - 2 - Hours (0 - 23)hWrite
PIV431Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].MinsSCH - Scheduller - Wednesday - 2 - Mins (0 - 59)min.Write
PIV432Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[1].UnitStatusSCH - Scheduller - Wednesday - 2 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV48Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].EnabledSCH - Scheduller - Wednesday - 3 - EnabledWrite0=OFF; 1=ON
BV49Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].Flag_EnabledSCH - Scheduller - Wednesday - 3 - Flag_EnabledWrite
PIV433Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].HoursSCH - Scheduller - Wednesday - 3 - Hours (0 - 23)hWrite
PIV434Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].MinsSCH - Scheduller - Wednesday - 3 - Mins (0 - 59)min.Write
PIV435Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[2].UnitStatusSCH - Scheduller - Wednesday - 3 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV50Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].EnabledSCH - Scheduller - Wednesday - 4 - EnabledWrite0=OFF; 1=ON
BV51Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].Flag_EnabledSCH - Scheduller - Wednesday - 4 - Flag_EnabledWrite
PIV436Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].HoursSCH - Scheduller - Wednesday - 4 - Hours (0 - 23)hWrite
PIV437Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].MinsSCH - Scheduller - Wednesday - 4 - Mins (0 - 59)min.Write
PIV438Scheduler_OnOffUnit.Scheduler_1.DaysSched[2].EVENT[3].UnitStatusSCH - Scheduller - Wednesday - 4 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV52Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].EnabledSCH - Scheduller - Thursday - 1 - EnabledWrite0=OFF; 1=ON
BV53Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].Flag_EnabledSCH - Scheduller - Thursday - 1 - Flag_EnabledWrite
PIV439Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].HoursSCH - Scheduller - Thursday - 1 - Hours (0 - 23)hWrite
PIV440Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].MinsSCH - Scheduller - Thursday - 1 - Mins (0 - 59)min.Write
PIV441Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[0].UnitStatusSCH - Scheduller - Thursday - 1 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV54Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].EnabledSCH - Scheduller - Thursday - 2 - EnabledWrite0=OFF; 1=ON
BV55Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].Flag_EnabledSCH - Scheduller - Thursday - 2 - Flag_EnabledWrite
PIV442Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].HoursSCH - Scheduller - Thursday - 2 - Hours (0 - 23)hWrite
PIV443Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].MinsSCH - Scheduller - Thursday - 2 - Mins (0 - 59)min.Write
PIV444Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[1].UnitStatusSCH - Scheduller - Thursday - 2 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV56Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].EnabledSCH - Scheduller - Thursday - 3 - EnabledWrite0=OFF; 1=ON
BV57Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].Flag_EnabledSCH - Scheduller - Thursday - 3 - Flag_EnabledWrite
PIV445Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].HoursSCH - Scheduller - Thursday - 3 - Hours (0 - 23)hWrite
PIV446Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].MinsSCH - Scheduller - Thursday - 3 - Mins (0 - 59)min.Write
PIV447Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[2].UnitStatusSCH - Scheduller - Thursday - 3 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV58Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].EnabledSCH - Scheduller - Thursday - 4 - EnabledWrite0=OFF; 1=ON
BV59Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].Flag_EnabledSCH - Scheduller - Thursday - 4 - Flag_EnabledWrite
PIV448Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].HoursSCH - Scheduller - Thursday - 4 - Hours (0 - 23)hWrite
PIV449Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].MinsSCH - Scheduller - Thursday - 4 - Mins (0 - 59)min.Write
PIV450Scheduler_OnOffUnit.Scheduler_1.DaysSched[3].EVENT[3].UnitStatusSCH - Scheduller - Thursday - 4 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV60Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].EnabledSCH - Scheduller - Friday - 1 - EnabledWrite0=OFF; 1=ON
BV61Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].Flag_EnabledSCH - Scheduller - Friday - 1 - Flag_EnabledWrite
PIV451Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].HoursSCH - Scheduller - Friday - 1 - Hours (0 - 23)hWrite
PIV452Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].MinsSCH - Scheduller - Friday - 1 - Mins (0 - 59)min.Write
PIV453Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[0].UnitStatusSCH - Scheduller - Friday - 1 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV62Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].EnabledSCH - Scheduller - Friday - 2 - EnabledWrite0=OFF; 1=ON
BV63Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].Flag_EnabledSCH - Scheduller - Friday - 2 - Flag_EnabledWrite
PIV454Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].HoursSCH - Scheduller - Friday - 2 - Hours (0 - 23)hWrite
PIV455Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].MinsSCH - Scheduller - Friday - 2 - Mins (0 - 59)min.Write
PIV456Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[1].UnitStatusSCH - Scheduller - Friday - 2 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV64Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].EnabledSCH - Scheduller - Friday - 3 - EnabledWrite0=OFF; 1=ON
BV65Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].Flag_EnabledSCH - Scheduller - Friday - 3 - Flag_EnabledWrite
PIV457Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].HoursSCH - Scheduller - Friday - 3 - Hours (0 - 23)hWrite
PIV458Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].MinsSCH - Scheduller - Friday - 3 - Mins (0 - 59)min.Write
PIV459Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[2].UnitStatusSCH - Scheduller - Friday - 3 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV66Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].EnabledSCH - Scheduller - Friday - 4 - EnabledWrite0=OFF; 1=ON
BV67Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].Flag_EnabledSCH - Scheduller - Friday - 4 - Flag_EnabledWrite
PIV460Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].HoursSCH - Scheduller - Friday - 4 - Hours (0 - 23)hWrite
PIV461Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].MinsSCH - Scheduller - Friday - 4 - Mins (0 - 59)min.Write
PIV462Scheduler_OnOffUnit.Scheduler_1.DaysSched[4].EVENT[3].UnitStatusSCH - Scheduller - Friday - 4 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV68Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].EnabledSCH - Scheduller - Saturday - 1 - EnabledWrite0=OFF; 1=ON
BV69Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].Flag_EnabledSCH - Scheduller - Saturday - 1 - Flag_EnabledWrite
PIV463Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].HoursSCH - Scheduller - Saturday - 1 - Hours (0 - 23)hWrite
PIV464Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].MinsSCH - Scheduller - Saturday - 1 - Mins (0 - 59)min.Write
PIV465Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[0].UnitStatusSCH - Scheduller - Saturday - 1 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV70Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].EnabledSCH - Scheduller - Saturday - 2 - EnabledWrite0=OFF; 1=ON
BV71Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].Flag_EnabledSCH - Scheduller - Saturday - 2 - Flag_EnabledWrite
PIV466Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].HoursSCH - Scheduller - Saturday - 2 - Hours (0 - 23)hWrite
PIV467Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].MinsSCH - Scheduller - Saturday - 2 - Mins (0 - 59)min.Write
PIV468Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[1].UnitStatusSCH - Scheduller - Saturday - 2 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV72Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].EnabledSCH - Scheduller - Saturday - 3 - EnabledWrite0=OFF; 1=ON
BV73Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].Flag_EnabledSCH - Scheduller - Saturday - 3 - Flag_EnabledWrite
PIV469Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].HoursSCH - Scheduller - Saturday - 3 - Hours (0 - 23)hWrite
PIV470Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].MinsSCH - Scheduller - Saturday - 3 - Mins (0 - 59)min.Write
PIV471Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[2].UnitStatusSCH - Scheduller - Saturday - 3 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV74Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].EnabledSCH - Scheduller - Saturday - 4 - EnabledWrite0=OFF; 1=ON
BV75Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].Flag_EnabledSCH - Scheduller - Saturday - 4 - Flag_EnabledWrite
PIV472Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].HoursSCH - Scheduller - Saturday - 4 - Hours (0 - 23)hWrite
PIV473Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].MinsSCH - Scheduller - Saturday - 4 - Mins (0 - 59)min.Write
PIV474Scheduler_OnOffUnit.Scheduler_1.DaysSched[5].EVENT[3].UnitStatusSCH - Scheduller - Saturday - 4 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV76Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].EnabledSCH - Scheduller - Sunday - 1 - EnabledWrite0=OFF; 1=ON
BV77Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].Flag_EnabledSCH - Scheduller - Sunday - 1 - Flag_EnabledWrite
PIV475Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].HoursSCH - Scheduller - Sunday - 1 - Hours (0 - 23)hWrite
PIV476Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].MinsSCH - Scheduller - Sunday - 1 - Mins (0 - 59)min.Write
PIV477Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[0].UnitStatusSCH - Scheduller - Sunday - 1 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV78Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].EnabledSCH - Scheduller - Sunday - 2 - EnabledWrite0=OFF; 1=ON
BV79Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].Flag_EnabledSCH - Scheduller - Sunday - 2 - Flag_EnabledWrite
PIV478Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].HoursSCH - Scheduller - Sunday - 2 - Hours (0 - 23)hWrite
PIV479Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].MinsSCH - Scheduller - Sunday - 2 - Mins (0 - 59)min.Write
PIV480Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[1].UnitStatusSCH - Scheduller - Sunday - 2 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV80Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].EnabledSCH - Scheduller - Sunday - 3 - EnabledWrite0=OFF; 1=ON
BV81Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].Flag_EnabledSCH - Scheduller - Sunday - 3 - Flag_EnabledWrite
PIV481Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].HoursSCH - Scheduller - Sunday - 3 - Hours (0 - 23)hWrite
PIV482Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].MinsSCH - Scheduller - Sunday - 3 - Mins (0 - 59)min.Write
PIV483Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[2].UnitStatusSCH - Scheduller - Sunday - 3 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV82Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].EnabledSCH - Scheduller - Sunday - 4 - EnabledWrite0=OFF; 1=ON
BV83Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].Flag_EnabledSCH - Scheduller - Sunday - 4 - Flag_EnabledWrite
PIV484Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].HoursSCH - Scheduller - Sunday - 4 - Hours (0 - 23)hWrite
PIV485Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].MinsSCH - Scheduller - Sunday - 4 - Mins (0 - 59)min.Write
PIV486Scheduler_OnOffUnit.Scheduler_1.DaysSched[6].EVENT[3].UnitStatusSCH - Scheduller - Sunday - 4 - UnitStatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
PIV487Scheduler_OnOffUnit.Scheduler_1.EnDayCopySCH - Scheduller - Time Band - Enable Copy to DayWrite0=NO; 1=YES
PIV488Scheduler_OnOffUnit.Scheduler_1.SaveDataSCH - Scheduller - Time Band - Save DataWrite0=NO; 1=YES
BV84Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].EnabledSCH - Scheduller - Special Days 1 - EnabledWrite0=OFF; 1=ON
PIV489Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].SpecialDaySCH - Scheduller - Special Days 1 - Day (1 - 31)Write
PIV490Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].SpecialMonthSCH - Scheduller - Special Days 1 - Month (1 - 12)Write
PIV491Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[0].UnitStatusSCH - Scheduller - Special Days 1 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV85Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].EnabledSCH - Scheduller - Special Days 2 - EnabledWrite0=OFF; 1=ON
PIV492Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].SpecialDaySCH - Scheduller - Special Days 2 - Day (1 - 31)Write
PIV493Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].SpecialMonthSCH - Scheduller - Special Days 2 - Month (1 - 12)Write
PIV494Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[1].UnitStatusSCH - Scheduller - Special Days 2 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV86Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].EnabledSCH - Scheduller - Special Days 3 - EnabledWrite0=OFF; 1=ON
PIV495Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].SpecialDaySCH - Scheduller - Special Days 3 - Day (1 - 31)Write
PIV496Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].SpecialMonthSCH - Scheduller - Special Days 3 - Month (1 - 12)Write
PIV497Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[2].UnitStatusSCH - Scheduller - Special Days 3 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV87Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].EnabledSCH - Scheduller - Special Days 4 - EnabledWrite0=OFF; 1=ON
PIV498Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].SpecialDaySCH - Scheduller - Special Days 4 - Day (1 - 31)Write
PIV499Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].SpecialMonthSCH - Scheduller - Special Days 4 - Month (1 - 12)Write
PIV500Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[3].UnitStatusSCH - Scheduller - Special Days 4 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV88Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].EnabledSCH - Scheduller - Special Days 5 - EnabledWrite0=OFF; 1=ON
PIV501Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].SpecialDaySCH - Scheduller - Special Days 5 - Day (1 - 31)Write
PIV502Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].SpecialMonthSCH - Scheduller - Special Days 5 - Month (1 - 12)Write
PIV503Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[4].UnitStatusSCH - Scheduller - Special Days 5 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV89Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].EnabledSCH - Scheduller - Special Days 6 - EnabledWrite0=OFF; 1=ON
PIV504Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].SpecialDaySCH - Scheduller - Special Days 6 - Day (1 - 31)Write
PIV505Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].SpecialMonthSCH - Scheduller - Special Days 6 - Month (1 - 12)Write
PIV506Scheduler_OnOffUnit.Scheduler_1.SpecDaysSched[5].UnitStatusSCH - Scheduller - Special Days 6 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
BV90Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].EnabledSCH - Scheduller - Time Band 1 - EnabledWrite0=OFF; 1=ON
PIV507Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].HoursSCH - Scheduller - Time Band 1 - Hours (0 - 23)hWrite
PIV508Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].MinsSCH - Scheduller - Time Band 1 - Minute (0 - 59)min.Write
PIV509Scheduler_OnOffUnit.Scheduler_1.Event_Msk[0].UnitStatusSCH - Scheduller - Time Band 1 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT
BV91Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].EnabledSCH - Scheduller - Time Band 2 - EnabledWrite0=OFF; 1=ON
PIV510Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].HoursSCH - Scheduller - Time Band 2 - Hours (0 - 23)hWrite
PIV511Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].MinsSCH - Scheduller - Time Band 2 - Minute (0 - 59)min.Write
PIV512Scheduler_OnOffUnit.Scheduler_1.Event_Msk[1].UnitStatusSCH - Scheduller - Time Band 2 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT
BV92Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].EnabledSCH - Scheduller - Time Band 3 - EnabledWrite0=OFF; 1=ON
PIV513Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].HoursSCH - Scheduller - Time Band 3 - Hours (0 - 23)hWrite
PIV514Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].MinsSCH - Scheduller - Time Band 3 - Minute (0 - 59)min.Write
PIV515Scheduler_OnOffUnit.Scheduler_1.Event_Msk[2].UnitStatusSCH - Scheduller - Time Band 3 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT
BV93Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].EnabledSCH - Scheduller - Time Band 4 - EnabledWrite0=OFF; 1=ON
PIV516Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].HoursSCH - Scheduller - Time Band 4 - Hours (0 - 23)hWrite
PIV517Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].MinsSCH - Scheduller - Time Band 4 - Minute (0 - 59)min.Write
PIV518Scheduler_OnOffUnit.Scheduler_1.Event_Msk[3].UnitStatusSCH - Scheduller - Time Band 4 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT
BV94Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EnabledSCH - Scheduller - Periods 1 - EnabledWrite0=OFF; 1=ON
PIV519Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EndDaySCH - Scheduller - Periods 1 - End Day (1 - 31)Write
PIV520Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].EndMonthSCH - Scheduller - Periods 1 - End Month (1 - 12)Write
PIV521Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].StartDaySCH - Scheduller - Periods 1 - Start Day (1 - 31)Write
PIV522Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].StartMonthSCH - Scheduller - Periods 1 - Start Month (1 - 12)Write
PIV523Scheduler_OnOffUnit.Scheduler_1.VacationsSched[0].UnitStatusSCH - Scheduller - Periods 1 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT
BV95Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EnabledSCH - Scheduller - Periods 2 - EnabledWrite0=OFF; 1=ON
PIV524Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EndDaySCH - Scheduller - Periods 2 - End Day (1 - 31)Write
PIV525Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].EndMonthSCH - Scheduller - Periods 2 - End Month (1 - 12)Write
PIV526Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].StartDaySCH - Scheduller - Periods 2 - Start Day (1 - 31)Write
PIV527Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].StartMonthSCH - Scheduller - Periods 2 - Start Month (1 - 12)Write
PIV528Scheduler_OnOffUnit.Scheduler_1.VacationsSched[1].UnitStatusSCH - Scheduller - Periods 2 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=COMFORT
BV96Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EnabledSCH - Scheduller - Periods 3 - EnabledWrite0=OFF; 1=ON
PIV529Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EndDaySCH - Scheduller - Periods 3 - End Day (1 - 31)Write
PIV530Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].EndMonthSCH - Scheduller - Periods 3 - End Month (1 - 12)Write
PIV531Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].StartDaySCH - Scheduller - Periods 3 - Start Day (1 - 31)Write
PIV532Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].StartMonthSCH - Scheduller - Periods 3 - Start Month (1 - 12)Write
PIV533Scheduler_OnOffUnit.Scheduler_1.VacationsSched[2].UnitStatusSCH - Scheduller - Periods 3 - Unit StatusWrite0=OFF; 1=ECONOMY; 2=OPTIMAL; 3=PRE-COMFORT; 4=COMFORT
PIV534SetTypSchedSP - WorkMode - ActualRead
PIV535TypSchedulerSCH - Scheduller - TypeWrite0=NONE; 1=BOARD; 2=HMI
BV97SchedActiveSCH - Scheduller - ActiveRead0=NO; 1=YES
PIV536CurrUnitStatusSCH - Scheduller - Actual mode from schedullerRead0=OFF; 1=ECO; 2=Optimal; 3=Comfort
BV98Al_ABB_ExhFan_1.TriggerAL - Alarm - Fan Return 1Read
BV99Al_ABB_ExhFan_10.TriggerAL - Alarm - Fan Return 10Read
BV100Al_ABB_ExhFan_2.TriggerAL - Alarm - Fan Return 2Read
BV101Al_ABB_ExhFan_3.TriggerAL - Alarm - Fan Return 3Read
BV102Al_ABB_ExhFan_4.TriggerAL - Alarm - Fan Return 4Read
BV103Al_ABB_ExhFan_5.TriggerAL - Alarm - Fan Return 5Read
BV104Al_ABB_ExhFan_6.TriggerAL - Alarm - Fan Return 6Read
BV105Al_ABB_ExhFan_7.TriggerAL - Alarm - Fan Return 7Read
BV106Al_ABB_ExhFan_8.TriggerAL - Alarm - Fan Return 8Read
BV107Al_ABB_ExhFan_9.TriggerAL - Alarm - Fan Return 9Read
BV108Al_ABB_Rotary.TriggerAL - Alarm - RotaryRead
BV109Al_ABB_SupFan_1.TriggerAL - Alarm - Fan Supply 1Read
BV110Al_ABB_SupFan_10.TriggerAL - Alarm - Fan Supply 10Read
BV111Al_ABB_SupFan_2.TriggerAL - Alarm - Fan Supply 2Read
BV112Al_ABB_SupFan_3.TriggerAL - Alarm - Fan Supply 3Read
BV113Al_ABB_SupFan_4.TriggerAL - Alarm - Fan Supply 4Read
BV114Al_ABB_SupFan_5.TriggerAL - Alarm - Fan Supply 5Read
BV115Al_ABB_SupFan_6.TriggerAL - Alarm - Fan Supply 6Read
BV116Al_ABB_SupFan_7.TriggerAL - Alarm - Fan Supply 7Read
BV117Al_ABB_SupFan_8.TriggerAL - Alarm - Fan Supply 8Read
BV118Al_ABB_SupFan_9.TriggerAL - Alarm - Fan Supply 9Read
BV119Al_AFreezeDIN.TriggerAL - Alarm - Antifreeze - Digital InputRead
BV120Al_AFreezePRB.TriggerAL - Alarm - Antifreeze - Back Water TemperatureRead
BV121Al_AFreezePreHeatPRB.TriggerAL - Alarm - Antifreeze - PreHeat Back Water TemperatureRead
BV122Al_AfterPreHeatCoilTempPrb.TriggerAL - Alarm - Probe - After preheating coil temperatureRead
BV123Al_BMS_Offline.TriggerAL - Alarm - BMS - OfflineRead
BV124Al_CfgError_cpCOe.TriggerAL - Alarm - Module IO - cPCOE - Configuration errorRead
BV125Al_CircuitFault_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - Circuit FaultRead
BV126Al_CircuitFault_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - Circuit FaultRead
BV127Al_CircuitFault_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - Circuit FaultRead
BV128Al_CircuitFault_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - Circuit FaultRead
BV129Al_CircuitFault_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - Circuit FaultRead
BV130Al_CircuitFault_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - Circuit FaultRead
BV131Al_CircuitFault_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - Circuit FaultRead
BV132Al_CircuitFault_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - Circuit FaultRead
BV133Al_CircuitFault_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - Circuit FaultRead
BV134Al_CircuitFault_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - Circuit FaultRead
BV135Al_CircuitFault_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - Circuit FaultRead
BV136Al_CircuitFault_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - Circuit FaultRead
BV137Al_CircuitFault_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - Circuit FaultRead
BV138Al_CircuitFault_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - Circuit FaultRead
BV139Al_CircuitFault_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - Circuit FaultRead
BV140Al_CircuitFault_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - Circuit FaultRead
BV141Al_CircuitFault_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - Circuit FaultRead
BV142Al_CircuitFault_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - Circuit FaultRead
BV143Al_CircuitFault_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - Circuit FaultRead
