Short answer

The V3.xx eQ Fläkt application on the Climatix POL6xx controller has a larger BACnet object set than V2.xx: third heating and cooling stages, pre-heater, extra filters, manual HMI/BMS output overrides and more configuration objects. Objects are exposed through the Climatix BACnet IP (POL908) or MS/TP (POL904) module.

This page lists 868 BACnet objects for the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FläktGroup’s own free documentation, linked below.

Manufacturer
FläktGroup
Model
eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx
Equipment
Air handling unit controller (Climatix)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
868 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
eQ, eQ Flakt V3, eQ Fläkt AHU V3.xx, Climatix eQ, DC_10159GB, POL908, POL904
Source document
eQ Controls - Climatix BACnet communication module, Installation and maintenance instruction (BACnet objects of eQ Fläkt V3.xx) · DC_10159GB 20180823_R0 · rev. 2018-08-23
Download CSV 868 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against FläktGroup’s current documentation and the live device before use. Not official FläktGroup information. Terms of use.

BMS integration notes: FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx

Integration in brief

Fit a Climatix BACnet IP (POL908) or MS/TP (POL904) module, set its network parameters on the controller and export the EDE file. Command the unit with the BMS time-switch-program objects (OpModeBmsTimeStSwtch or the steps/temperature variant) and the bus setpoint, then read operating mode, status, temperatures, fan signals and the alarm-class objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 8442OpModeBmsTimeStSwtchBMS operating command: 0 Auto, 1 Off, 2-4 stage 1-3Read
AV 1884ExtSetpointSpvCOMTemperature setpoint written over the bus, °CRead
MV 59480ResetGeneral alarm acknowledge / resetRead
MV 6080ActOpModeActual operating mode (off, comfort, economy...)Read
MV 32321ActOpStaActual operation status / stop reasonRead
AI 45150SupplyTmpSupply air temperatureRead
AI 28256ReturnAirTmpExtract air temperatureRead
AI 53218OutTmpOutdoor air temperatureRead
AO 59037SplyFanVarPosSupply fan output signal, 0-100 %Read
MV 42640AlmCl1Critical (A) alarm class activeRead

Enable & remote start

The document gives no access column. OpModeBmsTimeStSwtch (steps) and OpModeBmsTimeStTmpSwtch (steps/temperature) are the BMS time-switch-program commands (0 = Auto follows the unit's own program); which one applies depends on the unit's control mode.

Sensors & values from the BMS

ExtSetpointSpvCOM (AV 1884) is the external setpoint value from communication; the AI ExtSetpointSpv is the hard-wired external setpoint input.