BV144Al_CircuitFault_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - Circuit FaultRead
BV145Al_CommErr_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Communication ErrorRead
BV146Al_CommErr_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Communication ErrorRead
BV147Al_CommErr_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Communication ErrorRead
BV148Al_CommErr_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Communication ErrorRead
BV149Al_CommErr_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Communication ErrorRead
BV150Al_CommErr_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Communication ErrorRead
BV151Al_CommErr_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Communication ErrorRead
BV152Al_CommErr_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Communication ErrorRead
BV153Al_CommErr_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Communication ErrorRead
BV154Al_CommErr_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Communication ErrorRead
BV155Al_CommErr_Rotary.TriggerAL - Alarm - Rotary - CommUnitation ErrorRead
BV156Al_CommErr_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Communication ErrorRead
BV157Al_CommErr_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Communication ErrorRead
BV158Al_CommErr_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Communication ErrorRead
BV159Al_CommErr_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Communication ErrorRead
BV160Al_CommErr_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Communication ErrorRead
BV161Al_CommErr_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Communication ErrorRead
BV162Al_CommErr_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Communication ErrorRead
BV163Al_CommErr_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Communication ErrorRead
BV164Al_CommErr_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Communication ErrorRead
BV165Al_CommErr_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Communication ErrorRead
BV166Al_Cool.TriggerAL - Alarm - Cooling - Device AlarmRead
BV167Al_CoolFanFault_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Cooling Fan FaultRead
BV168Al_CoolFanFault_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Cooling Fan FaultRead
BV169Al_CoolFanFault_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Cooling Fan FaultRead
BV170Al_CoolFanFault_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Cooling Fan FaultRead
BV171Al_CoolFanFault_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Cooling Fan FaultRead
BV172Al_CoolFanFault_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Cooling Fan FaultRead
BV173Al_CoolFanFault_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Cooling Fan FaultRead
BV174Al_CoolFanFault_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Cooling Fan FaultRead
BV175Al_CoolFanFault_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Cooling Fan FaultRead
BV176Al_CoolFanFault_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Cooling Fan FaultRead
BV177Al_CoolFanFault_Rotary.TriggerAL - Alarm - Rotary - Cooling Fan FaultRead
BV178Al_CoolFanFault_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Cooling Fan FaultRead
BV179Al_CoolFanFault_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Cooling Fan FaultRead
BV180Al_CoolFanFault_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Cooling Fan FaultRead
BV181Al_CoolFanFault_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Cooling Fan FaultRead
BV182Al_CoolFanFault_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Cooling Fan FaultRead
BV183Al_CoolFanFault_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Cooling Fan FaultRead
BV184Al_CoolFanFault_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Cooling Fan FaultRead
BV185Al_CoolFanFault_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Cooling Fan FaultRead
BV186Al_CoolFanFault_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Cooling Fan FaultRead
BV187Al_CoolFanFault_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Cooling Fan FaultRead
BV188Al_CutOff_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - CutOffRead
BV189Al_CutOff_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - CutOffRead
BV190Al_CutOff_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - CutOffRead
BV191Al_CutOff_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - CutOffRead
BV192Al_CutOff_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - CutOffRead
BV193Al_CutOff_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - CutOffRead
BV194Al_CutOff_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - CutOffRead
BV195Al_CutOff_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - CutOffRead
BV196Al_CutOff_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - CutOffRead
BV197Al_CutOff_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - CutOffRead
BV198Al_CutOff_Rotary.TriggerAL - Alarm - Rotary - CutOffRead
BV199Al_CutOff_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - CutOffRead
BV200Al_CutOff_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - CutOffRead
BV201Al_CutOff_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - CutOffRead
BV202Al_CutOff_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - CutOffRead
BV203Al_CutOff_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - CutOffRead
BV204Al_CutOff_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - CutOffRead
BV205Al_CutOff_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - CutOffRead
BV206Al_CutOff_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - CutOffRead
BV207Al_CutOff_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - CutOffRead
BV208Al_CutOff_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - CutOffRead
BV209Al_DC_Ovld_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - DC Over loadRead
BV210Al_DC_Ovld_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - DC Over loadRead
BV211Al_DC_Ovld_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - DC Over loadRead
BV212Al_DC_Ovld_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - DC Over loadRead
BV213Al_DC_Ovld_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - DC Over loadRead
BV214Al_DC_Ovld_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - DC Over loadRead
BV215Al_DC_Ovld_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - DC Over loadRead
BV216Al_DC_Ovld_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - DC Over loadRead
BV217Al_DC_Ovld_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - DC Over loadRead
BV218Al_DC_Ovld_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - DC Over loadRead
BV219Al_DC_Ovld_Rotary.TriggerAL - Alarm - Rotary - DC OverloadRead
BV220Al_DC_Ovld_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - DC Over loadRead
BV221Al_DC_Ovld_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - DC Over loadRead
BV222Al_DC_Ovld_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - DC Over loadRead
BV223Al_DC_Ovld_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - DC Over loadRead
BV224Al_DC_Ovld_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - DC Over loadRead
BV225Al_DC_Ovld_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - DC Over loadRead
BV226Al_DC_Ovld_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - DC Over loadRead
BV227Al_DC_Ovld_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - DC Over loadRead
BV228Al_DC_Ovld_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - DC Over loadRead
BV229Al_DC_Ovld_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - DC Over loadRead
BV230Al_ElectTherm_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Electric ThermalRead
BV231Al_ElectTherm_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Electric ThermalRead
BV232Al_ElectTherm_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Electric ThermalRead
BV233Al_ElectTherm_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Electric ThermalRead
BV234Al_ElectTherm_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Electric ThermalRead
BV235Al_ElectTherm_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Electric ThermalRead
BV236Al_ElectTherm_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Electric ThermalRead
BV237Al_ElectTherm_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Electric ThermalRead
BV238Al_ElectTherm_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Electric ThermalRead
BV239Al_ElectTherm_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Electric ThermalRead
BV240Al_ElectTherm_Rotary.TriggerAL - Alarm - Rotary - Electric ThermalRead
BV241Al_ElectTherm_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Electric ThermalRead
BV242Al_ElectTherm_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Electric ThermalRead
BV243Al_ElectTherm_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Electric ThermalRead
BV244Al_ElectTherm_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Electric ThermalRead
BV245Al_ElectTherm_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Electric ThermalRead
BV246Al_ElectTherm_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Electric ThermalRead
BV247Al_ElectTherm_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Electric ThermalRead
BV248Al_ElectTherm_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Electric ThermalRead
BV249Al_ElectTherm_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Electric ThermalRead
BV250Al_ElectTherm_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Electric ThermalRead
BV251Al_Err_retain_write.TriggerAL - Alarm - Error retain writeRead
BV252Al_ExhTempPrb.TriggerAL - Alarm - Probe - Temperature ExhaustRead
BV253Al_ExtFaultA_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - External Fault ARead
BV254Al_ExtFaultA_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - External Fault ARead
BV255Al_ExtFaultA_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - External Fault ARead
BV256Al_ExtFaultA_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - External Fault ARead
BV257Al_ExtFaultA_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - External Fault ARead
BV258Al_ExtFaultA_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - External Fault ARead
BV259Al_ExtFaultA_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - External Fault ARead
BV260Al_ExtFaultA_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - External Fault ARead
BV261Al_ExtFaultA_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - External Fault ARead
BV262Al_ExtFaultA_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - External Fault ARead
BV263Al_ExtFaultA_Rotary.TriggerAL - Alarm - Rotary - External Fault ARead
BV264Al_ExtFaultA_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - External Fault ARead
BV265Al_ExtFaultA_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - External Fault ARead
BV266Al_ExtFaultA_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - External Fault ARead
BV267Al_ExtFaultA_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - External Fault ARead
BV268Al_ExtFaultA_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - External Fault ARead
BV269Al_ExtFaultA_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - External Fault ARead
BV270Al_ExtFaultA_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - External Fault ARead
BV271Al_ExtFaultA_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - External Fault ARead
BV272Al_ExtFaultA_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - External Fault ARead
BV273Al_ExtFaultA_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - External Fault ARead
BV274Al_ExtFaultB_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - External Fault BRead
BV275Al_ExtFaultB_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - External Fault BRead
BV276Al_ExtFaultB_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - External Fault BRead
BV277Al_ExtFaultB_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - External Fault BRead
BV278Al_ExtFaultB_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - External Fault BRead
BV279Al_ExtFaultB_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - External Fault BRead
BV280Al_ExtFaultB_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - External Fault BRead
BV281Al_ExtFaultB_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - External Fault BRead
BV282Al_ExtFaultB_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - External Fault BRead
BV283Al_ExtFaultB_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - External Fault BRead
BV284Al_ExtFaultB_Rotary.TriggerAL - Alarm - Rotary - External Fault BRead
BV285Al_ExtFaultB_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - External Fault BRead
BV286Al_ExtFaultB_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - External Fault BRead
BV287Al_ExtFaultB_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - External Fault BRead
BV288Al_ExtFaultB_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - External Fault BRead
BV289Al_ExtFaultB_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - External Fault BRead
BV290Al_ExtFaultB_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - External Fault BRead
BV291Al_ExtFaultB_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - External Fault BRead
BV292Al_ExtFaultB_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - External Fault BRead
BV293Al_ExtFaultB_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - External Fault BRead
BV294Al_ExtFaultB_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - External Fault BRead
BV295Al_ExtTempPrb.TriggerAL - Alarm - Probe - Temperature ExternalRead
BV296Al_Fire.TriggerAL - Alarm - FireRead
BV297Al_FireExh.TriggerAL - Alarm - Fire - Return TemperatureRead
BV298Al_GroundFault_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Ground FaultRead
BV299Al_GroundFault_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Ground FaultRead
BV300Al_GroundFault_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Ground FaultRead
BV301Al_GroundFault_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Ground FaultRead
BV302Al_GroundFault_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Ground FaultRead
BV303Al_GroundFault_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Ground FaultRead
BV304Al_GroundFault_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Ground FaultRead
BV305Al_GroundFault_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Ground FaultRead
BV306Al_GroundFault_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Ground FaultRead
BV307Al_GroundFault_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Ground FaultRead
BV308Al_GroundFault_Rotary.TriggerAL - Alarm - Rotary - Ground FaultRead
BV309Al_GroundFault_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Ground FaultRead
BV310Al_GroundFault_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Ground FaultRead
BV311Al_GroundFault_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Ground FaultRead
BV312Al_GroundFault_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Ground FaultRead
BV313Al_GroundFault_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Ground FaultRead
BV314Al_GroundFault_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Ground FaultRead
BV315Al_GroundFault_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Ground FaultRead
BV316Al_GroundFault_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Ground FaultRead
BV317Al_GroundFault_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Ground FaultRead
BV318Al_GroundFault_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Ground FaultRead
BV319Al_Heat.TriggerAL - Alarm - Heating - Device AlarmRead
BV320Al_HeatCoilTempPrb.TriggerAL - Alarm - Probe - Temperature Water Heating coilRead
BV321Al_HeatExchgWorkHrsWarn.TriggerAL - Alarm - HeatExchanger - HeatExchanger Works Hour WarningRead
BV322Al_HeatSink_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - HeatSinkRead
BV323Al_HeatSink_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - HeatSinkRead
BV324Al_HeatSink_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - HeatSinkRead
BV325Al_HeatSink_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - HeatSinkRead
BV326Al_HeatSink_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - HeatSinkRead
BV327Al_HeatSink_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - HeatSinkRead
BV328Al_HeatSink_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - HeatSinkRead
BV329Al_HeatSink_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - HeatSinkRead
BV330Al_HeatSink_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - HeatSinkRead
BV331Al_HeatSink_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - HeatSinkRead
BV332Al_HeatSink_Rotary.TriggerAL - Alarm - Rotary - HeatSinkRead
BV333Al_HeatSink_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - HeatSinkRead
BV334Al_HeatSink_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - HeatSinkRead
BV335Al_HeatSink_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - HeatSinkRead
BV336Al_HeatSink_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - HeatSinkRead
BV337Al_HeatSink_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - HeatSinkRead
BV338Al_HeatSink_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - HeatSinkRead
BV339Al_HeatSink_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - HeatSinkRead
BV340Al_HeatSink_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - HeatSinkRead
BV341Al_HeatSink_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - HeatSinkRead
BV342Al_HeatSink_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - HeatSinkRead
BV343AL_Hot_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - HotRead
BV344AL_Hot_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - HotRead
BV345AL_Hot_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - HotRead
BV346AL_Hot_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - HotRead
BV347AL_Hot_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - HotRead
BV348AL_Hot_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - HotRead
BV349AL_Hot_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - HotRead
BV350AL_Hot_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - HotRead
BV351AL_Hot_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - HotRead
BV352AL_Hot_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - HotRead
BV353AL_Hot_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - HotRead
BV354AL_Hot_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - HotRead
BV355AL_Hot_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - HotRead
BV356AL_Hot_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - HotRead
BV357AL_Hot_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - HotRead
BV358AL_Hot_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - HotRead
BV359AL_Hot_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - HotRead
BV360AL_Hot_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - HotRead
BV361AL_Hot_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - HotRead
BV362AL_Hot_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - HotRead
BV363Al_Hum.TriggerAL - Alarm - HumidifierRead
BV364Al_HumWorkHrsWarn.TriggerAL - Alarm - Humidity - Works Hour WarningRead
BV365Al_HW_Fault_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Hardware FaultRead
BV366Al_HW_Fault_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Hardware FaultRead
BV367Al_HW_Fault_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Hardware FaultRead
BV368Al_HW_Fault_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Hardware FaultRead
BV369Al_HW_Fault_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Hardware FaultRead
BV370Al_HW_Fault_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Hardware FaultRead
BV371Al_HW_Fault_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Hardware FaultRead
BV372Al_HW_Fault_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Hardware FaultRead
BV373Al_HW_Fault_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Hardware FaultRead
BV374Al_HW_Fault_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Hardware FaultRead
BV375Al_HW_Fault_Rotary.TriggerAL - Alarm - Rotary - Hardware FaultRead
BV376Al_HW_Fault_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Hardware FaultRead
BV377Al_HW_Fault_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Hardware FaultRead
BV378Al_HW_Fault_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Hardware FaultRead
BV379Al_HW_Fault_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Hardware FaultRead
BV380Al_HW_Fault_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Hardware FaultRead
BV381Al_HW_Fault_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Hardware FaultRead
BV382Al_HW_Fault_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Hardware FaultRead
BV383Al_HW_Fault_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Hardware FaultRead
BV384Al_HW_Fault_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Hardware FaultRead
BV385Al_HW_Fault_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Hardware FaultRead
BV386Al_I2RIGBTFault_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - I2RIGBT FaultRead
BV387Al_I2RIGBTFault_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - I2RIGBT FaultRead
BV388Al_I2RIGBTFault_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - I2RIGBT FaultRead
BV389Al_I2RIGBTFault_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - I2RIGBT FaultRead
BV390Al_I2RIGBTFault_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - I2RIGBT FaultRead
BV391Al_I2RIGBTFault_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - I2RIGBT FaultRead
BV392Al_I2RIGBTFault_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - I2RIGBT FaultRead
BV393Al_I2RIGBTFault_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - I2RIGBT FaultRead
BV394Al_I2RIGBTFault_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - I2RIGBT FaultRead
BV395Al_I2RIGBTFault_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - I2RIGBT FaultRead
BV396Al_I2RIGBTFault_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - I2RIGBT FaultRead
BV397Al_I2RIGBTFault_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - I2RIGBT FaultRead
BV398Al_I2RIGBTFault_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - I2RIGBT FaultRead
BV399Al_I2RIGBTFault_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - I2RIGBT FaultRead
BV400Al_I2RIGBTFault_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - I2RIGBT FaultRead
BV401Al_I2RIGBTFault_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - I2RIGBT FaultRead
BV402Al_I2RIGBTFault_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - I2RIGBT FaultRead
BV403Al_I2RIGBTFault_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - I2RIGBT FaultRead
BV404Al_I2RIGBTFault_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - I2RIGBT FaultRead
BV405Al_I2RIGBTFault_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - I2RIGBT FaultRead
BV406AL_IGBTOvercurrent_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - IGBT Over currentRead
BV407AL_IGBTOvercurrent_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - IGBT Over currentRead
BV408AL_IGBTOvercurrent_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - IGBT Over currentRead
BV409AL_IGBTOvercurrent_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - IGBT Over currentRead