Network setup

Watch out for

FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

868 of 868 shown
Type
Other
Show
FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx BACnet Points List
DescriptionStates
AI17074AftClg1HumHumidity after Cooling 1%RHRead
AI15862AftClg1TmpTemperature after Cooling 1°CRead
AI55662AftClg2HumHumidity after Cooling2%RHRead
AI42538AftClg2TmpTemperature after Cooling2°CRead
AI45018AftClg3HumHumidity after Cooling 3%RHRead
AI53406AftClg3TmpTemperature after Cooling 3°CRead
AI9285AftCmb1HumHumidity after Combi 1%RHRead
AI23297AftCmb1TmpTemperature after Combi 1°CRead
AI49049AftCmb2HumHumidity after Combi 2%RHRead
AI49373AftCmb2TmpTemperature after Combi 2°CRead
AI51501AftCmb3HumHumidity after Combi 3%RHRead
AI46697AftCmb3TmpTemperature after Combi 3°CRead
AI7183AfterMixHumHumidity after mixing%RHRead
AI7771AftHtg1HumHumidity after Heating 1%RHRead
AI24863AftHtg1TmpTemperature after Heating 1°CRead
AI34183AftHtg2HumHumidity after Heating 2%RHRead
AI64195AftHtg2TmpTemperature after Heating 2°CRead
AI62259AftHtg3HumHumidity after Heating 3%RHRead
AI35959AftHtg3TmpTemperature after Heating 3°CRead
AI31889AftMixingTmpTemperature after mixing°CRead
AI22396AftRtHumHumHumidity after Extract humidifier%RHRead
AI8095AftSplyHumHumHumidity after supply humidifier%RHRead
AI24795AftSplyHumTmpTemperature after supply humidifier°CRead
AI115AuxTmpAuxiliary temperature°CRead
AI28023BalPrsPressure balancingPaRead
AI48851Coil2WtrTmpCombi coil 2 water temperature°CRead
AI23945CoilWtrTmpCombi coil 1 wtr temperature°CRead
AI27360ExExtraFilterExtract extra filter 2PaRead
AI10582ExFilterExtract air filter sensorPaRead
AI40895ExhaustTmpExhaust air temperature°CRead
AI56135ExhaustTmp2Exhaust air temperature 2Read
AI58983ExhDensTmpExhaust density air temperature°CRead
AI32361ExhFan_DCLCurrentSupply fan DCL CurrentARead
AI9232ExhFan_DCLVoltageSupply fan DCL VoltageVRead
AI41627ExhFan_FanSpeedExhaust fan speedrpmRead
AI58193ExhFan_MaxSpeedExhaust fan max speedrpmRead
AI12204ExhFan_ModTempExhaust fan mod temperature°CRead
AI11254ExhFan_MotTempExhaust fan mot temperature°CRead
AI6069ExhFan_OpTimeExhaust fan - Operating timeRead
AI8243ExhFan_OpTimeHHExhaust fan - Operating time, hourshRead
AI36707ExhFan_OpTimeMMExhaust fan - Operating time, minutesminRead
AI2311ExhFan_PCBTempExhaust fan PCB temperature°CRead
AI42634ExhFan_PowerExhaust fan PowerWRead
AI48207ExhFanExtSpvExhaust fan external setpointPa or l/s depending on fan control type.Read
AI19767ExPreFilterExtract air pre-filter sensorPaRead
AI4854ExtraFrstTmpHeating 2 frost temperature°CRead
AI20915ExtraSupplyTmpSupply air temperature 2°CRead
AI12205ExtSetpointSpvExternal setpoint°CRead
AI852FrostTmpLowLimitHeating 1 frost temp sensor - Low limit activeRead0=Passive; 1=Active
AI39125HrecFrstPrsHeat recovery frost pressurePaRead
AI50488HrecInTakePrsHeat exchanger pressure dropPaRead
AI44798HrecSupplyTmpHeat recovery supply air temp°CRead
AI48181HrecSupplyTmp2Heat recovery supply air temperature 2°CRead
AI12446HrecWtrTmpHeat recovery water temperature°CRead
AI855Htg2FrostTmpLowLimitHeating 2 frost protection temperature - Low limit°CRead
AI857Htg3FrostTmpLowLimitHeating 3 frost protection temperature - Low limit°CRead
AI6535Htg3FrstTmpHeating 3 frost temperature°CRead
AI50341HtgFrstTmpHeating 1 frost temperature°CRead
AI45222OutHumOutdoor air relative humidity%RHRead
AImin53218OutTmpOutdoor air temperature°CRead
AI49723OutTmpWallOutdoor wall temperature sensor°CRead
AI856PreHtgFrostTmpLowLimitPre-heating frost temp sensor - Low limit°CRead
AI65041PreHtgFrstTmpPre-heater frost temperature°CRead
AI35237PreHtgSupplyTmpPre-heater supply air temperature°CRead
AImin28256ReturnAirTmpExtract air temperature°CRead
AI64377ReturnAirTmp2Extract air temperature after humidifier°CRead
AI38593ReturnFlowExhaust air flowl/sRead
AI39576ReturnPrsExhaust air pressurePaRead
AI37799RoomHumRoom relative humidity%RHRead
AI715RoomHum2Room humidity 2 (relative)%RHRead
AI60643RoomTmpRoom temperature°CRead
AI51635RoomTmp2Room temperature 2°CRead
AI3708RtHumExtract air humidity (relative)%H.r.Read
AI40647SplyDensTmpSupply air density temperatureRead
AI14967SplyExtraFilterSupply air extra filter 1PaRead
AI56927SplyFan_DCLCurrentSupply fan DCL CurrentARead
AI33830SplyFan_DCLVoltageSupply fan DCL VoltageVRead
AI48513SplyFan_FanSpeedSupply fan speedrpmRead
AI64587SplyFan_MaxSpeedSupply fan max speedrpmRead
AI28696SplyFan_ModTempSupply fan mod temperature°CRead
AI29762SplyFan_MotTempSupply fan mot temperature°CRead
AI8364SplyFan_OpTimeSupply fan - Operating timeRead
AI16169SplyFan_OpTimeHHSupply fan - Operating time, hourshRead
AI36985SplyFan_OpTimeMMSupply fan - Operating time, minutesminRead
AI22195SplyFan_PCBTempSupply fan PCB temperature°CRead
AI39978SplyFan_PowerSupply fan PowerWRead
AI30575SplyFanExtSpvSupply fan external setpointPa or l/s depending on fan control type.Read
AI59395SplyFilterOutdoor air filter sensorPaRead
AI44474SplyPreFilterOutdoor air pre-filter sensorPaRead
AI9497SupplyFlowSupply air flowl/sRead
AI53018SupplyHumSupply air relative humidity%RHRead
AI20400SupplyPrsSupply air pressurePaRead
AImin45150SupplyTmpSupply air temperature (values column printed 0=Ok / 1=Alarm)Read
AO22813AuxOutputAuxiliary analog output fan0-100%Read
AO57034BalanceCntrlPosPressure balancing extract damper controller output signal0-100%Read
AO38455BalCtlrSplyPosMixing outdoor damper controller output signal0-100%Read
AO5870Cooling3PosCooling 3 output signal0-100%Read
AO45643CoolingPmpVarPosCooling 1 pump output signal0-100%Read
AO30925CoolingPosCooling output signal0-100%Read
AO40119ExhFanVarPosExhaust fan output signal0-100%Read
AO59738ExtraClgPmpVarPosCooling 2 pump output signal0-100%Read
AO60283ExtraClgPosCooling 2 output signalRead0=Off; 1=On
AO166ExtraHtgPmpVarPosHeating 2 pump output signal0-100%Read
AO46994ExtraHtgPosHeating 2 output signalRead0=Off; 1=On
AO18705Heating3PosHeating 3 output signal0-100%Read
AO34442HeatingPmpVarPosHeating 1 pump output signal0-100%Read
AO26209HeatingPosHeating 1 output signalRead0=Off; 1=On
AO49662HrecDampPosHeat recovery damper output signal0-100%Read
AO29755HrecPmpVarPosHeat recovery pump output signal0-100%Read
AO5922HrecPosHeat recovery output signal0-100%Read
AO5392HumForceHtgPosForce heating output signal0-100%Read
AO51005HumidityCtrlPmpVarPosHumidifier pump output signal0-100%Read
AO39618HumidityCtrlPosHumidifier output signal0-100%Read
AO17784PreHeatingPosPre-heater output signal0-100%Read
AO23338ReCoolingPosReCooler cooling output signal0-100%Read
AO17798ReHeatingPosReCooler heating output signal0-100%Read
AO28431RtCoolingPosExtract air cooling output signal0-100%Read
AOmin59037SplyFanVarPosSupply fan output signal0-100%Read
AV2008ActBlkDHumTmpActual dew point block dehumidification°CRead
AV2735ActCascSpvClgActual supply cooling setpoint (when use of cascade control)°CRead
AV50248ActCascSpvDehActual supply dehumidification setpoint%RHRead
AV28804ActCascSpvHtgActual supply heating setpoint (when use of cascade control)°CRead
AV58111ActCascSpvHumActual supply humidification setpoint%RHRead
AV52988ActCtrlValActual controlled temperature°CRead
AV38385ActCtrlValHumActual controlled humidity%RHRead
AV3738ActHRDewSpActual heat recovery dewpoint setpoint value°CRead
AV30105ActMainSpvClgActual cooling setpoint, Main (depending on actual control mode)°CRead
AV47998ActMainSpvDehActual dehumidification setpoint%RHRead
AV4018ActMainSpvHtgActual heating setpoint, Main (depending on actual control mode)°CRead
AV40393ActMainSpvHumActual humidity setpoint%RHRead
AV3315ActvClgRecDevActivate cooling recovery - Temperature differenceKRead
AV21855AirQCmpCtrLoopKpAir quality compensation - Proportional factorRead
AV21857AirQCmpCtrLoopTDAir quality compensation - Differential factorsRead
AV21856AirQCmpCtrLoopTIAir quality compensation - Integral factorsRead
AV10236AirQCmpPrValActual air quality compensation0-100%Read
AV22649AirQSpvAir quality setpointppmRead
AV3737AirQualityAir qualityppmRead
AV1899AlmAckBtnCOMAlarm Ack button - Value comm.Read0=Off; 1=On
AV2429BalCtlrSplyLowLimitBalance control - Min pressure outdoor damperPaRead
AV31736BalDmpMaxTmBalance control - Max timesRead
AV5939BalDmpTmBalance control - Force damper at start timesRead
AV49991BalMaxDevBalance control - Max pressure deviationPaRead
AV28570BalPrsLowLmtBalance control - Min pressure extract damper0-100%Read
AV22141BalPrsSpBalance control - Pressure setpointPaRead
AV228BlkClgRecDevBlock cooling recovery - Temperature differenceKRead
AV33121BlkHtgRecDevBlock heat recovery - Temperature differenceKRead
AV44092BoostClgSpvBoost cooling setpoint°CRead
AV27113BoostHtgSpvBoost heating setpoint°CRead
AV3510BoostPreStrtTmBoost pre-start timeminRead
AV9430FanCmpTmpPrValActual fan compensation temperature0-100%Read
AV9756SplyTmpDevAlmMaxDevSupply temperature - Maximum deviation°CRead
AV9781SplyFanTD_FlwSupply fan controller (flow control) - Differential factorsRead
AV10627HumSpvRelSpvHumRelative humidity - Humidification setpoint%RH or g/kg depending on configurationRead
AV11342HumSpvRelSpvDehumRelative humidity - Dehumidity setpoint for humidification%RH or g/kg depending on configurationRead
AV11601WiCmpTmpDtaWinter compensation temperature deltaKRead
AV13266BoostRmSpvBoost room temperature setpoint°CRead
AV17241CalibrationActvTmCalibration - Time delaysRead
AV34380CalibrationExhFanStartCalibration - Q-min exhaust fan startl/sRead
AV46866CalibrationExhFanStopCalibration - Q-min exhaust fan stopl/sRead
AV32048CalibrationMaxDevCalibration - Maximum deviationl/sRead
AV38555CalibrationQCalibration Ql/sRead
AV38027CalibrationQExhCalibration Q Exhaustl/sRead
AV59099CalibrationQRedCalibration - Reduce Q0-100%Read
AV54865CalibrationQRtCalibration Q Extractl/sRead
AV48462CalibrationStoPmaxCalibration - P-max pressure heat exchangerPaRead
AV17936CalibrationStoPminCalibration - P-min pressure heat exchangerPaRead
AV52218CalibrationStoQmaxCalibration - Q-max flow heat exchangerl/sRead
AV12452CalibrationStoQminCalibration - Q-min flow heat exchangerl/sRead
AV57930CascFlowLmtMaxDevLmtDraught heating max deviation°CRead
AV27342CascFlowLmtMinDevLmtDraught cooling max deviation°CRead
AV40280CG_EM24_1ActPowerEnergy actual powerWRead
AV36000CG_EM24_1AvePowerEnergy save powerWRead
AV49048CG_EM24_1OpHoursEnergy operating hourshRead
AV19610CG_EM24_1ParEnergyEnergy partialkWhRead
AV61249CG_EM24_1TotEnergyEnergy totalkWhRead
AV875Clg1PmpActiveHourCooling 1 pump - Operating hourshRead
AV876Clg2PmpActiveHourCooling 2 pump - Operating hourshRead
AV878Clg3PmpActiveHourCooling 3 pump - Operating hourshRead
AV812Clg3VlvAutoCooling 3 output signal-Auto mode P100-100%Read
AV811Clg3VlvValueCooling 3 output signal-Manual HMI BMS0-100%Read
AV21849ClgReClgCtrLoopKpReCooler cooling controller - Proportional factorRead
AV21851ClgReClgCtrLoopTDReCooler cooling controller - Differential factorsRead
AV21850ClgReClgCtrLoopTIReCooler cooling controller - Integral factorsRead
AV802ClgVlvAutoCooling 1 output signal-Auto mode P100-100%Read
AV801ClgVlvValueCooling 1 output signal-Manual HMI BMS0-100%Read
AV47241CoHtgCurveSpvPrValActual calculated heating setpoint (comfort)°CRead
AV22000CoHtgToaCurveOutTX1calculated heating setpoint (comfort) - X1°CRead
AV22002CoHtgToaCurveOutTX2calculated heating setpoint (comfort) - X2°CRead
AV22004CoHtgToaCurveOutTX3calculated heating setpoint (comfort) - X3°CRead
AV22006CoHtgToaCurveOutTX4calculated heating setpoint (comfort) - X4°CRead
AV22001CoHtgToaCurveSpY1calculated heating setpoint (comfort) - Y1°CRead
AV22003CoHtgToaCurveSpY2calculated heating setpoint (comfort) - Y2°CRead
AV22005CoHtgToaCurveSpY3calculated heating setpoint (comfort) - Y3°CRead
AV22007CoHtgToaCurveSpY4calculated heating setpoint (comfort) - Y4°CRead
AV21951Cooling3CtrLoopKpCooling 3 - Proportional factorRead
AV21953Cooling3CtrLoopTDCooling 3 - Differential factorsRead
AV21952Cooling3CtrLoopTICooling 3 - Integral factorsRead
AV37768Cooling3OffTmpCooling 3 disable by outdoor temperature°CRead
AV21807CoolingCtrLoopKpCooling 1 - Proportional factorRead
AV21809CoolingCtrLoopTDCooling 1 - Differential factorsRead
AV21808CoolingCtrLoopTICooling 1 - Integral factorsRead
AV16471CoolingOffTmpCooling 1 disable by outdoor temperature°CRead
AV18421CounterFlowExchangerX1Counter flow heat exchanger - X1°CRead
AV30614CounterFlowExchangerX2Counter flow heat exchanger - X2°CRead
AV29892CounterFlowExchangerY1Counter flow heat exchanger - Y10-100%Read
AV17575CounterFlowExchangerY2Counter flow heat exchanger - Y20-100%Read
AV21825CRecDamperCtrLoopKpMixing damper cooling recovery controller - Proportional factorRead
AV21827CRecDamperCtrLoopTDMixing damper cooling recovery controller - Differential factorsRead
AV21826CRecDamperCtrLoopTIMixing damper cooling recovery controller - Integral factorsRead
AV33908CrecDampRecMixing damper cooling recovery output signal0-100%Read
AV28660DeFrstMxSpdHeat exchanger defrost max output signal°CRead
AV21957DeHum2CtrLoopKpDehumidification 2 - Proportional factorRead
AV21959DeHum2CtrLoopTDDehumidification 2 - Differential factorsRead
AV21958DeHum2CtrLoopTIDehumidification 2 - Integral factorsRead
AV21960DeHum3CtrLoopKpDehumidification 3 - Proportional factorRead
AV21962DeHum3CtrLoopTDDehumidification 3 - Differential factorsRead
AV21961DeHum3CtrLoopTIDehumidification 3 - Integral factorsRead
AV21939DeHumidityCtrLoopKpDehumidification 1 - Proportional factorRead
AV21941DeHumidityCtrLoopTDDehumidification 1 - Differential factorsRead
AV21940DeHumidityCtrLoopTIDehumidification 1 - Integral factorsRead
AV18150DeHumidityPrValActual dehumidification value0-100%Read
AV55315DeHumidityPrVal2Actual dehumidification value 20-100%Read
AV51250DeHumidityPrVal3Actual dehumidification value 30-100%Read
AV21292DewpointSupply dew point°CRead
AV41175DewpointDzDew point - Neutral zone°CRead
AV48409EcHtgCurveSpvPrValActual calculated heating setpoint (economy)Read
AV22016EcHtgToaCurveOutTX1Outdoor curve - temperature X1 (economy)°CRead
AV22018EcHtgToaCurveOutTX2Outdoor curve - temperature X2 (economy)°CRead
AV22020EcHtgToaCurveOutTX3Outdoor curve - temperature X3 (economy)°CRead
AV22022EcHtgToaCurveOutTX4Outdoor curve - temperature X4 (economy)°CRead
AV22017EcHtgToaCurveSpY1Outdoor curve - setpoint Y1 (economy)°CRead
AV22019EcHtgToaCurveSpY2Outdoor curve - setpoint Y2 (economy)°CRead
AV22021EcHtgToaCurveSpY3Outdoor curve - setpoint Y3 (economy)°CRead
AV22023EcHtgToaCurveSpY4Outdoor curve - setpoint Y4 (economy)°CRead
AV6033ElHtgFanLmtAreaArea, electrical heater 1m2Read
AV47462ElHtgFanLmtKfactorK-factor, electrical heater 10-100%Read
AV27650ElHtgFanLmtPrValPower reduction, electrical heater 10-100%Read
AV24382ElHtgFanLmtvv, Flow over heater, electrical heater 1m/sRead
AV52253ElHtgFanLmtvMaxvMax, air speed, electrical heater 1m/sRead
AV14147ElHtgFanLmtvMinvMin, air speed, electrical heater 1m/sRead
AV19481EnergyDisplayCooling1DaykWhEnergy display, cooling 1 - TodaykWhRead
AV9637EnergyDisplayCooling1kWEnergy display, cooling 1 - Actual powerkWRead
AV18492EnergyDisplayCooling1YearMWhEnergy display, cooling 1 - Actual yearMWhRead
AV33900EnergyDisplayCooling2DaykWhEnergy display, cooling 2 - TodaykWhRead
AV48761EnergyDisplayCooling2kWEnergy display, cooling 2 - Actual powerkWRead
AV63987EnergyDisplayCooling2YearMWhEnergy display, cooling 2 - Actual yearMWhRead
AV50111EnergyDisplayCooling3DaykWhEnergy display, cooling 3 - TodaykWhRead
AV51405EnergyDisplayCooling3kWEnergy display, cooling 3 - Actual powerkWRead
AV38582EnergyDisplayCooling3YearMWhEnergy display, cooling 3 - Actual yearMWhRead
AV16864EnergyDisplayFansFansPowkWEnergy display, fans - Actual powerkWRead
AV44942EnergyDisplayFansYearMWhEnergy display, fans - Actual yearMWhRead
AV15641EnergyDisplayHeating1DaykWhEnergy display, heating 1 - TodaykWhRead
AV15113EnergyDisplayHeating1kWEnergy display, heating 1 - Actual powerkWRead
AV29524EnergyDisplayHeating1YearMWhEnergy display, heating 1 - Actual yearMWhRead
AV62828EnergyDisplayHeating2DaykWhEnergy display, heating 2 - TodaykWhRead
AV41173EnergyDisplayHeating2kWEnergy display, heating 2 - Actual powerkWRead
AV49819EnergyDisplayHeating2YearMWhEnergy display, heating 2 - Actual yearMWhRead
AV45759EnergyDisplayHeating3DaykWhEnergy display, heating 3 - TodaykWhRead
AV54881EnergyDisplayHeating3kWEnergy display, heating 3 - Actual powerkWRead
AV44510EnergyDisplayHeating3YearMWhEnergy display, heating 3 - Actual yearMWhRead
AV62791EnergyDisplayHrecDaykWhEnergy display, heat recovery - TodaykWhRead
AV56834EnergyDisplayHreckWEnergy display, heat recovery - Actual powerkWRead
AV22418EnergyDisplayHrecYearMWhEnergy display, heat recovery - Actual yearMWhRead
AV16999EnergyDisplayPreHeatingDaykWhEnergy display pre-heating Day kWhkWhRead
AV27373EnergyDisplayPreHeatingkWEnergy display pre-heating kWkWRead
AV62570EnergyDisplayPreHeatingYearMWhEnergy display pre-heating Year MWhMWhRead
AV561EnergyDisplayTotCoolingEnergy display cooling totalMWhRead
AV24666EnergyDisplayTotFansEnergy display fans totalMWhRead
AV40656EnergyDisplayTotHeatingEnergy display heating totalMWhRead
AV20954EnergyDisplayTotRecoveryEnergy display heat recovery totalMWhRead
AV47894EnFanClgDevtemperature difference°KRead
AV59391EnFanHtgDevtemperature diff.°KRead
AV60513ExElHtgFanLmtAreaArea, electrical heater 2m2Read
AV56166ExElHtgFanLmtKfactorK-factor, electrical heater 20-100%Read
AV49782ExElHtgFanLmtPrValPower reduction, electrical heater 20-100%Read
AV7175ExElHtgFanLmtvv, Flow over heater, electrical heater 2m/sRead
AV14317ExElHtgFanLmtvMaxvMax, air speed, electrical heater 2m/sRead
AV52403ExElHtgFanLmtvMinvMin, air speed, electrical heater 2m/sRead
AV25356ExExtraFltPreAlmExtract air extra filter 2 Pre-alarmRead0=Ok; 1=Alarm
AV45194ExFilterPreAlmExtract air filter Pre-alarmPaRead
AV871ExhFanActiveHourExhaust fan - Operating hourshRead
AV33255ExhFanActSpvActual exhaust fan setpointl/sRead
AV59694ExhFanActValActual exhaust fan valueRead
AV52288ExhFanCurrentDanfoss / OJ-DV Exhaust fan currentARead
AV10675ExhFanCurvePrValActual calculated Exhfan.setpointRead
AV56254ExhFanDevAlmMaxDevExhaust fan - Maximum deviation (flow control)%, Pa or l/s depending on configurationRead
AV54886ExhFanDevAlmMaxDevPrsExhaust fan - Maximum deviation (pressure control)PaRead
AV58855ExhFanDevAlmMinLmtExhaust fan - Minimum limit (flow control)Read
AV48357ExhFanDevAlmMinLmtPrsExhaust fan - Minimum limit (pressure control)PaRead
AV7102ExhFanEnergyDanfoss exhaust fan EnergykWhRead
AV62586ExhFanKP_FlwExhaust fan controller (flow control) - Proportional factorRead
AV25921ExhFanKP_PrsExhaust fan controller - Proportional factor (pressure control)Read
AV14530ExhFanMotorVoltDanfoss / OJ-DV Exhaust fan motor voltageVRead
AV36017ExhFanOpDaysDanfoss / OJ-DV Exhaust fan - Operating daysdaysRead
AV27013ExhFanOpHrsDanfoss / OJ-DV Exhaust fan - Operating hourshRead
AV49021ExhFanOpMinutesDanfoss / OJ-DV Exhaust fan - Operating minutesminRead
AV65306ExhFanOutFreqDanfoss / OJ-DV Exhaust fan frequencyHzRead
AV42046ExhFanPowerDanfoss / OJ-DV Exhaust fan powerkWRead
AV55707ExhFanPrcOutDanfoss / OJ-DV Exhaust fan output signal0-100%Read
AV55889ExhFanSpeedDanfoss / OJ-DV Exhaust fan speedrpmRead
AV2525ExhFanSpvMaxForceExhaust fan max force setpoint%, Pa or l/s depending on configurationRead
AV45030ExhFanSpvSt1SpvExhaust fan step 1 setpoint%, Pa or l/s depending on configurationRead
AV13370ExhFanSpvSt2SpvExhaust fan step 2 setpoint%, Pa or l/s depending on configurationRead
AV17038ExhFanSpvSt3SpvExhaust fan step 3 setpoint%, Pa or l/s depending on configurationRead
AV17551ExhFanTD_FlwExhaust fan controller (flow control) - Differential factorsRead
AV54708ExhFanTD_PrsExhaust fan controller - Differential factor (pressure control)sRead
AV32009ExhFanTI_FlwExhaust fan controller (flow control) - Integral factorsRead
AV60466ExhFanTI_PrsExhaust fan controller - Integral factor (pressure control)sRead
AV12306ExhFanToaCurveOutTX1Exhaust fan outdoor compensation curve - temperature X1°CRead
AV113ExhFanToaCurveOutTX2Exhaust fan outdoor compensation curve - temperature X2°CRead
AV4176ExhFanToaCurveOutTX3Exhaust fan outdoor compensation curve - temperature X3°CRead
AV24759ExhFanToaCurveOutTX4Exhaust fan outdoor compensation curve - temperature X4°CRead
AV3444ExhFanToaCurveSpY1Exhaust fan outdoor compensation curve - setpoint Y10-100%Read
AV15639ExhFanToaCurveSpY2Exhaust fan outdoor compensation curve - setpoint Y20-100%Read
AV11574ExhFanToaCurveSpY3Exhaust fan outdoor compensation curve - setpoint Y30-100%Read
AV24017ExhFanToaCurveSpY4Exhaust fan outdoor compensation curve - setpoint Y40-100%Read
AV1908ExhOJEngyCOMOJ-DV Exhaust fan energykWhRead
AV23230ExPreFilterPreAlmExtract air pre-filter Pre-alarmPaRead
AV4853ExtControlDlyOfTmExt ctrl off delayhRead
AV21813ExtCoolingCtrLoopKpCooling 2 - Proportional factorRead