BV410AL_IGBTOvercurrent_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - IGBT Over currentRead
BV411AL_IGBTOvercurrent_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - IGBT Over currentRead
BV412AL_IGBTOvercurrent_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - IGBT Over currentRead
BV413AL_IGBTOvercurrent_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - IGBT Over currentRead
BV414AL_IGBTOvercurrent_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - IGBT Over currentRead
BV415AL_IGBTOvercurrent_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - IGBT Over currentRead
BV416AL_IGBTOvercurrent_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - IGBT Over currentRead
BV417AL_IGBTOvercurrent_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - IGBT Over currentRead
BV418AL_IGBTOvercurrent_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - IGBT Over currentRead
BV419AL_IGBTOvercurrent_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - IGBT Over currentRead
BV420AL_IGBTOvercurrent_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - IGBT Over currentRead
BV421AL_IGBTOvercurrent_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - IGBT Over currentRead
BV422AL_IGBTOvercurrent_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - IGBT Over currentRead
BV423AL_IGBTOvercurrent_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - IGBT Over currentRead
BV424AL_IGBTOvercurrent_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - IGBT Over currentRead
BV425AL_IGBTOvercurrent_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - IGBT Over currentRead
BV426Al_InvOverheat_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Inverter Over HeatRead
BV427Al_InvOverheat_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Inverter Over HeatRead
BV428Al_InvOverheat_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Inverter Over HeatRead
BV429Al_InvOverheat_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Inverter Over HeatRead
BV430Al_InvOverheat_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Inverter Over HeatRead
BV431Al_InvOverheat_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Inverter Over HeatRead
BV432Al_InvOverheat_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Inverter Over HeatRead
BV433Al_InvOverheat_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Inverter Over HeatRead
BV434Al_InvOverheat_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Inverter Over HeatRead
BV435Al_InvOverheat_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Inverter Over HeatRead
BV436Al_InvOverheat_Rotary.TriggerAL - Alarm - Rotary - Inverter OverHeatRead
BV437Al_InvOverheat_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Inverter Over HeatRead
BV438Al_InvOverheat_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Inverter Over HeatRead
BV439Al_InvOverheat_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Inverter Over HeatRead
BV440Al_InvOverheat_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Inverter Over HeatRead
BV441Al_InvOverheat_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Inverter Over HeatRead
BV442Al_InvOverheat_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Inverter Over HeatRead
BV443Al_InvOverheat_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Inverter Over HeatRead
BV444Al_InvOverheat_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Inverter Over HeatRead
BV445Al_InvOverheat_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Inverter Over HeatRead
BV446Al_InvOverheat_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Inverter Over HeatRead
BV447Al_InvOvld_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Inverter Over LoadRead
BV448Al_InvOvld_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Inverter Over LoadRead
BV449Al_InvOvld_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Inverter Over LoadRead
BV450Al_InvOvld_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Inverter Over LoadRead
BV451Al_InvOvld_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Inverter Over LoadRead
BV452Al_InvOvld_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Inverter Over LoadRead
BV453Al_InvOvld_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Inverter Over LoadRead
BV454Al_InvOvld_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Inverter Over LoadRead
BV455Al_InvOvld_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Inverter Over LoadRead
BV456Al_InvOvld_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Inverter Over LoadRead
BV457Al_InvOvld_Rotary.TriggerAL - Alarm - Rotary - Inverter OverLoadRead
BV458Al_InvOvld_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Inverter Over LoadRead
BV459Al_InvOvld_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Inverter Over LoadRead
BV460Al_InvOvld_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Inverter Over LoadRead
BV461Al_InvOvld_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Inverter Over LoadRead
BV462Al_InvOvld_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Inverter Over LoadRead
BV463Al_InvOvld_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Inverter Over LoadRead
BV464Al_InvOvld_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Inverter Over LoadRead
BV465Al_InvOvld_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Inverter Over LoadRead
BV466Al_InvOvld_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Inverter Over LoadRead
BV467Al_InvOvld_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Inverter Over LoadRead
BV468Al_LowSupplyTemp.TriggerAL - Alarm - Probe - Low Supply TemperatureRead
BV469Al_LowVolt_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Low VoltageRead
BV470Al_LowVolt_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Low VoltageRead
BV471Al_LowVolt_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Low VoltageRead
BV472Al_LowVolt_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Low VoltageRead
BV473Al_LowVolt_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Low VoltageRead
BV474Al_LowVolt_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Low VoltageRead
BV475Al_LowVolt_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Low VoltageRead
BV476Al_LowVolt_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Low VoltageRead
BV477Al_LowVolt_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Low VoltageRead
BV478Al_LowVolt_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Low VoltageRead
BV479Al_LowVolt_Rotary.TriggerAL - Alarm - Rotary - Low VoltageRead
BV480Al_LowVolt_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Low VoltageRead
BV481Al_LowVolt_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Low VoltageRead
BV482Al_LowVolt_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Low VoltageRead
BV483Al_LowVolt_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Low VoltageRead
BV484Al_LowVolt_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Low VoltageRead
BV485Al_LowVolt_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Low VoltageRead
BV486Al_LowVolt_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Low VoltageRead
BV487Al_LowVolt_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Low VoltageRead
BV488Al_LowVolt_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Low VoltageRead
BV489Al_LowVolt_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Low VoltageRead
BV490Al_MB_AO1.TriggerAL - Alarm - Control Circuit - AO1Read
BV491Al_MB_AO1_AO4_PWM.TriggerAL - Alarm - Control Circuit - AO1_AO4_PWMRead
BV492Al_MB_AO2.TriggerAL - Alarm - Control Circuit - AO2Read
BV493Al_MB_AO3.TriggerAL - Alarm - Control Circuit - AO3Read
BV494Al_MB_AO4.TriggerAL - Alarm - Control Circuit - AO4Read
BV495Al_MB_Control_Supply.TriggerAL - Alarm - Control Circuit - Control_SupplyRead
BV496Al_MB_Control_Temp.TriggerAL - Alarm - Control Circuit - Control_TempRead
BV497Al_MB_Humidity.TriggerAL - Alarm - Control Circuit - HumidityRead
BV498Al_MB_Press_Fan_Return.TriggerAL - Alarm - Control Circuit - Press_Fan_ReturnRead
BV499Al_MB_Press_Fan_Supply.TriggerAL - Alarm - Control Circuit - Press_Fan_SupplyRead
BV500Al_MB_Press_Filter_Return.TriggerAL - Alarm - Control Circuit - Press_Filter_ReturnRead
BV501Al_MB_Press_Filter_Supply.TriggerAL - Alarm - Control Circuit - Press_Filter_SupplyRead
BV502Al_MB_Supply24.TriggerAL - Alarm - Control Circuit - Supply24Read
BV503Al_MB_Temp_Fan_Return.TriggerAL - Alarm - Control Circuit - Temp_Fan_ReturnRead
BV504Al_MB_Temp_Fan_Supply.TriggerAL - Alarm - Control Circuit - Temp_Fan_SupplyRead
BV505Al_MB_Temp_Filter_Return.TriggerAL - Alarm - Control Circuit - Temp_Filter_ReturnRead
BV506Al_MB_Temp_Filter_Supply.TriggerAL - Alarm - Control Circuit - Temp_Filter_SupplyRead
BV507Al_MB_Temperature.TriggerAL - Alarm - Control Circuit - TemperatureRead
BV508Al_MotorFault_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - Motor FaultRead
BV509Al_MotorFault_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - Motor FaultRead
BV510Al_MotorFault_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - Motor FaultRead
BV511Al_MotorFault_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - Motor FaultRead
BV512Al_MotorFault_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - Motor FaultRead
BV513Al_MotorFault_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - Motor FaultRead
BV514Al_MotorFault_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - Motor FaultRead
BV515Al_MotorFault_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - Motor FaultRead
BV516Al_MotorFault_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - Motor FaultRead
BV517Al_MotorFault_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - Motor FaultRead
BV518Al_MotorFault_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - Motor FaultRead
BV519Al_MotorFault_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - Motor FaultRead
BV520Al_MotorFault_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - Motor FaultRead
BV521Al_MotorFault_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - Motor FaultRead
BV522Al_MotorFault_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - Motor FaultRead
BV523Al_MotorFault_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - Motor FaultRead
BV524Al_MotorFault_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - Motor FaultRead
BV525Al_MotorFault_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - Motor FaultRead
BV526Al_MotorFault_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - Motor FaultRead
BV527Al_MotorOverheat_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Motor Over heatRead
BV528Al_MotorOverheat_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Motor Over heatRead
BV529Al_MotorOverheat_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Motor Over heatRead
BV530Al_MotorOverheat_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Motor Over heatRead
BV531Al_MotorOverheat_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Motor Over heatRead
BV532Al_MotorOverheat_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Motor Over heatRead
BV533Al_MotorOverheat_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Motor Over heatRead
BV534Al_MotorOverheat_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Motor Over heatRead
BV535Al_MotorOverheat_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Motor Over heatRead
BV536Al_MotorOverheat_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Motor Over heatRead
BV537Al_MotorOverheat_Rotary.TriggerAL - Alarm - Rotary - Motor OverheatRead
BV538Al_MotorOverheat_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Motor Over heatRead
BV539Al_MotorOverheat_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Motor Over heatRead
BV540Al_MotorOverheat_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Motor Over heatRead
BV541Al_MotorOverheat_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Motor Over heatRead
BV542Al_MotorOverheat_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Motor Over heatRead
BV543Al_MotorOverheat_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Motor Over heatRead
BV544Al_MotorOverheat_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Motor Over heatRead
BV545Al_MotorOverheat_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Motor Over heatRead
BV546Al_MotorOverheat_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Motor Over heatRead
BV547Al_MotorOverheat_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Motor Over heatRead
BV548Al_Offline_cpCOe.TriggerAL - Alarm - Module IO - cPCOE - OfflineRead
BV549Al_Offline_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - OfflineRead
BV550Al_Offline_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - OfflineRead
BV551Al_Offline_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - OfflineRead
BV552Al_Offline_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - OfflineRead
BV553Al_Offline_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - OfflineRead
BV554Al_Offline_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - OfflineRead
BV555Al_Offline_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - OfflineRead
BV556Al_Offline_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - OfflineRead
BV557Al_Offline_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - OfflineRead
BV558Al_Offline_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - OfflineRead
BV559Al_Offline_MainBoard.TriggerAL - Alarm - Control Circuit - OfflineRead
BV560Al_Offline_Rotary.TriggerAL - Alarm - Rotary - OfflineRead
BV561Al_Offline_SP_ExhHum.TriggerAL - Alarm - Probe - Return Humidity - OfflineRead
BV562Al_Offline_SP_ExhPress.TriggerAL - Alarm - Probe - Return Air Pressure - OfflineRead
BV563Al_Offline_SP_SupplyHum.TriggerAL - Alarm - Probe - Supply humidity - OfflineRead
BV564Al_Offline_SP_SupplyPress.TriggerAL - Alarm - Probe - Supply Air Pressure - OfflineRead
BV565Al_Offline_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - OfflineRead
BV566Al_Offline_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - OfflineRead
BV567Al_Offline_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - OfflineRead
BV568Al_Offline_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - OfflineRead
BV569Al_Offline_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - OfflineRead
BV570Al_Offline_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - OfflineRead
BV571Al_Offline_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - OfflineRead
BV572Al_Offline_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - OfflineRead
BV573Al_Offline_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - OfflineRead
BV574Al_Offline_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - OfflineRead
BV575Al_Offline_THTN_1.TriggerAL - Alarm - HMI Basic - OfflineRead
BV576Al_Option_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - OptionRead
BV577Al_Option_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - OptionRead
BV578Al_Option_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - OptionRead
BV579Al_Option_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - OptionRead
BV580Al_Option_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - OptionRead
BV581Al_Option_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - OptionRead
BV582Al_Option_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - OptionRead
BV583Al_Option_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - OptionRead
BV584Al_Option_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - OptionRead
BV585Al_Option_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - OptionRead
BV586Al_Option_Rotary.TriggerAL - Alarm - Rotary - OptionRead
BV587Al_Option_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - OptionRead
BV588Al_Option_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - OptionRead
BV589Al_Option_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - OptionRead
BV590Al_Option_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - OptionRead
BV591Al_Option_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - OptionRead
BV592Al_Option_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - OptionRead
BV593Al_Option_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - OptionRead
BV594Al_Option_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - OptionRead
BV595Al_Option_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - OptionRead
BV596Al_Option_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - OptionRead
BV597Al_Overcurrent_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Over CurrentRead
BV598Al_Overcurrent_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Over CurrentRead
BV599Al_Overcurrent_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Over CurrentRead
BV600Al_Overcurrent_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Over CurrentRead
BV601Al_Overcurrent_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Over CurrentRead
BV602Al_Overcurrent_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Over currentRead
BV603Al_Overcurrent_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Over CurrentRead
BV604Al_Overcurrent_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Over CurrentRead
BV605Al_Overcurrent_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Over CurrentRead
BV606Al_Overcurrent_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Over CurrentRead
BV607Al_Overcurrent_Rotary.TriggerAL - Alarm - Rotary - OverCurrentRead
BV608Al_Overcurrent_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Over currentRead
BV609Al_Overcurrent_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Over CurrentRead
BV610Al_Overcurrent_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Over CurrentRead
BV611Al_Overcurrent_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Over CurrentRead
BV612Al_Overcurrent_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Over CurrentRead
BV613Al_Overcurrent_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Over currentRead
BV614Al_Overcurrent_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Over CurrentRead
BV615Al_Overcurrent_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Over CurrentRead
BV616Al_Overcurrent_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Over CurrentRead
BV617Al_Overcurrent_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Over CurrentRead
BV618Al_OverVolt_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Over VoltageRead
BV619Al_OverVolt_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Over VoltageRead
BV620Al_OverVolt_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Over VoltageRead
BV621Al_OverVolt_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Over VoltageRead
BV622Al_OverVolt_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Over VoltageRead
BV623Al_OverVolt_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Over voltageRead
BV624Al_OverVolt_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Over VoltageRead
BV625Al_OverVolt_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Over VoltageRead
BV626Al_OverVolt_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Over VoltageRead
BV627Al_OverVolt_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Over VoltageRead
BV628Al_OverVolt_Rotary.TriggerAL - Alarm - Rotary - OverVoltageRead
BV629Al_OverVolt_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Over voltageRead
BV630Al_OverVolt_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Over VoltageRead
BV631Al_OverVolt_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Over VoltageRead
BV632Al_OverVolt_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Over VoltageRead
BV633Al_OverVolt_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Over VoltageRead
BV634Al_OverVolt_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Over voltageRead
BV635Al_OverVolt_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Over VoltageRead
BV636Al_OverVolt_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Over VoltageRead
BV637Al_OverVolt_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Over VoltageRead
BV638Al_OverVolt_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Over VoltageRead
BV639AL_Overvoltage_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - Over voltageRead
BV640AL_Overvoltage_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - Over voltageRead
BV641AL_Overvoltage_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - Over voltageRead
BV642AL_Overvoltage_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - Over voltageRead
BV643AL_Overvoltage_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - Over voltageRead
BV644AL_Overvoltage_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - Over voltageRead
BV645AL_Overvoltage_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - Over voltageRead
BV646AL_Overvoltage_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - Over voltageRead
BV647AL_Overvoltage_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - Over voltageRead
BV648AL_Overvoltage_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - Over voltageRead
BV649AL_Overvoltage_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - Over voltageRead
BV650AL_Overvoltage_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - Over voltageRead
BV651AL_Overvoltage_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - Over voltageRead
BV652AL_Overvoltage_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - Over voltageRead
BV653AL_Overvoltage_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - Over voltageRead
BV654AL_Overvoltage_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - Over voltageRead
BV655AL_Overvoltage_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - Over voltageRead
BV656AL_Overvoltage_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - Over voltageRead
BV657AL_Overvoltage_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - Over voltageRead
BV658AL_Overvoltage_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - Over voltageRead
BV659Al_Ovld_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Over LoadRead
BV660Al_Ovld_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Over LoadRead
BV661Al_Ovld_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Over LoadRead
BV662Al_Ovld_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Over LoadRead
BV663Al_Ovld_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Over LoadRead
BV664Al_Ovld_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Over loadRead
BV665Al_Ovld_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Over LoadRead
BV666Al_Ovld_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Over LoadRead
BV667Al_Ovld_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Over LoadRead
BV668Al_Ovld_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Over LoadRead
BV669Al_Ovld_Rotary.TriggerAL - Alarm - Rotary - OverLoadRead
BV670Al_Ovld_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Over loadRead
BV671Al_Ovld_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Over LoadRead
BV672Al_Ovld_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Over LoadRead
BV673Al_Ovld_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Over LoadRead
BV674Al_Ovld_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Over LoadRead
BV675Al_Ovld_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Over loadRead
BV676Al_Ovld_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Over LoadRead
BV677Al_Ovld_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Over LoadRead
BV678Al_Ovld_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Over LoadRead
BV679Al_Ovld_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Over LoadRead
BV680Al_ParamErr_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Parameters ErrorRead
BV681Al_ParamErr_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Parameters ErrorRead
BV682Al_ParamErr_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Parameters ErrorRead
BV683Al_ParamErr_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Parameters ErrorRead
BV684Al_ParamErr_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Parameters ErrorRead
BV685Al_ParamErr_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Parameter save ErrorRead
BV686Al_ParamErr_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Parameters ErrorRead
BV687Al_ParamErr_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Parameters ErrorRead
BV688Al_ParamErr_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Parameters ErrorRead
BV689Al_ParamErr_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Parameters ErrorRead
BV690Al_ParamErr_Rotary.TriggerAL - Alarm - Rotary - Parameters ErrorRead
BV691Al_ParamErr_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Parameter save ErrorRead
BV692Al_ParamErr_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Parameters ErrorRead
BV693Al_ParamErr_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Parameters ErrorRead
BV694Al_ParamErr_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Parameters ErrorRead
BV695Al_ParamErr_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Parameters ErrorRead
BV696Al_ParamErr_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Parameter save ErrorRead
BV697Al_ParamErr_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Parameters ErrorRead
BV698Al_ParamErr_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Parameters ErrorRead
BV699Al_ParamErr_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Parameters ErrorRead
BV700Al_ParamErr_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Parameters ErrorRead
BV701AL_ParametersCRC_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - Parameters CRCRead
BV702AL_ParametersCRC_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - Parameters CRCRead
BV703AL_ParametersCRC_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - Parameters CRCRead
BV704AL_ParametersCRC_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - Parameters CRCRead
BV705AL_ParametersCRC_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - Parameters CRCRead
BV706AL_ParametersCRC_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - Parameters CRCRead
BV707AL_ParametersCRC_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - Parameters CRCRead
BV708AL_ParametersCRC_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - Parameters CRCRead
BV709AL_ParametersCRC_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - Parameters CRCRead
BV710AL_ParametersCRC_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - Parameters CRCRead
BV711AL_ParametersCRC_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - Parameters CRCRead
BV712AL_ParametersCRC_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - Parameters CRCRead
BV713AL_ParametersCRC_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - Parameters CRCRead
BV714AL_ParametersCRC_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - Parameters CRCRead
BV715AL_ParametersCRC_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - Parameters CRCRead
BV716AL_ParametersCRC_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - Parameters CRCRead
BV717AL_ParametersCRC_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - Parameters CRCRead
BV718AL_ParametersCRC_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - Parameters CRCRead
BV719AL_ParametersCRC_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - Parameters CRCRead
BV720AL_ParametersCRC_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - Parameters CRCRead
BV721AL_PhaseLoss_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - Phase LossRead
BV722AL_PhaseLoss_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - Phase LossRead
BV723AL_PhaseLoss_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - Phase LossRead
BV724AL_PhaseLoss_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - Phase LossRead
BV725AL_PhaseLoss_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - Phase LossRead
BV726AL_PhaseLoss_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - Phase LossRead
BV727AL_PhaseLoss_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - Phase LossRead
BV728AL_PhaseLoss_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - Phase LossRead
BV729AL_PhaseLoss_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - Phase LossRead
BV730AL_PhaseLoss_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - Phase LossRead
BV731AL_PhaseLoss_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - Phase LossRead
BV732AL_PhaseLoss_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - Phase LossRead
BV733AL_PhaseLoss_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - Phase LossRead
BV734AL_PhaseLoss_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - Phase LossRead
BV735AL_PhaseLoss_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - Phase LossRead
BV736AL_PhaseLoss_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - Phase LossRead
BV737AL_PhaseLoss_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - Phase LossRead
BV738AL_PhaseLoss_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - Phase LossRead
BV739AL_PhaseLoss_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - Phase LossRead
BV740AL_PhaseLoss_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - Phase LossRead
BV741Al_PhLost_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Phase LostRead
BV742Al_PhLost_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Phase LostRead
BV743Al_PhLost_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Phase LostRead
BV744Al_PhLost_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Phase LostRead
BV745Al_PhLost_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Phase LostRead
BV746Al_PhLost_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Phase LostRead
BV747Al_PhLost_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Phase LostRead
BV748Al_PhLost_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Phase LostRead
BV749Al_PhLost_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Phase LostRead
BV750Al_PhLost_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Phase LostRead
BV751Al_PhLost_Rotary.TriggerAL - Alarm - Rotary - Phase LostRead
BV752Al_PhLost_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Phase LostRead
BV753Al_PhLost_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Phase LostRead
BV754Al_PhLost_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Phase LostRead
BV755Al_PhLost_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Phase LostRead
BV756Al_PhLost_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Phase LostRead
BV757Al_PhLost_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Phase LostRead
BV758Al_PhLost_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Phase LostRead
BV759Al_PhLost_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Phase LostRead
BV760Al_PhLost_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Phase LostRead
BV761Al_PhLost_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Phase LostRead
BV762Al_PhOpen_ExhFan_1.TriggerAL - Alarm - Fan Return 1 - Phase OpenRead
BV763Al_PhOpen_ExhFan_10.TriggerAL - Alarm - Fan Return 10 - Phase OpenRead
BV764Al_PhOpen_ExhFan_2.TriggerAL - Alarm - Fan Return 2 - Phase OpenRead
BV765Al_PhOpen_ExhFan_3.TriggerAL - Alarm - Fan Return 3 - Phase OpenRead
BV766Al_PhOpen_ExhFan_4.TriggerAL - Alarm - Fan Return 4 - Phase OpenRead
BV767Al_PhOpen_ExhFan_5.TriggerAL - Alarm - Fan Return 5 - Phase OpenRead
BV768Al_PhOpen_ExhFan_6.TriggerAL - Alarm - Fan Return 6 - Phase OpenRead
BV769Al_PhOpen_ExhFan_7.TriggerAL - Alarm - Fan Return 7 - Phase OpenRead
BV770Al_PhOpen_ExhFan_8.TriggerAL - Alarm - Fan Return 8 - Phase OpenRead
BV771Al_PhOpen_ExhFan_9.TriggerAL - Alarm - Fan Return 9 - Phase OpenRead
BV772Al_PhOpen_Rotary.TriggerAL - Alarm - Rotary - Phase OpenRead
BV773Al_PhOpen_SupFan_1.TriggerAL - Alarm - Fan Supply 1 - Phase OpenRead
BV774Al_PhOpen_SupFan_10.TriggerAL - Alarm - Fan Supply 10 - Phase OpenRead
BV775Al_PhOpen_SupFan_2.TriggerAL - Alarm - Fan Supply 2 - Phase OpenRead
BV776Al_PhOpen_SupFan_3.TriggerAL - Alarm - Fan Supply 3 - Phase OpenRead
BV777Al_PhOpen_SupFan_4.TriggerAL - Alarm - Fan Supply 4 - Phase OpenRead
BV778Al_PhOpen_SupFan_5.TriggerAL - Alarm - Fan Supply 5 - Phase OpenRead
BV779Al_PhOpen_SupFan_6.TriggerAL - Alarm - Fan Supply 6 - Phase OpenRead
BV780Al_PhOpen_SupFan_7.TriggerAL - Alarm - Fan Supply 7 - Phase OpenRead
BV781Al_PhOpen_SupFan_8.TriggerAL - Alarm - Fan Supply 8 - Phase OpenRead
BV782Al_PhOpen_SupFan_9.TriggerAL - Alarm - Fan Supply 9 - Phase OpenRead
BV783Al_PreHeatCoilTempPrb.TriggerAL - Alarm - Probe - Temperature Water PreHeating CoilRead
BV784Al_RDT_Fan.TriggerAL - Alarm - Fan GroupRead
BV785Al_RecSupplyTemp.TriggerAL - Alarm - Probe - Supply Recovery TemperatureRead
BV786Al_ReheatCoilWorkHrsWarn.TriggerAL - Alarm - ReHeatCoil - Works Hour WarningRead
BV787Al_retain.TriggerAL - Alarm - RetainRead
BV788Al_RetAir_CO2_Lev_Prb.TriggerAL - Alarm - Probe - CO2 Return Level ProbeRead
BV789Al_RetAirFlwSwWarn.TriggerAL - Alarm - Probe - Air Flow Return SW WarningRead
BV790Al_RetAirP_Prb.TriggerAL - Alarm - Probe - Pressure Return AirRead
BV791Al_RetFanWorkHrsWarn.TriggerAL - Alarm - Fan Return - Works Hour WarningRead
BV792Al_RetFilt.TriggerAL - Alarm - Filter - ReturnRead
BV793Al_RetTempPrb.TriggerAL - Alarm - Probe - Return TemperatureRead
BV794Al_SupplyAirFlwSwWarn.TriggerAL - Alarm - Probe - Supply Air Flow SW WarningRead
BV795Al_SupplyAirP_Prb.TriggerAL - Alarm - Probe - Supply Air PressureRead
BV796Al_SupplyFanWorkHrsWarn.TriggerAL - Alarm - Fan Supply - Works Hour WarningRead
BV797Al_SupplyFilt.TriggerAL - Alarm - Filter - SupplyRead
BV798Al_SupplyTempPrb.TriggerAL - Alarm - Probe - Supply TemperatureRead
BV799Al_SwPrototype.TriggerAL - Alarm - Software Version - PrototypeRead
BV800Al_ThTune_ClkBrd.TriggerAL - Alarm - HMI Basic - Clock BoardRead
BV801Al_ThTune_HumPrb.TriggerAL - Alarm - HMI Basic - Humidity ProbeRead
BV802Al_ThTune_TempPrb.TriggerAL - Alarm - HMI Basic - Temperature ProbeRead
BV803Al_TooHot_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - TooHotRead
BV804Al_TooHot_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - TooHotRead
BV805Al_TooHot_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - TooHotRead
BV806Al_TooHot_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - TooHotRead
BV807Al_TooHot_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - TooHotRead
BV808Al_TooHot_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - TooHotRead
BV809Al_TooHot_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - TooHotRead
BV810Al_TooHot_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - TooHotRead
BV811Al_TooHot_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - TooHotRead
BV812Al_TooHot_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - TooHotRead
BV813Al_TooHot_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - TooHotRead
BV814Al_TooHot_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - TooHotRead
BV815Al_TooHot_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - TooHotRead
BV816Al_TooHot_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - TooHotRead
BV817Al_TooHot_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - TooHotRead
BV818Al_TooHot_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - TooHotRead
BV819Al_TooHot_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - TooHotRead
BV820Al_TooHot_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - TooHotRead
BV821Al_TooHot_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - TooHotRead
BV822Al_TooHot_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - TooHotRead
BV823Al_Undervoltage_EC_ExhFan1.TriggerAL - Alarm - Fan Return 1 EC - UndervoltageRead
BV824Al_Undervoltage_EC_ExhFan10.TriggerAL - Alarm - Fan Return 10 EC - UndervoltageRead
BV825Al_Undervoltage_EC_ExhFan2.TriggerAL - Alarm - Fan Return 2 EC - UndervoltageRead
BV826Al_Undervoltage_EC_ExhFan3.TriggerAL - Alarm - Fan Return 3 EC - UndervoltageRead
BV827Al_Undervoltage_EC_ExhFan4.TriggerAL - Alarm - Fan Return 4 EC - UndervoltageRead
BV828Al_Undervoltage_EC_ExhFan5.TriggerAL - Alarm - Fan Return 5 EC - UndervoltageRead
BV829Al_Undervoltage_EC_ExhFan6.TriggerAL - Alarm - Fan Return 6 EC - UndervoltageRead
BV830Al_Undervoltage_EC_ExhFan7.TriggerAL - Alarm - Fan Return 7 EC - UndervoltageRead
BV831Al_Undervoltage_EC_ExhFan8.TriggerAL - Alarm - Fan Return 8 EC - UndervoltageRead
BV832Al_Undervoltage_EC_ExhFan9.TriggerAL - Alarm - Fan Return 9 EC - UndervoltageRead
BV833Al_Undervoltage_EC_SupFan1.TriggerAL - Alarm - Fan Supply 1 EC - UndervoltageRead
BV834Al_Undervoltage_EC_SupFan10.TriggerAL - Alarm - Fan Supply 10 EC - UndervoltageRead
BV835Al_Undervoltage_EC_SupFan2.TriggerAL - Alarm - Fan Supply 2 EC - UndervoltageRead
BV836Al_Undervoltage_EC_SupFan3.TriggerAL - Alarm - Fan Supply 3 EC - UndervoltageRead
BV837Al_Undervoltage_EC_SupFan4.TriggerAL - Alarm - Fan Supply 4 EC - UndervoltageRead
BV838Al_Undervoltage_EC_SupFan5.TriggerAL - Alarm - Fan Supply 5 EC - UndervoltageRead
BV839Al_Undervoltage_EC_SupFan6.TriggerAL - Alarm - Fan Supply 6 EC - UndervoltageRead
BV840Al_Undervoltage_EC_SupFan7.TriggerAL - Alarm - Fan Supply 7 EC - UndervoltageRead
BV841Al_Undervoltage_EC_SupFan8.TriggerAL - Alarm - Fan Supply 8 EC - UndervoltageRead
BV842Al_Undervoltage_EC_SupFan9.TriggerAL - Alarm - Fan Supply 9 EC - UndervoltageRead
BV843CfgErrAlrm.TriggerAL - Alarm - Device - Wrong configurationRead
BV844OfflineAlrm.TriggerAL - Alarm - Device - OfflineRead
BVmin845AlarmMng.AlrmResByBmsAL - Alarm - BMS - ResetWrite0=; 1=RESET
BV846Al_ABB_ExhFan_1.ActiveAL - Alarm - Fan Return 1Read
BV847Al_ABB_ExhFan_10.ActiveAL - Alarm - Fan Return 10Read
BV848Al_ABB_ExhFan_2.ActiveAL - Alarm - Fan Return 2Read
BV849Al_ABB_ExhFan_3.ActiveAL - Alarm - Fan Return 3Read
BV850Al_ABB_ExhFan_4.ActiveAL - Alarm - Fan Return 4Read
BV851Al_ABB_ExhFan_5.ActiveAL - Alarm - Fan Return 5Read
BV852Al_ABB_ExhFan_6.ActiveAL - Alarm - Fan Return 6Read
BV853Al_ABB_ExhFan_7.ActiveAL - Alarm - Fan Return 7Read
BV854Al_ABB_ExhFan_8.ActiveAL - Alarm - Fan Return 8Read
BV855Al_ABB_ExhFan_9.ActiveAL - Alarm - Fan Return 9Read
BV856Al_ABB_Rotary.ActiveAL - Alarm - RotaryRead
BV857Al_ABB_SupFan_1.ActiveAL - Alarm - Fan Supply 1Read
BV858Al_ABB_SupFan_10.ActiveAL - Alarm - Fan Supply 10Read
BV859Al_ABB_SupFan_2.ActiveAL - Alarm - Fan Supply 2Read
BV860Al_ABB_SupFan_3.ActiveAL - Alarm - Fan Supply 3Read
BV861Al_ABB_SupFan_4.ActiveAL - Alarm - Fan Supply 4Read
BV862Al_ABB_SupFan_5.ActiveAL - Alarm - Fan Supply 5Read
BV863Al_ABB_SupFan_6.ActiveAL - Alarm - Fan Supply 6Read
BV864Al_ABB_SupFan_7.ActiveAL - Alarm - Fan Supply 7Read
BV865Al_ABB_SupFan_8.ActiveAL - Alarm - Fan Supply 8Read
BV866Al_ABB_SupFan_9.ActiveAL - Alarm - Fan Supply 9Read
BV867Al_AFreezeDIN.ActiveAL - Alarm - Antifreeze - Digital InputRead
BV868Al_AFreezePRB.ActiveAL - Alarm - Antifreeze - Back Water TemperatureRead
BV869Al_AFreezePreHeatPRB.ActiveAL - Alarm - Antifreeze - PreHeat Back Water TemperatureRead
BV870Al_AfterPreHeatCoilTempPrb.ActiveAL - Alarm - Probe - After preheating coil temperatureRead
BV871Al_BMS_Offline.ActiveAL - Alarm - BMS - OfflineRead
BV872Al_CfgError_cpCOe.ActiveAL - Alarm - Module IO - cPCOE - Configuration errorRead
BV873Al_CircuitFault_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - Circuit FaultRead
BV874Al_CircuitFault_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - Circuit FaultRead
BV875Al_CircuitFault_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - Circuit FaultRead
BV876Al_CircuitFault_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - Circuit FaultRead
BV877Al_CircuitFault_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - Circuit FaultRead
BV878Al_CircuitFault_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - Circuit FaultRead
BV879Al_CircuitFault_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - Circuit FaultRead
BV880Al_CircuitFault_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - Circuit FaultRead
BV881Al_CircuitFault_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - Circuit FaultRead
BV882Al_CircuitFault_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - Circuit FaultRead
BV883Al_CircuitFault_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - Circuit FaultRead
BV884Al_CircuitFault_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - Circuit FaultRead
BV885Al_CircuitFault_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - Circuit FaultRead
BV886Al_CircuitFault_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - Circuit FaultRead
BV887Al_CircuitFault_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - Circuit FaultRead
BV888Al_CircuitFault_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - Circuit FaultRead
BV889Al_CircuitFault_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - Circuit FaultRead
BV890Al_CircuitFault_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - Circuit FaultRead
BV891Al_CircuitFault_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - Circuit FaultRead
BV892Al_CircuitFault_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - Circuit FaultRead
BV893Al_CommErr_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Communication ErrorRead
BV894Al_CommErr_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Communication ErrorRead
BV895Al_CommErr_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Communication ErrorRead
BV896Al_CommErr_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Communication ErrorRead
BV897Al_CommErr_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Communication ErrorRead
BV898Al_CommErr_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Communication ErrorRead
BV899Al_CommErr_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Communication ErrorRead
BV900Al_CommErr_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Communication ErrorRead
BV901Al_CommErr_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Communication ErrorRead
BV902Al_CommErr_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Communication ErrorRead
BV903Al_CommErr_Rotary.ActiveAL - Alarm - Rotary - CommUnitation ErrorRead
BV904Al_CommErr_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Communication ErrorRead
BV905Al_CommErr_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Communication ErrorRead
BV906Al_CommErr_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Communication ErrorRead
BV907Al_CommErr_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Communication ErrorRead
BV908Al_CommErr_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Communication ErrorRead
BV909Al_CommErr_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Communication ErrorRead
BV910Al_CommErr_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Communication ErrorRead
BV911Al_CommErr_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Communication ErrorRead
BV912Al_CommErr_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Communication ErrorRead
BV913Al_CommErr_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Communication ErrorRead
BV914Al_Cool.ActiveAL - Alarm - Cooling - Device AlarmRead
BV915Al_CoolFanFault_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Cooling Fan FaultRead
BV916Al_CoolFanFault_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Cooling Fan FaultRead
BV917Al_CoolFanFault_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Cooling Fan FaultRead
BV918Al_CoolFanFault_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Cooling Fan FaultRead
BV919Al_CoolFanFault_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Cooling Fan FaultRead
BV920Al_CoolFanFault_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Cooling Fan FaultRead
BV921Al_CoolFanFault_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Cooling Fan FaultRead
BV922Al_CoolFanFault_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Cooling Fan FaultRead
BV923Al_CoolFanFault_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Cooling Fan FaultRead
BV924Al_CoolFanFault_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Cooling Fan FaultRead
BV925Al_CoolFanFault_Rotary.ActiveAL - Alarm - Rotary - Cooling Fan FaultRead
BV926Al_CoolFanFault_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Cooling Fan FaultRead
BV927Al_CoolFanFault_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Cooling Fan FaultRead
BV928Al_CoolFanFault_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Cooling Fan FaultRead
BV929Al_CoolFanFault_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Cooling Fan FaultRead
BV930Al_CoolFanFault_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Cooling Fan FaultRead
BV931Al_CoolFanFault_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Cooling Fan FaultRead
BV932Al_CoolFanFault_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Cooling Fan FaultRead
BV933Al_CoolFanFault_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Cooling Fan FaultRead
BV934Al_CoolFanFault_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Cooling Fan FaultRead
BV935Al_CoolFanFault_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Cooling Fan FaultRead
BV936Al_CutOff_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - CutOffRead
BV937Al_CutOff_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - CutOffRead
BV938Al_CutOff_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - CutOffRead
BV939Al_CutOff_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - CutOffRead
BV940Al_CutOff_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - CutOffRead
BV941Al_CutOff_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - CutOffRead
BV942Al_CutOff_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - CutOffRead
BV943Al_CutOff_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - CutOffRead
BV944Al_CutOff_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - CutOffRead
BV945Al_CutOff_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - CutOffRead
BV946Al_CutOff_Rotary.ActiveAL - Alarm - Rotary - CutOffRead
BV947Al_CutOff_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - CutOffRead
BV948Al_CutOff_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - CutOffRead
BV949Al_CutOff_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - CutOffRead
BV950Al_CutOff_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - CutOffRead
BV951Al_CutOff_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - CutOffRead
BV952Al_CutOff_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - CutOffRead
BV953Al_CutOff_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - CutOffRead
BV954Al_CutOff_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - CutOffRead
BV955Al_CutOff_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - CutOffRead
BV956Al_CutOff_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - CutOffRead
BV957Al_DC_Ovld_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - DC Over loadRead