AV21815ExtCoolingCtrLoopTDCooling 2 - Differential factorsRead
AV21814ExtCoolingCtrLoopTICooling 2 - Integral factorsRead
AV21810ExtHeatingCtrLoopKpHeating 2 - Proportional factorRead
AV21812ExtHeatingCtrLoopTDHeating 2 - Differential factorsRead
AV21811ExtHeatingCtrLoopTIHeating 2 - Integral factorsRead
AV54677ExtraClgOffTmpCooling 2 off temperature°CRead
AV4625ExtraHtgFrstSpvHeating 2 frost protection setpoint°CRead
AV60579ExtraHtgFrstSpvStByHeating 2 frost protection setpoint stand-by0 - 100%Read
AV27620ExtraHtgPreHtgX1Heating 2, pre-heating - X1°CRead
AV23431ExtraHtgPreHtgX2Heating 2, pre-heating - X2°CRead
AV22741ExtraHtgPreHtgY1Heating 2, pre-heating - Y1°CRead
AV26806ExtraHtgPreHtgY2Heating 2, pre-heating - Y20 - 100%Read
AV806ExtraHtgPrValAutoHeating 2 output signal-Auto mode P10Read
AV805ExtraHtgPrValValueHeating 2 output signal-Manual HMI BMSRead
AV58349ExtraSpvExtra Sequence setpoint°CRead
AV13916ExtraSpv2Extra setpoint 2°CRead
AV21837ExtrPrsBalCtrLoopKpExtract air pressure balance controller - Proportional factorRead
AV21839ExtrPrsBalCtrLoopTDExtract air pressure balance controller - Differential factorsRead
AV21838ExtrPrsBalCtrLoopTIExtract air pressure balance controller - Integral factorsRead
AV1886ExtSetpExhFanCOMExhaust fan external setpoint - Value comm.Pa or l/s depending on fan control type.Read
AVmin1884ExtSetpointSpvCOMExternal setpoint - Value comm.°CRead
AV1885ExtSetpSplyFanCOMSupply fan external setpoint - Value comm.Pa or l/s depending on fan control type.Read
AV21864FanClgCtrLoopKpFan cooling - Proportional factorRead
AV21866FanClgCtrLoopTDFan cooling - Differential factorsRead
AV21865FanClgCtrLoopTIFan cooling - Integral factorsRead
AV58670FanClgPrValActual fan cooling value0-100%Read
AV54041FanCmpClgDzFan compensation - Cooling neutral zone°CRead
AV41346FanCmpHtgDzFan compensation - Heating neutral zone°CRead
AV21933FanCmpHumCtrLoopKpFan compensation (humidification) - Proportional factorRead
AV21935FanCmpHumCtrLoopTDFan compensation (humidification) - Differential factorsRead
AV21934FanCmpHumCtrLoopTIFan compensation (humidification) - Integral factorsRead
AV15399FanCmpHumPrValActual fan compensation (humidification)0-100%Read
AV53848FanCmpHumSpvFan compensation humidity setpoint%RHRead
AV21858FanCmpTmpCtrLoopKpFan compensation (temp) - Proportional factorRead
AV21860FanCmpTmpCtrLoopTDFan compensation (temp) - Differential factorsRead
AV21859FanCmpTmpCtrLoopTIFan compensation (temp) - Integral factorsRead
AV59241FanCmpTmpSpvFan compensation - Temperature setpoint°CRead
AV21861FanHtgCtrLoopKpFan heating - Proportional factorRead
AV21863FanHtgCtrLoopTDFan heating - Differential factorsRead
AV21862FanHtgCtrLoopTIFan heating - Integral factorsRead
AV49915FanHtgPrValActual fan heating value0-100%Read
AV21948Heating3CtrLoopKpHeating 3 - Proportional factorRead
AV21950Heating3CtrLoopTDHeating 3 - Differential factorsRead
AV21949Heating3CtrLoopTIHeating 3 - Integral factorsRead
AV41995Heating3FrstSpvHeating 3 frost setpointRead
AV48713Heating3FrstSpvStByStandby setpoint htg 3Read
AV46841Heating3PreHtgX1Heating 3, pre-heating - X1Read
AV34248Heating3PreHtgY1Heating 3, pre-heating - Y1Read
AV46507Heating3PreHtgY2Heating 3, pre-heating - Y2Read
AV21801HeatingCtrLoopKpHeating 1 - Proportional factorRead
AV21803HeatingCtrLoopTDHeating 1 - Differential factorsRead
AV21802HeatingCtrLoopTIHeating 1 - Integral factorsRead
AV35635HeatingFrstSpvHeating 1 frost protection setpoint°CRead
AV12781HeatingFrstSpvStByHeating 1 frost protection setpoint stand-by°CRead
AV23412HeatingPreHtgX1Heating 1 Pre-heating - X10 - 100%Read
AV27415HeatingPreHtgX2Heating 1 Pre-heating - X2°CRead
AV26693HeatingPreHtgY1Heating 1 Pre-heating - Y1°CRead
AV22566HeatingPreHtgY2Heating 1 Pre-heating - Y20 - 100%Read
AV67312HRDewpointHeat recovery dew point°CRead
AV23404HRDewpointDz'Heat recovery dew point dead zone°CRead
AV21819HRecCtrLoopKpHeat recovery - Proportional factorRead
AV21821HRecCtrLoopTDHeat recovery - Differential factorsRead
AV21820HRecCtrLoopTIHeat recovery - Integral factorsRead
AV21822HRecDamperCtrLoopKpMixing damper controller - Proportional factorRead
AV21824HRecDamperCtrLoopTDMixing damper controller - Differential factorsRead
AV21823HRecDamperCtrLoopTIMixing damper controller - Integral factorsRead
AV21211HrecDampRecHeat recovery damper recovery value0-100%Read
AV21834HrecDewPProtCtrLoopKpHeat recovery frost protection pressure - Proportional factorRead
AV21836HrecDewPProtCtrLoopTDHeat recovery frost protection pressure - Differential factorsRead
AV21835HrecDewPProtCtrLoopTIHeat recovery frost protection pressure - Integral factorsRead
AV46606HrecDmpPosCtlrPrValMixing damper output signal0-100%Read
AV28958HrecDmpPosHrecX1Mixing - mixing damper - heat recovery X10-100%Read
AV16765HrecDmpPosHrecX2Mixing - mixing damper - heat recovery X20-100%Read
AV16943HrecDmpPosHrecY1Mixing - mixing damper - heat recovery Y10-100%Read
AV29260HrecDmpPosHrecY2Mixing - mixing damper - heat recovery Y20-100%Read
AV14531HrecDmpPosQminOutMixing damper - Q min outl/sRead
AV39790HrecDmpPosSplyX1Mixing - outdoor damper X10-100%Read
AV43789HrecDmpPosSplyX2Mixing - outdoor damper X20-100%Read
AV43103HrecDmpPosSplyY1Mixing - outdoor damper Y10-100%Read
AV38972HrecDmpPosSplyY2Mixing - outdoor damper Y20-100%Read
AV48520HrecDmpPosStrtupTmMixing damper - Start up timesRead
AV17247HrecEffEffHeat recovery efficiency0-100%Read
AV21831HRecFrstCtrLoopKpHeat recovery frost protection - Proportional factorRead
AV21833HRecFrstCtrLoopTDHeat recovery frost protection - Differential factorsRead
AV21832HRecFrstCtrLoopTIHeat recovery frost protection - Integral factorsRead
AV15072HRecFrstMinTmHeat exchanger - Frost min timeminRead
AV51620HrecFrstSpvHeat exchanger frost protection setpoint°CRead
AV33748HRecMBPreHtgPlate heat exchanger - Pre-heatingRead
AV24981HRecMBRtHumPlate heat exchanger - Return humidityRead
AV7889HRecMBRtTmpPHE Return temperature°CRead
AV30547HRecMBToaPHE Outside temperature°CRead
AV872HRecPmpActiveHourHeat exchanger pump - Operating hourshRead
AV21828HRecPrsFrstCtrLoopKpHeat recovery frost protection pressure - Proportional factorRead
AV21830HRecPrsFrstCtrLoopTDHeat recovery frost protection pressure - Differential factorsRead
AV21829HRecPrsFrstCtrLoopTIHeat recovery frost protection pressure - Integral factorsRead
AV2152HrecPrsFrstSpvHeat recovery frost setpoint st1°CRead
AV55606HrecPrsFrstSpvStByHeat recovery frost setpoint st2°CRead
AV50666HRExhDewPActv'Heat recovery exhaust temperature dew point activated°CRead
AV873Htg1PmpActiveHourHeating 1 pump - Operating hourshRead
AV874Htg2PmpActiveHourHeating 2 pump - Operating hourshRead
AV877Htg3PmpActiveHourHeating 3 pump - Operating hourshRead
AV810Htg3VlvAutoHeating 3 output signal-Auto mode P100-100%Read
AV809Htg3VlvValueHeating 3 output signal-Manual HMI BMS0-100%Read
AV804HtgPrValAutoHeating1 output signal-Auto mode P100-100%Read
AV803HtgPrValValueHeating1 output signal-Manual HMI BMS0-100%Read
AV21852HtgReClgCtrLoopKpReCooler heating controller - Proportional factorRead
AV21854HtgReClgCtrLoopTDReCooler heating controller - Differential factorsRead
AV21853HtgReClgCtrLoopTIReCooler heating controller - Integral factorsRead
AV814HumFrcHtgAutoForce heating output signal-Auto mode P100-100%Read
AV21954HumFrcHtgCtrLoopKpForce heating - Proportional factorRead
AV21956HumFrcHtgCtrLoopTDForce heating - Differential factorsRead
AV21955HumFrcHtgCtrLoopTIForce heating - Integral factorsRead
AV813HumFrcHtgValueForce heating output signal-Manual HMI BMS0-100%Read
AV21936HumidityCtrLoopKpHumidification - Proportional factorRead
AV21938HumidityCtrLoopTDHumidification - Differential factorsRead
AV21937HumidityCtrLoopTIHumidification - Integral factorsRead
AV57438HumMaxCtlrMaxSpvSupply humidification max setpoint (pure room/extract control)%RH or g/kg depending on configurationRead
AV21930HumMaxCtrLoopKpHumidification max - Proportional factorRead
AV21932HumMaxCtrLoopTDHumidification max - Differential factorsRead
AV21931HumMaxCtrLoopTIHumidification max - Integral factorsRead
AV62563HumSpvAbsCmpDeHumOutTmpX1Dehumidification outdoor compensation curve - temperature X1 (abs)°CRead
AV50176HumSpvAbsCmpDeHumOutTmpX2Dehumidification outdoor compensation curve - temperature X2 (abs)°CRead
AV54305HumSpvAbsCmpDeHumOutTmpX3Dehumidification outdoor compensation curve - temperature X3 (abs)°CRead
AV42182HumSpvAbsCmpDeHumOutTmpX4Dehumidification outdoor compensation curve - temperature X4 (abs)°CRead
AV31702HumSpvAbsCmpDeHumPrValActual calculated dehumidification setpoint (abs.)g/kgRead
AV50286HumSpvAbsCmpDeHumSpY1Dehumidification outdoor compensation curve - setpoint Y1 (abs)g/kgRead
AV62477HumSpvAbsCmpDeHumSpY2Dehumidification outdoor compensation curve - setpoint Y2 (abs)g/kgRead
AV58412HumSpvAbsCmpDeHumSpY3Dehumidification outdoor compensation curve - setpoint Y3 (abs)g/kgRead
AV38091HumSpvAbsCmpDeHumSpY4Dehumidification outdoor compensation curve - setpoint Y4 (abs)g/kgRead
AV41780HumSpvAbsCmpHumOutTmpX1Humidification outdoor compensation curve - temperature X1 (abs)°CRead
AV37719HumSpvAbsCmpHumOutTmpX2Humidification outdoor compensation curve - temperature X2 (abs)°CRead
AV33654HumSpvAbsCmpHumOutTmpX3Humidification outdoor compensation curve - temperature X3 (abs)°CRead
AV62353HumSpvAbsCmpHumOutTmpX4Humidification outdoor compensation curve - temperature X4 (abs)°CRead
AV4907HumSpvAbsCmpHumPrValActual calculated humidification setpoint (abs.)g/kgRead
AV40157HumSpvAbsCmpHumSpY1Humidification outdoor compensation curve - setpoint Y1 (abs)g/kgRead
AV44222HumSpvAbsCmpHumSpY2Humidification outdoor compensation curve - setpoint Y2 (abs)g/kgRead
AV48287HumSpvAbsCmpHumSpY3Humidification outdoor compensation curve - setpoint Y3 (abs)g/kgRead
AV52344HumSpvAbsCmpHumSpY4Humidification outdoor compensation curve - setpoint Y4 (abs)g/kgRead
AV61029HumSpvAbsDzAbsolute humidity - Neutral zone%RH or g/kg depending on configurationRead
AV20105HumSpvAbsSpvAbsolute humidity - Setpoint%RH or g/kg depending on configurationRead
AV62747HumSpvAbsSpvDehumAbsolute humidity - Dehumidification setpoint%RH or g/kg depending on configurationRead
AV22791HumSpvAbsSpvHumAbsolute humidity - Humidification setpoint%RH or g/kg depending on configurationRead
AV1776HumSpvRelCmpDeHumOutTmpX1Dehumidification outdoor compensation curve - temperature X1 (rel)°CRead
AV13971HumSpvRelCmpDeHumOutTmpX2Dehumidification outdoor compensation curve - temperature X2 (rel)°CRead