BV958Al_DC_Ovld_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - DC Over loadRead
BV959Al_DC_Ovld_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - DC Over loadRead
BV960Al_DC_Ovld_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - DC Over loadRead
BV961Al_DC_Ovld_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - DC Over loadRead
BV962Al_DC_Ovld_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - DC Over loadRead
BV963Al_DC_Ovld_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - DC Over loadRead
BV964Al_DC_Ovld_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - DC Over loadRead
BV965Al_DC_Ovld_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - DC Over loadRead
BV966Al_DC_Ovld_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - DC Over loadRead
BV967Al_DC_Ovld_Rotary.ActiveAL - Alarm - Rotary - DC OverloadRead
BV968Al_DC_Ovld_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - DC Over loadRead
BV969Al_DC_Ovld_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - DC Over loadRead
BV970Al_DC_Ovld_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - DC Over loadRead
BV971Al_DC_Ovld_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - DC Over loadRead
BV972Al_DC_Ovld_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - DC Over loadRead
BV973Al_DC_Ovld_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - DC Over loadRead
BV974Al_DC_Ovld_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - DC Over loadRead
BV975Al_DC_Ovld_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - DC Over loadRead
BV976Al_DC_Ovld_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - DC Over loadRead
BV977Al_DC_Ovld_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - DC Over loadRead
BV978Al_ElectTherm_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Electric ThermalRead
BV979Al_ElectTherm_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Electric ThermalRead
BV980Al_ElectTherm_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Electric ThermalRead
BV981Al_ElectTherm_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Electric ThermalRead
BV982Al_ElectTherm_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Electric ThermalRead
BV983Al_ElectTherm_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Electric ThermalRead
BV984Al_ElectTherm_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Electric ThermalRead
BV985Al_ElectTherm_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Electric ThermalRead
BV986Al_ElectTherm_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Electric ThermalRead
BV987Al_ElectTherm_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Electric ThermalRead
BV988Al_ElectTherm_Rotary.ActiveAL - Alarm - Rotary - Electric ThermalRead
BV989Al_ElectTherm_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Electric ThermalRead
BV990Al_ElectTherm_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Electric ThermalRead
BV991Al_ElectTherm_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Electric ThermalRead
BV992Al_ElectTherm_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Electric ThermalRead
BV993Al_ElectTherm_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Electric ThermalRead
BV994Al_ElectTherm_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Electric ThermalRead
BV995Al_ElectTherm_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Electric ThermalRead
BV996Al_ElectTherm_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Electric ThermalRead
BV997Al_ElectTherm_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Electric ThermalRead
BV998Al_ElectTherm_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Electric ThermalRead
BV999Al_Err_retain_write.ActiveAL - Alarm - Error retain writeRead
BV1000Al_ExhTempPrb.ActiveAL - Alarm - Probe - Temperature ExhaustRead
BV1001Al_ExtFaultA_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - External Fault ARead
BV1002Al_ExtFaultA_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - External Fault ARead
BV1003Al_ExtFaultA_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - External Fault ARead
BV1004Al_ExtFaultA_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - External Fault ARead
BV1005Al_ExtFaultA_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - External Fault ARead
BV1006Al_ExtFaultA_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - External Fault ARead
BV1007Al_ExtFaultA_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - External Fault ARead
BV1008Al_ExtFaultA_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - External Fault ARead
BV1009Al_ExtFaultA_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - External Fault ARead
BV1010Al_ExtFaultA_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - External Fault ARead
BV1011Al_ExtFaultA_Rotary.ActiveAL - Alarm - Rotary - External Fault ARead
BV1012Al_ExtFaultA_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - External Fault ARead
BV1013Al_ExtFaultA_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - External Fault ARead
BV1014Al_ExtFaultA_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - External Fault ARead
BV1015Al_ExtFaultA_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - External Fault ARead
BV1016Al_ExtFaultA_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - External Fault ARead
BV1017Al_ExtFaultA_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - External Fault ARead
BV1018Al_ExtFaultA_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - External Fault ARead
BV1019Al_ExtFaultA_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - External Fault ARead
BV1020Al_ExtFaultA_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - External Fault ARead
BV1021Al_ExtFaultA_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - External Fault ARead
BV1022Al_ExtFaultB_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - External Fault BRead
BV1023Al_ExtFaultB_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - External Fault BRead
BV1024Al_ExtFaultB_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - External Fault BRead
BV1025Al_ExtFaultB_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - External Fault BRead
BV1026Al_ExtFaultB_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - External Fault BRead
BV1027Al_ExtFaultB_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - External Fault BRead
BV1028Al_ExtFaultB_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - External Fault BRead
BV1029Al_ExtFaultB_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - External Fault BRead
BV1030Al_ExtFaultB_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - External Fault BRead
BV1031Al_ExtFaultB_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - External Fault BRead
BV1032Al_ExtFaultB_Rotary.ActiveAL - Alarm - Rotary - External Fault BRead
BV1033Al_ExtFaultB_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - External Fault BRead
BV1034Al_ExtFaultB_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - External Fault BRead
BV1035Al_ExtFaultB_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - External Fault BRead
BV1036Al_ExtFaultB_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - External Fault BRead
BV1037Al_ExtFaultB_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - External Fault BRead
BV1038Al_ExtFaultB_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - External Fault BRead
BV1039Al_ExtFaultB_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - External Fault BRead
BV1040Al_ExtFaultB_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - External Fault BRead
BV1041Al_ExtFaultB_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - External Fault BRead
BV1042Al_ExtFaultB_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - External Fault BRead
BV1043Al_ExtTempPrb.ActiveAL - Alarm - Probe - Temperature ExternalRead
BV1044Al_Fire.ActiveAL - Alarm - FireRead
BV1045Al_FireExh.ActiveAL - Alarm - Fire - Return TemperatureRead
BV1046Al_GroundFault_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Ground FaultRead
BV1047Al_GroundFault_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Ground FaultRead
BV1048Al_GroundFault_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Ground FaultRead
BV1049Al_GroundFault_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Ground FaultRead
BV1050Al_GroundFault_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Ground FaultRead
BV1051Al_GroundFault_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Ground FaultRead
BV1052Al_GroundFault_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Ground FaultRead
BV1053Al_GroundFault_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Ground FaultRead
BV1054Al_GroundFault_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Ground FaultRead
BV1055Al_GroundFault_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Ground FaultRead
BV1056Al_GroundFault_Rotary.ActiveAL - Alarm - Rotary - Ground FaultRead
BV1057Al_GroundFault_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Ground FaultRead
BV1058Al_GroundFault_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Ground FaultRead
BV1059Al_GroundFault_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Ground FaultRead
BV1060Al_GroundFault_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Ground FaultRead
BV1061Al_GroundFault_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Ground FaultRead
BV1062Al_GroundFault_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Ground FaultRead
BV1063Al_GroundFault_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Ground FaultRead
BV1064Al_GroundFault_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Ground FaultRead
BV1065Al_GroundFault_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Ground FaultRead
BV1066Al_GroundFault_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Ground FaultRead
BV1067Al_Heat.ActiveAL - Alarm - Heating - Device AlarmRead
BV1068Al_HeatCoilTempPrb.ActiveAL - Alarm - Probe - Temperature Water Heating coilRead
BV1069Al_HeatExchgWorkHrsWarn.ActiveAL - Alarm - HeatExchanger - HeatExchanger Works Hour WarningRead
BV1070Al_HeatSink_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - HeatSinkRead
BV1071Al_HeatSink_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - HeatSinkRead
BV1072Al_HeatSink_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - HeatSinkRead
BV1073Al_HeatSink_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - HeatSinkRead
BV1074Al_HeatSink_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - HeatSinkRead
BV1075Al_HeatSink_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - HeatSinkRead
BV1076Al_HeatSink_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - HeatSinkRead
BV1077Al_HeatSink_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - HeatSinkRead
BV1078Al_HeatSink_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - HeatSinkRead
BV1079Al_HeatSink_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - HeatSinkRead
BV1080Al_HeatSink_Rotary.ActiveAL - Alarm - Rotary - HeatSinkRead
BV1081Al_HeatSink_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - HeatSinkRead
BV1082Al_HeatSink_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - HeatSinkRead
BV1083Al_HeatSink_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - HeatSinkRead
BV1084Al_HeatSink_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - HeatSinkRead
BV1085Al_HeatSink_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - HeatSinkRead
BV1086Al_HeatSink_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - HeatSinkRead
BV1087Al_HeatSink_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - HeatSinkRead
BV1088Al_HeatSink_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - HeatSinkRead
BV1089Al_HeatSink_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - HeatSinkRead
BV1090Al_HeatSink_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - HeatSinkRead
BV1091AL_Hot_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - HotRead
BV1092AL_Hot_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - HotRead
BV1093AL_Hot_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - HotRead
BV1094AL_Hot_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - HotRead
BV1095AL_Hot_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - HotRead
BV1096AL_Hot_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - HotRead
BV1097AL_Hot_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - HotRead
BV1098AL_Hot_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - HotRead
BV1099AL_Hot_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - HotRead
BV1100AL_Hot_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - HotRead
BV1101AL_Hot_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - HotRead
BV1102AL_Hot_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - HotRead
BV1103AL_Hot_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - HotRead
BV1104AL_Hot_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - HotRead
BV1105AL_Hot_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - HotRead
BV1106AL_Hot_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - HotRead
BV1107AL_Hot_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - HotRead
BV1108AL_Hot_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - HotRead
BV1109AL_Hot_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - HotRead
BV1110AL_Hot_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - HotRead
BV1111Al_Hum.ActiveAL - Alarm - HumidifierRead
BV1112Al_HumWorkHrsWarn.ActiveAL - Alarm - Humidity - Works Hour WarningRead
BV1113Al_HW_Fault_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Hardware FaultRead
BV1114Al_HW_Fault_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Hardware FaultRead
BV1115Al_HW_Fault_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Hardware FaultRead
BV1116Al_HW_Fault_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Hardware FaultRead
BV1117Al_HW_Fault_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Hardware FaultRead
BV1118Al_HW_Fault_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Hardware FaultRead
BV1119Al_HW_Fault_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Hardware FaultRead
BV1120Al_HW_Fault_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Hardware FaultRead
BV1121Al_HW_Fault_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Hardware FaultRead
BV1122Al_HW_Fault_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Hardware FaultRead
BV1123Al_HW_Fault_Rotary.ActiveAL - Alarm - Rotary - Hardware FaultRead
BV1124Al_HW_Fault_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Hardware FaultRead
BV1125Al_HW_Fault_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Hardware FaultRead
BV1126Al_HW_Fault_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Hardware FaultRead
BV1127Al_HW_Fault_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Hardware FaultRead
BV1128Al_HW_Fault_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Hardware FaultRead
BV1129Al_HW_Fault_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Hardware FaultRead
BV1130Al_HW_Fault_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Hardware FaultRead
BV1131Al_HW_Fault_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Hardware FaultRead
BV1132Al_HW_Fault_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Hardware FaultRead
BV1133Al_HW_Fault_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Hardware FaultRead
BV1134Al_I2RIGBTFault_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - I2RIGBT FaultRead
BV1135Al_I2RIGBTFault_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - I2RIGBT FaultRead
BV1136Al_I2RIGBTFault_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - I2RIGBT FaultRead
BV1137Al_I2RIGBTFault_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - I2RIGBT FaultRead
BV1138Al_I2RIGBTFault_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - I2RIGBT FaultRead
BV1139Al_I2RIGBTFault_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - I2RIGBT FaultRead
BV1140Al_I2RIGBTFault_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - I2RIGBT FaultRead
BV1141Al_I2RIGBTFault_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - I2RIGBT FaultRead
BV1142Al_I2RIGBTFault_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - I2RIGBT FaultRead
BV1143Al_I2RIGBTFault_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - I2RIGBT FaultRead
BV1144Al_I2RIGBTFault_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - I2RIGBT FaultRead
BV1145Al_I2RIGBTFault_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - I2RIGBT FaultRead
BV1146Al_I2RIGBTFault_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - I2RIGBT FaultRead
BV1147Al_I2RIGBTFault_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - I2RIGBT FaultRead
BV1148Al_I2RIGBTFault_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - I2RIGBT FaultRead
BV1149Al_I2RIGBTFault_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - I2RIGBT FaultRead
BV1150Al_I2RIGBTFault_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - I2RIGBT FaultRead
BV1151Al_I2RIGBTFault_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - I2RIGBT FaultRead
BV1152Al_I2RIGBTFault_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - I2RIGBT FaultRead
BV1153Al_I2RIGBTFault_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - I2RIGBT FaultRead
BV1154AL_IGBTOvercurrent_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - IGBT Over currentRead
BV1155AL_IGBTOvercurrent_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - IGBT Over currentRead
BV1156AL_IGBTOvercurrent_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - IGBT Over currentRead
BV1157AL_IGBTOvercurrent_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - IGBT Over currentRead
BV1158AL_IGBTOvercurrent_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - IGBT Over currentRead
BV1159AL_IGBTOvercurrent_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - IGBT Over currentRead
BV1160AL_IGBTOvercurrent_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - IGBT Over currentRead
BV1161AL_IGBTOvercurrent_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - IGBT Over currentRead
BV1162AL_IGBTOvercurrent_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - IGBT Over currentRead
BV1163AL_IGBTOvercurrent_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - IGBT Over currentRead
BV1164AL_IGBTOvercurrent_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - IGBT Over currentRead
BV1165AL_IGBTOvercurrent_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - IGBT Over currentRead
BV1166AL_IGBTOvercurrent_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - IGBT Over currentRead
BV1167AL_IGBTOvercurrent_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - IGBT Over currentRead
BV1168AL_IGBTOvercurrent_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - IGBT Over currentRead
BV1169AL_IGBTOvercurrent_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - IGBT Over currentRead
BV1170AL_IGBTOvercurrent_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - IGBT Over currentRead
BV1171AL_IGBTOvercurrent_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - IGBT Over currentRead
BV1172AL_IGBTOvercurrent_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - IGBT Over currentRead
BV1173AL_IGBTOvercurrent_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - IGBT Over currentRead
BV1174Al_InvOverheat_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Inverter Over HeatRead
BV1175Al_InvOverheat_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Inverter Over HeatRead
BV1176Al_InvOverheat_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Inverter Over HeatRead
BV1177Al_InvOverheat_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Inverter Over HeatRead
BV1178Al_InvOverheat_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Inverter Over HeatRead
BV1179Al_InvOverheat_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Inverter Over HeatRead
BV1180Al_InvOverheat_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Inverter Over HeatRead
BV1181Al_InvOverheat_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Inverter Over HeatRead
BV1182Al_InvOverheat_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Inverter Over HeatRead
BV1183Al_InvOverheat_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Inverter Over HeatRead
BV1184Al_InvOverheat_Rotary.ActiveAL - Alarm - Rotary - Inverter OverHeatRead
BV1185Al_InvOverheat_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Inverter Over HeatRead
BV1186Al_InvOverheat_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Inverter Over HeatRead
BV1187Al_InvOverheat_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Inverter Over HeatRead
BV1188Al_InvOverheat_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Inverter Over HeatRead
BV1189Al_InvOverheat_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Inverter Over HeatRead
BV1190Al_InvOverheat_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Inverter Over HeatRead
BV1191Al_InvOverheat_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Inverter Over HeatRead
BV1192Al_InvOverheat_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Inverter Over HeatRead
BV1193Al_InvOverheat_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Inverter Over HeatRead
BV1194Al_InvOverheat_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Inverter Over HeatRead
BV1195Al_InvOvld_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Inverter Over LoadRead
BV1196Al_InvOvld_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Inverter Over LoadRead
BV1197Al_InvOvld_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Inverter Over LoadRead
BV1198Al_InvOvld_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Inverter Over LoadRead
BV1199Al_InvOvld_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Inverter Over LoadRead
BV1200Al_InvOvld_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Inverter Over LoadRead
BV1201Al_InvOvld_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Inverter Over LoadRead
BV1202Al_InvOvld_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Inverter Over LoadRead
BV1203Al_InvOvld_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Inverter Over LoadRead
BV1204Al_InvOvld_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Inverter Over LoadRead
BV1205Al_InvOvld_Rotary.ActiveAL - Alarm - Rotary - Inverter OverLoadRead
BV1206Al_InvOvld_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Inverter Over LoadRead
BV1207Al_InvOvld_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Inverter Over LoadRead
BV1208Al_InvOvld_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Inverter Over LoadRead
BV1209Al_InvOvld_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Inverter Over LoadRead
BV1210Al_InvOvld_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Inverter Over LoadRead
BV1211Al_InvOvld_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Inverter Over LoadRead
BV1212Al_InvOvld_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Inverter Over LoadRead
BV1213Al_InvOvld_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Inverter Over LoadRead
BV1214Al_InvOvld_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Inverter Over LoadRead
BV1215Al_InvOvld_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Inverter Over LoadRead
BV1216Al_LowSupplyTemp.ActiveAL - Alarm - Probe - Low Supply TemperatureRead
BV1217Al_LowVolt_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Low VoltageRead
BV1218Al_LowVolt_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Low VoltageRead
BV1219Al_LowVolt_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Low VoltageRead
BV1220Al_LowVolt_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Low VoltageRead
BV1221Al_LowVolt_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Low VoltageRead
BV1222Al_LowVolt_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Low VoltageRead
BV1223Al_LowVolt_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Low VoltageRead
BV1224Al_LowVolt_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Low VoltageRead
BV1225Al_LowVolt_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Low VoltageRead
BV1226Al_LowVolt_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Low VoltageRead
BV1227Al_LowVolt_Rotary.ActiveAL - Alarm - Rotary - Low VoltageRead
BV1228Al_LowVolt_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Low VoltageRead
BV1229Al_LowVolt_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Low VoltageRead
BV1230Al_LowVolt_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Low VoltageRead
BV1231Al_LowVolt_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Low VoltageRead
BV1232Al_LowVolt_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Low VoltageRead
BV1233Al_LowVolt_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Low VoltageRead
BV1234Al_LowVolt_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Low VoltageRead
BV1235Al_LowVolt_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Low VoltageRead
BV1236Al_LowVolt_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Low VoltageRead
BV1237Al_LowVolt_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Low VoltageRead
BV1238Al_MB_AO1.ActiveAL - Alarm - Control Circuit - AO1Read
BV1239Al_MB_AO1_AO4_PWM.ActiveAL - Alarm - Control Circuit - AO1_AO4_PWMRead
BV1240Al_MB_AO2.ActiveAL - Alarm - Control Circuit - AO2Read
BV1241Al_MB_AO3.ActiveAL - Alarm - Control Circuit - AO3Read
BV1242Al_MB_AO4.ActiveAL - Alarm - Control Circuit - AO4Read
BV1243Al_MB_Control_Supply.ActiveAL - Alarm - Control Circuit - Control_SupplyRead
BV1244Al_MB_Control_Temp.ActiveAL - Alarm - Control Circuit - Control_TempRead
BV1245Al_MB_Humidity.ActiveAL - Alarm - Control Circuit - HumidityRead
BV1246Al_MB_Press_Fan_Return.ActiveAL - Alarm - Control Circuit - Press_Fan_ReturnRead
BV1247Al_MB_Press_Fan_Supply.ActiveAL - Alarm - Control Circuit - Press_Fan_SupplyRead
BV1248Al_MB_Press_Filter_Return.ActiveAL - Alarm - Control Circuit - Press_Filter_ReturnRead
BV1249Al_MB_Press_Filter_Supply.ActiveAL - Alarm - Control Circuit - Press_Filter_SupplyRead
BV1250Al_MB_Supply24.ActiveAL - Alarm - Control Circuit - Supply24Read
BV1251Al_MB_Temp_Fan_Return.ActiveAL - Alarm - Control Circuit - Temp_Fan_ReturnRead
BV1252Al_MB_Temp_Fan_Supply.ActiveAL - Alarm - Control Circuit - Temp_Fan_SupplyRead
BV1253Al_MB_Temp_Filter_Return.ActiveAL - Alarm - Control Circuit - Temp_Filter_ReturnRead
BV1254Al_MB_Temp_Filter_Supply.ActiveAL - Alarm - Control Circuit - Temp_Filter_SupplyRead
BV1255Al_MB_Temperature.ActiveAL - Alarm - Control Circuit - TemperatureRead
BV1256Al_MotorFault_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - Motor FaultRead
BV1257Al_MotorFault_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - Motor FaultRead
BV1258Al_MotorFault_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - Motor FaultRead
BV1259Al_MotorFault_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - Motor FaultRead
BV1260Al_MotorFault_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - Motor FaultRead
BV1261Al_MotorFault_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - Motor FaultRead
BV1262Al_MotorFault_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - Motor FaultRead
BV1263Al_MotorFault_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - Motor FaultRead
BV1264Al_MotorFault_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - Motor FaultRead
BV1265Al_MotorFault_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - Motor FaultRead
BV1266Al_MotorFault_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - Motor FaultRead
BV1267Al_MotorFault_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - Motor FaultRead
BV1268Al_MotorFault_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - Motor FaultRead
BV1269Al_MotorFault_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - Motor FaultRead
BV1270Al_MotorFault_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - Motor FaultRead
BV1271Al_MotorFault_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - Motor FaultRead
BV1272Al_MotorFault_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - Motor FaultRead
BV1273Al_MotorFault_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - Motor FaultRead
BV1274Al_MotorFault_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - Motor FaultRead
BV1275Al_MotorOverheat_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Motor Over heatRead
BV1276Al_MotorOverheat_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Motor Over heatRead
BV1277Al_MotorOverheat_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Motor Over heatRead
BV1278Al_MotorOverheat_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Motor Over heatRead
BV1279Al_MotorOverheat_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Motor Over heatRead
BV1280Al_MotorOverheat_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Motor Over heatRead
BV1281Al_MotorOverheat_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Motor Over heatRead
BV1282Al_MotorOverheat_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Motor Over heatRead
BV1283Al_MotorOverheat_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Motor Over heatRead
BV1284Al_MotorOverheat_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Motor Over heatRead
BV1285Al_MotorOverheat_Rotary.ActiveAL - Alarm - Rotary - Motor OverheatRead
BV1286Al_MotorOverheat_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Motor Over heatRead
BV1287Al_MotorOverheat_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Motor Over heatRead
BV1288Al_MotorOverheat_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Motor Over heatRead
BV1289Al_MotorOverheat_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Motor Over heatRead
BV1290Al_MotorOverheat_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Motor Over heatRead
BV1291Al_MotorOverheat_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Motor Over heatRead
BV1292Al_MotorOverheat_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Motor Over heatRead
BV1293Al_MotorOverheat_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Motor Over heatRead
BV1294Al_MotorOverheat_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Motor Over heatRead
BV1295Al_MotorOverheat_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Motor Over heatRead
BV1296Al_Offline_cpCOe.ActiveAL - Alarm - Module IO - cPCOE - OfflineRead
BV1297Al_Offline_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - OfflineRead
BV1298Al_Offline_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - OfflineRead
BV1299Al_Offline_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - OfflineRead
BV1300Al_Offline_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - OfflineRead
BV1301Al_Offline_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - OfflineRead
BV1302Al_Offline_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - OfflineRead
BV1303Al_Offline_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - OfflineRead
BV1304Al_Offline_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - OfflineRead
BV1305Al_Offline_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - OfflineRead
BV1306Al_Offline_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - OfflineRead
BV1307Al_Offline_MainBoard.ActiveAL - Alarm - Control Circuit - OfflineRead
BV1308Al_Offline_Rotary.ActiveAL - Alarm - Rotary - OfflineRead
BV1309Al_Offline_SP_ExhHum.ActiveAL - Alarm - Probe - Return Humidity - OfflineRead
BV1310Al_Offline_SP_ExhPress.ActiveAL - Alarm - Probe - Return Air Pressure - OfflineRead
BV1311Al_Offline_SP_SupplyHum.ActiveAL - Alarm - Probe - Supply humidity - OfflineRead
BV1312Al_Offline_SP_SupplyPress.ActiveAL - Alarm - Probe - Supply Air Pressure - OfflineRead
BV1313Al_Offline_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - OfflineRead
BV1314Al_Offline_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - OfflineRead
BV1315Al_Offline_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - OfflineRead
BV1316Al_Offline_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - OfflineRead
BV1317Al_Offline_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - OfflineRead
BV1318Al_Offline_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - OfflineRead
BV1319Al_Offline_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - OfflineRead
BV1320Al_Offline_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - OfflineRead
BV1321Al_Offline_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - OfflineRead
BV1322Al_Offline_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - OfflineRead
BV1323Al_Offline_THTN_1.ActiveAL - Alarm - HMI Basic - OfflineRead
BV1324Al_Option_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - OptionRead
BV1325Al_Option_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - OptionRead
BV1326Al_Option_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - OptionRead
BV1327Al_Option_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - OptionRead
BV1328Al_Option_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - OptionRead
BV1329Al_Option_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - OptionRead
BV1330Al_Option_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - OptionRead
BV1331Al_Option_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - OptionRead
BV1332Al_Option_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - OptionRead
BV1333Al_Option_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - OptionRead
BV1334Al_Option_Rotary.ActiveAL - Alarm - Rotary - OptionRead
BV1335Al_Option_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - OptionRead
BV1336Al_Option_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - OptionRead
BV1337Al_Option_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - OptionRead
BV1338Al_Option_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - OptionRead
BV1339Al_Option_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - OptionRead
BV1340Al_Option_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - OptionRead
BV1341Al_Option_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - OptionRead
BV1342Al_Option_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - OptionRead
BV1343Al_Option_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - OptionRead
BV1344Al_Option_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - OptionRead
BV1345Al_Overcurrent_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Over CurrentRead
BV1346Al_Overcurrent_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Over CurrentRead
BV1347Al_Overcurrent_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Over CurrentRead
BV1348Al_Overcurrent_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Over CurrentRead
BV1349Al_Overcurrent_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Over CurrentRead
BV1350Al_Overcurrent_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Over currentRead
BV1351Al_Overcurrent_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Over CurrentRead
BV1352Al_Overcurrent_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Over CurrentRead
BV1353Al_Overcurrent_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Over CurrentRead
BV1354Al_Overcurrent_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Over CurrentRead
BV1355Al_Overcurrent_Rotary.ActiveAL - Alarm - Rotary - OverCurrentRead
BV1356Al_Overcurrent_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Over currentRead
BV1357Al_Overcurrent_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Over CurrentRead
BV1358Al_Overcurrent_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Over CurrentRead
BV1359Al_Overcurrent_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Over CurrentRead
BV1360Al_Overcurrent_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Over CurrentRead
BV1361Al_Overcurrent_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Over currentRead
BV1362Al_Overcurrent_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Over CurrentRead
BV1363Al_Overcurrent_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Over CurrentRead
BV1364Al_Overcurrent_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Over CurrentRead
BV1365Al_Overcurrent_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Over CurrentRead
BV1366Al_OverVolt_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Over VoltageRead
BV1367Al_OverVolt_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Over VoltageRead
BV1368Al_OverVolt_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Over VoltageRead
BV1369Al_OverVolt_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Over VoltageRead
BV1370Al_OverVolt_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Over VoltageRead
BV1371Al_OverVolt_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Over voltageRead
BV1372Al_OverVolt_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Over VoltageRead
BV1373Al_OverVolt_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Over VoltageRead
BV1374Al_OverVolt_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Over VoltageRead
BV1375Al_OverVolt_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Over VoltageRead
BV1376Al_OverVolt_Rotary.ActiveAL - Alarm - Rotary - OverVoltageRead
BV1377Al_OverVolt_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Over voltageRead
BV1378Al_OverVolt_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Over VoltageRead
BV1379Al_OverVolt_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Over VoltageRead
BV1380Al_OverVolt_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Over VoltageRead
BV1381Al_OverVolt_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Over VoltageRead
BV1382Al_OverVolt_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Over voltageRead
BV1383Al_OverVolt_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Over VoltageRead
BV1384Al_OverVolt_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Over VoltageRead
BV1385Al_OverVolt_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Over VoltageRead
BV1386Al_OverVolt_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Over VoltageRead
BV1387AL_Overvoltage_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - Over voltageRead
BV1388AL_Overvoltage_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - Over voltageRead
BV1389AL_Overvoltage_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - Over voltageRead
BV1390AL_Overvoltage_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - Over voltageRead
BV1391AL_Overvoltage_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - Over voltageRead
BV1392AL_Overvoltage_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - Over voltageRead
BV1393AL_Overvoltage_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - Over voltageRead
BV1394AL_Overvoltage_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - Over voltageRead
BV1395AL_Overvoltage_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - Over voltageRead
BV1396AL_Overvoltage_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - Over voltageRead
BV1397AL_Overvoltage_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - Over voltageRead
BV1398AL_Overvoltage_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - Over voltageRead
BV1399AL_Overvoltage_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - Over voltageRead
BV1400AL_Overvoltage_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - Over voltageRead
BV1401AL_Overvoltage_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - Over voltageRead
BV1402AL_Overvoltage_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - Over voltageRead
BV1403AL_Overvoltage_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - Over voltageRead
BV1404AL_Overvoltage_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - Over voltageRead
BV1405AL_Overvoltage_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - Over voltageRead
BV1406AL_Overvoltage_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - Over voltageRead
BV1407Al_Ovld_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Over LoadRead
BV1408Al_Ovld_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Over LoadRead
BV1409Al_Ovld_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Over LoadRead
BV1410Al_Ovld_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Over LoadRead
BV1411Al_Ovld_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Over LoadRead
BV1412Al_Ovld_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Over loadRead
BV1413Al_Ovld_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Over LoadRead
BV1414Al_Ovld_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Over LoadRead
BV1415Al_Ovld_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Over LoadRead
BV1416Al_Ovld_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Over LoadRead
BV1417Al_Ovld_Rotary.ActiveAL - Alarm - Rotary - OverLoadRead
BV1418Al_Ovld_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Over loadRead
BV1419Al_Ovld_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Over LoadRead
BV1420Al_Ovld_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Over LoadRead
BV1421Al_Ovld_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Over LoadRead
BV1422Al_Ovld_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Over LoadRead
BV1423Al_Ovld_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Over loadRead
BV1424Al_Ovld_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Over LoadRead
BV1425Al_Ovld_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Over LoadRead
BV1426Al_Ovld_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Over LoadRead
BV1427Al_Ovld_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Over LoadRead
BV1428Al_ParamErr_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Parameters ErrorRead
BV1429Al_ParamErr_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Parameters ErrorRead
BV1430Al_ParamErr_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Parameters ErrorRead
BV1431Al_ParamErr_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Parameters ErrorRead
BV1432Al_ParamErr_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Parameters ErrorRead
BV1433Al_ParamErr_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Parameter save ErrorRead
BV1434Al_ParamErr_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Parameters ErrorRead
BV1435Al_ParamErr_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Parameters ErrorRead
BV1436Al_ParamErr_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Parameters ErrorRead
BV1437Al_ParamErr_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Parameters ErrorRead
BV1438Al_ParamErr_Rotary.ActiveAL - Alarm - Rotary - Parameters ErrorRead
BV1439Al_ParamErr_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Parameter save ErrorRead
BV1440Al_ParamErr_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Parameters ErrorRead
BV1441Al_ParamErr_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Parameters ErrorRead
BV1442Al_ParamErr_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Parameters ErrorRead
BV1443Al_ParamErr_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Parameters ErrorRead
BV1444Al_ParamErr_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Parameter save ErrorRead
BV1445Al_ParamErr_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Parameters ErrorRead
BV1446Al_ParamErr_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Parameters ErrorRead
BV1447Al_ParamErr_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Parameters ErrorRead
BV1448Al_ParamErr_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Parameters ErrorRead
BV1449AL_ParametersCRC_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - Parameters CRCRead
BV1450AL_ParametersCRC_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - Parameters CRCRead
BV1451AL_ParametersCRC_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - Parameters CRCRead
BV1452AL_ParametersCRC_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - Parameters CRCRead
BV1453AL_ParametersCRC_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - Parameters CRCRead
BV1454AL_ParametersCRC_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - Parameters CRCRead
BV1455AL_ParametersCRC_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - Parameters CRCRead
BV1456AL_ParametersCRC_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - Parameters CRCRead
BV1457AL_ParametersCRC_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - Parameters CRCRead
BV1458AL_ParametersCRC_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - Parameters CRCRead
BV1459AL_ParametersCRC_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - Parameters CRCRead
BV1460AL_ParametersCRC_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - Parameters CRCRead
BV1461AL_ParametersCRC_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - Parameters CRCRead
BV1462AL_ParametersCRC_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - Parameters CRCRead
BV1463AL_ParametersCRC_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - Parameters CRCRead
BV1464AL_ParametersCRC_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - Parameters CRCRead
BV1465AL_ParametersCRC_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - Parameters CRCRead
BV1466AL_ParametersCRC_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - Parameters CRCRead
BV1467AL_ParametersCRC_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - Parameters CRCRead
BV1468AL_ParametersCRC_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - Parameters CRCRead
BV1469AL_PhaseLoss_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - Phase LossRead
BV1470AL_PhaseLoss_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - Phase LossRead
BV1471AL_PhaseLoss_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - Phase LossRead
BV1472AL_PhaseLoss_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - Phase LossRead
BV1473AL_PhaseLoss_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - Phase LossRead
BV1474AL_PhaseLoss_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - Phase LossRead
BV1475AL_PhaseLoss_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - Phase LossRead
BV1476AL_PhaseLoss_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - Phase LossRead
BV1477AL_PhaseLoss_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - Phase LossRead
BV1478AL_PhaseLoss_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - Phase LossRead
BV1479AL_PhaseLoss_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - Phase LossRead
BV1480AL_PhaseLoss_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - Phase LossRead
BV1481AL_PhaseLoss_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - Phase LossRead
BV1482AL_PhaseLoss_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - Phase LossRead
BV1483AL_PhaseLoss_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - Phase LossRead
BV1484AL_PhaseLoss_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - Phase LossRead