AV9906HumSpvRelCmpDeHumOutTmpX3Dehumidification outdoor compensation curve - temperature X3 (rel)°CRead
AV22101HumSpvRelCmpDeHumOutTmpX4Dehumidification outdoor compensation curve - temperature X4 (rel)°CRead
AV41445HumSpvRelCmpDeHumPrValActual calculated dehumidification setpoint (rel.)%RHRead
AV37518HumSpvRelCmpDeHumSpY1Dehumidification outdoor compensation curve - setpoint Y1 (rel)%RHRead
AV41709HumSpvRelCmpDeHumSpY2Dehumidification outdoor compensation curve - setpoint Y2 (rel)%RHRead
AV45772HumSpvRelCmpDeHumSpY3Dehumidification outdoor compensation curve - setpoint Y3 (rel)%RHRead
AV49707HumSpvRelCmpDeHumSpY4Dehumidification outdoor compensation curve - setpoint Y4 (rel)%RHRead
AV64003HumSpvRelCmpHumOutTmpX1Humidification outdoor compensation curve - temperature X1 (rel)°CRead
AV51808HumSpvRelCmpHumOutTmpX2Humidification outdoor compensation curve - temperature X2 (rel)°CRead
AV55873HumSpvRelCmpHumOutTmpX3Humidification outdoor compensation curve - temperature X3 (rel)°CRead
AV43686HumSpvRelCmpHumOutTmpX4Humidification outdoor compensation curve - temperature X4 (rel)°CRead
AV64865HumSpvRelCmpHumPrValActual calculated humidification setpoint (rel.)%RHRead
AV38546HumSpvRelCmpHumSpY1Humidification outdoor compensation curve - setpoint Y1 (rel)%RHRead
AV42737HumSpvRelCmpHumSpY2Humidification outdoor compensation curve - setpoint Y2 (rel)%RHRead
AV46800HumSpvRelCmpHumSpY3Humidification outdoor compensation curve - setpoint Y3 (rel)%RHRead
AV50743HumSpvRelCmpHumSpY4Humidification outdoor compensation curve - setpoint Y4 (rel)%RHRead
AV37532HumSpvRelDzRelative humidity - Neutral zone%RH or g/kg depending on configurationRead
AV2194HumSpvRelSpvRelative humidity - Setpoint%RH or g/kg depending on configurationRead
AV24572MinV1CircReCoolerReCooler - Minimum value 1 circuit0-100%Read
AV45358MinV2CircReCoolerReCooler - Minimum value 2 circuits0-100%Read
AV7039MinV3CircReCoolerReCooler - Minimum value 3 circuits0-100%Read
AV4465NightCoolMinOutTmpNight free cooling - Min outdoor temperature°CRead
AV1475NightCoolOnDiffNight free cooling - Delta°CRead
AV17755NightCoolRmHysNight free cooling - Hysteresis°CRead
AV7412NightCoolRmSpvNight free cooling room setpoint°CRead
AV56045OutDewpointOutdoor air dew point°CRead
AV57226OutEnthOutdoor air enthalpykJ/kgRead
AV16390OutHumAbsOutdoor air humidity absoluteg/kgRead
AV1887OutHumCOMOutdoor air relative humidity - Value comm.0 - 100 %RHRead
AV1882OutTmpCOMOutdoor air temperature - Value comm.°CRead
AV1883OutTmpWallCOMOutdoor temperature wall sensor - Value comm.°CRead
AV6439PreElHtgFanLmtAreaArea, electrical pre-heaterm2Read
AV22371PreElHtgFanLmtKfactorK-factor, electrical pre-heater0-100%Read
AV15308PreElHtgFanLmtPrValPower reduction, electrical pre-heater0-100%Read
AV36755PreElHtgFanLmtvv, Flow over heater, electrical pre-heaterm/sRead
AV49835PreElHtgFanLmtvMaxvMax, air speed, electrical pre-heaterm/sRead
AV14837PreElHtgFanLmtvMinvMin, air speed, electrical pre-heaterm/sRead
AV21945PreHeatingCtrLoopKpPre-heater - Proportional factorRead
AV21947PreHeatingCtrLoopTDPre-heating - Differential factorsRead
AV21946PreHeatingCtrLoopTIPre-heating - Integral factorsRead
AV34181PreHeatingFrstSpvPre-heater frost setpoint°CRead
AV57320PreHeatingFrstSpvStByPre-heater standby setpoint°CRead
AV3258PreHeatingPreHtgX1Pre-heater outdoor temperature X1°CRead
AV15577PreHeatingPreHtgX2Pre-heater outdoor temperature X2°CRead
AV16267PreHeatingPreHtgY1Pre-heater pos Y10-100%Read
AV4072PreHeatingPreHtgY2Pre-heater pos Y20-100%Read
AV879PreHtgPmpActiveHourPre-heater pump - Operating hourshRead
AV808PreHtgPrValAutoPre-heater output signal-Auto mode P100-100%Read
AV807PreHtgPrValValuePre-heater output signal-Manual HMI BMS0-100%Read
AV6627PreHtgSpvPre-heater setpoint°CRead
AV1577RecDampminFrshAirMixing damper - Min fresh air0 - 100%Read
AV61369RmEnthRoom enthalpykJ/kgRead
AV17315RmHumAbsRoom humidity absoluteg/kgRead
AV39703RmHumDevAlmMaxDevMax deviation room hum%RHRead
AV1888RoomHumCOMRoom relative humidity - Value comm.0 - 100 %RHRead
AV1881RoomTmp2COMRoom temperature 2 - Value comm.°CRead
AV1880RoomTmpCOMRoom temperature - Value comm.°CRead
AV7266RtClcTCalculated temperature°CRead
AV816RtClgAutoExtract air cooling output signal-Auto mode P100-100%Read
AV815RtClgValueExtract air cooling output signal-Manual HMI BMS0-100%Read
AV17311RtEnthExtract air enthalpykJ/kgRead
AV24340RtHumAbsExtract air humidity (absolute)g/kgRead
AV61586RtRmTmpDevAlmMaxDevExtract/Room temperature - Maximum deviation°CRead
AV32099RtTwbWetbulb temp°CRead
AV52945SFPThe current SFP value of the unitkW/(m3/s)Read
AV24823SlaveOffsetSlave offsetl/sRead
AV29558SplyEnthSupply air enthalpykJ/kgRead
AV48318SplyExtraFltPreAlmSupply air extra filter 1 Pre-alarmRead0=Ok; 1=Alarm
AV870SplyFanActiveHourSupply fan - Operating hourshRead
AV46589SplyFanActSpvActual supply fan setpointl/sRead
AV56628SplyFanActValActual sply fan valueRead
AV15012SplyFanCurrentDanfoss / OJ-DV Supply fan currentARead
AV10903SplyFanCurvePrValActual calculated supply fan setpointRead
AV57203SplyFanDevAlmMaxDevSupply fan - Maximum deviation (flow control)%, Pa or l/s depending on configurationRead
AV27310SplyFanDevAlmMaxDevPrsSupply fan - Maximum deviation (pressure control)PaRead
AV57642SplyFanDevAlmMinLmtSupply fan - Minimum limit (flow control)Read
AV45SplyFanDevAlmMinLmtPrsSupply fan - Minimum limit (pressure control)PaRead
AV30980SplyFanEnergyDanfoss Supply fan EnergykWhRead
AV38592SplyFanKP_FlwSupply fan controller (flow control) - Proportional factorRead
AV2043SplyFanKP_PrsSupply fan controller - Proportional factor (pressure control)Read
AV15375SplyFanMotorVoltDanfoss / OJ-DV Supply fan motor voltageVRead
AV60939SplyFanOpDaysDanfoss / OJ-DV Supply fan - Operating daysdaysRead
AV40024SplyFanOpHrsDanfoss / OJ-DV Supply fan - Operating hourshRead
AV48048SplyFanOpMinutesDanfoss / OJ-DV Supply fan - Operating minutesMinRead
AV2558SplyFanOutFreqDanfoss / OJ-DV Supply fan frequencyHzRead
AV20963SplyFanPowerDanfoss / OJ-DV Supply fan powerkWRead
AV47905SplyFanPrcOutDanfoss / OJ-DV Supply fan output signal0-100%Read
AV12172SplyFanSpeedDanfoss / OJ-DV Supply fan speedrpmRead
AV25092SplyFanSpvMaxForceSupply fan max force setpoint%, Pa or l/s depending on configurationRead
AV52572SplyFanSpvSt1SpvSupply fan step 1 setpoint%, Pa or l/s depending on configurationRead
AV22144SplyFanSpvSt2SpvSupply fan step 2 setpoint%, Pa or l/s depending on configurationRead
AV8244SplyFanSpvSt3SpvSupply fan step 3 setpoint%, Pa or l/s depending on configurationRead
AV46862SplyFanTD_PrsSupply fan controller - Differential factor (pressure control)sRead
AV8115SplyFanTI_FlwSupply fan controller (flow control) - Integral factorsRead
AV36488SplyFanTI_PrsSupply fan controller - Integral factor (pressure control)sRead
AV41824SplyFanToaCurveOutTX1Supply fan outdoor compensation curve - temperature X1°CRead
AV37635SplyFanToaCurveOutTX2Supply fan outdoor compensation curve - temperature X2°CRead
AV33570SplyFanToaCurveOutTX3Supply fan outdoor compensation curve - temperature X3°CRead
AV62405SplyFanToaCurveOutTX4Supply fan outdoor compensation curve - temperature X4°CRead
AV41763SplyFanToaCurveSpY1Supply fan outdoor compensation curve - setpoint Y10-100%Read
AV37696SplyFanToaCurveSpY2Supply fan outdoor compensation curve - setpoint Y20-100%Read
AV33633SplyFanToaCurveSpY3Supply fan outdoor compensation curve - setpoint Y30-100%Read
AV62342SplyFanToaCurveSpY4Supply fan outdoor compensation curve - setpoint Y40-100%Read
AV32127SplyFilterPreAlmOutdoor air filter Pre-alarmPaRead
AV13958SplyHumAbsSupply air humidity absoluteg/kgRead
AV22230SplyHumDevAlmMaxDevMax deviation supply humg/kg %RH or g/ kg depending on configurationRead
BI22605AuxAlmAuxiliary alarmRead0=Ok; 1=Alarm
BI21522AuxInpAuxiliary inputRead0=0; 1=1
BI24467Clg3PmpAlmCooling 3 pump alarmRead0=Ok; 1=Alarm
BI45154ClgAlmCooling 1 DX alarmRead0=Ok; 1=Alarm
BI40242ClgPmpAlmCooling 1 pump alarmRead0=Ok; 1=Alarm
BI47934Cooling3PmpCmdFBFbValCooling 3 pump feedbackRead0=Ok; 1=Alarm
BI43526CoolingFBFbValCooling 1 DX feedbackRead0=Ok; 1=Alarm
BI51912CoolingPmpCmdFBFbValCooling 1 pump feedbackRead0=Ok; 1=Alarm
BI27338DamperExhFBFbValExhaust air damper feedbackRead0=Ok; 1=Alarm
BI6336DamperSplyFBFbValOutdoor air damper feedbackRead0=Ok; 1=Alarm
BI4964ElHtgAlmElectrical Heating 1 alarmRead0=Ok; 1=Alarm
BI9864EmergencyStopEmergency stop inputRead0=Off; 1=On
BI1897EmergencyStopCOMEmergency Stop input - Value comm.Read0=Off; 1=On
BI55865ExhFanAlmExhaust fan alarmRead0=Ok; 1=Alarm
BI32844ExhFanFBFbValExhaust fan feedbackRead0=Ok; 1=Alarm
BI45320ExhFilterAlmExtract filter alarmRead0=Ok; 1=Alarm
BI8711ExhPreFilterAlmExtract pre-filter DI alarmRead0=Ok; 1=Alarm
BI1903ExtAlm1COMExternal alarm 1 - Value comm.Read0=Ok; 1=Alarm
BI1904ExtAlm2COMExternal alarm 2 - Value comm.Read0=Ok; 1=Alarm
BI11643ExtCtrl1External control input 1Read0=Off; 1=On
BI1895ExtCtrl1COMExternal control input 1 - Value comm.Read0=Off; 1=On
BI7448ExtCtrl2External control input 2Read0=Off; 1=On
BI1896ExtCtrl2COMExternal control input 2 - Value comm.Read0=Off; 1=On
BI48824ExtraClgAlmCooling 2 DX alarmRead0=Ok; 1=Alarm
BI47898ExtraClgFBFbValCooling 2 DX feedbackRead0=Ok; 1=Alarm
BI31967ExtraClgPmpAlmCooling 2 pump alarmRead0=Ok; 1=Alarm
BI54719ExtraClgPmpCmdFBFbValCooling 2 pump feedbackRead0=Ok; 1=Alarm
BI23132ExtraElHtgAlmElectrical Heating 2 alarmRead0=Ok; 1=Alarm
BI34361ExtraFrstDtctrHeating 2 frost monitorRead0=Ok; 1=Alarm
BI23306ExtraHtgPmpAlmHeating 2 pump alarmRead0=Ok; 1=Alarm
BI13329ExtraHtgPmpCmdFBFbValHeating 2 pump feedbackRead0=Ok; 1=Alarm
BI8558FanAlmFan alarmRead0=Ok; 1=Alarm
BI13699FilterAlmFilter alarmRead0=Ok; 1=Alarm
BI28514FireAlmFire alarm alarmRead0=Ok; 1=Alarm
BI59736FireAlm2Fire alarm 2 alarmRead0=Ok; 1=Alarm
BI1901FireAlm2COMFire alarm input 2 - Value comm.Read0=Ok; 1=Alarm
BI63865FireAlm3Fire alarm 3 alarmRead0=Ok; 1=Alarm
BI1902FireAlm3COMFire alarm input 3 - Value comm.Read0=Ok; 1=Alarm
BI1900FireAlmCOMFire alarm - Value comm.Read0=Ok; 1=Alarm
BI53169FireDamper1FdbkClsdFire damper closedRead0=Ok; 1=Alarm
BI3118FireDamper1FdbkOpnFire damper openedRead0=Ok; 1=Alarm
BI44469FireDamper1NoMoveFire damper no moveRead0=Ok; 1=Alarm
BI5685FireDamper2FdbkClsdFire damper 2 closedRead0=Ok; 1=Alarm
BI2231FireDamper2FdbkOpnFire damper 2 openedRead
BI7990FireDamper2NoMoveFire damper 2 no moveRead