BV1485AL_PhaseLoss_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - Phase LossRead
BV1486AL_PhaseLoss_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - Phase LossRead
BV1487AL_PhaseLoss_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - Phase LossRead
BV1488AL_PhaseLoss_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - Phase LossRead
BV1489Al_PhLost_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Phase LostRead
BV1490Al_PhLost_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Phase LostRead
BV1491Al_PhLost_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Phase LostRead
BV1492Al_PhLost_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Phase LostRead
BV1493Al_PhLost_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Phase LostRead
BV1494Al_PhLost_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Phase LostRead
BV1495Al_PhLost_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Phase LostRead
BV1496Al_PhLost_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Phase LostRead
BV1497Al_PhLost_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Phase LostRead
BV1498Al_PhLost_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Phase LostRead
BV1499Al_PhLost_Rotary.ActiveAL - Alarm - Rotary - Phase LostRead
BV1500Al_PhLost_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Phase LostRead
BV1501Al_PhLost_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Phase LostRead
BV1502Al_PhLost_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Phase LostRead
BV1503Al_PhLost_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Phase LostRead
BV1504Al_PhLost_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Phase LostRead
BV1505Al_PhLost_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Phase LostRead
BV1506Al_PhLost_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Phase LostRead
BV1507Al_PhLost_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Phase LostRead
BV1508Al_PhLost_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Phase LostRead
BV1509Al_PhLost_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Phase LostRead
BV1510Al_PhOpen_ExhFan_1.ActiveAL - Alarm - Fan Return 1 - Phase OpenRead
BV1511Al_PhOpen_ExhFan_10.ActiveAL - Alarm - Fan Return 10 - Phase OpenRead
BV1512Al_PhOpen_ExhFan_2.ActiveAL - Alarm - Fan Return 2 - Phase OpenRead
BV1513Al_PhOpen_ExhFan_3.ActiveAL - Alarm - Fan Return 3 - Phase OpenRead
BV1514Al_PhOpen_ExhFan_4.ActiveAL - Alarm - Fan Return 4 - Phase OpenRead
BV1515Al_PhOpen_ExhFan_5.ActiveAL - Alarm - Fan Return 5 - Phase OpenRead
BV1516Al_PhOpen_ExhFan_6.ActiveAL - Alarm - Fan Return 6 - Phase OpenRead
BV1517Al_PhOpen_ExhFan_7.ActiveAL - Alarm - Fan Return 7 - Phase OpenRead
BV1518Al_PhOpen_ExhFan_8.ActiveAL - Alarm - Fan Return 8 - Phase OpenRead
BV1519Al_PhOpen_ExhFan_9.ActiveAL - Alarm - Fan Return 9 - Phase OpenRead
BV1520Al_PhOpen_Rotary.ActiveAL - Alarm - Rotary - Phase OpenRead
BV1521Al_PhOpen_SupFan_1.ActiveAL - Alarm - Fan Supply 1 - Phase OpenRead
BV1522Al_PhOpen_SupFan_10.ActiveAL - Alarm - Fan Supply 10 - Phase OpenRead
BV1523Al_PhOpen_SupFan_2.ActiveAL - Alarm - Fan Supply 2 - Phase OpenRead
BV1524Al_PhOpen_SupFan_3.ActiveAL - Alarm - Fan Supply 3 - Phase OpenRead
BV1525Al_PhOpen_SupFan_4.ActiveAL - Alarm - Fan Supply 4 - Phase OpenRead
BV1526Al_PhOpen_SupFan_5.ActiveAL - Alarm - Fan Supply 5 - Phase OpenRead
BV1527Al_PhOpen_SupFan_6.ActiveAL - Alarm - Fan Supply 6 - Phase OpenRead
BV1528Al_PhOpen_SupFan_7.ActiveAL - Alarm - Fan Supply 7 - Phase OpenRead
BV1529Al_PhOpen_SupFan_8.ActiveAL - Alarm - Fan Supply 8 - Phase OpenRead
BV1530Al_PhOpen_SupFan_9.ActiveAL - Alarm - Fan Supply 9 - Phase OpenRead
BV1531Al_PreHeatCoilTempPrb.ActiveAL - Alarm - Probe - Temperature Water PreHeating CoilRead
BV1532Al_RDT_Fan.ActiveAL - Alarm - Fan GroupRead
BV1533Al_RecSupplyTemp.ActiveAL - Alarm - Probe - Supply Recovery TemperatureRead
BV1534Al_ReheatCoilWorkHrsWarn.ActiveAL - Alarm - ReHeatCoil - Works Hour WarningRead
BV1535Al_retain.ActiveAL - Alarm - RetainRead
BV1536Al_RetAir_CO2_Lev_Prb.ActiveAL - Alarm - Probe - CO2 Return Level ProbeRead
BV1537Al_RetAirFlwSwWarn.ActiveAL - Alarm - Probe - Air Flow Return SW WarningRead
BV1538Al_RetAirP_Prb.ActiveAL - Alarm - Probe - Pressure Return AirRead
BV1539Al_RetFanWorkHrsWarn.ActiveAL - Alarm - Fan Return - Works Hour WarningRead
BV1540Al_RetFilt.ActiveAL - Alarm - Filter - ReturnRead
BV1541Al_RetTempPrb.ActiveAL - Alarm - Probe - Return TemperatureRead
BV1542Al_SupplyAirFlwSwWarn.ActiveAL - Alarm - Probe - Supply Air Flow SW WarningRead
BV1543Al_SupplyAirP_Prb.ActiveAL - Alarm - Probe - Supply Air PressureRead
BV1544Al_SupplyFanWorkHrsWarn.ActiveAL - Alarm - Fan Supply - Works Hour WarningRead
BV1545Al_SupplyFilt.ActiveAL - Alarm - Filter - SupplyRead
BV1546Al_SupplyTempPrb.ActiveAL - Alarm - Probe - Supply TemperatureRead
BV1547Al_SwPrototype.ActiveAL - Alarm - Software Version - PrototypeRead
BV1548Al_ThTune_ClkBrd.ActiveAL - Alarm - HMI Basic - Clock BoardRead
BV1549Al_ThTune_HumPrb.ActiveAL - Alarm - HMI Basic - Humidity ProbeRead
BV1550Al_ThTune_TempPrb.ActiveAL - Alarm - HMI Basic - Temperature ProbeRead
BV1551Al_TooHot_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - TooHotRead
BV1552Al_TooHot_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - TooHotRead
BV1553Al_TooHot_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - TooHotRead
BV1554Al_TooHot_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - TooHotRead
BV1555Al_TooHot_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - TooHotRead
BV1556Al_TooHot_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - TooHotRead
BV1557Al_TooHot_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - TooHotRead
BV1558Al_TooHot_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - TooHotRead
BV1559Al_TooHot_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - TooHotRead
BV1560Al_TooHot_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - TooHotRead
BV1561Al_TooHot_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - TooHotRead
BV1562Al_TooHot_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - TooHotRead
BV1563Al_TooHot_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - TooHotRead
BV1564Al_TooHot_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - TooHotRead
BV1565Al_TooHot_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - TooHotRead
BV1566Al_TooHot_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - TooHotRead
BV1567Al_TooHot_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - TooHotRead
BV1568Al_TooHot_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - TooHotRead
BV1569Al_TooHot_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - TooHotRead
BV1570Al_TooHot_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - TooHotRead
BV1571Al_Undervoltage_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - UndervoltageRead
BV1572Al_Undervoltage_EC_ExhFan10.ActiveAL - Alarm - Fan Return 10 EC - UndervoltageRead
BV1573Al_Undervoltage_EC_ExhFan2.ActiveAL - Alarm - Fan Return 2 EC - UndervoltageRead
BV1574Al_Undervoltage_EC_ExhFan3.ActiveAL - Alarm - Fan Return 3 EC - UndervoltageRead
BV1575Al_Undervoltage_EC_ExhFan4.ActiveAL - Alarm - Fan Return 4 EC - UndervoltageRead
BV1576Al_Undervoltage_EC_ExhFan5.ActiveAL - Alarm - Fan Return 5 EC - UndervoltageRead
BV1577Al_Undervoltage_EC_ExhFan6.ActiveAL - Alarm - Fan Return 6 EC - UndervoltageRead
BV1578Al_Undervoltage_EC_ExhFan7.ActiveAL - Alarm - Fan Return 7 EC - UndervoltageRead
BV1579Al_Undervoltage_EC_ExhFan8.ActiveAL - Alarm - Fan Return 8 EC - UndervoltageRead
BV1580Al_Undervoltage_EC_ExhFan9.ActiveAL - Alarm - Fan Return 9 EC - UndervoltageRead
BV1581Al_Undervoltage_EC_SupFan1.ActiveAL - Alarm - Fan Supply 1 EC - UndervoltageRead
BV1582Al_Undervoltage_EC_SupFan10.ActiveAL - Alarm - Fan Supply 10 EC - UndervoltageRead
BV1583Al_Undervoltage_EC_SupFan2.ActiveAL - Alarm - Fan Supply 2 EC - UndervoltageRead
BV1584Al_Undervoltage_EC_SupFan3.ActiveAL - Alarm - Fan Supply 3 EC - UndervoltageRead
BV1585Al_Undervoltage_EC_SupFan4.ActiveAL - Alarm - Fan Supply 4 EC - UndervoltageRead
BV1586Al_Undervoltage_EC_SupFan5.ActiveAL - Alarm - Fan Supply 5 EC - UndervoltageRead
BV1587Al_Undervoltage_EC_SupFan6.ActiveAL - Alarm - Fan Supply 6 EC - UndervoltageRead
BV1588Al_Undervoltage_EC_SupFan7.ActiveAL - Alarm - Fan Supply 7 EC - UndervoltageRead
BV1589Al_Undervoltage_EC_SupFan8.ActiveAL - Alarm - Fan Supply 8 EC - UndervoltageRead
BV1590Al_Undervoltage_EC_SupFan9.ActiveAL - Alarm - Fan Supply 9 EC - UndervoltageRead
BV1591CfgErrAlrm.ActiveAL - Alarm - Device - Wrong configurationRead
BV1592Al_MotorFault_EC_ExhFan1.ActiveAL - Alarm - Fan Return 1 EC - Motor FaultRead
BV1593OfflineAlrm.ActiveAL - Alarm - Device - OfflineRead
BV1594Al_Offline_IO_PCB.ActiveAL - Alarm - Module IO - EC-PCB - OfflineRead
BV1595Al_DXRev.ActiveAL - Alarm - Reverse unitRead
BV1596Al_WarningFilterHigh.ActiveAL - Alarm - Filter - High pressureRead
BV1597Al_RRG_WorkConfirm.ActiveAL - Alarm - Recovery - Rotary - Work confirmRead
BV1598Al_ClkBrd_THTN_1.ActiveAL - Alarm - HMI Basic - Clock BoardRead
BV1599Al_ClkBrd_THTN_1.TriggerAL - Alarm - HMI Basic - Clock BoardRead
BV1600Al_DXRev.TriggerAL - Alarm - Reverse unitRead
BV1601Al_HumPrb_THTN_1.ActiveAL - Alarm - HMI Basic - Humidity sensorRead
BV1602Al_HumPrb_THTN_1.TriggerAL - Alarm - HMI Basic - Humidity sensorRead
BV1603Al_Offline_IO_PCB.TriggerAL - Alarm - Module IO - EC-PCB - OfflineRead
BV1604Al_RRG_WorkConfirm.TriggerAL - Alarm - Recovery - Rotary - Work confirmRead
BV1605Al_TempPrb_THTN_1.ActiveAL - Alarm - HMI Basic - Temperature sensorRead
BV1606Al_TempPrb_THTN_1.TriggerAL - Alarm - HMI Basic - Temperature sensorRead
BV1607Al_WarningFilterHigh.TriggerAL - Alarm - Filter - Pressure HighRead
BV1608CfgErrAlrm_CPCOE_1.ActiveAL - Alarm - Module IO - cPCOE - ConfigurationRead
BV1609CfgErrAlrm_CPCOE_1.TriggerAL - Alarm - Module IO - cPCOE - ConfigurationRead
BV1610OfflineAlrm_CPCOE_1.ActiveAL - Alarm - Module IO - cPCOE - OfflineRead
BV1611OfflineAlrm_CPCOE_1.TriggerAL - Alarm - Module IO - cPCOE - OfflineRead
PIV537DayInCLK - Time - Setting - Day (1 - 31)Write
BV1612EnDateCLK - Time - Setting - Change EnableWrite0=NO; 1=YES
PIV538GeneralMng.Zone_TZCLK - Time - Setting - ZoneWrite
PIV539HourInCLK - Time - Setting - HourhWrite
PIV540MinuteInCLK - Time - Setting - Minutemin.Write
PIV541MonthInCLK - Time - Setting - Month (1 - 12)Write
PIV542SecondInCLK - Time - Setting - Secondsec.Write
PIV543YearInCLK - Time - Setting - Year (0 - 99)Write
PIV544DayCLK - Time - Day (1 - 31)Read
PIV545DayOfWeekCLK - Time - Setting - Day of WeekRead1=MON; 2=TUE; 3=WED; 4=THU; 5=FRI; 6=SAT; 7=SUN
PIV546HourCLK - Time - HourhRead
PIV547MinuteCLK - Time - Minutemin.Read
PIV548MonthCLK - Time - Month (1 - 12)Read
PIV549SecondCLK - Time - Secondsec.Read
PIV550YearCLK - Time - Year (0 - 99)Read
AV240AlrmExhAirP_MskPAR - Fan - Return - Warning Threshold Air PressurePaWrite
AV241AlrmSupplyAirP_MskPAR - Fan - Supply - Warning Threshold Air PressurePaWrite
AV242AFreezeExtMaxTempPAR - Heating - Antifreeze - External Temperature - Maximum°CWrite
AV243AFreezeExtMinTempPAR - Heating - Antifreeze - External Temperature - Minimum°CWrite
AV244AfreezeHeatMaxPAR - Heating - Antifreeze - Valve Open - Maximum (0 - 100 %)%Write
PIV551AFreezeHeatMaxTPAR - Heating - Antifreeze - Time - Maximumsec.Write
AV245AfreezeHeatMinPAR - Heating - Antifreeze - Valve Open - Minimum (0 - 100 %)%Write
PIV552AFreezeHeatMinTPAR - Heating - Antifreeze - Time - Minimumsec.Write
AV246AlrmExhAirPPAR - Fan - Return - Warning Threshold PressurePaWrite
AV247AlrmSupplyAirPPAR - Fan - Supply - Warning Threshold PressurePaWrite
BV1613Cool_1.LogicPAR - Cooling - Main Cooler - LogicWrite0=NC; 1=NO
PIV553Cool_1.ManPAR - Cooling - Main Cooler - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
BV1614Cool_2.LogicPAR - Cooling - Main Cooler DX - LogicWrite0=NC; 1=NO
PIV554Cool_2.ManPAR - Cooling - Main Cooler DX - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
PIV555CoolDX_ResTypPAR - Cooling - Main Cooler DX - Operating BlockWrite0=NONE; 1=ECO; 2=ECO + OPTIMAL
AV248CoolExtTempThrshPAR - Regulation - ChangeOver - External Temperature - Cool Threshold°CWrite
PIV556CoolMinOffTPAR - Cooling - Main Cooler DX - Time - Minimum OFFsec.Write
PIV557CoolMinOnOnSameTPAR - Cooling - Main Cooler DX - Time - Between startssec.Write
PIV558CoolMinOnTPAR - Cooling - Main Cooler DX - Time - Minimum ONsec.Write
PIV559CoolVlv.ManPAR - Cooling - Main Cooler - Manual Analog (0 - 100 %)%Write
AV249DeltaDew_PID.KpPAR - Regulation PID - Humidity - Dewpoint - Proportional gainKpWrite
PIV560DeltaDew_PID.TiPAR - Regulation PID - Humidity - Dewpoint - Integral timeTi - sec.Write
AV250DeltaDewTempPAR - Regulation PID - Humidity - Dewpoint - Delta (0 - 100 %)%Write
AV251DevCfg_PID_Seq_CO2[0].KpPAR - Regulation PID - CO2 Mixing - Proportional gainKpWrite
PIV561DevCfg_PID_Seq_CO2[0].TiPAR - Regulation PID - CO2 Mixing - Integral timeTi - sec.Write
AV252DevCfg_PID_Seq_CO2[1].KpPAR - Regulation PID - CO2 Fan Compensation - Proportional gainKpWrite
PIV562DevCfg_PID_Seq_CO2[1].TiPAR - Regulation PID - CO2 Fan Compensation - Integral timeTi - sec.Write
AV253DevCfg_PID_Seq_Cool[2].KpPAR - Regulation PID - Recovery - Cooling - Proportional gainKpWrite
PIV563DevCfg_PID_Seq_Cool[2].TiPAR - Regulation PID - Recovery - Cooling - Integral timeTi - sec.Write
AV254DevCfg_PID_Seq_Cool[4].KpPAR - Regulation PID - Main Cooler - Proportional gainKpWrite
PIV564DevCfg_PID_Seq_Cool[4].TiPAR - Regulation PID - Main Cooler - Integral timeTi - sec.Write
AV255DevCfg_PID_Seq_Cool[5].KpPAR - Regulation PID - Mixing - Cooling - Proportional gainKpWrite
PIV565DevCfg_PID_Seq_Cool[5].TiPAR - Regulation PID - Mixing - Cooling - Integral timeTi - sec.Write
AV256DevCfg_PID_Seq_Heat[2].KpPAR - Regulation PID - Recovery - Heating - Proportional gainKpWrite
PIV566DevCfg_PID_Seq_Heat[2].TiPAR - Regulation PID - Recovery - Heating - Integral timeTi - sec.Write
AV257DevCfg_PID_Seq_Heat[4].KpPAR - Regulation PID - Main Heater - Proportional gainKpWrite
PIV567DevCfg_PID_Seq_Heat[4].TiPAR - Regulation PID - Main Heater - Integral timeTi - sec.Write
AV258DevCfg_PID_Seq_Heat[5].KpPAR - Regulation PID - Mixing - Heating - Proportional gainKpWrite
PIV568DevCfg_PID_Seq_Heat[5].TiPAR - Regulation PID - Mixing - Heating - Integral timeTi - sec.Write
AV259DevCfg_PID_Seq_Heat[6].KpPAR - Regulation PID - ReHeating - Proportional gainKpWrite
PIV569DevCfg_PID_Seq_Heat[6].TiPAR - Regulation PID - ReHeating - Integral timeTi - sec.Write
PIV570DOff_ExhFanPAR - Fan - Return - Time - OFF Delaysec.Write
PIV571DOff_SupplyFanPAR - Fan - Supply - Time - OFF Delaysec.Write
PIV572DT_ChangeHumPAR - Humidity - Time - Change Delaysec.Write
PIV573DT_DmpPAR - Fan - Supply - Time - OFF Dampersec.Write
PIV574DT_ExhFanPAR - Fan - Return - Time - ON Delaysec.Write
PIV575DT_SupplyFanPAR - Fan - Supply - Time - ON Delaysec.Write
BV1615En_CoolRecPAR - Recovery - Cooling - EnableWrite0=NO; 1=YES
BV1616En_FreeCoolHeatPAR - System - Free Cool/Heat - EnableWrite0=NO; 1=YES
BV1617En_Rev_MixDamperPAR - Mixing damper - Reverse signalWrite0=NO; 1=YES
BV1618En_Rev_RecoveryPAR - Recovery - Reverse signalWrite0=NO; 1=YES
AV260ExhAirFlowSet_MskPAR - Fan - Return - Flow - Maximum (For airflow < 32767)m3/hWrite
AV261ExhAirPSet_MskPAR - Fan - Return - Pressure - MaximumPaWrite
AV262FastCoolThrshPAR - Recovery - Cooling Limit (0 - 100 %)%Write
BV1619FastHeatEnPAR - Recovery - Fast Heating - EnableWrite0=NO; 1=YES
BV1620FastHeatStopPAR - Recovery - Stop Fast Heat - EnableWrite0=NO; 1=YES
PIV576FastHeatTPAR - Recovery - Startup Timesec.Write
AV263FastHeatThrshPAR - Recovery - Heating Limit (0 - 100 %)%Write
BV1621FastHeatTrigPAR - Recovery - Start Fast Heat - EnableWrite0=NO; 1=YES
AV264FilterF7_MaxPAR - Filter - Maximum pressure F7PaWrite
AV265FilterF9_MaxPAR - Filter - Maximum pressure F9PaWrite
AV266FilterPG4_MaxPAR - Filter - Maximum pressure PG4PaWrite
IV577FilterRet_TypePAR - Filter - Return typeWrite0=None; 1=PG4/G4; 2=M5/F7; 3=F9
IV578FilterSup_TypePAR - Filter - Supply typeWrite0=None; 1=PG4/G4; 2=M5/F7; 3=F9
AV267FireExhSpeedPAR - Fan - Fire Setting - Return Speed (0 - 100 %)%Write
AV268FireSupplySpeedPAR - Fan - Fire Setting - Supply Speed (0 - 100 %)%Write
AV269FireThrshPAR - Fan - Fire Setting - Threshold°CWrite
BV1622HC_Cool_1.ResPAR - Cooling - Main Cooler - ResetWrite0=NO; 1=YES
BV1623HC_Cool_2.ResPAR - Cooling - Main Cooler DX - ResetWrite0=NO; 1=YES
BV1624HC_ExhFan_1.ResPAR - Fan - Return 1 - ResetWrite0=NO; 1=YES
BV1625HC_ExhFan_2.ResPAR - Fan - Return 2 - ResetWrite0=NO; 1=YES
BV1626HC_Heat_1.ResPAR - Heating - Main Heater - ResetWrite0=NO; 1=YES
BV1627HC_Heat_2.ResPAR - Heating - Main Device 2 - ResetWrite0=NO; 1=YES
BV1628HC_Hum.ResPAR - Humidity - ResetWrite0=NO; 1=YES
BV1629HC_PreHeat.ResPAR - Heating - PreHeating - ResetWrite0=NO; 1=YES
BV1630HC_RecoveryPump.ResPAR - Recovery - ResetWrite0=NO; 1=YES
BV1631HC_ReHeat.ResPAR - Heating - ReHeating - ResetWrite0=NO; 1=YES
BV1632HC_SupplyFan_1.ResPAR - Fan - Supply 1 - ResetWrite0=NO; 1=YES
BV1633HC_SupplyFan_2.ResPAR - Fan - Supply 2 - ResetWrite0=NO; 1=YES
AV270HE_Pwr[0]PAR - Heating - Main Heater - Maximum Power Modulating (0 - 100 %)%Write
AV271HE_Pwr[1]PAR - Heating - Main Heater - Maximum Power 1 Stage (0 - 100 %)%Write
AV272HE_Pwr[2]PAR - Heating - Main Heater - Maximum Power 2 Stage (0 - 100 %)%Write
BV1634Heat_1.LogicPAR - Heating - Main Heater - LogicWrite0=NC; 1=NO
PIV579Heat_2.ManPAR - Heating - Main Device 2 - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
AV273HeatExtTempThrshPAR - Regulation - ChangeOver - External Temperature - Heat Threshold°CWrite
PIV580HeatMinOffTPAR - Heating - Main Heater DX - Time - Minimum OFFsec.Write
PIV581HeatMinOnOnSameTPAR - Heating - Main Heater DX - Time - Between startssec.Write
PIV582HeatMinOnTPAR - Heating - Main Heater DX - Time - Minimum ONsec.Write
PIV583HeatRecovery.ManPAR - Recovery - Manual Analog (0 - 100 %)%Write
PIV584HeatVlv.ManPAR - Heating - Main Heater - Manual Analog (0 - 100 %)%Write
BV1635Hum.LogicPAR - Humidity - LogicWrite0=NC; 1=NO
PIV585Hum.ManPAR - Humidity - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
AV274Hum_PID.DeadBandPAR - Regulation PID - Humidity - DeadBandg/m3Write
AV275Hum_PID.KpPAR - Regulation PID - Humidity - Proportional gainKpWrite
PIV586Hum_PID.TiPAR - Regulation PID - Humidity - Integral timeTi - sec.Write
AV276HW_SetPAR - Heating - Main Water - SetPoint°CWrite
PIV587IdleT_ExhFanPAR - Fan - Return - Idle Timesec.Write
PIV588IdleT_SupplyFanPAR - Fan - Supply - Idle Timesec.Write
AV277K_FactorExhPAR - Fan - Return - K-FactorWrite
PIV589K_FactorExhCodePAR - Fan - Return - Fan CodeWrite0=CUSTOM; 1=VS-225; 2=VS-250; 3=VS-315; 4=VS-355; 5=VS-400; 6=VS-450; 7=VS-500; 8=VS-560; 9=VS-630
AV278K_FactorSupplyPAR - Fan - Supply - K-FactorWrite
PIV590K_FactorSupplyCodePAR - Fan - Supply - Fan CodeWrite0=CUSTOM; 1=VS-225; 2=VS-250; 3=VS-315; 4=VS-355; 5=VS-400; 6=VS-450; 7=VS-500; 8=VS-560; 9=VS-630
AV279LowSupplyTempThrshPAR - Heating - Supply Limit - Threshold°CWrite
AV280MainCoolMinPAR - Cooling - Main Cooler - Minimum Power (0 - 100 %)%Write
AV281MainCW_MinPIDPAR - Cooling - Main Cooler Water - Minimum Valve Signal (0 - 100 %)%Write
AV282MainHeatMinPAR - Heating - Main Heater - Minimum Power (0 - 100 %)%Write
AV283MainHW_MinPIDPAR - Heating - Main Water - Minimum Valve Singal (0 - 100 %)%Write
AV284ManExhFanIdlePAR - Fan - Return - Idle Power (0 - 100 %)%Write
AV285ManSupplyFanIdlePAR - Fan - Supply - Idle Power (0 - 100 %)%Write
AV286MinHeatRecPAR - Recovery - Heating - Minimum Power (0 - 100 %)%Write
PIV591ModulHum.ManPAR - Humidity - Manual Analog (0 - 100 %)%Write
PIV592ModulMixDamp.ManPAR - Mix Damper - Manual Analog (0 - 100 %)%Write
AV287ModulMixDampMaxValPAR - Mix Damper - Limits - Maximum Openning (0 - 100 %)%Write
AV288ModulMixDampMinValPAR - Mix Damper - Limits - Minimum Openning (0 - 100 %)%Write
PIV593ModulPreHeat.ManPAR - Heating - PreHeating - Manual Analog (0 - 100 %)%Write
PIV594NightKickHourPAR - System - Night Kick Time - HourhWrite
PIV595NightKickMinutePAR - System - Night Kick Time - Minutemin.Write
AV289PID_Exh.KpPAR - Regulation PID - Fan Return - Proportional gainKpWrite
PIV596PID_Exh.TdPAR - Regulation PID - Fan Return - Derivative timeTd - sec.Write
PIV597PID_Exh.TiPAR - Regulation PID - Fan Return - Integral timeTi - sec.Write
AV290PID_FrostProt.KpPAR - Regulation PID - Recovery - Frost - Proportional gainKpWrite
AV291PID_FrostProt.SetPPAR - Recovery - Frost Protection - SetPoint°CWrite
PIV598PID_FrostProt.TiPAR - Regulation PID - Recovery - Frost - Integral timeTi - sec.Write
AV292PID_HeatHW.KpPAR - Regulation PID - Main Water - Proportional gainKpWrite
PIV599PID_HeatHW.TiPAR - Regulation PID - Main Water - Integral timeTi - sec.Write
AV293PID_PreHeatCoil.KpPAR - Regulation PID - PreHeating - Proportional gainKpWrite
PIV600PID_PreHeatCoil.TiPAR - Regulation PID - PreHeating - Integral timeTi - sec.Write
AV294PID_PreHeatHW.KpPAR - Regulation PID - PreHeater Water - Proportional gainKpWrite
PIV601PID_PreHeatHW.TiPAR - Regulation PID - PreHeater Water - Integral timeTi - sec.Write
AV295PID_Supply.KpPAR - Regulation PID - Fan Supply - Proportional gainKpWrite
PIV602PID_Supply.TdPAR - Regulation PID - Fan Supply - Derivative timeTd - sec.Write
PIV603PID_Supply.TiPAR - Regulation PID - Fan Supply - Integral timeTi - sec.Write
BV1636PreHeaterPump.LogicPAR - Heating - PreHeating - LogicWrite0=NC; 1=NO
PIV604PreHeaterPump.ManPAR - Heating - PreHeating - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
AV296PreHeatHE_Pwr[0]PAR - Heating - PreHeating - Maximum Power Modulating (0 - 100 %)%Write
AV297PreHeatHE_Pwr[1]PAR - Heating - PreHeating - Maximum Power 1 Stage (0 - 100 %)%Write
AV298PreHeatMinPAR - Heating - PreHeating - Minimum Power (0 - 100 %)%Write
PIV605PreHeatMinOffTPAR - Heating - PreHeating DX - Time - Minimum OFFsec.Write
PIV606PreheatMinOnOnSameTPAR - Heating - PreHeating DX - Time - Between startssec.Write
PIV607PreHeatMinOnTPAR - Heating - PreHeating DX - Time - Minimum ONsec.Write
IV608PreHeatRotConf.DevNoPerCircPAR - Heating - PreHeating - TypeWrite1=MODULATING; 2=MOD. + 1 STAGE
AV299PreHeatSetPAR - Heating - PreHeater Water - SetPoint°CWrite
AV300PreHW_MinPIDPAR - Heating - PreHeater Water - Minimum Valve Signal (0 - 100 %)%Write
AV301Rec_MinPIDPAR - Recovery - Heating - Minimum Recovery (0 - 100 %)%Write
BV1637RecoveryPump.LogicPAR - Recovery - LogicWrite0=NC; 1=NO
PIV609RecoveryPump.ManPAR - Recovery - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
BV1638ReHeat.LogicPAR - Heating - ReHeating - LogicWrite0=NC; 1=NO
PIV610ReHeat.ManPAR - Heating - ReHeating - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
AV302ReHeatHE_Pwr[0]PAR - Heating - ReHeating - Maximum Power Modulating (0 - 100 %)%Write
AV303ReHeatHE_Pwr[1]PAR - Heating - ReHeating - Maximum Power 1 Stage (0 - 100 %)%Write
AV304ReHeatMinPAR - Heating - ReHeating - Minimum Power (0 - 100 %)%Write
PIV611ReHeatMinOffTPAR - Heating - ReHeater DX - Time - Minimum OFFsec.Write
PIV612ReHeatMinOnOnSameTPAR - Heating - ReHeater DX - Time - Between startssec.Write
PIV613ReHeatMinOnTPAR - Heating - ReHeater DX - Time - Minimum ONsec.Write
IV614ReHeatRotConf.CompMinPwrPAR - Heating - ReHeating - Minimum Power (0 - 100 %)%Write
IV615ReHeatRotConf.DevNoPerCircPAR - Heating - ReHeating - TypeWrite1=MODULATING; 2=MOD. + 1 STAGE