BI64454Heating3PmpCmdFBFbValHeating 3 pump feedbackRead
BI15639HeatingPmpCmdFBFbValHeating 1 pump feedbackRead
BI62931HRecAlmHeat recovery alarmRead0=Ok; 1=Alarm
BI61487HRecFdbkAlmHeat exchanger feedback alarmRead0=Ok; 1=Alarm
BI31092HrecFrstDtctrHeat recovery frost monitorRead0=Ok; 1=Alarm
BI18003HRecPmpAlmHeat recovery pump alarmRead0=Ok; 1=Alarm
BI34557HrecPmpCmdFBFbValHeat recovery pump feedbackRead0=Ok; 1=Alarm
BI13429Htg3FrstDtctrHeating 3 frost monitorRead0=Ok; 1=Alarm
BI56854Htg3PmpAlmHeating 3 pump alarmRead0=Ok; 1=Alarm
BI21294HtgFrstDtctrHeating 1 frost monitorRead0=Ok; 1=Alarm
BI47847HtgPmpAlmHeating 1 pump alarmRead0=Ok; 1=Alarm
BI14608HumidityCtrlCmdFBFbValHumidifier feedbackRead0=Ok; 1=Alarm
BI24144HumidityCtrlPmpCmdFBFbValHumidifier pump feedbackRead0=Ok; 1=Alarm
BI3706HumPmpAlmHumidifier pump alarmRead0=Ok; 1=Alarm
BI57484PreElHtgAlmElectrical pre-heater alarmRead0=Ok; 1=Alarm
BI31186PreHeatingPmpCmdFBFbValPre-heater pump feedbackRead0=OK; 1=No Fdbk
BI24111PreHtgFrstDtctrPre-heater frost monitorRead0=Ok; 1=Alarm
BI36251PreHtgPmpAlmPre-heater pump alarmRead0=Ok; 1=Alarm
BI36836RtHumAlmExtract air humidity (cooling)Read0=Ok; 1=Alarm
BI28757SplyFanAlmSupply fan alarmRead0=Ok; 1=Alarm
BI64102SplyFanFBFbValSupply fan feedback alarmRead0=Ok; 1=Alarm
BI34066SplyFilterAlmOutdoor filter alarmRead0=Ok; 1=Alarm
BI55258SplyPreFilterAlmOutdoor pre-filter DI alarmRead0=Ok; 1=Alarm
BI26679SuWiSwtchSummer/Winter changeover inputRead0=Winter; 1=Summer
BI1898SuWiSwtchCOMSummer/Winter changeover input - Value comm.Read0=Winter; 1=Summer
BO5714AlmOutHighAlarm output 1Read0=Normal; 1=Alarm
BO8035AlmOutLowAlarm output 2Read0=Normal; 1=Alarm
BO5163AuxOpModeIndAuxiliary operation mode outputRead0=Off; 1=On
BO22528AuxTspOutputAuxiliary time switch program outputRead0=Off; 1=On
BO53375Cooling3PmpCmdOnOffCooling 3 pump cmdRead0=Off; 1=On
BO10276CoolingPmpCmdOnOffCooling pump commandRead0=Off; 1=On
BO43251DamperExhOnOffExhaust air damper commandRead0=Off; 1=On
BO6170DamperSplyOnOffOutdoor air damper commandRead0=Off; 1=On
BO9054ExhFanCmdOnOffExhaust fan cmdRead0=Off; 1=On
BO63601ExtraClgPmpCmdOnOffCooling 2 pump commandRead0=Off; 1=On
BO29000ExtraHtgCmdStOnOffHeating 2 El cmdRead0=Off; 1=On
BO31944ExtraHtgPmpCmdOnOffHeating 2 pump commandRead0=Off; 1=On
BO12328FireDamper1CmdFire damper commandRead0=Off; 1=On
BO64011FireDamper2CmdFire damper 2 cmdRead0=Off; 1=On
BO60543Heating3PmpCmdOnOffHeating 3 pump cmdRead0=Off; 1=On
BO63332HeatingCmdStOnOffHtg1 El cmdRead0=Off; 1=On
BO10264HeatingPmpCmdOnOffHeating 1 pump commandRead0=Off; 1=On
BO3016HrecOnOffHeat recovery on/offRead0=Off; 1=On
BO59969HrecPmpCmdOnOffHeat recovery (pump) commandRead0=Off; 1=On
BO9278HumForceHtgOnOffForce heating CmdRead0=Off; 1=On
BO18044HumidityCtrlCmdOnOffHumidifier commandRead0=Off; 1=On
BO49625HumidityCtrlPmpCmdOnOffHumidifier pump commandRead0=Off; 1=On
BO22734PreHeatingCmdStOnOffHtg1 El cmdRead0=Off; 1=On
BO12792PreHeatingPmpCmdOnOff'Pre-heater pump cmdRead0=Off; 1=On
BO16868SplyFanCmdOnOffSupply fan cmdRead0=Off; 1=On
BV20016ActvClgRecPrValCooling recoveryRead0=Passive; 1=Active
BV27019BlkClgRecPrValBlock cooling recoveryRead0=Inactive; 1=Active
BV32783BlkHtgRecPrValBlock heat recoveryRead0=Inactive; 1=Active
BV12464CalibrationAlmCalibration alarmRead0=Ok; 1=Alarm
BV49897CgEm24ModbusAlmCG-EM24 com alarmRead0=Ok; 1=Alarm
BV60516CommTestCommunication test pulseRead0=0; 1=1
BV9543DefrostActvReCoolerReCooler - Defrosting activatedRead0=Inactive; 1=Active
BV3269DewPCtrlActDewpoint control activatedRead0=Off; 1=On
BV48629EconetAlmEconet alarmRead0=Ok; 1=Alarm
BV14622EconetModbusAlmEconet com alarmRead0=Ok; 1=Alarm
BV25633EnFanClgPrValActivateRead0=Passive; 1=Active
BV17396EnFanHtgPrValActivateRead0=Passive; 1=Active
BV19549ExhFanBrkChopFltWarnOJ-DV exhaust fan break chopper fault warningRead0=Ok; 1=Alarm
BV45653ExhFanComErMOCAlmOJ-DV exhaust fan com. error MOC alarmRead0=Ok; 1=Alarm
BV31724ExhFanDevAlmAlmExh fan deviationRead0=Passive; 1=Active
BV851ExhFanDevInAlarmExhaust fan deviation - AlarmRead0=Passive; 1=Active
BV42595ExhFanEEPromWarnOJ-DV exhaust fan EEPROM error warningRead0=Ok; 1=Alarm
BV20714ExhFanExt24VOverloadOJ-DV exhaust fan ext.24V supply overloadRead0=Ok; 1=Alarm
BV35044ExhFanIHiAlmOJ-DV exhaust fan I HI alarmRead0=Ok; 1=Alarm
BV48716ExhFanInpPhaseWarnOJ-DV exhaust fan input phase errorRead0=Ok; 1=Alarm
BV12014ExhFanIntHWAlmOJ-DV exhaust fan internal HW fault alarmRead0=Ok; 1=Alarm
BV11735ExhFanIntStopAlmOJ-DV exhaust fan internal stop alarmRead0=Ok; 1=Alarm
BV61771ExhFanLimitWarnOJ-DV exhaust fan limit warningRead0=Ok; 1=Alarm
BV2305ExhFanModbusAlmExhaust fan com alarmRead0=Ok; 1=Alarm
BV28131ExhFanMotorPhaseAlmOJ-DV exhaust fan motor phase error alarmRead0=Ok; 1=Alarm
BV18566ExhFanRotBlkWarnOJ-DV exhaust fan rotor blocked errorRead0=Ok; 1=Alarm
BV3591ExhFanRotDirAlmOJ-DV exhaust fan rotor direction alarmRead0=Ok; 1=Alarm
BV3294ExhFanTmpHiWarnOJ-DV exhaust fan temperature high warningRead0=Ok; 1=Alarm
BV34793ExhFanWarnOJ-DV exhaust fan warningRead0=Ok; 1=Alarm
BV22371ExhFanVHiAlmOJ-DV exhaust fan V HI alarmRead0=Ok; 1=Alarm
BV63996ExhFanVLoAlmOJ-DV exhaust fan V LO alarmRead0=Ok; 1=Alarm
BV49301ExhFanVRippleWarnOJ-DV exhaust fan V ripple warningRead0=Ok; 1=Alarm
BV36120FanOpHrsAlmFan operating hours alarmRead0=Ok; 1=Alarm
BV47413HRecMBDefrostPlate heat exchanger - DefrostRead0=Off; 1=On
BV29571HRecMBGT3AlmPlate heat exchanger - GT3 AlarmRead0=Ok; 1=Alarm
BV38576HRecMBLiveBitAlmPlate heat exchanger - LiveBit AlarmRead0=Ok; 1=Alarm
BV40927HRecMBOvrHtgPlate heat exchanger - OverheatingRead0=Ok; 1=Alarm
BV47333HRecMBPrsSwiPlate heat exchanger - Prs-switchRead0=Off; 1=On
BV19292HRecMBSaAlmPlate heat exchanger - S-AlarmRead0=Ok; 1=Alarm
BV11442HRecModbusAlmHeat exchanger com alarmRead0=Ok; 1=Alarm
BV18571Htg1ModbusAlmMB-Htg1 AlmRead0=Ok; 1=Alarm
BV54103Htg2ModbusAlmMB-Htg2 AlmRead0=Ok; 1=Alarm
BV42467Htg3ModbusAlmMB-Heating 3 alarmRead0=Ok; 1=Alarm
BV24032ManualModeManual modeRead0=Auto; 1=Manual
BV57614MBCommAlmModbus communication alarmRead0=Ok; 1=Alarm
BV668PreHtgModbusAlmMB-Pre-heater alarmRead0=Ok; 1=Alarm
BV57971ReCoolerCirc1AlmReCooler circuit 1 alarmRead0=Ok; 1=Alarm
BV31151ReCoolerCirc2AlmReCooler circuit 2 alarmRead0=Ok; 1=Alarm
BV3867ReCoolerCirc3AlmReCooler circuit 3 alarmRead0=Ok; 1=Alarm
BV43898ReCoolerCompAlmReCooler compressor alarmRead0=Ok; 1=Alarm
BV22662ReCoolerDiffPrsAlmReCooler diff.pressure alarmRead0=Ok; 1=Alarm
BV23528ReCoolerDischaPrbAlmReCooler discharge probe error alarmRead0=Ok; 1=Alarm
BV51749ReCoolerDischaTmpAlmReCooler discharge temp alarmRead0=Ok; 1=Alarm
BV14095ReCoolerEEVAlmReCooler EEV error alarmRead0=Ok; 1=Alarm
BV58255ReCoolerHighEnvlAlmReCooler high envelope alarmRead0=Ok; 1=Alarm
BV27958ReCoolerLowEnvlAlmReCooler low envelope alarmRead0=Ok; 1=Alarm
BV51788ReCoolerLowSupHeatAlmReCooler low super heat alarmRead0=Ok; 1=Alarm
BV42357ReCoolerMaxPrsAlmReCooler max pressure alarmRead0=Ok; 1=Alarm
BV11761ReCoolerMinPrsAlmReCooler min pressure alarmRead0=Ok; 1=Alarm
BV51899ReCoolerRotorAlmReCooler rotor alarmRead0=Ok; 1=Alarm
BV42594ReCoolerSucPrbAlmReCooler suction probe error alarmRead0=Ok; 1=Alarm
BV64374ReCoolerVFDAlmReCooler VFD alarmRead0=Off; 1=On
BV56902ReCoolerVFDOffLineAlmReCooler VFD offline alarmRead0=Ok; 1=Alarm
BV5243RevClgModbusAlmReCooler alarmRead0=Ok; 1=Alarm
BV21718RmHumDevAlmAlmRoom air humidity deviationRead0=Passive; 1=Active
BV46256RtHumModbusAlmMB-Extract humidity (cooling)Read0=Ok; 1=Alarm
BV7373RtRmTmpDevAlmAlmExtract/Room air temperature deviationRead0=Passive; 1=Active
BV4286RtTmpFireAlmExtract air temperature fire alarmRead0=Ok; 1=Alarm
BV20345SplyFanBrkChopFltWarnOJ-DV supply fan break chopper fault warningRead0=Ok; 1=Alarm
BV30320SplyFanComErMOCAlmOJ-DV supply fan com. error MOC alarmRead0=Ok; 1=Alarm
BV6486SplyFanDevAlmAlmSupply fan deviationRead0=Passive; 1=Active
BV850SplyFanDevInAlarmSupply fan deviation - AlarmRead0=Ok; 1=Alarm
BV11239SplyFanEEPromWarnOJ-DV supply fan EEPROM error warningRead0=Ok; 1=Alarm
BV21454SplyFanExt24VOverloadOJ-DV supply fan ext.24V supply overloadRead0=Ok; 1=Alarm
BV59998SplyFanIHiAlmOJ-DV supply fan I HI alarmRead0=Ok; 1=Alarm
BV644SplyFanInpPhaseWarnOJ-DV supply fan input phase errorRead0=Ok; 1=Alarm
BV17719SplyFanIntHWAlmOJ-DV supply fan internal HW fault alarmRead0=Ok; 1=Alarm
BV41043SplyFanIntStopAlmOJ-DV supply fan internal stop alarmRead0=Ok; 1=Alarm
BV62854SplyFanLimitWarnOJ-DV supply fan limit warningRead0=Ok; 1=Alarm
BV45899SplyFanModbusAlmSupply fan com alarmRead0=Ok; 1=Alarm
BV50100SplyFanMotorPhaseAlmOJ-DV supply fan motor phase error alarmRead0=Ok; 1=Alarm
BV50434SplyFanRotBlkWarnOJ-DV supply fan rotor blocked errorRead0=Ok; 1=Alarm
BV2762SplyFanRotDirAlmOJ-DV supply fan rotor direction alarmRead0=Ok; 1=Alarm
BV2067SplyFanTmpHiWarnOJ-DV supply fan temperature high warningRead0=Ok; 1=Alarm
BV64963SplyFanWarnOJ-DV supply fan warningRead0=Ok; 1=Alarm
BV13785SplyFanVHiAlmOJ-DV supply fan V HI alarmRead0=Ok; 1=Alarm
BV39750SplyFanVLoAlmOJ-DV supply fan V LO alarmRead0=Ok; 1=Alarm
BV1200SplyFanVRippleWarnOJ-DV supply fan V ripple warningRead0=Ok; 1=Alarm
BV57113SplyHumDevAlmAlmSupply air humidity deviationRead0=Passive; 1=Active
BV38175SplyTmpDevAlmAlmSupply air temperature deviationRead0=Passive; 1=Active
BV44098SplyTmpFireAlmSupply air temperature fire alarmRead0=Ok; 1=Alarm
BV9042TWCtrlrTwin Wheel controller alarmRead0=Ok; 1=Alarm
BV61922ZoneCtrlrZone controllerRead0=Ok; 1=Alarm
MO30094CoolingCmdDxStCooling DX commandRead0=Auto; 1=Off; 2=St1; 3=St2; 4=St3
MO27550ExtraClgCmdDxStCooling 2 DX commandRead0=Auto; 1=Off; 2=St1; 3=St2; 4=St3
MV39130AckAlmPlsAlarm acknowledgeRead0=Off; 1=On
MV28561ActCtrlModeActual temperature control modeRead0=Room; 1=Return; 2=Supply
MV25131ActCtrlModeHumActual humidification control modeRead0=Room; 1=Return; 2=Supply
MV28279ActFanStepActual fan stepRead0=Off; 1=Stage1; 2=Stage2; 3=Stage3
MVmin6080ActOpModeActual operating modeRead0=Off; 1=On/Comfort; 2=Economy; 3=Na; 4=Osstp; 5=Nightcooling; 6=Unoccupied (Temperature start); 7=Nightkick (Test temperature); 8=Firedamper test; 9=Fire; 10=Stop; 11=Overrun; 12=Startup
MVmin32321ActOpStaActual operation statusRead0=Nu; 1=Configuration error; 2=SUF; 3=Fire alarm activated; 4=MsgCl0; 5=Emergency Stop; 6=MsgCl1; 7=Fire damper test activated; 8=Manual operation; 9=ExtC; 10=BMS; 11=Time scheduling program; 12=Boost; 13=Night heating/Night cooling
MV19801ActvClgRecKvalActivate cooling recovery - KValRead0=Lower; 1=Higher
MV22887AdvHumFnctAdvanced humidifcation functionRead0=No; 1=Yes
MV46769AlmCl0Alarm class Danger alarm (A) statusRead0=Normal; 1=Alarm
MVmin42640AlmCl1Alarm class Critical alarm (A) statusRead0=Normal; 1=Alarm
MV38643AlmCl2Alarm class Low alarm (B) statusRead0=Normal; 1=Alarm
MV34514AlmCl3Alarm class Warning alarm (C) statusRead0=Normal; 1=Alarm
MV48172AuxiliaryBmsTimeAuxSwtchAux BMS TSP outputRead0=Auto; 1=Off; 2=On
MV44050AuxiliaryTspCopyAuxPlsAuxiliaryTspCopyAux.PlsRead0=Auto; 1=Off; 2=On
MV39893BlkClgRecKvalBlock cooling recovery - KValRead0=Lower; 1=Higher
MV40828BlkHtgRecKvalBlock heat recovery - KValRead0=Lower; 1=Higher
MV2103BlockDHumDew point blocks dehumidificationRead0=No; 1=Yes
MV53050CG_EM24_1ResetParPlsEnergy meter reset partialRead0=Passive; 1=Active
MV13545ClgStartBMSCooling 1 start BMSRead0=Off; 1=On
MV1708CommTestEnEnable communication testRead0=No; 1=Yes
MV3329CounterFlowExchOffsetBoostCounter flow heat exchanger - Offset boostRead0=Low Boost; 1=Normal Boost; 2=High Boost
MV41930DamperDamper functionRead0=No; 1=Combined; 2=Outside; 3=Outside+Exhaust
MV50593DencityCorrDensity compensationRead0=No; 1=ExhFlow; 2=ExhFlow+SplyFlow
MV48718DewPSwtchDewpoint control switchRead0=H-Recov.; 1=Pre Htg.
MV56633DmpModbusAlmModbus damperRead0=Auto; 1=Normal; 2=adr150 (Outdoor air damper 1); 3=adr151 (Outdoor air damper 2); 4=adr152 (Exhaust air damper 1); 5=adr153 (Exhaust air damper 2); 6=adr154 (Extract air damper 1); 7=adr155 (Extract air damper 2); 8=adr156 (Mixing/Recirculation air; damper 1); 9=adr157 (Mixing/Recirculation air; damper 2); 10=adr158 (Plate by-pass damper); 11=adr159 (Extra supply air VVX damper; 1); 12=adr160 (Extra supply air VVX damper; 2); 13=adr161 (Supply air damper 1); 14=adr162 (Supply air damper 2); 15=adr163 (Extra extract air VVX damper; 1); 16=adr164 (Extra extract air VVX damper; 2); 17=adr165 (Fire by-pass damper 1); 18=adr166 (Fire by-pass damper 2)
MV30051DPTSnsrModbusAlmDPT sensor com alarmRead0=Ok; 1=Alarm
MV50595EconetActOpModeEconet operation modeRead0=Stop; 1=Alarm; 2=Idle; 3=Startup; 4=Heatrec; 5=Cooling; 6=Coolrec; 7=Manual
MV32613EnFanClgKValFunction < - >Read0=Lower; 1=Higher
MV3356EnFanHtgKValFunction < - >Read0=Lower; 1=Higher
MV43819ExhEngUnitExhaust fan engineering unitRead0=%; 1=Pa; 2=l/s; 3=m³/h
MV18848ExhFanActAlmExhaust fan alarmRead0=Nu; 1=MOvrVlt.; 2=MUndrVlt.; 3=DClinkUndrVlt; 4=DClinkOvrVlt; 5=IntElectr; 6=Locked; 7=HallSnsr; 8=Ovrh
MV39335ExhFanActWarnExhaust fan warningRead0=Nu; 1=OpenCircutInp; 2=ActSpdLowLlim; 3=BrkOp; 4=DCLlinkVlt; 5=ElectrTmp; 6=MtrTmp; 7=OutpStgTmp; 8=Mes
MV56664ExhFanExtSetPFnctExhaust fan external setpoint functionRead0=Relative; 1=Absolute
MV30666ExhFanPrsCtrlModeExhaust fan pressure controlRead0=lnactive; 1=Step; 2=Linear
MV64292ExhSnsrExhaust air temperatureRead0=No; 1=One; 2=Two
MV30799ExtControlActModeActual operation mode external controlRead0=Auto; 1=Off; 2=Stage1; 3=Stage2; 4=Stage3
MV28852ExtControlStepExternal control fan stepRead0=Auto; 1=Off; 2=1Step; 3=2Step; 4=3Step
MV42910ExtractFanExhFanRead0=No; 1=Yes; 2=Combined
MV24454ExtraHtgPreHtgactvPre htg 2 stateRead
MV46124FanControlModeFan control modeRead0=Passive; 1=Active
MV314FanExtSetPFnctFan external setpoint functionRead0=Relative; 1=Absolute
MV60264FanExtSpFan external setpointRead0=No; 1=Supply; 2=Exhaust; 3=Sply; 4=Exh
MV9703FireDamper1OperationFire damper 1 modeRead1=OK; 2=Test; 3=Alarm
MV24347FireDamper1StateFire damper stateRead0=NotDefined; 1=Closed; 2=Moving; 3=Opened
MV64867FireDamper1TestStrtHMIPlsFire damper testRead0=Passive; 1=Active
MV64435FireDamper2OperationFire damper 2 modeRead1=OK; 2=Test; 3=Alarm
MV45701FireDamper2StateFire damper 2 stateRead0=NotDefined; 1=Closed; 2=Moving; 3=Opened
MV47843FireDamper2TestStrtHMIPlsFire damper 2 testRead0=Passive; 1=Active
MV28592FireFunctionFan fire function - Fire alarm 1Read0=InActv; 1=Stop; 2=Run Sply; 3=Run Exh; 4=Run Both; 5=Ctrl St1
MV15192FireFunction2Fan fire function - Fire alarm 2Read0=InActv; 1=Stop; 2=Run Sply; 3=Run Exh; 4=Run Both; 5=Ctrl St1
MV11129FireFunction3Fan fire function - Fire alarm 3Read0=InActv; 1=Stop; 2=Run Sply; 3=Run Exh; 4=Run Both; 5=Ctrl St1
MV36630FlowDisplayFlowDisplayRead0=No; 1=Yes; 2=Yes+Outp; 3=Yes+Prs; 4=Yes+Prs+Outp
MV65377Heating3PreHtgactvPre-heater stateRead0=Passive; 1=Active
MV55722HeatingPreHtgactvHeating 1 Pre-heating stateRead0=Passive; 1=Active
MV22321HRecMBRunModePlate heat exchanger - Run ModeRead
MV26068HRecSplySnsrHeat recovery supply temp°CRead
MV12352HtgStartBMSHeating 1 start BMSRead0=Off; 1=On
MV13725HumEngUnitHumidity engineering unitRead0=%r.H.; 1=g/kg
MV35440IPSUMActiveIPSUMRead0=No; 1=Yes
MV5664IPSUMComModeIPSUM Com.methodRead0=Analog; 1=RTU; 2=TCP-direct; 3=TCP-shared
MV28147IPSUMOpModeIPSUMRead0=Auto; 1=Stopped; 2=Supply only; 3=Extract only
MV55404IPSUMTempCtrlModeIPSUM Temp CtrlRead0=Inactive; 1=Active
MV59996MECHactvCooling recovery activatedRead0=Off; 1=On
MV37857MixingFanControlRatioMixing fan control ratioRead0=Static; 1=Proportional
MV65099ModBusHKInstrFilterAlarmMB Filter alarmRead
MV19346ModBusHKInstrFlowSensorMB Flow sensorRead0=No; 1=Supply; 2=Extract; 3=Supply+Extract
MV19204ModBusHKInstrPreFilterAlarmMB Pre-filter alarmRead0=No; 1=Supply; 2=Extract; 3=Supply+Extract
MV64813ModBusHKInstrPressureSensorMB Pressure sensorRead0=No; 1=Supply; 2=Extract; 3=Supply+Extract
MV41855ModBusHKInstrType(Dubble/Single)HK-Instruments TypeRead0=Single; 1=Dual Sply; 2=Dual Exh; 3=Both
MV43500Nbr_CircReCoolerReCooler number of circuitsRead0=NotUsed; 1=eQKR008; 2=eQKR011; 3=eQKR018; 4=eQKR023; 5=eQKR032; 6=eQKR041; 7=eQKR050; 8=eQKR072
MV40097NghtCoolingConfigNight coolingRead0=No; 1=Yes
MV3688NightCoolOpMBMSNight cooling operational mode BMSRead0=Off; 1=On
MV6316NightUnoccCoolingModeCooling coil (night cooling)Read0=Inactive; 1=Active
MV17477NightUnoccHeatingModeHeating coil (night heating)Read0=Inactive; 1=Active
MV31604OpModeAutoManStSwtchManual operation (steps)Read0=Auto; 1=Off; 2=Stage1; 3=Stage2; 4=Stage3
MV60288OpModeAutoManStTmpSwtchManual operation (steps/temperature)Read0=Auto; 1=Off; 2=Eco St1; 3=Comf St1; 4=Eco St2; 5=Comf St2; 6=Eco St3; 7=Comf St3
MVmin8442OpModeBmsTimeStSwtchBMS TSP stepsRead0=Auto; 1=Off; 2=Stage 1; 3=Stage 2; 4=Stage 3
MV32040OpModeBmsTimeStTmpSwtchBMS TSP steps/temperatureRead0=Auto; 1=Off; 2=Eco St1; 3=ComfSt1; 4=Eco St2; 5=Comf St2; 6=EcoSt3; 7=Comf St3
MV33544OpModeTspCopyUnitPlsOpModeTspCopyUnit.PlsRead0=Monday to; 1=Tu to Fr
MV41090OpStaReCoolerReCooler operation statusRead0=Stop; 1=Running Full; 2=Defrost; 3=In Alarm; 4=Heating; 5=Cooling; 6=Mandatory OFF; 7=Stand By; 8=Start Up
MV57729OpStaReCooler1ReCooler circuit 1 operation statusRead0=Stand By; 1=Init; 2=Unit running; 3=Defrost; 4=Rev. cycle defrost; 5=Exh. Coil low temp; 6=Start phase; 7=Pressure diff. limit; 8=Start delay; 9=Alarm; 10=Compressor shut off; 11=Cool/Heat mode select; 12=Heater run; 13=Alarm unit 1; 14=Alarm unit 2; 15=Alarm unit 3; 16=Defrost ramp up; 17=Check refrigerator charge; 18=Quick start
MV53730OpStaReCooler2ReCooler circuit 2 operation statusRead0=Stand By; 1=Init; 2=Unit running; 3=Defrost; 4=Rev. cycle defrost; 5=Exh. Coil low temp; 6=Start phase; 7=Pressure diff. limit; 8=Start delay; 9=Alarm; 10=Compressor shut off; 11=Cool/Heat mode select; 12=Heater run; 13=Alarm unit 1; 14=Alarm unit 2; 15=Alarm unit 3; 16=Defrost ramp up; 17=Check refrigerator charge; 18=Quick start
MV49603OpStaReCooler3ReCooler circuit 3 operation statusRead0=Stand By; 1=Init; 2=Unit running; 3=Defrost; 4=Rev. cycle defrost; 5=Exh. Coil low temp; 6=Start phase; 7=Pressure diff. limit; 8=Start delay; 9=Alarm; 10=Compressor shut off; 11=Cool/Heat mode select; 12=Heater run; 13=Alarm unit 1; 14=Alarm unit 2; 15=Alarm unit 3; 16=Defrost ramp up; 17=Check refrigerator charge; 18=Quick start
MV50249OutTempSensorOutdoor temperature sensorRead0=No; 1=Yes; 2=Yes+Hold; 3=Yes+Hold+Wall
MV30208PreHeatingPreHtgactvPre-heater stateRead0=Passive; 1=Active
MV46288PressuresFilterChPlsFilters changed, pre-alarm acknowledgeRead0=Passive; 1=Active
MV49408ReCoolingReCoolerRead0=No; 1=1 Circuit; 2=2 Circuits; 3=3 Circuits
MVmin59480ResetRead
MV62785Return/ExtTempSensorExtract temperature sensorRead0=No; 1=Yes; 2=Yes+Hold
MV1756RoomRHSensorRoom humidity sensorRead0=No; 1=1 Sensor; 2=2 Sensors
MV39400RoomtempSensorRoom temperature sensorRead0=No; 1=1 Sensor; 2=2 Sensors; 3=1 Room unit; 4=1 Sensor + 1 Room unit; 5=2 Room units
MV47975RtCoolingExtract air coolingRead0=No; 1=Yes; 2=Modbus
MV25185RtHumSnsrExtract air humidity sensorRead0=No; 1=Yes
MV64493SeqHumEngUnitHumidification engineering unitRead0=%r.H.; 1=g/kg
MV53317SnsrModbusAlmSensors com alarmRead0=Ok; 1=Alarm
MV54155SplyEngUnitSupply fan engineering unitRead0=%; 1=Pa; 2=l/s; 3=m³/h
MV32186SplyFanActAlmSupply fan alarmRead0=Nu; 1=MOvrVlt.; 2=MUndrVlt.; 3=DClinkUndrVlt; 4=DClinkOvrVlt; 5=IntElectr; 6=Locked; 7=HallSnsr; 8=Ovrh
MV62832SplyFanActWarnSupply fan warningRead0=Nu; 1=OpenCircutInp; 2=ActSpdLowLlim; 3=BrkOp; 4=DCLlinkVlt; 5=ElectrTmp; 6=MtrTmp; 7=OutpStgTmp; 8=Mes
MV6941SplyFanPrsCtrlModeSupply pressure controlRead0=Inactive; 1=Step; 2=Linear
MV3566SupplyRHSensorSupply humidity sensorRead0=No; 1=Yes
MV24616SuWiSwtchCheckStateSummer/Winter modeRead0=Winter; 1=Summer
MV56125TempControlModeTemperature control modeRead0=Supply; 1=RmSplyC; 2=ExtSplyC; 3=RmSplyC Su; 4=ExSplyC Su; 5=Room; 6=Extract; 7=HOTC
MV19178TempExtSetPFnctExternal setpoint functionRead0=Relative; 1=Absolute
MV52222TimeSchedAuxAux TSP outputRead0=Off; 1=On
MV12316TimeSchedStActual time switch program (steps)Read0=Off; 1=Stage1; 2=Stage2; 3=Stage3
MV596TimeSchedStTmpActual time switch program (steps/temperature)Read0=Auto; 1=Off; 2=Eco St1; 3=Comf St1; 4=Eco St2; 5=Comf St2; 6=Eco St3; 7=Comf St3
PIV15816ExhFanAlmWarnDanfoss / OJ-DV Exhaust fan alarm warningRead
PIV52012SplyFanAlmWarnDanfoss/OJ-DV Supply fan alarm warning and Critical Air solutions to support every application innovative technologies, high2018 Copyright © FG_DC_10159GB_Climatix_IN-MA_20180821_R0_150dpi WWW.FLAKTGROUP.COM CLIMATIX area. We offer our customers performance supported by more The widest product range in 65 countries worldwide, guarantee Excellence in Solutions. Air Distribution Air Filtration & Heating Controls ServiceRead
Object ID lookup: FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx

How many BACnet points does the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx have?

This list has 868 BACnet objects: 93 analog inputs, 25 analog outputs, 452 analog values, 70 binary inputs, 25 binary outputs, 93 binary values, 2 multi-state outputs, 106 multi-state values, 2 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx BACnet documentation?

The source is eQ Controls - Climatix BACnet communication module, Installation and maintenance instruction (BACnet objects of eQ Fläkt V3.xx) (DC_10159GB 20180823_R0), revision 2018-08-23, published free by FläktGroup at https://www.flaktgroup.com/api/v1/Documents/129344/Download.

What are the minimum BACnet points to integrate the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx?

Start with MV 8442 OpModeBmsTimeStSwtch (BMS operating command: 0 Auto, 1 Off, 2-4 stage 1-3); AV 1884 ExtSetpointSpvCOM (Temperature setpoint written over the bus, °C); MV 59480 Reset (General alarm acknowledge / reset); MV 6080 ActOpMode (Actual operating mode (off, comfort, economy...)); MV 32321 ActOpSta (Actual operation status / stop reason); AI 45150 SupplyTmp (Supply air temperature); AI 28256 ReturnAirTmp (Extract air temperature); AI 53218 OutTmp (Outdoor air temperature); AO 59037 SplyFanVarPos (Supply fan output signal, 0-100 %); MV 42640 AlmCl1 (Critical (A) alarm class active).

How do I enable BMS control of the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx?

The document gives no access column. OpModeBmsTimeStSwtch (steps) and OpModeBmsTimeStTmpSwtch (steps/temperature) are the BMS time-switch-program commands (0 = Auto follows the unit's own program); which one applies depends on the unit's control mode.

Can the BMS supply sensor values to the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx?

ExtSetpointSpvCOM (AV 1884) is the external setpoint value from communication; the AI ExtSetpointSpv is the hard-wired external setpoint input.

How do I check these points on the real eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More FläktGroup BACnet points lists

Source: eQ Controls - Climatix BACnet communication module, Installation and maintenance instruction (BACnet objects of eQ Fläkt V3.xx) · DC_10159GB 20180823_R0 · rev. 2018-08-23. Object names, instances and units are reproduced as published; descriptions are our own.