PIV616ReHeatVlv.ManPAR - Heating - ReHeating - Manual Analog (0 - 100 %)%Write
AV305ReHW_MinPIDPAR - Heating - ReHeating - Minimum Valve Signal (0 - 100 %)%Write
AV306Ret_NrPolePAR - Fan - Return - Number of poleWrite
BV1639RevOut_1.LogicPAR - Heating - Reverse Device 1 - LogicWrite0=NC; 1=NO
PIV617RevOut_1.ManPAR - Heating - Reverse Device 1 - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
BV1640RevOut_2.LogicPAR - Heating - Reverse Device 2 - LogicWrite0=NC; 1=NO
PIV618RevOut_2.ManPAR - Heating - Reverse Device 2 - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
PIV619RevOutVlv.ManPAR - Heating - Reverse Device 1 - Manual Analog (0 - 100 %)%Write
AV307RoomReg_SetP_Offs_KpPAR - Regulation PID - Room Compnsation - Proportional gainKpWrite
PIV620RoomReg_SetP_Offs_TiPAR - Regulation PID - Room Compnsation - Integral timesec.Write
IV621RotConf.CompMinPwrPAR - Heating - Main Heater - Minimum Power (0 - 100 %)%Write
IV622RotConf.DevNoPerCircPAR - Heating - Main Heater - TypeWrite1=MODULATING; 2=MOD. + 1 STAGE; 3=MOD. + 2 STAGES
AV308RRG_NrPolePAR - Recovery - Rotary - Numver of poleWrite
AV309SetMaxLimitPAR - Regulation - Limits - Return / Room - Maximum°CWrite
AV310SetMinLimitPAR - Regulation - Limits - Return / Room - Minimum°CWrite
PIV623StandbyTPAR - System - StandBy - Timesec.Write
AV311StartHumPercPAR - Humidity - Digital - Start (0 - 100 %)%Write
AV312StopHumPercPAR - Humidity - Digital - Stop (0 - 100 %)%Write
AV313Sup_NrPolePAR - Fan - Supply - Number of poleWrite
AV314SupplyAirFlowSet_MskPAR - Fan - Supply - Flow - Maximum (For airflow < 32767)m3/hWrite
AV315SupplyAirPSet_MskPAR - Fan - Supply - Pressure - MaximumPaWrite
AV316SupplyDewPointPAR - Humidity - Supply Dewpoint°CWrite
AV317SupplyFanMaxPAR - CO2 - Fan Compensation - Max Air-Flow Quality (0 - 100 %)%Write
AV318SupplyMaxSetPAR - Regulation - Limits - Temperature Supply - Maximum°CWrite
AV319SupplyMinSetPAR - Regulation - Limits - Temperature Supply - Minimum°CWrite
PIV624SupplyTemp_CoolHeatDTPAR - Regulation - ChangeOver - External Temperature - Time Delaysec.Write
AV320ThrshOffCool_1PAR - Cooling - Main Cooler DX - Stop Step 1 (0 - 100 %)%Write
AV321ThrshOffCool_2PAR - Cooling - Main Cooler DX - Stop Step 2 (0 - 100 %)%Write
AV322ThrshOffHeat_1PAR - Heating - Main Heater DX - Stop Step 1 (0 - 100 %)%Write
AV323ThrshOffHeat_2PAR - Heating - Main Heater DX - Stop Step 2 (0 - 100 %)%Write
AV324ThrshOnCool_1PAR - Cooling - Main Cooler DX - Start Step 1 (0 - 100 %)%Write
AV325ThrshOnCool_2PAR - Cooling - Main Cooler DX - Start Step 2 (0 - 100 %)%Write
AV326ThrshOnHeat_1PAR - Heating - Main Heater DX - Start Step 1 (0 - 100 %)%Write
AV327ThrshOnHeat_2PAR - Heating - Main Heater DX - Start Step 2 (0 - 100 %)%Write
AV328W_HeatFreezeSetPAR - Heating - Main Water - Frreeze SetPoint°CWrite
AV329W_PreHeatFreezeSetPAR - Heating - PreHeater Water - Freeze SetPoint°CWrite
PIV625WakeUpTPAR - System - Wake Up - Timesec.Write
AV330WarnThrshExhFlw_MskPAR - Fan - Return - Warning Threshold Air Flowm3/hWrite
AV331WarnThrshSupplyFlw_MskPAR - Fan - Supply - Warning Threshold Air Flowm3/hWrite
AV332AbsHumPAR - Humidity - ABS Humidityg/m3Read
AV333AbsHumSetPAR - Humidity - ABS SetPointg/m3Read
AV334AfterPreHeatReqPAR - Regulation PID - PreHeating - Output (0 - 100 %)%Read
AV335AirQualFanPAR - Regulation PID - CO2 Fan Compensation - Output (0 - 100 %)%Read
AV336AirQualReq_1PAR - Regulation PID - CO2 Mixing - Output (0 - 100 %)%Read
AV337Cooling_PID_Seq[2]PAR - Regulation PID - Recovery - Cooling - Output (0 - 100 %)%Read
AV338Cooling_PID_Seq[3]PAR - Regulation PID - Reverse - Cooling - Output (0 - 100 %)%Read
AV339Cooling_PID_Seq[4]PAR - Regulation PID - Main Cooler - Output (0 - 100 %)%Read
AV340Cooling_PID_Seq[5]PAR - Regulation PID - Mixing - Cooling - Output (0 - 100 %)%Read
AV341FrostProtReqPAR - Regulation PID - Recovery - Frost - Output (0 - 100 %)%Read
AV342Heating_PID_Seq[2]PAR - Regulation PID - Recovery - Heating - Output (0 - 100 %)%Read
AV343Heating_PID_Seq[3]PAR - Regulation PID - Reverse - Heating - Output (0 - 100 %)%Read
AV344Heating_PID_Seq[4]PAR - Regulation PID - Main Heater - Output (0 - 100 %)%Read
AV345Heating_PID_Seq[5]PAR - Regulation PID - Mixing - Heating - Output (0 - 100 %)%Read
AV346Heating_PID_Seq[6]PAR - Regulation PID - ReHeating - Output (0 - 100 %)%Read
AV347Heating_PID_Seq[7]PAR - Regulation PID - Fan Heating - Output (0 - 100 %)%Read
AV348HumDehumReqPAR - Regulation PID - Humidity - Output (0 - 100 %)%Read
AV349HW_AfreezeReqPAR - Regulation PID - Main Water - Output (0 - 100 %)%Read
AV350PID_DewCompensPAR - Regulation PID - Humidity - Dewpoint - Output (0 - 100 %)%Read
AV351PID_RegCompensPAR - Regulation PID - Room Compnsation - Output (0 - 100 %)%Read
AV352PreW_AfreezeReqPAR - Regulation PID - PreHeater Water - Output (0 - 100 %)%Read
AV353MainHeatMaxPAR - Heating - Main Heater - Maximum Power (0 - 100 %)%Write
AV354RevHeat_Sig_MinPAR - Heating - Reverse Device 1 - Heating - Minimum signal (0 - 100 %)%Write
AV355RevHeat_Sig_MaxPAR - Heating - Reverse Device 1 - Heating - Maximum signal (0 - 100 %)%Write
AV356RevCool_Sig_MinPAR - Heating - Reverse Device 1 - Cooling - Minimum signal (0 - 100 %)%Write
AV357RevCool_Sig_MaxPAR - Heating - Reverse Device 1 - Cooling - Maximum signal (0 - 100 %)%Write
AV358RevTemp_EnPAR - Heating - Reverse Device 1 - Permistion from external temperature°CWrite
AV359ReHeatMaxPAR - Heating - ReHeating - Maximum Power (0 - 100 %)%Write
AV360PreHeatMaxPAR - Heating - PreHeating - Maximum Power (0 - 100 %)%Write
PIV626LowTempAlrmDT_RunPAR - Heating - Supply Limit - Threshold delaysec.Write
BV1641LowSupplyTemp_OffPAR - Heating - Supply Limit - Threshold unit STOPWrite0=NO; 1=YES
BV1642PreHeat_AlwaysPAR - Heating - Main Heater HW - Pre-Heat always startWrite0=NO; 1=YES
AV361MainStartupValuePAR - Heating - Main Heater HW - Pre-Heat always start - Minimum signal (0 -%Write
PIV627HE_Alarm_DelayPAR - Heating - Main Heater HE - Alarm delaysec.Write
AV362Pump_ExtTempPAR - Heating - Main Heater HW - Active pump when external temp lower°CWrite
AV363Valve_ExtTempPAR - Heating - Main Heater HW - Active vavlve when external temp lower°CWrite
AV364MainHW_MinPID_TextPAR - Heating - Main Heater HW - Minimum signal for winter valve (0 - 100%Write
IV628FanFlowAlarm_DelayPAR - Fan - Supply - Warning Threshold Pressure delaysec.Write
PIV629DoubleFanRotTPAR - Fan - Redundant - Time rotationhWrite
BV1643DoubleFanRot_ManualPAR - Fan - Redundant - Manual rotationWrite0=NO; 1=YES
PIV630DoubleDamp.ManPAR - Fan - Redundant - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
BV1644FanTempRegPAR - Fan - Temperature regulation - EnableWrite0=NO; 1=YES
AV365FanTempReg_SigPAR - Fan - Temperature regulation - Output (0 - 100 %)%Write
AV366DevCfg_PID_Seq_Heat[7].KpPAR - Fan - Temperature regulation - Proportional gainKpWrite
PIV631DevCfg_PID_Seq_Heat[7].TiPAR - Fan - Temperature regulation - Integral timeTi - sec.Write
AV367FanTempReg_MaxPAR - Fan - Temperature regulation - Maximum fan signal correction (0 - 100 %)%Write
BV1645RRG_0_10VPAR - Recovery - Rotery - Enable 0-10V on Y3 for RRGWrite0=NO; 1=YES
BV1646En_RRG_AlarmPAR - Recovery - Rotery - Alarm enableWrite0=NO; 1=YES
AV368RRG_MinValueFor_AlPAR - Recovery - Rotery - Minium signal for active power (0 - 100 %)%Write
AV369RRG_MinPower_AlPAR - Recovery - Rotery - Minimum power for alarmWWrite
IV632RRG_Alarm_DelayPAR - Recovery - Rotery - Dlarm delaysec.Write
BV1647Mix_Mode_ECOPAR - Mixing - Manual mode ECO - EnableWrite0=NO; 1=YES
AV370Mix_Val_ECOPAR - Mixing - Manual mode ECO - Signal (0 - 100 %)%Write
BV1648Mix_Mode_OPTIMALPAR - Mixing - Manual mode Optimal - EnableWrite0=NO; 1=YES
AV371Mix_Val_OPTIMALPAR - Mixing - Manual mode Optimal - Signal (0 - 100 %)%Write
BV1649Mix_Mode_COMFORTPAR - Mixing - Manual mode Comfort - EnableWrite0=NO; 1=YES
AV372Mix_Val_COMFORTPAR - Mixing - Manual mode Comfort - Signal (0 - 100 %)%Write
AV373AFreezeHeatOutPAR - Heater - Antifreeze - Output (0 - 100 %)%Write
PIV633AFreezeHeatOutTPAR - Heater - Antifreeze - Output T (0 - 100 %)%Write
PIV634__SYSVA_BEEP_ONSYS - Hardware - Activate Buzzer for a while (Virtual HMI)Write
IV635__SYSVA_CURSOR_COLUMNSYS - Hardware - Display cursor current X coordinate (Virtual HMI)Write
IV636__SYSVA_CURSOR_ROWSYS - Hardware - Display cursor current Y coordinate (Virtual HMI)Write
IV637__SYSVA_CURSOR_VARSYS - Hardware - Display cursor for scrolling lists (Virtual HMI)Write
IV638__SYSVA_KEY_COUNTERSYS - Hardware - Key pressed time (Virtual HMI)Write
PIV639__SYSVA_KEY_PRESSEDSYS - Hardware - Key pressed flag (Virtual HMI)Write
PIV640__SYSVA_MANUAL_BUZZER_OFFSYS - Hardware - Deactivates the alarm buzzer (Virtual HMI)Write
PIV641__SYSVA_MANUAL_BUZZER_ONSYS - Hardware - Activate Buzzer when controlled manually (Virtual HMI)Write
PIV642__SYSVA_TMP_VALUESYS - Hardware - Temp value for field editing (Virtual HMI)Write
BV1650AfterPreHeatCoilTemp.EnabledSYS - IO Setting - Enable Inputs - Temperature - After PreHeatWrite0=NO; 1=YES
PIV643AfterPreHeatCoilTemp.ManSYS - IO Setting - Manual - Temperature - After PreHeat°CWrite0=AUTO; OR 1 - 100%
AV374AfterPreHeatCoilTemp.OffsetSYS - IO Setting - Offset - Temperature - After PreHeat°CWrite
PIV644AppCode_BoardSYS - Application Code - Board - _ _ - _ . _ . _ .Write0=uPC3 XS; 1=uPC3 XS; 2=uPC3 Small; 3=uPC3 XS; 4=uPC3 XS; 5=uPC3 XS; 6=uPC3 XS
PIV645AppCode_CoolSYS - Application Code - Cooling - _ _ - _ . X . _ .Write0=None; 1=Chilled water; 2=DX
PIV646AppCode_EcoSYS - Application Code - ECO - _ _ - _ . _ . _ .Write0=NO; 1=YES
PIV647AppCode_HeatSYS - Application Code - Heating - _ _ - X . _ . _ .Write0=None; 1=Hot water; 2=DX; 3=Electric heater; 4=Steam
PIV648AppCode_HumSYS - Application Code - Humidity - _ _ - _ . _ . _ .Write0=None; 1=Evaporative; 2=Steam
PIV649AppCode_PreHeatSYS - Application Code - PreHeating - _ _ - _ . _ . _ .Write0=None; 1=Hot water; 2=DX; 3=Electric heater
PIV650AppCode_RecSYS - Application Code - Recirculation - XX - _ . _ . _ . _Write0=AS:Supply; 1=AD: S+E; 2=AR: S/E & Rotary; 3=AP: S/E + Cross; 4=AG: S/E + Glycol
PIV651AppCode_ReHeatSYS - Application Code - Recirculation Heating - _ _ - _ . _ . _Write0=None; 1=Hot water; 2=DX; 3=Electric heater
PIV652AppCode_RevSYS - Application Code - Rev - _ _ - _ . _ . X .Write0=None; 1=Hydronic; 2=DX
BV1651AppCool_CWSYS - Application Code - Cooling coilWrite0=NO; 1=YES
BV1652AppCool_DXSYS - Application Code - Direct ExpansionWrite0=NO; 1=YES
BV1653AppEcoSYS - Application Code - Mixing damperWrite0=NO; 1=YES
BV1654AppHeat_DXSYS - Application Code - Heat - Direct ExpansionWrite0=NO; 1=YES
BV1655AppHeat_HESYS - Application Code - Electric HeatingWrite0=NO; 1=YES
BV1656AppHeat_HWSYS - Application Code - Heating CoilWrite0=NO; 1=YES
BV1657AppHeat_SteamSYS - Application Code - Heating SteamWrite0=NO; 1=YES
BV1658AppHum_EvapSYS - Application Code - Humidity - EvapWrite0=NO; 1=YES
BV1659AppHum_SteamSYS - Application Code - Humidity - SteamWrite0=NO; 1=YES
PIV653AppHumRegSYS - Unit Configuration - Humidity RegulationWrite0=NONE; 1=SUPPLY; 2=RETURN; 3=ROOM
BV1660AppPreHeat_DXSYS - Application Code - PreHeat_DXWrite0=NO; 1=YES
BV1661AppPreHeat_HESYS - Application Code - PreHeat_HEWrite0=NO; 1=YES
BV1662AppPreHeat_HWSYS - Application Code - PreHeat_HWWrite0=NO; 1=YES
BV1663AppRec_EnExhSYS - Application Code - ReturnWrite0=NO; 1=YES
BV1664AppRec_GlycolSYS - Application Code - Rec_GlycolWrite0=NO; 1=YES
BV1665AppRec_PlateSYS - Application Code - Rec_PlateWrite0=NO; 1=YES
BV1666AppRec_RotarySYS - Application Code - Recovery - RotaryWrite0=NO; 1=YES
BV1667AppRec_SupplyOnlySYS - Application Code - Rec_SupplyOnlyWrite0=NO; 1=YES
BV1668AppReg_RetSYS - Application Code - Reg_RetWrite0=NO; 1=YES
BV1669AppReg_RoomSYS - Application Code - Reg_RoomWrite0=NO; 1=YES
BV1670AppReg_SupplySYS - Application Code - Reg_SupplyWrite0=NO; 1=YES
BV1671AppReHeat_DXSYS - Application Code - ReHeat_DXWrite0=NO; 1=YES
BV1672AppReHeat_HESYS - Application Code - ReHeat_HEWrite0=NO; 1=YES
BV1673AppReHeat_HWSYS - Application Code - ReHeat_HWWrite0=NO; 1=YES
BV1674AppRev_DXSYS - Application Code - Rev_DXWrite0=NO; 1=YES
BV1675AppRev_WSYS - Application Code - Rev_WWrite0=NO; 1=YES
BV1676AppRevCoolDXSYS - Application Code - RevCoolDXWrite0=NO; 1=YES
BV1677AppRevCoolWSYS - Application Code - RevCoolWWrite0=NO; 1=YES
BV1678AppRevHeatDXSYS - Application Code - RevHeatDXWrite0=NO; 1=YES
BV1679AppRevHeatWSYS - Application Code - RevHeatWWrite0=NO; 1=YES
PIV654AppTempRegSYS - Unit Configuration - Temperature RegulationWrite0=SUPPLY; 1=RETURN; 2=ROOM
BV1680BacNetSelSYS - Unit Configuration - BacNet PortWrite0=ETHERNET; 1=PLAN
PIV655BMS_AddrSYS - Unit Configuration - BMS port - Address (1 - 32)Write
BV1681CO2_Simulation_EnSYS - IO Setting - CO2 Simulate - EnabledWrite0=NO; 1=YES
IV656CO2_Simulation_VarSYS - IO Setting - CO2 Simulate - ValueppmWrite
BV1682CoolAlrm.LogicSYS - IO Setting - Digital Input - Logic - Alarm - CoolWrite0=NC; 1=NO
PIV657CoolAlrm.ManSYS - IO Setting - Digital Input - Manual - Alarm - CoolWrite0=AUTO; 1=OFF; 2=ON
PIV658DriveTypSYS - Unit Configuration - Import / Export - Memory TypeWrite0=FLASH MEMORY; 1=USB
BV1684En_BuzzSYS - Unit Configuration - Enable BuzzerWrite0=NO; 1=YES
BV1685En_HumTHTN_1SYS - Unit Configuration - HMI Basic - Humidity ProbeWrite0=NO; 1=YES
BV1686En_RetAir_CO2SYS - IO Setting - Enable Modbus - CO2Write0=NO; 1=YES
BV1687En_RetAirPSYS - IO Setting - Enable Modbus - Pressure - ReturnWrite0=NO; 1=YES
BV1688En_RetHumSYS - IO Setting - Enable Modbus - Humidity - ReturnWrite0=NO; 1=YES
BV1689En_SupplyAirPSYS - IO Setting - Enable Modbus - Pressure - SupplyWrite0=NO; 1=YES
BV1690En_SupplyHumSYS - IO Setting - Enable Modbus - Humidity - SupplyWrite0=NO; 1=YES
BV1691ExhAirDamp.LogicSYS - IO Setting - Digital Output - Logic - Damper - SupplyWrite0=NC; 1=NO
PIV659ExhFanRegTypSYS - Unit Configuration - Regulation ReturnWrite0=NONE; 1=VAV; 2=CAV
PIV660ExhMultiSYS - Unit Configuration - Config ReturnWrite0=1 FAN; 1=REDUNDANT; 2=2 FANS; 3=3 FANS; 4=4 FANS; 5=5 FANS; 6=6 FANS; 7=7 FANS; 8=8 FANS; 9=9 FANS; 10=10 FANS
PIV661ExhTemp.ManSYS - IO Setting - Manual - Temperature Exhaust°CWrite0=AUTO; OR 1 - 100%
AV375ExhTemp.OffsetSYS - IO Setting - Offset - Temperature Exhaust°CWrite
BV1692ExtTemp.EnabledSYS - IO Setting - Enable Inputs - Temperature - ExternalWrite0=NO; 1=YES
PIV662ExtTemp.ManSYS - IO Setting - Manual - Temperature - External°CWrite0=AUTO; OR 1 - 100%
AV376ExtTemp.OffsetSYS - IO Setting - Offset - Temperature - External°CWrite
IV663FB_Baud_mskSYS - Unit Configuration - FieldBus Port - BaudrateWrite0=4800; 1=9600; 2=19200; 3=38400
BV1693FireAlrm.LogicSYS - IO Setting - Digital Input - Logic - Alarm FireWrite0=NC; 1=NO
PIV664FireAlrm.ManSYS - IO Setting - Digital Input - Manual - Alarm FireWrite0=AUTO; 1=OFF; 2=ON
BV1694Heat_2.LogicSYS - IO Setting - Digital Output - Logic - Heating 2Write0=NC; 1=NO
BV1696HumAlrm.LogicSYS - IO Setting - Digital Input - Logic - Alarm - HumidifierWrite0=NC; 1=NO
PIV665HumAlrm.ManSYS - IO Setting - Digital Input - Manual - Alarm - HumidifierWrite0=AUTO; 1=OFF; 2=ON
BV1697ID2_Alrm.LogicSYS - IO Setting - Digital Input - Logic - Alarm - HeatWrite0=NC; 1=NO
PIV666ID2_Alrm.ManSYS - IO Setting - Digital Input - Manual - Alarm - HeatWrite0=AUTO; 1=OFF; 2=ON
IV667ImpExpFileNameSYS - Unit Configuration - Import / Export - File Name (0 - 99)Write
IV668LangChangeSYS - Unit Configuration - LanguageWrite0=EN; 1=PL
AV377MinFanPwrRetSYS - Unit Configuration - Minimum Speed - Return (0 - 100 %)%Write
AV378MinFanPwrSupSYS - Unit Configuration - Minimum Speed - Supply (0 - 100 %)%Write
PIV669OffTotMinutesSYS - Hardware - Time last blackoutmin.Write
PIV670OnOffStatusSYS - Hardware - Machine Statusmsec.Write
PIV671PrgCycleMsSYS - Hardware - Cyclemsec.Write
BV1699RecSupplyTemp.EnabledSYS - IO Setting - Enable Inputs - Temperature - Supply RecoveryWrite0=NO; 1=YES
PIV672RecSupplyTemp.ManSYS - IO Setting - Manual - Temperature - Supply Recovery°CWrite0=AUTO; OR 1 - 100%
AV379RecSupplyTemp.OffsetSYS - IO Setting - Offset - Temperature - Supply Recovery°CWrite
BV1701RemoteOn.LogicSYS - IO Setting - Digital Input - Logic - Remote ONWrite0=NC; 1=NO
PIV673RemoteOn.ManSYS - IO Setting - Digital Input - Manual - Remote ONWrite0=AUTO; 1=OFF; 2=ON
BV1702RetFilter.LogicSYS - IO Setting - Digital Input - Logic - Filter - ReturnWrite0=NC; 1=NO
PIV674RetFilter.ManSYS - IO Setting - Digital Input - Manual - Filter - ReturnWrite0=AUTO; 1=OFF; 2=ON
BV1703RetTemp.EnabledSYS - IO Setting - Enable Inputs - Temperature - ReturnWrite0=NO; 1=YES
PIV675RetTemp.ManSYS - IO Setting - Manual - Temperature - Return°CWrite0=AUTO; OR 1 - 100%
AV380RetTemp.OffsetSYS - IO Setting - Offset - Temperature - Return°CWrite
BV1704SrsAlrm.LogicSYS - IO Setting - Digital Output - Logic - Global AlarmWrite0=NC; 1=NO
PIV676SupplyFanRegTypSYS - Unit Configuration - Regulation SupplyWrite0=NONE; 1=VAV; 2=CAV
BV1705SupplyFilter.LogicSYS - IO Setting - Digital Input - Logic - Filter - SupplyWrite0=NC; 1=NO
PIV677SupplyFilter.ManSYS - IO Setting - Digital Input - Manual - Filter - SupplyWrite0=AUTO; 1=OFF; 2=ON
PIV678SupplyMultiSYS - Unit Configuration - Config SupplyWrite0=1 FAN; 1=REDUNDANT; 2=2 FANS; 3=3 FANS; 4=4 FANS; 5=5 FANS; 6=6 FANS; 7=7 FANS; 8=8 FANS; 9=9 FANS; 10=10 FANS
PIV679SupplyTemp.ManSYS - IO Setting - Manual - Temperature - Supply°CWrite0=AUTO; OR 1 - 100%
AV381SupplyTemp.OffsetSYS - IO Setting - Offset - Temperature - Supply°CWrite
PIV680Typ_SP_CO2SYS - IO Setting - Modbus Probe Type - CO2Write0=TYPE 1; 1=TYPE 2
PIV681Typ_SP_HumSYS - IO Setting - Modbus Probe Type - HumidityWrite0=TYPE 1; 1=TYPE 2
PIV682Typ_SP_PressureSYS - IO Setting - Modbus Probe Type - PressureWrite0=TYPE 1; 1=TYPE 2
PIV683TypVFDSYS - Unit Configuration - Supply Fan VFD TypeWrite0=iC5; 1=iG5; 2=ABB; 3=EC; 4=DFI; 5=M100; 6=None
PIV684TypVFD_2SYS - Unit Configuration - Return Fan VFD TypeWrite0=iC5; 1=iG5; 2=ABB; 3=EC; 4=DFI; 5=M100; 6=None
PIV685TypVFD_RotorSYS - Unit Configuration - Rotor Fan VFD TypeWrite0=iC5; 1=iG5; 2=ABB; 3=EC; 4=DFI; 5=M100; 6=None
BV1706UnitConfiguredSYS - Unit Configuration - EnabledWrite0=NO; 1=YES
IV686Uom_MskSYS - Unit Configuration - Unit of MeasureWrite1=INTERNATIONAL; 2=USA
BV1707W_HeatCoilTemp.EnabledSYS - IO Setting - Enable Inputs - Temperature - Water HeatWrite0=NO; 1=YES
PIV687W_HeatCoilTemp.ManSYS - IO Setting - Manual - Temperature - Water Heat°CWrite0=AUTO; OR 1 - 100%
AV382W_HeatCoilTemp.OffsetSYS - IO Setting - Offset - Temperature - Water Heat°CWrite
BV1708W_PreHeatCoilTemp.EnabledSYS - IO Setting - Enable Inputs - Temperature - Water PreHeatWrite0=NO; 1=YES
PIV688W_PreHeatCoilTemp.ManSYS - IO Setting - Manual - Temperature - Water PreHeat°CWrite0=AUTO; OR 1 - 100%
AV383W_PreHeatCoilTemp.OffsetSYS - IO Setting - Offset - Temperature - Water PreHeat°CWrite
BV1709WinSum.EnabledSYS - IO Setting - Enable Inputs - Summer / WinterWrite0=NO; 1=YES
BV1710WinSum.LogicSYS - IO Setting - Digital Input - Logic - Winter / SummerWrite0=NC; 1=NO
PIV689WinSum.ManSYS - IO Setting - Digital Input - Manual - Winter / SummerWrite0=AUTO; 1=OFF; 2=ON
PIV690CurrVer.DSYS - System - Application Version - _ . _ . _ _ _ _ DRead
BV1711CurrVer.IsBetaSYS - System - Application Version - _ . _ . _ _ _ B _Read
PIV691CurrVer.XSYS - System - Application Version - X . _ . _ _ _ _ _Read
PIV692CurrVer.YSYS - System - Application Version - _ . Y . _ _ _ _ _Read
PIV693CurrVer.ZSYS - System - Application Version - _ . _ . Z Z Z _ _Read
BV1712ExhTemp.EnabledSYS - IO Setting - Enable Inputs - Temperature ExhaustRead0=NO; 1=YES
BV1713Manual_PreHeatSYS - PreHeater - Manual mode activeRead0=NO; 1=YES
BV1714Manual_RecoverySYS - Recovery - Manual mode activeRead0=NO; 1=YES
BV1715Manual_HeatSYS - Heater - Manual mode activeRead0=NO; 1=YES
BV1716Manual_CoolSYS - Cooler - Manual mode activeRead0=NO; 1=YES
BV1717Manual_ReHeatSYS - ReHeater - Manual mode activeRead0=NO; 1=YES
BV1718Manual_ReverseSYS - Reverse unit - Manual mode activeRead0=NO; 1=YES
BV1719Manual_MixSYS - Mixing damper - Manual mode activeRead0=NO; 1=YES
BV1720Manual_HumiditySYS - Humidifier - Manual mode activeRead0=NO; 1=YES
BV1721Manual_RedDampSYS - Redundant Damper - Manual mode activeRead0=NO; 1=YES
BV1722Manual_ActiveSYS - Manual mode activeRead0=NO; 1=YES
AV694Reverse_Val_AOIO - Analog Output - Reverse unit (0 - 100 %)%Read
AV698UnitSetP.AirFlwSetP.StandBySP - Setpoint - Air Flow - Supply - 4 - Standby (0 - 100 %)%Write
AV697UnitSetP.AirQualitySetP.StandBySP - Setpoint - Air Quality - 3 - StandbyppmWrite
AV696UnitSetP.HumSetP.StandBySP - Setpoint - Humidity - 4 - Standby (0 - 100 %)%Write
AV699UnitSetP.RetAirFlwSetP.StandBySP - Setpoint - Air Flow - Return - 4 - Standby (0 - 100 %)%Write
AV695UnitSetP.RoomTempSetP.StandBySP - Setpoint - Temperature - Room - 4 - Standby°CWrite
PIV700Heat_1.ManPAR - Heating - Main Device 1 - Manual DigitalWrite0=AUTO; 1=OFF; 2=ON
AV712SupplyAirFlow_2IO - Probe - Air Flow - Supply (For airflow > 32767)m3/hRead
AV713ExhAirFlow_2IO - Probe - Air Flow - Return (For airflow > 32767)m3/hRead
AV714ExhAirFlowSet_Msk_2PAR - Fan - Return - Flow - Maximum (For airflow > 32767)m3/hWrite
AV715SupplyAirFlowSet_Msk_2PAR - Fan - Supply - Flow - Maximum (For airflow > 32767)m3/hWrite
Object ID lookup: FläktGroup vQ Stream unit with Carel uPC3 controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the vQ Stream unit with Carel uPC3 controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the FläktGroup vQ Stream unit with Carel uPC3 controller

How many BACnet points does the FläktGroup vQ Stream unit with Carel uPC3 controller have?

This list has 2422 BACnet objects: 393 analog values, 1718 binary values, 20 integer values, 291 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which FläktGroup vQ Stream unit with Carel uPC3 controller BACnet points are writable?

595 of the 2422 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official FläktGroup vQ Stream unit with Carel uPC3 controller BACnet documentation?

The source is vQ Stream - Communication list for BMS (uPC3 - BMS Variable), published free by FläktGroup at https://www.flaktgroup.com/api/v1/Documents/1240712/Download.

What are the minimum BACnet points to integrate the FläktGroup vQ Stream unit with Carel uPC3 controller?

Start with PIV 397 SetTyp (Work mode: 0 Off, 1 Eco, 2 Optimal, 3 Comfort, 5 Auto); AV 207 UnitSetP.RoomTempSetP.Comfort (Comfort room temperature setpoint, °C); BV 845 AlarmMng.AlrmResByBms (Alarm reset from the BMS (1 = reset)); AV 194 RegTemp (Current temperature setpoint value, °C); BV 24 RunSupplyFan (Supply fan running); AV 36 SupplyTemp.Val (Supply air temperature, °C); AV 32 RetTemp.Val (Return / room air temperature, °C); AV 6 ExtTemp.Val (Outdoor (external) air temperature, °C); AV 191 SupplyFanVal (Supply fan output, %); BV 18 SrsAlrm.Val (Global alarm output (printed 0 = ON)).

How do I enable BMS control of the FläktGroup vQ Stream unit with Carel uPC3 controller?

PIV 397 SetTyp (ReadWrite) is the work-mode selection; 5 = Auto follows the unit's scheduler. The setpoints used in each mode are the UnitSetP.* AVs (Economy, Optimal/PreComfort, Comfort, Standby).

How do I check these points on the real vQ Stream unit with Carel uPC3 controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More FläktGroup BACnet points lists

Source: vQ Stream - Communication list for BMS (uPC3 - BMS Variable). Object names, instances and units are reproduced as published; descriptions are our own.